Wqip-h3-Ilf-dwt-00039 v6, Pump Station and Generator Building-Structural Drawings

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

Drawings Submittal Form ‫ﻧﻤﻮذج ﺗﻘﺪ ﻢ ﻣﺨﻄﻄﺎت‬

Submittal Serial No ‫ اﻟﺮﻗﻢ اﻟ ﺴﻠﺴ‬: WQIP-H3-ILF-DWT-00039 V6 Date ‫ اﻟﺘﺎر ــﺦ‬: 07‐May‐24


Location ‫ اﻟﻤﻨﻄﻘﺔ‬: Eastern Province
Project Title ‫ إﺳﻢ اﻟﻤ وع‬: Water Quality Improvement Project‐ Strategic Network and Reservoirs‐ AlHasa Project 3
Consultant ‫ اﻹﺳ ﺸﺎري‬: ILF Consulting Engineering for Engineering Consultancy
Contractor ‫ اﻟﻤﻘﺎول‬: Civil Works Company
Part A: By the Contractor: ‫ ﻳﺘﻢ إﺳﺘ ﻤﺎﻟﻪ ﻣﻦ ﺧﻼل اﻟﻤﻘﺎول‬: (‫اﻟﺠﺰء )أ‬
Civil Architectural Mechanical Electrical Other (specify)
Discipline ‫ اﻟﺘﺼ ﻒ‬:
‫إ ﺸﺎ‬ ‫ﻣﻌﻤﺎري‬ ‫ﻣ ﺎﻧ ﺎ‬ ‫ﻛﻬ ﺎء‬ (‫أﺧﺮى )ﺣﺪد‬
Drawings Description PUMP STATION AND GENERATOR BUILDING‐STRUCTURAL DRAWINGS ‫وﺻﻒ اﻟﻤﺨﻄﻂ‬

SN Drawing No. Rev Description Reference Contract Drawing


‫م‬ ‫رﻗﻢ اﻟﻤﺨﻄﻂ‬ ‫اﻹﺻﺪار‬ ‫وﺻﻒ اﻟﻤﺨﻄﻂ ‐ إﺳﻢ اﻟﻠﻮﺣﺔ‬ ‫اﻟﺮﻗﻢ اﻟﻤﺮﺟ ﻟﻠﻤﺨﻄﻂ ﻣﺴ ﻨﺪات اﻟﻌﻘﺪ‬
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
02200016411‐H3‐CWC ‐
1 01 AND GENERATORS BUILDING FORMWORK DRAWINGS ‐
010GEN‐STR‐SH‐00046
(SHEETS 01 To 09)

PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


02200016411‐H3‐CWC ‐
2 01 AND GENERATORS BUILDING REINFORCEMENT DRAWINGS ‐
010GEN‐STR‐RD‐00047
(SHEETS 01 To 06)

PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


02200016411‐H3‐CWC ‐
3 01 AND GENERATORS BUILDING SECTIONS AND R.C ‐
010GEN‐STR‐RD‐00049
DETAILS (SHEETS 01 To 06)

We certify that Drawings mentioned above is in accordance with the Contract Specification and Approved Materials.
‫ﺸﻬﺪ ﺄن اﻟﻤﺨﻄﻄﺎت أﻋﻼە و ﻓﻘﺎ ﻟﻤﻮاﺻﻔﺎت اﻟﻌﻘﺪ و اﻟﻤﻮاد اﻟﻤﻌﺘﻤﺪة‬
Designation‫ ﻔﺔ اﻟﻮﻇ‬:Project
Name ‫ اﻻﺳﻢ‬: Mohamad Ali Signature ‫ اﻟﺘﻮﻗﻴﻊ‬: Date ‫ اﻟﺘﺎر ــﺦ‬: .May-07-24
Manager of Al‐Ahsa 3 Project
Part B: By the Consultant: ‫ ﻳﺘﻢ إﺳﺘ ﻤﺎﻟﻪ ﻣﻦ ﺧﻼل اﻹﺳ ﺸﺎري‬:(‫اﻟﺠﺰء )ب‬
Consultant's Eng. Comments ‫ﻣﻼﺣﻈﺎت ﻣﻬﻨﺪس اﻹﺳ ﺸﺎري‬

Name ‫ اﻻﺳﻢ‬: Signature ‫ اﻟﺘﻮﻗﻴﻊ‬: Designation ‫ اﻟﻮﻇ ﻔﺔ‬: Date ‫ اﻟﺘﺎر ــﺦ‬:
Resident Engineer Final Comments & Decision: ‫ﻣﻼﺣﻈﺎت ﻣﺪﻳﺮ اﻟﻤ وع ‐ إﺳ ﺸﺎري‬

Approved Approved with Comments Comply Comments and Resubmit Rejected


‫ﻌﺘﻤﺪ‬ ‫ﻌﺘﻤﺪ ﻤﻼﺣﻈﺎت‬ ‫ﻣﻌﺎﻟﺠﺔ اﻟﻤﻼﺣﻈﺎت و إﻋﺎدة اﻟﺘﻘﺪ ﻢ‬ ‫ﻣﺮﻓﻮض‬
Name ‫ اﻻﺳﻢ‬: Signature ‫ اﻟﺘﻮﻗﻴﻊ‬: Date ‫ اﻟﺘﺎر ــﺦ‬:
Acceptance does not relieve the contractor from his responsibility and liability concerning compliance with the contract requirement.
‫إن ﻫﺬە اﻟﻤــﻮاﻓﻘﺔ ﻻ ﺗــﻌﻔــﻲ اﻟﻤ ـﻘ ــﺎول ﻣﻦ ﻣﺴــﺆوﻟـ ـﺎﺗـﻪ ﺗـﺠــﺎە ﻣـﻄـﺎ ـﻘـﺔ ﻣـﺘﻄـﻠـ ـﺎت اﻟـﻌـﻘــﺪ‬

All dates to be entered in format: dd/mm/yyyy


DWT‐FORM 1 of 1
g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150 p

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100
m

700 700 700 700 700 700 700 700 700 700 700 700
700 350 350 350 350 350 350 350 350 350 350 350 350 600 300 300 300

RW RW RW RW RW RW RW RW RW RW RW RW

600

600

600

600
700

700

700

700

700

700

700

700

700

700

700

700

700
0000
C3 KEY PLAN
C3 C3 C3 C3

600
C1 C2 C2 C2 C2 C2 C2 C2 C2 C2 C2 C2 C1 600 600 600 600
3585

RW
RW

0000
700
1215

600
300 300 600

500 100

500 100

100

100
600
350

350
C3
700

700

600

600
C2 C2 C3 C3 C3 C3
C3

600
700
600 600 300
0000

RW
4000

RW
17385

700
600
350

350
C3
700

700
0000
C1 300 300 300
1085

C2

600
700 NOTES:

300

300
600

600

600
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

300

300
RW C3 C3 C3 C3
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED

600
400 225 600 600 600 600
RW
3. REFER TO GENERAL NOTES GENERAL DETAILS
2915

400
0000

C4
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
700

1305
600 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275

350
C3 6. COVER (mm):
700

700
0000
C1 COLUMNS=40 , SLAB & SLAB BEAMS = 25

600
C2 700
ALL STRUCTURES IN CONTACT WITH SOIL=75
ALL STRUCTURES IN CONTACT WITH WATER=50
RW RW
4585

3450
600 600
350 350 350 350 350 350 350 350 350 350 350 400

400
C1 C2 C2 C2 C2 C2 C2 C2 C2 C2 C1 C1 C1 600 300 300

600

600
C3 C3
C4
700

700

700

700

700

700

700

700

700

700

700

700

700
C3

600

600
C3 C3
ABBREVIATIONS AND LEGEND -
RW RW RW RW RW RW RW RW RW RW RW RW

400

400

400
600
0000
700 700 700 700 700 700 700 700 700 700 700 700 700 600 600

ABBREVIATIONS:
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
1 COLUMNS LAYOUT FROM FOUNDATION TO SLAB-ON-GRADE
0000-000 SCALE 1:50 DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

ENGINEER'S STAMP CONTRACTOR'S STAMP

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

700 700 700 700 700 700 700 700 700 700 700 700 F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
700 350 350 350 350 350 350 350 350 350 350 350 350 600 300 300 300

E GENERAL REVISION 15-01-24

600

600

600

600
D.K. M.K. L.S.
700

700

700

700

700

700

700

700

700

700

700

700

700
0000
C3
C3 C3 C3 C3

600
C1 C2 C2 C2 C2 C2 C2 C2 C2 350 C2 C2 C2 C1 600 600 600 600
D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
3585

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.


