Date :12.FEB.

2024
REVISION :00
UNIT.NO. : RF-EAF-01 FLOOR :ROOF

DUCTS PRESSURE LOSSES BOARD


AIR FLOW PRESSURE
S.NO DESCRIPTION DUCT SIZE (MM) DROP REMARK
LPS CFM (PA)
EXHAUST
1 FLEXIBLE DUCT CONNECTOR DIA 350 504 1067.5 1.0
2 MOUTH CONNECTION DIA 350 / 450X400 504 1067.5 1.0
3 STRAIGHT DUCT 450X400 504 1067.5 0.7
4 90 DEG ELBOW 450X400 504 1067.5 1.0
5 STRAIGHT DUCT 450X400 504 1067.5 1.0
6 90 DEG ELBOW 450X400 504 1067.5 1.0
7 STRAIGHT DUCT - RISER 450X400 504 1067.5 0.9
8 90 DEG ELBOW 450X400 504 1067.5 1.0
9 STRAIGHT DUCT 450X400 504 1067.5 1.8
10 90 DEG ELBOW 450X400 504 1067.5 1.0
11 VCD 450X400 504 1067.5 1.0
12 STRAIGHT DUCT 450X400 504 1067.5 2.7
13 90 DEG ELBOW 450X400 504 1067.5 1.0
14 TEE 450X400 / 300X200 / 250X250 379 802.7 20.0 MAX.
15 VCD 250X250 379 802.7 1.0
16 STRAIGHT DUCT 250X250 379 802.7 0.3
17 45 DEG ELBOW 250X250 379 802.7 26.0
18 STRAIGHT DUCT 250X250 379 802.7 1.4
19 45 DEG ELBOW 250X250 379 802.7 26.0
20 STRAIGHT DUCT 250X250 379 802.7 1.0
21 90 DEG ELBOW 250X250 379 802.7 4.0
22 STRAIGHT DUCT 250X250 379 802.7 4.2
23 TEE 250X250 / 250X150 / 250X250 329 696.8 30.0
24 STRAIGHT DUCT 250X250 329 696.8 2.7
24a TEE 200X150 179 379.1 15.0
25 STRAIGHT DUCT 200X150 179 379.1 4.1
26 45 DEG BRANCH 200X150 / 200X100 94 199.1 1.0
27 REDUCER 200X150 / 150X150 85 180.0 0.1
28 STRAIGHT DUCT 150X150 85 180.0 0.7
29 45 DEG ELBOW 150X150 85 180.0 10.0
30 STRAIGHT DUCT 150X150 85 180.0 3.2
31 45 DEG ELBOW 150X150 85 180.0 10.0
31a BRANCH DIA 150 43 91.1 1.0
32 STRAIGHT DUCT 150X150 42 89.0 1.3
33 COLLAR DIA 150 43 91.1 2.0
33a VCD DIA 150 43 91.1 1.0
34 FLEXIBLE DUCT DIA 150 43 91.1 1.0
35 PLENUM BOX 1100X200X200 43 91.1 1.0
36 ELSD 1M X 2 SLOT 43 91.1 1.0

CALCULATED PRESSURE DROP 184.1


ADDED 30% SAFETY FACTOR 239.3
IFC PRESSURE DROP 200.0
PROPOSED FAN PRESSURE DROP 243.0