Report - Water Rect - Bungalow-stp-pmu-ppu..Etc
Report - Water Rect - Bungalow-stp-pmu-ppu..Etc
CONSULTANT: DEVELOPER:
Submission no.: 1 2 3 4 5
Date of submission:
BEKALAN AIR UNTUK CADANGAN PEMBINAAN SATU (1) UNIT RUMAH
SESEBUAH/PPU/STP/PMU ATAS LOT 358 MUKIM PLENTONG,
JOHOR BAHRU.
1.0 INTRODUCTION
8.0 CONCLUSION
APPENDIX
1. SPAN Certificate
2. Pressure test result from SAJ (water source)
3. Kebenaran Merancang (KM) - Approval Plan
4. Building Plan (Dev. without KM) – Approval Plan
5. Specifications and Standard Drawing For
Pipeworks (SSD Form)
DRAWING
Reticulation Pipe
Schematic for Average flow
Schematic for Peak Flow
1
BEKALAN AIR UNTUK CADANGAN PEMBINAAN SATU (1) UNIT RUMAH
SESEBUAH/PPU/STP/PMU ATAS LOT 358 MUKIM PLENTONG,
JOHOR BAHRU.
1.0 INTRODUCTION
This development is located at Lot ………, Mukim Tebrau, Johor Bahru, Johor. This
development classified as residential/commercial consist of one (1) unit double story
bungalow.
2
KEY PLAN
3
LOCATION PLAN
4
2.0 PURPOSE OF APPLICATION
This submission is to seek approval of communication pipe 51mm Ø PA pipe and meter
stand.
Source of water supply for this development will obtained from………... SAJ’s letter Bil.
( ) dlm. SAJH/PP/PT/JB……..dated 30.10.2013 are related.
The distribution of water supply for this development is direct supply from existing 200mm
Ø mild steel at Jalan Persiaran Nusa Indah.
Internal storage with a capacity of 1800 gallons will be provided in this bungalow as
below:-
There are several criteria that were considered during designing of pipe reticulation as
follows: -
a) Analysis of average flow for pipe reticulation will be checked with factor 1.0.
5
b) Analysis of peak flow for pipe reticulation will be checked with factor 2.5 (2.5 x
average flow).
d) HSL for analysis peak flow refer to TWL of internal water tank for landed
properties (less than 15m height of building) and suction for high-rise.
f) The minimum allowable head loss in pipe due to friction is 2/1000 for peak flow.
g) Convey flows with a velocity of not less than 0.3 m/sec and maximum is 2.0m/sec
for average flow.
h) Water demand and design shall be based on the Uniform Technical Guideline for
Water Reticulation and Plumbing.
Based on the pressure test results received from SAJ via letter reference
(6)SAJH.JB/PT/2/582-1 dated 7.4.2014, the location of the pressure test is estimated
0.98km away from the proposed connection point (location plan attached). Therefore, here
is available pressure at proposed connection point:-
= 36.0m
6
b. Available pressure at location of proposed connection point;
= 0.023lps
= 0.058lps
Based on available pressure, 67.04m that the water can be supply directly to the individual
tank.
7
8.0 CONCLUSION
Based on the results of hydraulic analysis, here are conclusions of this report:-
1. The residual pressure refers to HSL for the peak and fire flow analysis shows the
value exceeding 7.5m.
2. The pressure head loss due to friction of the peak flow value less than 2/1000.
3. Convey flows with a velocity of not less than 0.3 m/sec and maximum is 2.0m/sec for
average flow.
8
APPENDIX
Appendix 1
1. - SPAN Certificate
Appendix 2
2. - Pressure test result from SAJ (water source)
Appendix 3
3. - Kebenaran Merancang (KM) - Approval Plan
9
DRAWING
10
BEKALAN AIR UNTUK CADANGAN PEMBINAAN SATU (1) UNIT RUMAH
SESEBUAH/PPU/STP/PMU ATAS LOT 358 MUKIM PLENTONG,
JOHOR BAHRU.
LIST OF DRAWING
11