0000
700
1215

600
300 300 600 A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

500 100

500 100

100

100
600
350

350
C3
700

700

600

600
C2 C2 C3 C3 C3 C3 REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

600
700
600 600 300
0000

OWNER
4000
17385

700
600
350

350
C3
700

700
0000
C1 300 300 300
1085

C2

600
700

300

300
600

600

600
300

300
C3 C3 C3 C3

600
600 600 600 600 CONSULTANT
2915

0000

700
ILF CONSULTING ENGINEERING FOR
600
ENGINEERING CONSULTANCY

350
C3
700

700
0000
C1

600
C2 700

CONTRACTOR
CIVIL WORKS COMPANY
4585

350 350 350 350 350 350 350 350 350 350 350
C1 600 300 300
600 600 cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
C1 C2 C2 C2 C2 C2 C2 C2 C2 C2 C1 C1

600

600
C3 C3 T.P. 03 8572205 FAX. 03 8574733
700

700

700

700

700

700

700

700

700

700

700

700

700

C3

600

600
C3 C3

400

400
600
0000
700 700 700 700 700 700 700 700 700 700 700 700 700 600 600

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

2 COLUMNS LAYOUT FROM SLAB-ON-GRADE TO ROOF AT LEVEL +5.00


0000-000 SCALE 1:50 DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 01 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 01 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
p

90150 m

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100 p

700
700
350
700
350
700
350
700
350
700
350
700
350
700
350
700
350
700
350
700
350
700
350
700
350 300 KEY PLAN

600

600
700

700

700

700

700

700

700

700

700

700

700

700

700
0000

C1 C2 C2 C2 C2 C2 C2 C2 C2 350 C2 C2 C2 C1 600 C3 600 C3


3585

0000
700
1215

600

100

100
600
350

350
700

700

600

600
C2 C2 C3 C3
700
300
0000
4000
17385

700
NOTES:
350

350
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
700

700
0000
C1 300 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
1085

C2
700

300
3. REFER TO GENERAL NOTES GENERAL DETAILS

600
300
C3 C3 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa

300
600 600
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
2915

0000
6. COVER (mm):
700 COLUMNS=40 , SLAB & SLAB BEAMS = 25
ALL STRUCTURES IN CONTACT WITH SOIL=75

350
700

700
0000
C1 ALL STRUCTURES IN CONTACT WITH WATER=50
C2 700
4585

600 600

C1
350
C2
350
C2
350
C2
350
C2
350
C2
350
C2
350
C2
350
C2
350
C2
350
C1
350
C1 C1 ABBREVIATIONS AND LEGEND -

600

600
C3 C3
700

700

700

700

700

700

700

700

700

700

700

700

700
ABBREVIATIONS:

400

400
0000
700 700 700 700 700 700 700 700 700 700 700 700 700
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

3 COLUMNS LAYOUT ROOF AT LEVEL +5.00 TO ROOF AT LEVEL +8.50 REFERENCE DRAWINGS
0000-000 SCALE 1:50

DRAWING TITLE DRAWING NUMBER


Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE

PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 02 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 02 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
p

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100 p

59450 l

1000 N
100

100
980
E
KEY PLAN
650

650
1600 2020
1000

100
0000

900
100
1600

3200

3200
2000

750

3200
3585

-4.05 325 1000


T.O.C. of Trench -4.80 1885 1000 2115 3860 1000
1000 2885 4650 1000 5315 1000 1000 6360 1000 T.O.C. of Pit
1600

1800
1800

1800

1800

1800

1800

1800

1800
Φ90 PRESSURE PVC STRIP FOUNDATION
UP INTO -0.30 F.F.R.L.
Ø125 mm DRAIN
PIPE RUNNING 500 mm THICK
SLAB
1825

270
185

185

185

185

185

185

185
-4.75 -4.55
200

250

200
0000
T.O.C. of Trench

915
T.O.C. of Pit M
1215

850 A Ø150 mm SLEEVE


250

100

500
500

900
830
845

845

845

845

845

845

845

845
850

850

1910
560 285 500

200
1995

50
STRIP FOUNDATION

-4.55

900
-3.80
250

250
T.O.C. of Trench -4.55 250
1000

1000

1000

1000

1000

1000

1000

1000

50
500 mm THICK

0000 T.O.C. of Trench T.O.C. of Trench 1695


2470 -4.75
130 STEEL PIPE SUPPORT 1380
4000

300
T.O.C. of Pit M
STEEL 1830 1800 115

250
1885 250 900 250 250 900 250 1800

STRIP FOUNDATION
1170

500
1800 2370 2330 1800 330 1800 1670

250
PIPE

500

500 mm THICK
17385

SUPPORT 670 1130 250 900 250 630 2225 3200

150
50
NOTES:

250 900

900
500
2000 2000 500

50
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

17385
75

75

75

75

75

75

75

75
2000 2000 2000 2000 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED

250
0000 500 900 250

380

380

380
1085

-2.70 -2.70 -2.70 -2.70 -2.70


-2.70 -2.70 -2.70 -2.70

505
1500

1500

1500

1500

1500

1500

1500

1500

1500

255
T.O.P.

T.O.P. T.O.P. T.O.P. T.O.P. T.O.P. T.O.P. 3. REFER TO GENERAL NOTES GENERAL DETAILS

1750
T.O.P. T.O.P. 200

250
250 2000 4300 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
TYP.
F1 -4.55 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275

250 900
0000
475 4025 250 3975 525 A 975 3525 4475 25 2975 1525 1475 3025 250
TYP.

TYP.

3200 2475 2025 T.O.C. of Trench


250

250

G G

1800
6. COVER (mm):
2915

TYP. N TYP.
R R
475 1000

475 1000

475 1000

475 1000

475 1000

475 1000

1000
440 1035
COLUMNS=40 , SLAB & SLAB BEAMS = 25

2260
1575 445 200 ALL STRUCTURES IN CONTACT WITH SOIL=75

605
670 1130 830 1950 1800 870 1170 330 1800 1800 1370 1670 130 1685 115

500
630 250 900
ALL STRUCTURES IN CONTACT WITH WATER=50

475

700
0000 STEEL PIPE SUPPORT 335 STEEL PIPE SUPPORT
1180

1180

1180

1180

1180

1180

1180

1180
1000 2885 350 650 4350 970 1000 3030 1965 1000 4325 1000 1000 1890 1000 3870 1000
RAFT FOUNDATION D D

900
695
F F 350 mm THICK
T.O.C -3.60 B C -4.55
1600

1800

1800

1800

1800

1800

1800

1800

1800
4585

T.O.C. of Trench

535
-4.80

2750
-4.05
1850

STEEL PIPE SUPPORT T.O.C. of Trench


T.O.C. of Pit
ABBREVIATIONS AND LEGEND -
1005

750
3200

3200
ABBREVIATIONS:
STRIP FOUNDATION
1000

150
T.O.C: Top of Concrete
750

750
0000
500 mm THICK
B.O.C: Bottom of Conrete
980
100

B C
E T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45
4 TOP VIEW OF FOUNDATION PLAN OF PUMP STATION ROOM
0000-000 SCALE 1:50 REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
ENGINEER'S STAMP CONTRACTOR'S STAMP
90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

59450

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.


1600 2020
0000 Pipe Penetration E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.


3585

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.


