LOAD SHCEDULE

PANEL REF. MDB PROJECT REFERENCE Commercial Building


INCOMER 1600A TP ACB MAIN CONTRACTOR Al Qodorat Engineering General Contracting LLC
INCOMER

TOTAL LOAD (KW) #REF! ELECTRICAL CONTRACTOR BIRDS ELECTRO-MECHNICAL CONTRACTING CO. L.L.C
OUTGOING 14 WAY INCOMING CABLE 7x1C,630mm² XLPE/AWA/PVC
FED FROM TRANSFORMER LOCATION LV ROOM
MCCB PHASE LOAD IN KW TCL IN DFL IN
SL.N0 RAT.Amp DESCRIPTION CABLE SIZE KW KW REMARKS
R Y B
RYB1 100A TP SMDB-SH 4c,25mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB2 300A TP SMDB-1F 4c,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB3 300A TP SMDB-2F 4c,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB4 300A TP SMDB-3F 4c,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC 46.09 46.09 46.09 138.28 73.01
RYB5 300A TP SMDB-4F 4c,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC 46.09 46.09 46.09 138.28 73.01
1600A TP ACB MAIN

RYB6 300A TP SMDB-5F 4c,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC 46.09 46.09 46.09 138.28 73.01
RYB7 125A TP SMDB-SERVICE 4C,35mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB8 125A TP SMDB-E 4C,35mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB9 800A TP MCC PANEL 2x4c,240mm² XLPE/SWA/PVC+2x1c,120mm²Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB10 100A TP FIRE PUMP 4c,25mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC 13.30 13.40 13.30 40.00 0.00 ELA
RYB11 300A TP CAP. BANK 150 KVAR 4c,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC
RYB12 100A TP SPARE+PADLOCK
RYB13 63A TP SPARE+PADLOCK
RYB14 63A TP SPARE+PADLOCK
GRAND TOTAL PHASE LOAD: #REF! #REF! #REF! #REF! #REF!
TOTAL CONNECTED LOAD: #REF! KW
TOTAL DIVERSIFIED LOAD: #REF! KW
LOAD SHCEDULE
PANEL REF. PROJECT REFERENCE
INCOMER MAIN CONTRACTOR
INCOMER

TOTAL LOAD (KW) ELECTRICAL CONTRACTOR


OUTGOING INCOMING CABLE
FED FROM LOCATION
MCCB PHASE LOAD IN KW TCL IN DFL IN
SL.N0 RAT.Amp DESCRIPTION CABLE SIZE KW KW REMARKS
R Y B

GRAND TOTAL PHASE LOAD: 0.00 0.00 0.00 0.00 0.00


TOTAL CONNECTED LOAD: 0.00 KW
TOTAL DIVERSIFIED LOAD: 0.00 KW
LOAD SHCEDULE
PANEL REF. SMDB-2F PROJECT REFERENCE Commercial Building
INCOMER 300A TP MCCB MAIN CONTRACTOR Al Qodorat Engineering General Contracting LLC
INCOMER

TOTAL LOAD(KW) #REF! ELECTRICAL CONTRACTOR BIRDS ELECTRO-MECHNICAL CONTRACTING CO. L.L.C
OUTGOING 10 WAY INCOMING CABLE 4C,150mm² XLPE/SWA/PVC + 1C,70mm² Y/G ECC
FED FROM MDB SMDB LOCATION 2ND FLOOR ELECTRICAL ROOM
MCCB PHASE LOAD IN KW TCL IN DFL IN
SL.N0 DESCRIPTION CABLE SIZE REMARKS
RAT.Amp R Y B KW KW
RYB1 63A TP DB-F1-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC 6.25 6.20 7.55 20.00 10.68
RYB2 63A TP DB-F2-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB3 63A TP DB-F3-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
300A TP MCCB MAIN

