Wall Load EFFECT ON SLAB FORCES & DESIGN

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

WALL UNIFORM LOAD

WALL LOAD DEFLICTION

BENDING MOMENT X STRIPS


BENDING MOMENT Y STRIPS

WALL LINE LOAD

WALL LOAD DEFLICTION


BENDING MOMENT X STRIPS

BENDING MOMENT Y STRIPS


Comparing results

Line load Uniform load Difference


Max wall load deflection 11.22 mm 8.75 mm 28%
Total wall reaction 3556 KN 3780 KN 6%
Max +ve BMD strip S6A X direction 46.75 24.0 95 %
for wall load
Max -ve BMD strip S6A X direction 51.70 33.2845 55%
for wall load
Max +ve BMD strip S7B X direction 58.8 31.80 85%
for wall load
Max -ve BMD strip S7B X direction 82.0 69.0 18%
for wall load

CONCLUSION

USING ACTUAL LINE LOAD DESTRIBUTION IS MORE ACCURATE AND RECOMMENDED TO BE APPLIED
IN THE STRUCTURAL MODELS