PIPE PENETRATION
B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

0000
1215

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

0000

OWNER
4000
17385

17385
75

75

0000
1085

1500

1500

CONSULTANT
0000
2915

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY
0000

CONTRACTOR
CIVIL WORKS COMPANY
4585

PIPE PENETRATION

cWc P.O.BOX 7012, DAMMAM - 34162


KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733
750

0000

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3
5 FOUNDATION LAYOUT OF PUMP STATION ROOM
0000-000 SCALE 1:50
DRAWING TITLE

PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 03 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 03 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


0000 0000 0000 0000 0000

g
i

7800 7200 5600 10100


p

3000 100 3000


1970 2600
100

100
F3 F3
m

100

1200
1200
l

1000
F2

2600
500mm 500mm

3000
700

150
500mm

150
p

3000
0000
TB(30x50) TB(30x50) TB(30x50)

1600

300

1800
1800
T.O.C -1.00 T.O.C -1.00 T.O.C -1.00

1300 1300 1500 1800 1200


1500

TB(30x50)

TB(30x50)

TB(30x50)
7780 1970
100
3000 100 3000
KEY PLAN
2600
100
0000 F3 F3 100

1300
1300
3000
F2

1265

1100
2600
500mm 500mm
500mm

50
50

3000
TB(30x50) TB(30x50) TB(30x50)

300

300
1500

1700
1700
T.O.C -1.00 T.O.C -1.00 T.O.C -1.00
0000 RAFT FOUNDATION
500 mm THICK
1300 1300 1800 1200
1500 1500

TB(30x50)

TB(30x50)
5200

TB(30x50)
T.O.C -1.00 1300 1200 1200
100
2600 F4
700mm HEA 180
F4
700mm HEA 180

1200

1200
100

250

250
17385
TB(30x50)
F3 F3
100

1530

1530
500mm 500mm

2600

3000
F2

1300
0000

935

100
500mm 100
TB(30x50) TB(30x50) TB(30x50)

3000
TB(30x50)

TB(30x50)
300
300

1300

1470
1470
T.O.C -1.00 T.O.C -1.00
0000
T.O.C -1.00
5200

1300 1300
1300 1200 1200 NOTES:
1500 1500 1800 1200 Base plate
3000
F4
700mm HEA 180 F4
700mm HEA 180 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

1200

1200
3000

250

250
TB(30x50) 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
3. REFER TO GENERAL NOTES GENERAL DETAILS

TB(30x50)

TB(30x50)
TB(30x50)
0000

4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa


300 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
300 150
100 100
6. COVER (mm):
2600 COLUMNS=40 , SLAB & SLAB BEAMS = 25
100 F3 F3
ALL STRUCTURES IN CONTACT WITH SOIL=75

3000
500mm

2200
500mm

2200

300
F2

2600
ALL STRUCTURES IN CONTACT WITH WATER=50

1600
500mm

3000
300
TB(30x50)
TB(30x50) TB(30x50)

550
150
700

700
0000

800

800
1000
T.O.C -1.00 T.O.C -1.00 T.O.C -1.00

100
1300 1300 1500 1500 1800 1200
3000 3000
ABBREVIATIONS AND LEGEND -
ABBREVIATIONS:
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
6 FOUNDATION LAYOUT OF MBD & GENERATOR ROOM T.O.B: Top of Beam
0000-000 SCALE 1:50
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE

PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 04 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 04 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
0000 0000

90150
p

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

KEY PLAN

GB (30x50)

GB (30x50)

GB (30x50)
P 1450
2700

1000
200

-1.35 GB (30x50) GB (30x50)

200
0000

900
T.O.C.

50
GB (30x50)

1800
+0.20 350
SLAB-ON-GRADE
200MMTHICK

600
T.O.C OF WALL J

1000
-0.50 T.O.C.+0.20

200
25

500
T.O.C.
3585

2585
800 -0.50 950 50 3125

GB (30x50)
GB (30x50)

GB (30x50)

GB (30x50)
900

GB (30x50)
T.O.C.

GB (30x50)
200

300
1400
200

3020
600
-0.50

GB (30x50)
T.O.C.

550
600
Inverted GB (30x50)
H H

200
0000 530 250
1215

800
200 250
2150

1250
GB (30x50)

500

Inverted GB (30x50)
GB (30x50)

900
200

GB (30x50)
5570
GB (30x50)
200

2870
0000
BELOW TRANSFORMER OIL
2875 +0.05
3700 CATCHMENT BASIN 500mm
WIDTH
T.O.P. of Trench

7030
4000

3300

GB (30x50)
2730 50

500
500

200
200 150 2735
17385

530 NOTES:

4215
250
200 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

200
1735
+0.50

2155
1300

900
3175
T.O.P. of Pad 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
50

2575
0000 710 +0.05
1250 3. REFER TO GENERAL NOTES GENERAL DETAILS
1085

T.O.P. of Trench
150 1250

385

585
200

200
I 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa

975
GB (30x50)

200
290
+0.20 -0.20
Q 200
3" PIPE CONNECTED
TO THE END OIL
CONNECTION PIT
T.O.C.
900
T.O.C.
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275

1250
900
0000

200
250 6. COVER (mm):

900
1100
BELOW TRANSFORMER OIL

430
CATCHMENT BASIN 500mm
WIDTH
2915

DB (20x60) I

GB (30x50)
2730 2730 COLUMNS=40 , SLAB & SLAB BEAMS = 25
200 500 10

200
530 ALL STRUCTURES IN CONTACT WITH SOIL=75

200
2550 1370

200
3300 900 J 755

810
-0.50 ALL STRUCTURES IN CONTACT WITH WATER=50

4715
Q T.O.C.

GB (30x50)
2155
1300
-0.50

900

GB (30x50)
0000
T.O.C.

1260
300

DB (20x60)
D D 1755

900
SOLID SLAB 200

200
2730

5735
200MMTHICK

Inverted GB (30x50)
T.O.C.+0.20 3" PIPE CONNECTED
TO THE END OIL
+0.20
2230
4585

CONNECTION PIT

T.O.C. 1755
SLAB-ON-GRADE
ABBREVIATIONS AND LEGEND -

3470

3240
3775 200MMTHICK 1100 -0.50
-0.50

2785
T.O.C.+0.20 1350 T.O.C.
+0.20 T.O.C. 7355
330
T.O.C OF WALL
GB(30x50) GB (30x50) GB (30x50) GB (30x50)
ABBREVIATIONS:
Inverted GB(30x50) T.O.C: Top of Concrete

350

400

610
0000

200 P 200 200 200 B.O.C: Bottom of Conrete

1905
200 T.O.B: Top of Beam

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)
-1.35 B.O.B: Bottom of Beam

S
K K T.O.C. 50 P.F.L: Pavement Floor Level
200 1100

1100
LEGEND:
255
Reinforced Concrete

S
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
7 TOP VIEW OF GROUND FLOOR LAYOUT
0000-000 SCALE 1:50
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

ENGINEER'S STAMP CONTRACTOR'S STAMP

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
0000 0000

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100 H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

GB (30x50)

GB (30x50)

GB (30x50)
200
E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

0000 -1.35 GB (30x50) GB (30x50) D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
GB (30x50) T.O.C.
+0.20
T.O.C OF WALL C GENERAL REVISION 23-11-23 D.K. M.K. L.S.
3585

-0.50
T.O.C. -0.50

GB (30x50)
GB (30x50)
B GENERAL REVISION 03-11-23

GB (30x50)

GB (30x50)
D.K. M.K. L.S.

GB (30x50)
T.O.C.

GB (30x50)
200 -0.50

GB (30x50)
T.O.C.
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.
Inverted GB (30x50)
0000
1215

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

GB (30x50)

OWNER

Inverted GB (30x50)

GB (30x50)
GB (30x50)
0000 +0.05
T.O.P. of Trench
4000

GB (30x50)
17385

+0.50
T.O.P. of Pad
0000 +0.05
1085

T.O.P. of Trench

CONSULTANT
GB (30x50)
+0.20 -0.20
0000
T.O.C.
BELOW TRANSFORMER OIL
CATCHMENT BASIN 500mm
T.O.C.
ILF CONSULTING ENGINEERING FOR
ENGINEERING CONSULTANCY
WIDTH
2915

DB (20x60)

GB (30x50)
-0.50
T.O.C.