RYB4 63A TP DB-F4-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB5 63A TP DB-F5-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB6 63A TP DB-F6-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB7 63A TP DB-F7-2F 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!
RYB8 63A TP SPARE + PADLOCK
RYB9 63A TP SPARE + PADLOCK
RYB10 SPACE
GRAND TOTAL PHASE LOAD: #REF! #REF! #REF! #REF! #REF!
TOTAL CONNECTED LOAD: #REF! KW
TOTAL DIVERSIFIED LOAD: #REF! KW
NOTE: SMDB-2F TO SMDB-5F ARE TYPICAL
LOAD SHCEDULE
PANEL REF. PROJECT REFERENCE
INCOMER MAIN CONTRACTOR
INCOMER

TOTAL LOAD(KW) ELECTRICAL CONTRACTOR


OUTGOING INCOMING CABLE
FED FROM SMDB LOCATION
MCCB PHASE LOAD IN KW TCL IN DFL IN
SL.N0 DESCRIPTION CABLE SIZE REMARKS
RAT.Amp R Y B KW KW

GRAND TOTAL PHASE LOAD: 0.00 0.00 0.00 0.00 0.00


TOTAL CONNECTED LOAD: 0.00 KW
TOTAL DIVERSIFIED LOAD: 0.00 KW
NOTE:
LOAD SHCEDULE
PANEL REF. MCC PANEL PROJECT REFERENCE Commercial Building
INCOMER 800A TP MCCB MAIN CONTRACTOR Al Qodorat Engineering General Contracting LLC
INCOMER

TOTAL LOAD(KW) #REF! ELECTRICAL CONTRACTOR BIRDS ELECTRO-MECHNICAL CONTRACTING CO. L.L.C
OUTGOING 6 WAY INCOMING CABLE 2X4C,240mm² XLPE/SWA/PVC + 2x1C,120mm² Y/G ECC
FED FROM MDB LOCATION ROOF FLOOR MCC ROOM
MCCB PHASE LOAD IN KW TCL IN DFL IN
SL.N0 DESCRIPTION CABLE SIZE REMARKS
RAT.Amp R Y B KW KW

RYB1 350A TP CHILLER-1 4C,185mm² XLPE/SWA/PVC + 1C,95mm² Y/G ECC 49.33 49.33 49.34 148.00 133.20

RYB2 350A TP CHILLER-2 4C,185mm² XLPE/SWA/PVC + 1C,95mm² Y/G ECC 49.33 49.33 49.34 148.00 133.20
800A TP MCCB MAIN

RYB3 40A TP MCC-CHWP 4C,10mm² XLPE/SWA/PVC + 1C,10mm² Y/G ECC #REF! #REF! #REF! #REF! #REF!

RYB4 40A TP FAHU 4C,10mm² XLPE/SWA/PVC + 1C,10mm² Y/G ECC 4.57 4.57 4.57 13.70 12.33 ISO+RCD(
100mA)
RYB5 40A TP SPARE + PADLOCK

RYB6 40A TP SPARE + PADLOCK

GRAND TOTAL PHASE LOAD: #REF! #REF! #REF! #REF! #REF!


TOTAL CONNECTED LOAD: #REF! KW
TOTAL DIVERSIFIED LOAD: #REF! KW
LOAD SHCEDULE
PANEL REF. PROJECT REFERENCE Commercial Building
INCOMER MAIN CONTRACTOR
INCOMER

TOTAL LOAD(KW) ELECTRICAL CONTRACTOR


OUTGOING INCOMING CABLE
FED FROM LOCATION
MCCB PHASE LOAD IN KW TCL IN DFL IN
SL.N0 DESCRIPTION CABLE SIZE REMARKS
RAT.Amp R Y B KW KW

GRAND TOTAL PHASE LOAD: 0.00 0.00 0.00 0.00 0.00


TOTAL CONNECTED LOAD: 0.00 KW
TOTAL DIVERSIFIED LOAD: 0.00 KW
LOAD DISTRIBUTION SCHEDULE
PANEL REF. : DB-F1-1F PROJECT : Commercial Building
INCOMER : 63A TPN ISOLATOR MAIN CONTRACTOR :
INCOMER
ISOLATOR RAT.

