Professional Documents
Culture Documents
Relay Coordination Setting
Relay Coordination Setting
RELAY TYPE 7SJ647 7SJ647 7SJ647 7SJ647 7SJ647 7SJ647 7SJ647 7SJ647 7SJ647
FAULT CURRENT (A) 714.3 714.3 714.3 2500.0 2500.0 2500.0 2500.0 2500.0 2500.0
CT RATIO PRIMARY (A) 500 500 200 500 200 200 200 400 1000
CURRENT SETTING (PU) 1.00 1.00 0.60 0.85 1.00 1.00 1.00 1.00 1.00
TMS 0.090 0.090 0.32 0.21 0.13 0.13 0.13 0.10 0.105
OPERATION TIME (SEC) 1.76 1.76 1.21 0.81 0.35 0.35 0.35 0.38 0.79
HIGH SET CURRENT (PU) 4.0 4.0 5.0 4.0 4.0 4.0 4.0 2.5 2.0