GB (30x50)
-0.50

GB (30x50)
0000
T.O.C.
DB (20x60)

CONTRACTOR
CIVIL WORKS COMPANY
cWc

Inverted GB (30x50)
+0.20
P.O.BOX 7012, DAMMAM - 34162
4585

T.O.C. KINGDOM OF SAUDI ARABIA


-0.50
-0.50
T.O.C. T.P. 03 8572205 FAX. 03 8574733
+0.20 T.O.C.
T.O.C OF WALL
GB(30x50) GB (30x50) GB (30x50) GB (30x50)
Inverted GB(30x50)
DESIGN OFFICE
0000

200 200 200 200 P.O. Box. 126579, Abu Dhabi, U.A.E.
200 TEL: +971-2-6339940,
GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)

GB (30x50)
-1.35
T.O.C. FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

GROUND FLOOR LAYOUT- MEP RESERVATIONS DRAWING TITLE


8
0000-000 SCALE 1:50 PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 05 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 05 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000

0000 0000 0000

KEY PLAN
GB (30x50)

0000 0000 0000


GB (30x50)

0000 0000 0000

RHS 100x50x3
+6.75

SHS 100x3.2
Corrugated sheets thk=0.7mm
RHS 100x50x3 RHS 100x50x3 RHS 100x50x3 RHS 100x50x3

1600
RHS 100x50x3
+5.80 RHS 100x50x3 RHS 100x50x3

950 SHS 100x3.2

925
0000 0000 RHS 100x50x3 0000
RHS 100x50x3

NOTES:

900
RHS 100x50x3 SHS 100x3.2
5100

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

6600
0000 SLAB-ON-GRADE 0000 0000

900
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED

5650
200MMTHICK SHS 100x3.2
RHS 100x50x3 RHS 100x50x3
T.O.C.+0.072 HEA 180

10
HEA 180 3. REFER TO GENERAL NOTES GENERAL DETAILS

925
RHS 100x50x3 SHS 100x3.2 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
RHS 100x50x3 RHS 100x50x3 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
GB (30x50)

0000 0000 0000


6. COVER (mm):

550
1850 1205 1195 1205 550
6700 Base plate thk=15mm Anchors 20/400

RC foundation 1200x1200x700
COLUMNS=40 , SLAB & SLAB BEAMS = 25
ALL STRUCTURES IN CONTACT WITH SOIL=75
ALL STRUCTURES IN CONTACT WITH WATER=50
Section a-a
Scale 1/50

0000 0000 0000

ABBREVIATIONS AND LEGEND -


ABBREVIATIONS:
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:

9 SLAB ON GRADE OF STEEL SHELTER AT LEVEL +0.072 10 INCLINED ROOF FLOOR OF STEEL SHELTER 11 CLADDING LAYOUT OF STEEL SHELTER Reinforced Concrete
0000-000 SCALE 1:50 0000-000 SCALE 1:50 0000-000 SCALE 1:50
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

ENGINEER'S STAMP CONTRACTOR'S STAMP

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100 H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

+6.28
950
150 T.O.P. F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
+6.28 950 150 1000 4000
T.O.P.
E GENERAL REVISION 15-01-24 D.K. M.K. L.S.
400

400

650

650

650
150

500
600

200 400
0000 DB (20x60) DB (30x60) DB (30x60)
D

820
GENERAL REVISION 07-12-23 D.K. M.K. L.S.
DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00
CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) 650
600

600

600

600

600

600

600

600

600

600

600

600
300

300

1135
at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 20mm E.J.

DB (30x60)
300 500 C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

450
DB (30x60) at +4.00
700 700 700 700 700 700 700 700 700 700 700 700 700
3585

DB (30x60)
DB (30x60) at +4.00

DB (30x60)
DB (30x60)

DB (30x60)
1215 500 B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
+6.28

450
T.O.P.

465
315

315
415
1100 1100 A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

150
0000 300
3830 300 1275 500 550 1250
1215

900

900
835
REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

300

500

500
DB (30x60) DB (30x60) DB (30x60)

785
250 300
975 565 300

DB (30x60) at +4.00
20mm E.J. OWNER

2225

2225
DB (30x60) at +4.00

PAD

250
0000

DB (30x60)
775
430MMTHICK

DB (30x60)
T.O.C.+5.43
1100 1100
4000

DB (30x60)
525

DB (30x60)
DB (30x60)
900

900
835
17385

775
3830 PAD
430MMTHICK
T.O.C.+5.43

300

2460
DB (30x60) 695
0000

300
1085

1100 1100

200

200

1340
1455

1455

1455
DB (30x60) at +4.00
DB (30x60) at +4.00

DB (30x60) DB (30x60) CONSULTANT

900

900
3830 835
655 300

DB (30x60)
ILF CONSULTING ENGINEERING FOR

1080

1080

1080
0000

900 1015

1015
2915

1100 1100
300
300
995 1080 1185 1080 1185 1080 ENGINEERING CONSULTANCY

900
835

300

DB (30x60)

DB (30x60)

DB (30x60)
DB (30x60)

DB (30x60)
0000

795
300
100 SOLID SLAB
200MM THICK CONTRACTOR

DB (30x60) at +4.00
DB (30x60) at +4.00

700
T.O.C.+5.00
300 300
CIVIL WORKS COMPANY

DB (30x60)
300 300

cWc
2001100 1100
P.O.BOX 7012, DAMMAM - 34162
4585

KINGDOM OF SAUDI ARABIA

900

900
3830 835 PAD
700 700 700 700 700 700 700 700 700 700 700 700
700 430MMTHICK
740 T.O.C.+5.43 300 T.P. 03 8572205 FAX. 03 8574733
CR(70x100/50) 250
300

CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50)
600

600

600

600

600

600

600

600

600

600

600

600

200
1480

1480
at +4.938 at +4.938 at +5.00 at +4.938 at +5.00 at +4.938 at +4.938 at +4.938 at +5.00 at +4.938 at +4.938 at +4.938 at +4.938 DB (20x60) DB (20x60)
300

DB (20x60)

655
DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00 DB (30x60) at +4.00
600

500

250
400

1050
2460
150

250

600
0000
DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
400

+6.28
T.O.P.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 06 OF 09
12 ROOF FLOOR AT LEVEL +5.00
0000-000 SCALE 1:50
DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 06 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

KEY PLAN

600 600

600

600
0000

CR(60x100/50) CR(60x100/50)
at +5.672 at +5.672
3585

0000
1215

600 600

500

500
600

600
CR(60x100/50) CR(60x100/50)
at +5.672 at +5.672
0000
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
4000

2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED


17385

3. REFER TO GENERAL NOTES GENERAL DETAILS


4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
0000
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
600 600
1085

6. COVER (mm):

300

300
600

600
COLUMNS=40 , SLAB & SLAB BEAMS = 25
0000
CR(60x100/50) CR(60x100/50) ALL STRUCTURES IN CONTACT WITH SOIL=75
at +5.672 at +5.672
ALL STRUCTURES IN CONTACT WITH WATER=50
2915

0000

ABBREVIATIONS AND LEGEND -


4585

ABBREVIATIONS:
600 600 T.O.C: Top of Concrete

300
B.O.C: Bottom of Conrete

600

600
DB (30x60) at +6.40 T.O.B: Top of Beam
CR(60x100/50) CR(60x100/50)
at +5.672 at +5.672
B.O.B: Bottom of Beam

400
0000

P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047


13 LAYOUT AT LEVEL +6.55
0000-000 SCALE 1:50
ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 07 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 07 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
p

90150 m

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100 p

+9.78
T.O.P.
650 950

340

340

150
500
650

500 150
+9.78
1300 1300 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100
150

T.O.P.