TOTAL LOAD : 20.00 KW ELECTRICAL CONTRACTOR : BIRDS ELECTRO-MECHNICAL CONTRACTING CO. L.L.C
OUTGOING : (4+6)10 WAY TPN DB INCOMING CABLE : 4C,16mm² XLPE/SWA/PVC + 1C,16mm² Y/G ECC
FED FROM : SMDB-1F DB LOCATION : 1ST FLOOR FLAT-1

Bus. MCB Phase & Earth TOTAL LOAD PER CIRCUIT LOAD (KW)
CIRCUIT DFL in
Sec./ RATINGS Neutral Size LOAD DESCRIPTION NO. OF POINT DF REMARKS
NO. KW
RCD (A) Size mm² mm² POINTS (WATT) R Y B
R1 10 2.5 1.5 LIGHT TYPE-F10 (KITCHEN) 3 50 0.15 0.75 0.11
Y1 20 4.0 2.5 FCU-1 (KITCHEN) 1 200 0.20 0.90 0.18
B1 10 2.5 1.5 LIGHT TYPE-F1,F6 (BEDROOM) 5 50 0.25 0.75 0.19
R2 10 SPARE
40A 4P RCD (100mA)

Y2 10 SPARE
B2 16 2.5 1.5 LIGHT TYPE-F4,F11,F18(LIVING/DINING) 8/2/1/1 50/300/4 1.40 0.75 1.05
R3 10 SPARE
Y3 10 SPARE
B3 20 4.0 2.5 FCU-2 (BATH) 1 200 0.20 0.90 0.18
R4 10 SPARE
Y4 10 SPARE
B4 20 FUTURE LOAD 1 500 0.50 0.50 0.25
SECTION-1 / SUB TOTAL LOAD = 2.70 K.W 0.15 0.20 2.35
R5 32 4.0 2.5 S6-S8, RING (KITCHEN) 3d 400 1.20 0.50 0.60
63A TP ISOLATOR MAIN

Y5 32 6.0 4.0 CCU (KITCHEN) 1 6000 6.00 0.50 3.00


B5 32 4.0 2.5 S2-S5, RING(BED ROOM/LOBBY) 3d/1S 400/200 1.40 0.50 0.70
R6 20 4.0 2.5 20A DP SWITCH WITH FLEX OUTLET(DW) 1 1500 1.50 0.50 0.75
Y6 20 SPARE
B6 32 4.0 2.5 S9-S12, RING (LIVING/DINING) 4d 400 1.60 0.50 0.80
R7 20 4.0 2.5 OUT LET FOR LPG 1 200 0.20 0.50 0.10
40A 4P RCD (30mA)

Y7 20 SPARE
B7 20 4.0 2.5 WATER HEATER (BATH) 1 1500 1.50 0.50 0.75
R8 20 4.0 2.5 OUT LET FOR KITCHEN HOOD 1 200 0.20 0.50 0.10
Y8 32 SPARE
B8 10 2.5 1.5 LIGHT TYPE-F2,F13 (TOILET) 2 50 0.10 0.75 0.08
R9 20 4.0 2.5 20A DP SWITCH WITH FLEX OUTLET(WW) 1 1500 1.50 0.50 0.75
Y9 20 SPARE
B9 10 2.5 1.5 LIGHT TYPE-F2,F13,SHAVER (BATH) 2/1 50/100 0.20 0.75 0.15
R10 20 4.0 2.5 WATER HEATER (KITCHEN) 1 1500 1.50 0.50 0.75
Y10 20 SPARE
B10 20 4.0 2.5 S1, RADIAL (ONU) 1 400 0.40 0.50 0.20
SECTION-2 / SUB TOTAL LOAD = 17.30 K.W 6.10 6.00 5.20
TOTAL CONNECTED LOAD : 6.25 6.20 7.55 10.68
TOTAL CONNECTED LOAD IN KW : 20.00 K.W
TOTAL DIVERSIFIED LOAD IN KW : 10.68 K.W
NOTE: DB-F1-1F,DB-F2-1F,DB-F12-1,FDB-F13-1F ARE TYPICAL
LOAD DISTRIBUTION SCHEDULE
PANEL REF. : PROJECT :
INCOMER : MAIN CONTRACTOR :
INCOMER
ISOLATOR RAT.

