CAT. NO.

1220-TCT
ELASTIMOLD@ Issue Date 2/93
r
TCT TERMINATORS
69kV-Class
(for maximum system voltage thru 72kV)
The 69TCT Terminator prqvides a Class 1 termination for
cable systems rated through 69kV class. It conforms to
IEC-840 AND IEEE-48. This terminator is designed for
solid dielectric cables with insulation diameters up to
86,4mm (3.400") and it accomodates conductor sizes from
90mm2 (4/0) to 1700mm2 (3500 kcmil). Various aerial lugs
are available for the conductor connection.

The durable elastomer construction eliminates glaze


damage failures associated with porcelain. A state-of-the-
art shed design ensures a non-continuous drip path and
the non-tracking polymer requires no surface oil or grease.

INSTAllATION
~ The 69TCT Terminator is lightweight 14kg (30Ib.) and easy'
to handle. It can be assembled horizontally on the ground
and then raised to the installation position without a crane.
The installation can be accomplished in 45 minutes (using
the Elastimold TCJ-ATK-U Universal Assembly Tool) after
the cable preparation is completed. The 69TCT 'can utilize
standard support systems.

ELECTRICAL DATA 69TCT


NOMINAL VOLTAGE Uo/U
40kV/69kV
MAXIMUM WORKING VOLTAGE 72.5kV
PARTIAL DISCHARGE <3pC @ 60kV
BIL (@1.2 x 50 microsecond wave) 350kV
10 positive, 10 negative
AC WITHSTAND 60Hz 1 MINUTE DRY 175kV

[Iii [ ELASTIMOLD ]

Route 24, Hackettstown,New Jersey 07840 USA


CATALOG 1220-TCT Page 2 10:2/93 69TCT

.~
AERIAL LUG
Optional configurations
are available

WEATHER TIGHT SEAL DESIGN FEATURES

1. Molded EPDM elastomer housing is


durable under severe environmental
conditions. It does not require a surface
oil/grease to maintain non-tracking properties.

Q) 2. Shed design employs unequal diameters


TERMINATOR MODULE to interrupt the drip path from shed to shed.
CABLE INSULATION
3. Housing is designed to slide over cable
insulation to provide required creep path
and waterseal.

4. Molded stress relief is computer-


designed to assure proper stress relief for
the terminated cable.
@
DIMENSION
A
TERMINATOR BASE

DIMENSIONA ~
94cm (37.0") minimum
May be increased as required
for severe service.
GROUND STRAP
~
TERMINAL

CABLE SEAL

MASTIC SEAL

CABLE SHIELD (SCREEN)


Any configuration can
be accomodated

CABLE DATAREQUIRED FOR TERMINATORSELECTION

MATERIAL SIZE OUTSIDE DIAMETER


. Conductor . Metal Shield mm'orMCM mm or Inches

I . CONDUCTOR

. Insulation . Inner Jacket I . METAL SHIELD

NOMINAL THICKNESS NOMINAL OUTSIDE DIAMETER


MATERIAL
Semi-Conductive . Armor mm or Inches mm or inches
Conductor . INSULATION
Screen
. Outer Jacket . INNER JACKET

. ARMOR
* ~
. OUTER JACKET *
Semi-COnductive
Insulation Screen *" .ppilcabie

Contact your local ELAST/MOLO representative or the ELAST/MOLO factory for a specific proposal based on your requirements.