KEY PLAN
650

650

650
1825 1825 1850 1850 1850 1850 1850 1850 1850 1600 1850 1765 4025 1755

750

750

750

750
750

750

750

750

750

750

750

750
400

400

300
0000 DB (30x60)
500

280

280

280

280

280

280

280

280

280

280
280

280

285

285
DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70)

1500
1470 1470 1470 1470 1470 300 300 1470

DB (30x70)
150 500 300
3585

SOLID SLAB

1000
DB (30x70)

PAD
200MMTHICK

1265

1265

1265

1265

1265

1265
PAD 300 PAD 300 430MMTHICK 300 PAD 300 PAD
430MMTHICK
T.O.C.+8.93
430MMTHICK
T.O.C.+8.93
T.O.C.+8.93 430MMTHICK
T.O.C.+8.93
PAD 430MMTHICK
T.O.C.+8.50 650

DB (30x60)
430MMTHICK
1780 600 1765 600 1765 600 1765 600 1515 T.O.C.+8.93
T.O.C.+8.93

1470 1470 1470 1470 1470 1680

DB (30x60)
1085
1470
300

650
300 300 300 500
300
1265

1265

1265

1265

1265
1265
PAD
595

595

595

595

595

595
0000 430MMTHICK PAD 600 PAD
600 PAD
600
PAD
430MMTHICK
PAD
430MMTHICK 150
600
1215

T.O.C.+8.93 430MMTHICK 430MMTHICK 430MMTHICK


T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93
T.O.C.+8.93
300

300

300

300

300

300

300

300

300
150

150

150

150

150

150

150

150

150

150

150
1790 1765 1765 1765 1765 1680
DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70)
310

310

310

310

310
245
DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (40x70)

DB(60x150)

DB(60x150)

400
PAD

DB (30x70)
885 150 500 300 430MMTHICK
300 500 150
DB (30x70)

0000 T.O.C.+8.93
SOLID SLAB
200MMTHICK

DB (30x60)
4000

+9.78 +9.78
T.O.P. T.O.P.
T.O.C.+8.50 +9.78 1430 1815 1100 1815

DB (30x60)
2135
2135
T.O.P.
17385

DB(60x150)

DB(60x150)

DB(60x150)

DB(60x150)

DB(60x150)

DB(60x150)

DB(60x150)

DB(60x150)

DB(60x150)
+9.78
T.O.P.

NOTES:
300

300

300

300

300

300

300

300

300

300

300
900
150

150

150

150

150

150

150

150

150

150

150

150
710
DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70)
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
0000
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
1085

DB (30x70)
3. REFER TO GENERAL NOTES GENERAL DETAILS
DB (30x70)

DB (40x70)
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa

1000

200
400
0000
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
2915

1000
DB(60x150)
6. COVER (mm):

DB(60x150)
85
COLUMNS=40 , SLAB & SLAB BEAMS = 25

1095
300

300

300

300

300

300

300

300

300

300
150

150

150

150

150

150

150

150

150

150

150
650 950
DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) ALL STRUCTURES IN CONTACT WITH SOIL=75
ALL STRUCTURES IN CONTACT WITH WATER=50

DB (30x60)
DB (30x60)
0000

700 795

1095
255

255

255

255

255

255
200
200
2315 2610 1925 2610 1540 2610 1150 2610 1260 2610 1050 2610
DB (30x70)

PAD PAD PAD PAD PAD


430MMTHICK 430MMTHICK 430MMTHICK 430MMTHICK 430MMTHICK
PAD

400
T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93
430MMTHICK

3630

3630

3630

3630

3630

3630
T.O.C.+8.93
4585

ABBREVIATIONS AND LEGEND -

400
400

400
DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (30x70) DB (40x70)

400

500
ABBREVIATIONS:
150 500

150 500
650

650

650

650
0000
T.O.C: Top of Concrete
650 950 650 B.O.C: Bottom of Conrete

150
L
+9.78
T.O.P. 650
+9.78 T.O.B: Top of Beam
T.O.P.
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

14 ROOF FLOOR LAYOUT AT LEVEL +8.50 Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047


0000-000 SCALE 1:50
ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 08 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 08 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

KEY PLAN

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150
5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 7800 7200 5600 10100
150
1470 1470 1470 1470 1470 1470 1470 1470 1470 1470 1470 1470 1815 1815
430

430

430

430

430

430

430

430
+8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93
1480

1480
T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C.

200
600

600
+8.5 +8.5

430

430

430

430

430

430
+8.50 +8.5
T.O.C. T.O.C. T.O.C. T.O.C.

650
700

700
200
650
1500

1500

1500

1500

1500

1500

1500

1500

1500

1500

1500
300 300 300
300

600 600 600 600 600 600 600 600 600 600 600
KONECRANES 10t

+5.672
T.O.C.

600

600

600

600

600
500
+5.0 +5.00
CRANE CAPACITY 10.00 TON +5.00
T.O.C. T.O.C. T.O.C.

1000
NOTES:

200
CRANE CAPACITY 6.00 TON

600
300 300 300 300 300 300
700 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
300 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
600

700 20mm E.J. 3. REFER TO GENERAL NOTES GENERAL DETAILS


700
600 600 600 600 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
+1.15
T.O.C. 250 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
250
350 350
2565 200 200 2754 200 200
500 6. COVER (mm):
58750 600 200 200
1250 3680 1250
300 150 150 +0.5
T.O.C.
600 COLUMNS=40 , SLAB & SLAB BEAMS = 25
+0.15
+0.2 300 +0.2 300 +0.2 +0.15
P.F.L. T.O.C. T.O.C. T.O.C.
+0.05
T.O.C.
+0.05
T.O.C.
+0.05
T.O.C.
+0.20
T.O.C. P.F.L.
ALL STRUCTURES IN CONTACT WITH SOIL=75

700

700
70
500

200

200
200

500

200
ALL STRUCTURES IN CONTACT WITH WATER=50

150
-0.50 -0.50 -0.50

150
500

500

150
T.O.C. T.O.C. T.O.C.

500

500
-1.0 -1.0 -1.0
T.O.C. T.O.C. T.O.C.

500
9750 2600 3400 3400
INTERNAL WATERSTOP
TYP. 4500 4500 4500 4500 4500 4500 4500 4500 700
1000 -2.7
T.O.C.
-2.7
T.O.C.
-2.7
T.O.C.
-2.7
T.O.C.
-2.7
T.O.C.
-2.7
T.O.C.
-2.7
T.O.C.
-2.7
T.O.C. 100mm BLINDING CONCRETE
CONSTRUCTION
JOINT
FULL TANKING MEMBRANE
900

900

900

900

900

900
900

900
4125

950

500
495 -3.6 1000
-3.6
T.O.C.
-3.6
T.O.C. T.O.C.
ABBREVIATIONS AND LEGEND -
350

350

350

350

350

350

350

350
350

350

350

350

350
350

350
350

250 250 250 250 250 250 250 250 250 250 250 250 250 250 250
250 -4.55
500

3200 T.O.C.
3200
ABBREVIATIONS:
INSULATION ANTIVIBRATION 100mm BLINDING CONCRETE 100mm BLINDING CONCRETE 100mm BLINDING CONCRETE 50mm BLINDING CONCRETE 50mm BLINDING CONCRETE
100mm BLINDING CONCRETE T.O.C: Top of Concrete
FULL TANKING MEMBRANE
(THICKNESS AS PER MANUFACTURER)

FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level

LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
1 SECTION THROUGH X-DIRECTION
0000-000 SCALE 1:100
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.


0000 0000 0000 0000 0000 0000 0000
0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

17385 G GENERAL REVISION 15-03-24 D.K. M.K. L.S.


17385 17385
4585 2915 1085 4000 1215 3585 4585 2915 1085 4000 1215 3585 4585 2915 1085 4000 1215 3585
150 150 F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
1265
T12@150
430

+8.93
1480
1480

+8.5 +8.5
T.O.C.
+8.5 +8.5 +8.50 E GENERAL REVISION 15-01-24 D.K. M.K. L.S.
T.O.C. T.O.C. T.O.C. T.O.C. T.O.C.
700
700

650 DB6 (300x700)


200

650 D GENERAL REVISION 07-12-23 D.K. M.K. L.S.


1500

DB (600x1500)
3535 3300 3300 3790
6.55 C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

1500
T.O.C.
700 700 700 700 700
KONECRANES 6t B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
+5.0
+5.00
T.O.C.
T.O.C.
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.
1000

500

+4.00
+4.00
T.O.C.
T.O.C.
REV. DESCRIPTION DATE PREPARED CHECKED APPROVED
DB1 (300x600)
600
600

600

600

600

OWNER
12100

12100
11900

700
700
350 +1.15
+1.15
T.O.C.
350 T.O.C.
100 700
1PVC ducts Ø50mm ( 1 for control)
350 @ -3.75
+0.15
+0.15 +0.15
note (under toc with 15 cm) P.F.L.
+0.15 +0.15 +0.15
P.F.L. P.F.L. P.F.L.
P.F.L. P.F.L.
700 700

2485 2485 2525


2PVC ducts Ø50mm (1for power, 1 2525 700
4750

1PVC ducts Ø50mm 700


(1 for control) @-3.8 for control) @ -3.75 CONSULTANT
note (under toc with 20 cm) note (under toc with 15 cm)

1500
INTERNAL WATERSTOP
TYP.
-2.7
T.O.C.
INTERNAL WATERSTOP
TYP. -2.7 ILF CONSULTING ENGINEERING FOR
1590

1585

T.O.C.