TOTAL LOAD : ELECTRICAL CONTRACTOR :


OUTGOING : INCOMING CABLE :
FED FROM : DB LOCATION :

Bus. MCB Phase & Earth TOTAL LOAD PER CIRCUIT LOAD (KW)
CIRCUIT DFL in
Sec./ RATINGS Neutral Size LOAD DESCRIPTION NO. OF POINT DF REMARKS
NO. KW
RCD (A) Size mm² mm² POINTS (WATT) R Y B

SECTION-1 / SUB TOTAL LOAD = 0.00 K.W 0.00 0.00 0.00

SECTION-2 / SUB TOTAL LOAD = 0.00 K.W 0.00 0.00 0.00

TOTAL CONNECTED LOAD : 0.00 0.00 0.00 0.00

TOTAL CONNECTED LOAD IN KW : 0.00 K.W

TOTAL DIVERSIFIED LOAD IN KW : 0.00 K.W

NOTE:
LOAD SCHEDULE
Project/Building Name : Commercial Building Main Contractor : Al Qodorat Engineering General Contracting LLC
Adress/Location : Electrical Contractor : Birds Electro-Mechanical Cont.Co.LLC
Panel Ref : CU-ER Incoming Cable Size/Type : : 2c,10mm²XLPE/SWA/PVC+1C,10mm²ECC
Feed From : E-SMDB CU Size & Main Breaker Type & Rating : 12 Ways , 40A SP ISO. MAIN

Diversifei
Divercity
Watts

d Load
Factor
RCBO Rating (A) Wire Size ECC Size No. Of Load in

(Kw)
CKT REF. Point Referance per

(%)
mm2 mm2 Points Points KW

CKT-1 10A (100mA) 2.5 1.5 AIR CRAFT LIGHT TYPE-F19 1 300 0.3 0.75 0.22

CKT-2 10A (100mA) 2.5 1.5 AIR CRAFT LIGHT TYPE-F19 1 300 0.3 0.75 0.22

CKT-3 32A (30mA) 4.0 2.5 S1-S2, RING (GSM RM) 2d 200 0.8 0.50 0.40

CKT-4 20A (30mA) 4.0 2.5 20A ISO FOR GSM EQUIPMENT-1 1 1500 1.5 0.50 0.75

CKT-5 20A (30mA) 4.0 2.5 20A ISO FOR GSM EQUIPMENT-1 1 1500 1.5 0.50 0.75

CKT-6 20A (100mA) SPARE


CKT-7 20A (100mA) SPARE
CKT-8 20A (100mA) SPARE
TOTAL (KW) 4.40 2.35
TCL 4.40 KW
TDL 2.35 KW
LOAD SCHEDULE
Project/Building Name : Main Contractor :
Adress/Location : Electrical Contractor :
Panel Ref : Incoming Cable Size/Type : :
Feed From : CU Size & Main Breaker Type & Rating :

Diversifei
Divercity
Watts

d Load
Factor
CKT REF. MCB/RCBO Rating Wire Size ECC Size No. Of Load in

(Kw)
Point Referance per

(%)
(A) mm2 mm2 Points Points KW

TOTAL (KW) 0.00 0.00


TCL 0.00 KW
TDL 0.00 KW