RECOMMENDED THICKNESS
APCOFLEX POLYOLEFIN FOAM INSULATION
ApcoFlex Polyolefin Foam (Rubber) With Embossed Reinforced Aluminum Facing and Self
Adhesive backing for Ductwork but without Self Adhesive For Pipe Work
Duct Insulation Application Schedule/ Recommended Thickness :
Indoor Installation/ in conditioned areas Supply And Return 12mm
Fresh Air and
Indoor & Out Door 12mm
Ventilation
Indoor but outside conditioned Areas/ Inside
All 19mm
shafts or risers in Un-conditioned Areas
Outdoor & Over the roof All 25mm

Pipe Insulation Thickness Schedule


Pipe Size in conditioned areas in non conditioned Areas
1
Chilled Water Supply& Return
Up To 100mm (4 In) and Less. 25mm (1") 32 mm (1 1/4")
125mm (5 In) and above 25mm (1") 38 mm (1 1/2")
Larger Than 250mm (10") 32mm (1 1/4") 50mm (2")
Horizontal Condensate Drains
Expect with Fan Coil Units Enclosure All 12mm (1/2")
2 Pipe Sizes
Refrigerant piping - suction lines. 19 mm (34")
3 Hot & Cold Water Pipe 25 mm(1")

ApcoFlex Polyolefin Foam Rubber Standards Compliance and Testing Certificates


Test Method Testing Authority/ Laboratory Results
BS 476 :Part 6 – 1989 Warrington Fire Global safety (United
British Standard – Fire propagation Class (O)
Kingdom)
BS 476 :Part 7 – 1997 Warrington Fire Global safety (United
Class (1)
British Standard – Surface Spread Of Flame Kingdom)
(UL) 723 – ASTM E-84 – NFPA 255, 90A , 90B
Underwriters Laboratories Inc. (USA) 0
Flame Spread Index (FSI)
(UL) 723 – ASTM E-84 – NFPA 255, 90A , 90B
Smoke Developed Index (SDI) Underwriters Laboratories Inc. (USA) 10
2010 Dubai Green Building Regulations and
Dubai Central Laboratory Comply
Specifications
Smoke and Toxicity – IMO Resolution MSC
Exova Warringtonfire Comply
307 (88 FTP Code): Annex 1: Part 2 : 2010
Sound Absorption Test TUV Comply
ASTM C518
Dubai Municipality Central Laboratory 0.040 W/mk
Thermal Conductivity & mean Temp. 36C
Measured Density Dubai Municipality Central Laboratory 40 Kg/m3
ASTM E-96
Dubai Municipality Central Laboratory 0.00
Water Vapor Transmission Of Materials
ASTM C 209 :1998 Water Absorption Dubai Municipality Central Laboratory 0.030 gm/Nh
Anti Bacterial ASTM G22-96 AL Futaim Exova - Dubai No Growth (0)
Anti Microbial (Anti Fungal) ASTM
AL Futaim Exova - Dubai No Growth (0)
C1338-08
Hydrofluorocarbons (HFC’s) AL Futaim Exova - Dubai Free
Hydrochlorofluorocarbons ( HCFC’s) AL Futaim Exova - Dubai Free
Asbestos ( Using EPA 600/R-93/116) LCS Laboratory -Canada Free
Formaldehyde (Using NIOSH 5700 & NIOSH
LCS Laboratory -Canada Free
3500
VOC Content (Using ASTM 1868-10) SGS Laboratories Free