400

395
400

400

1000 2155 1000 1800


CONSTRUCTION JOINT
1000 CONSTRUCTION JOINT
ENGINEERING CONSULTANCY

900
900

-3.60 -3.60 -3.60 -3.6 750 650 -3.6

400
750 T.O.C. T.O.C. T.O.C.
650 T.O.C.
-3.6
T.O.C.
750 -3.60 -3.60 -3.60 650 T.O.C.
T.O.C. T.O.C. T.O.C.
450

1000

450
450
450

250 250

950
950
250

500

-4.55 -4.55
2PVC ducts Ø50mm T.O.C. T.O.C. Protection Board

250
550 (1for power, 1 for control) @-3.8
4 PVC ducts Ø110mm (for INSULATION
550 note (under toc with 20 cm) 550 550 ANTIVIBRATION
power) @ -3.78 (THICKNESS AS PER

note (under toc with 18 cm) 4 PVC ducts Ø75mm (for


MANUFACTURER)
50mm BLINDING CONCRETE
50mm BLINDING CONCRETE
FULL TANKING MEMBRANE CONTRACTOR
INSULATION ANTIVIBRATION
(THICKNESS AS PER PVC ducts Ø50mm
(1 for control) @-3.75
earthing) @-3.75
note (under toc with 15 cm)
250 1500 250 FULL TANKING MEMBRANE

CIVIL WORKS COMPANY


cWc
MANUFACTURER)
note (under toc with 15 cm)
P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

4 FRAME AT AXIS 4 DETAILS


3 FRAME AT AXIS 1 DETAILS 000-000 1:100
SCALE 1:100
0000-000
DESIGN OFFICE
2
0000-000
SECTION THROUGH Y-DIRECTION
SCALE 1:100 P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING FORMWORK DRAWINGS
SHEET 09 OF 09

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-SH-00046 09 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100 m

RW RW RW RW RW RW RW RW RW RW RW RW C3 KEY PLAN
0000

C1 C2 C2 C2 C2 C2 C2 C2 C2 C2 C2 C2 C1 C3 C3 C3 C3
3585

RW
RW

0000
1215

C3
C2 C2 C3 C3 C3 C3
C3

0000

RW
4000

RW
17385

C3
0000
NOTES:
C1
1085

C2 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED


2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
RW C3 C3 C3 C3
3. REFER TO GENERAL NOTES GENERAL DETAILS
RW
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
2915

0000

5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275


C4
6. COVER (mm):
C3 COLUMNS=40 , SLAB & SLAB BEAMS = 25
0000
C1 ALL STRUCTURES IN CONTACT WITH SOIL=75
C2
ALL STRUCTURES IN CONTACT WITH WATER=50

RW RW
4585

C1 C2 C2 C2 C2 C2 C2 C2 C2 C2 C1 C1 C1
C3 C3
C4 C3
C3 C3
ABBREVIATIONS AND LEGEND -
0000 RW RW RW RW RW RW RW RW RW RW RW RW

ABBREVIATIONS:
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level
LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
1 COLUMNS LAYOUT FROM FOUNDATION TO SLAB-ON-GRADE
0000-000 SCALE 1:100 DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Formwork Drawings 02200016411-H3-CWC-010GEN-STR-SH-00046

ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

COLUMNS SCHEDULE C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

COLUMN MARK C1 COLUMN MARK C2 COLUMN MARK C3 COLUMN MARK C4


A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED


COLUMN SIZE 700x700 COLUMN SIZE 700x700 COLUMN SIZE 600x600 COLUMN SIZE 400x400

400 OWNER

VERTICAL BARS 20T20 VERTICAL BARS 20T25 VERTICAL BARS 20T16 VERTICAL BARS 12T14

400
TIES T10@200 TIES T10@200 TIES T10@200 TIES T10@200

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING REINFORCEMENT DRAWINGS
SHEET 01 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00047 01 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 m

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

N
1000 KEY PLAN

Add. Bot. T14@150mm, L=4m


980
E
55100
650

650
0000
3200 Pipe Penetration
3585

T14@150 TOP MESH STRIP FOUNDATION

500STRIP FOUNDATION
T16@150 BOTTOM MESH
500 mm THICK

500 mm THICK
PIPE
PENETRATION

250

250
0000
M
1215

500

900
STRIP FOUNDATION

230
PIPE SUPPORT

20

250

250
1000
500 mm THICK

0000

500
M
4000

1800

250
NOTES:
17385

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED


2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED

12410
12385

0000
3. REFER TO GENERAL NOTES GENERAL DETAILS
1085

T14@150 TOP MESH 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa


T16@150 BOTTOM MESH
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
6. COVER (mm):

250

500
0000
A 200
G G N F1 COLUMNS=40 , SLAB & SLAB BEAMS = 25

1820
2915

RAFT FOUNDATION
350 mm THICK R R ALL STRUCTURES IN CONTACT WITH SOIL=75
T14@150 TOP MESH Add. Bot. T12@150mm, L=4m
T16@150 BOTTOM MESH
T.O.C -3.60 ALL STRUCTURES IN CONTACT WITH WATER=50

500
250
0000
T12@150 TOP MESH
Add. Bot. T12@150mm, L=4m T12@150 BOTTOM MESH
D D
F F

Add. Bot. T14@150mm, L=4m


B C

250
4585

500
PIPE
PENETRATION
55050
ABBREVIATIONS AND LEGEND -

2750
850
3200

ABBREVIATIONS:
T.O.C: Top of Concrete
STRIP FOUNDATION
750

750
0000

500 mm THICK
B.O.C: Bottom of Conrete
980 T.O.B: Top of Beam

1000
B C
E B.O.B: Bottom of Beam
T14@150 TOP MESH P.F.L: Pavement Floor Level
T16@150 BOTTOM MESH
LEGEND:
Reinforced Concrete
Blinding Concrete

FOUNDATION LAYOUT OF PUMP STATION ROOM Full Tanking Membrane


2
0000-000 SCALE 1:100
+0.00 = +140.45
0000 0000 0000 0000 0000

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
7800 7200 5600 10100
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Formwork Drawings 02200016411-H3-CWC-010GEN-STR-SH-00046


F3 F3
F2 500mm 500mm
500mm
ENGINEER'S STAMP CONTRACTOR'S STAMP
0000
TB(30x50) TB(30x50) TB(30x50)

T.O.C -1.00 T.O.C -1.00 T.O.C -1.00


3585

TB(30x50)

TB(30x50)

TB(30x50)
0000 F3 F3
H GENERAL REVISION 02-05-24 D.K. M.K. L.S.
1215

F2 500mm 500mm
500mm

2600
TB(30x50) TB(30x50) TB(30x50) G GENERAL REVISION 15-03-24 D.K. M.K. L.S.
RAFT FOUNDATION
Add. Bot. T12@150mm, L=4.6m T.O.C -1.00 T.O.C -1.00 T.O.C -1.00
500 mm THICK
F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

Add. Bot. T12@150mm, L=10m


0000

T.O.C -1.00
4000

TB(30x50)
E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

TB(30x50)

TB(30x50)
17385

3270
F4
700mm HEA 180
F4
700mm HEA 180 D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
T16@150 TOP MESH TB(30x50)
T14@150 BOTTOM MESH F3 F3
0000 F2 500mm 500mm C GENERAL REVISION 23-11-23 D.K. M.K. L.S.
1085

500mm
TB(30x50) TB(30x50) TB(30x50)

TB(30x50)
2600

TB(30x50)
B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
Add. Bot. T12@150mm, L=4.6m T.O.C -1.00 T.O.C -1.00
0000
T.O.C -1.00
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.
2915

Base plate
REV.
F4
700mm HEA 180 F4
700mm HEA 180 DESCRIPTION DATE PREPARED CHECKED APPROVED
TB(30x50)

TB(30x50)

TB(30x50)
TB(30x50)
0000

OWNER
4585

F3 F3
500mm 500mm
F2
500mm
TB(30x50)
2300

TB(30x50) TB(30x50)
CONSULTANT
0000
Add. Bot. T12@150mm, L=4.6m T.O.C -1.00 T.O.C -1.00 T.O.C -1.00

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR

FOUNDATION LAYOUT OF MBD & GENERATOR ROOM


CIVIL WORKS COMPANY
2'
0000-000 SCALE 1:100 cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
Tie Beams Schedule
TEL: +971-2-6339940,
FOOTINGS SCHEDULE
FAX: +971-2-6339946,
DIMENSIONS BOTTOM STEEL TOP STEEL Size Top Reinforcement Bottom Reinforcement Stirrups ENGINEERING & MANAGEMENT
email: info@salfo.ae
TYPE
LENGTH WIDTH DEPTH LONG SHORT LONG SHORT Label Width (mm) Depth (mm) Straight Extra Over Cont. Straight Extra at Mid Span Mid Span
Skin bars Up to L/3 from Support Remarks PROJECT NAME
(mm) (mm) (mm) BARS BARS BARS BARS
Left Sup. Right Sup. Water Quality Improvement project strategic Network and
F1 1800 1800 500 T14@150 T14@150 T12@150 T12@150
Reservoirs AlHasa- project 3
F2 2600 2600 500 T14@150 T14@150 T12@150 T12@150 TB 300 500 3T16 - - 3T16 - - T10 @ 150mm T10 @ 200mm 2 Legs

DRAWING TITLE
F3 3000 3000 500 T16@100 T16@100 T12@100 T12@100
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING REINFORCEMENT DRAWINGS
F4 1200 1200 700 T16@150 T16@150 T12@150 T12@150 SHEET 02 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00047 02 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000
0000 0000

90150
p

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

T10@200 TOP MESH


T10@200 BOTTOM MESH

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)
P
200 T10@200 TOP MESH
KEY PLAN
T10@200 BOTTOM MESH
0000 -1.35 GB1 (30x50) GB4 (30x50)
GB6 (30x50) T.O.C.
+0.20 SLAB-ON-GRADE
200MMTHICK
T.O.C OF WALL -0.50 J T.O.C.+0.20

T.O.C.
3585

-0.50

GB1 (30x50)
GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)
GB1 (30x50)
T.O.C.
200 -0.50

GB1 (30x50)
T.O.C.
Inverted GB3 (30x50)
0000
H H
1215

GB3 (30x50)

Inverted GB1 (30x50)


GB5 (30x50)

GB1 (30x50)
GB1 (30x50)
0000 +0.05
BELOW TRANSFORMER OIL
CATCHMENT BASIN 500mm T.O.P. of Trench
WIDTH

GB1 (30x50)
4000
17385

NOTES:
+0.50 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
T.O.P. of Pad
+0.05
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
0000
1085

T.O.P. of Trench
3. REFER TO GENERAL NOTES GENERAL DETAILS
I
GB5 (30x50) 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
3" PIPE CONNECTED +0.20 -0.20
Q TO THE END OIL
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
CONNECTION PIT
T.O.C. T.O.C.
0000
BELOW TRANSFORMER OIL
CATCHMENT BASIN 500mm
WIDTH 6. COVER (mm):
2915

DB (20x60) I
COLUMNS=40 , SLAB & SLAB BEAMS = 25
ALL STRUCTURES IN CONTACT WITH SOIL=75

GB1 (30x50)
J
-0.50
Q T.O.C.
ALL STRUCTURES IN CONTACT WITH WATER=50

GB1 (30x50)
-0.50

GB2 (30x50)
0000
T12@125 TOP MESH T.O.C.

DB (20x60)
T12@125 BOTTOM MESH
D D
SOLID SLAB

Inverted GB2 (30x50)


200MMTHICK
T.O.C.+0.20 3" PIPE CONNECTED
TO THE END OIL
+0.20
4585

CONNECTION PIT

T.O.C.
SLAB-ON-GRADE
200MMTHICK -0.50
-0.50
+0.20
T.O.C OF WALL
T.O.C.+0.20 T.O.C. T10@200 TOP MESH
T10@200 BOTTOM MESH
T.O.C.
ABBREVIATIONS AND LEGEND -
GB2 (30x50) Inverted GB1 (30x50) GB2 (30x50) GB1 (30x50) GB4 (30x50)
ABBREVIATIONS:
0000

200 P 200 200 200 T.O.C: Top of Concrete


200 B.O.C: Bottom of Conrete

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)

GB1 (30x50)
-1.35 T.O.B: Top of Beam

S
K K T.O.C. B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level
LEGEND:
T10@200 TOP MESH T10@200 TOP MESH T10@200 TOP MESH T10@200 TOP MESH T10@200 TOP MESH Reinforced Concrete

S
T10@200 BOTTOM MESH T10@200 BOTTOM MESH T10@200 BOTTOM MESH T10@200 BOTTOM MESH T10@200 BOTTOM MESH
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45
3 GROUND FLOOR LAYOUT
0000-000 SCALE 1:100 REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Formwork Drawings 02200016411-H3-CWC-010GEN-STR-SH-00046

0000
ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

0000
F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.


GB1 (30x50)

Ground Floor Beams Schedule


D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

Size Top Reinforcement Bottom Reinforcement Stirrups


C GENERAL REVISION 23-11-23 D.K. M.K. L.S.
0000

Extra Over Cont.


Label B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
Width (mm) Depth (mm) Straight Left Sup. Right Sup. Straight Extra at Mid Span Skin bars Up to L/3 from Support Mid Span Remarks
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.
GB1 (30x50)

0000

DB1 200 600 3T14 - - 3T14 - - T10 @ 200mm T10 @ 200mm 2 Legs REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER
GB1 300 500 3T16 - - 3T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

SLAB-ON-GRADE
0000
200MMTHICK
T.O.C.+0.072
GB2 300 500 3T16 2T14 2T14 3T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

0000

GB3 300 500 3T16 - - 3T20 3T20 - T10 @ 200mm T10 @ 200mm 2 Legs
T10@200 TOP MESH CONSULTANT
T10@200 BOTTOM MESH

ILF CONSULTING ENGINEERING FOR


GB1 (30x50)

0000 GB4 300 500 3T20 3T20 3T20 3T16 2T14 - T10 @ 200mm T10 @ 200mm 2 Legs
ENGINEERING CONSULTANCY
GB5 300 500 3T16 - - 3T16 2T14 - T10 @ 200mm T10 @ 200mm 2 Legs

CONTRACTOR
GB6 300 500 3T16 - - 3T25 - - T10 @ 200mm T10 @ 200mm 2 Legs CIVIL WORKS COMPANY

0000
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

3' SLAB ON GRADE OF STEEL SHELTER AT LEVEL +0.072 PROJECT NAME


0000-000 SCALE 1:100
Water Quality Improvement project strategic Network and
Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING REINFORCEMENT DRAWINGS
SHEET 03 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00047 03 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150 p

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

+6.28
T.O.P.
+6.28
T.O.P. KEY PLAN

0000 DB9 (20x60) DB2 (30x60) DB4 (30x60)


DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00
CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50)
at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 20mm E.J.

DB1 (30x60)
DB1 (30x60) at +4.00
3585

DB1 (30x60)
DB1 (30x60) at +4.00

DB1 (30x60)
DB1 (30x60)

DB1 (30x60)
+6.28
T.O.P.

0000
1215

DB3 (30x60) DB2 (30x60) DB2 (30x60)

DB1 (30x60) at +4.00


DB1 (30x60) at +4.00

PAD

DB1 (30x60)
0000
430MMTHICK

DB1 (30x60)
T.O.C.+5.43

DB1 (30x60)
4000

DB1 (30x60)
DB1 (30x60)
17385

PAD
NOTES:

Add. Top. T12@300mm, L=5m


430MMTHICK
20mm E.J. T.O.C.+5.43
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

3675
0000 DB7 (30x60) 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
1085

Add. Top. T12@200mm, L=2m


3. REFER TO GENERAL NOTES GENERAL DETAILS
DB1 (30x60) at +4.00

DB1 (30x60) at +4.00


DB3 (30x60) DB2 (30x60)
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa

DB1 (30x60)
0000
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
20mm E.J.
6. COVER (mm):
2915

1830
COLUMNS=40 , SLAB & SLAB BEAMS = 25
ALL STRUCTURES IN CONTACT WITH SOIL=75

DB6 (30x60)

DB5 (30x60)

DB2 (30x60)
DB7 (30x60) ALL STRUCTURES IN CONTACT WITH WATER=50

DB1 (30x60)
0000
SOLID SLAB
200MM THICK
DB1 (30x60) at +4.00

DB1 (30x60) at +4.00


T.O.C.+5.00

DB1 (30x60)
T12@150 TOP MESH
4585

T12@150 BOTTOM MESH


PAD
430MMTHICK
T.O.C.+5.43
ABBREVIATIONS AND LEGEND -
CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50) CR(70x100/50)
at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938 at +4.938
DB8 (20x60) DB8 (20x60) DB8 (20x60)
DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 DB1 (30x60) at +4.00 ABBREVIATIONS:
0000 T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
+6.28 T.O.B: Top of Beam
T.O.P.
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level
LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
ROOF FLOOR AT LEVEL +5.00 Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100
4
0000-000 SCALE 1:100
Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

Formwork Drawings 02200016411-H3-CWC-010GEN-STR-SH-00046

ENGINEER'S STAMP CONTRACTOR'S STAMP

Roof Floor at +5.00 Beams Schedule

Size Top Reinforcement Bottom Reinforcement Stirrups

Extra Over Cont.


Label
H GENERAL REVISION 02-05-24 D.K. M.K. L.S.
Width (mm) Depth (mm) Straight Left Sup. Right Sup. Straight Extra at Mid Span Skin bars Up to L/3 from Support Mid Span Remarks
G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

F GENERAL REVISION 31-01-24 D.K. M.K. L.S.


DB1 300 600 3T16 - - 3T16 - - T10 @ 200mm T10 @ 200mm 2 Legs
E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

T10 @ 200mm T10 @ 200mm 2 Legs


D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
DB2 300 600 3T16 2T14 2T14 3T16 -
C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

DB3 300 600 3T16 3T14 3T14 3T16 2T14 - T10 @ 200mm T10 @ 200mm 2 Legs B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

DB4 300 600 3T20 2T20 2T20 3T20 - - T10 @ 200mm T10 @ 200mm 2 Legs REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

DB5 300 600 3T20 2T14 2T14 3T20 - - T10 @ 200mm T10 @ 200mm 2 Legs

DB6 300 600 3T20 2T20 2T20 3T20 2T14 - T10 @ 150mm T10 @ 200mm 2 Legs

CONSULTANT

DB7 300 600 3T16 3T14 3T14 3T16 2T14 - T12 @ 100mm T10 @ 200mm 2 Legs
ILF CONSULTING ENGINEERING FOR
ENGINEERING CONSULTANCY
DB8 200 600 3T16 2T14 2T14 3T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

CONTRACTOR
DB9 200 600 3T16 3T14 3T14 3T16 2T14 - T10 @200mm T10 @ 200mm 2 Legs CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING REINFORCEMENT DRAWINGS
SHEET 04 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00047 04 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

90150 p

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

KEY PLAN
0000

CR(60x100/50) CR(60x100/50)
at +5.672 at +5.672
3585

0000
1215

CR(60x100/50) CR(60x100/50)
at +5.672 at +5.672
0000
4000

NOTES:
17385

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED


2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
0000
3. REFER TO GENERAL NOTES GENERAL DETAILS
1085

4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa


CR(60x100/50) CR(60x100/50) 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
0000 at +5.672 at +5.672
6. COVER (mm):
2915

COLUMNS=40 , SLAB & SLAB BEAMS = 25


ALL STRUCTURES IN CONTACT WITH SOIL=75
ALL STRUCTURES IN CONTACT WITH WATER=50
0000
4585

ABBREVIATIONS AND LEGEND -


DB1 (30x60) at +6.40
CR(60x100/50) CR(60x100/50) ABBREVIATIONS:
at +5.672 at +5.672
0000
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level
LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

5 LAYOUT AT LEVEL +5.672


Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004
0000-000 SCALE 1:100

Formwork Drawings 02200016411-H3-CWC-010GEN-STR-SH-00046

ENGINEER'S STAMP CONTRACTOR'S STAMP


Roof Floor at +6.40 Beams Schedule

Size Top Reinforcement Bottom Reinforcement Stirrups

Extra Over Cont.


Label
Width (mm) Depth (mm) Straight Left Sup. Right Sup. Straight Extra at Mid Span Skin bars Up to L/3 from Support Mid Span Remarks H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

DB1 300 600 3T16 2T14 2T14 3T16 2T14 - T10 @ 200mm T10 @ 200mm 2 Legs F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING REINFORCEMENT DRAWINGS
SHEET 05 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00047 05 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


g
i

0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 p

90150

5300 5000 5000 5000 5000 5000 5000 5000 5000 4500 4825 4825 20 7780 7200 5600 10100

KEY PLAN
+9.78
+9.78 T.O.P.
T.O.P.

0000 DB4 (30x60)


DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70)

DB6 (30x70)
SOLID SLAB
3585

DB6 (30x70)

200MMTHICK
PAD
430MMTHICK
T.O.C.+8.93
PAD
430MMTHICK
PAD
430MMTHICK
PAD
430MMTHICK
PAD
430MMTHICK
PAD
430MMTHICK T.O.C.+8.50

DB1 (30x60)
T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93
T.O.C.+8.93 T.O.C.+8.93

DB1 (30x60)
PAD PAD PAD PAD
0000 PAD 430MMTHICK 430MMTHICK PAD
430MMTHICK 430MMTHICK 430MMTHICK 430MMTHICK
1215

T.O.C.+8.93 T.O.C.+8.93
T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93

DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB7 (30x70)

DB7 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB5 (40x70)

DB6 (30x70)
PAD
SOLID SLAB 430MMTHICK
DB6 (30x70)

0000 200MMTHICK T.O.C.+8.93


T.O.C.+8.50 NOTES:

DB1 (30x60)
4000

+9.78 +9.78
T.O.P. T.O.P.

+9.78 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED

DB1 (30x60)
DB11(60x150)

DB11(60x150)

DB11(60x150)

DB11(60x150)

DB11(60x150)

DB11(60x150)

DB11(60x150)

DB11(60x150)

DB10(60x150)
T.O.P. +9.78
DB9(60x150)

2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED

DB11(60x150)
17385

T.O.P.
T12@200TOP MESH
T12@200 BOTTOM MESH 3. REFER TO GENERAL NOTES GENERAL DETAILS
DB8 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB8 (30x70) 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
0000
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
1085

DB6 (30x70)
6. COVER (mm):
DB6 (30x70)

DB5 (40x70)
COLUMNS=40 , SLAB & SLAB BEAMS = 25
0000
ALL STRUCTURES IN CONTACT WITH SOIL=75
2915

ALL STRUCTURES IN CONTACT WITH WATER=50


T12@150 TOP MESH
T12@150 BOTTOM MESH
DB7 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB7 (30x70)

DB2 (30x60)
DB2 (30x60)
0000

DB6 (30x70)
DB6 (30x70)

ABBREVIATIONS AND LEGEND -


PAD PAD PAD PAD
430MMTHICK PAD PAD
T.O.C.+8.93 430MMTHICK 430MMTHICK 430MMTHICK 430MMTHICK 430MMTHICK
T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93 T.O.C.+8.93
4585

ABBREVIATIONS:
L
T.O.C: Top of Concrete
DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB6 (30x70) DB5 (40x70) B.O.C: Bottom of Conrete
0000
T.O.B: Top of Beam
B.O.B: Bottom of Beam
L P.F.L: Pavement Floor Level
+9.78
T.O.P. +9.78
T.O.P. LEGEND:
Reinforced Concrete
Blinding Concrete
Full Tanking Membrane
+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Structural General Notes 02200016411-H3-CWC -010GEN-STR-GE-00100

Structural General Details 02200016411-H3-CWC -010GEN-STR-GE-00004

6 ROOF FLOOR LAYOUT AT LEVEL +8.50 Formwork Drawings 02200016411-H3-CWC-010GEN-STR-SH-00046


0000-000 SCALE 1:100

ENGINEER'S STAMP CONTRACTOR'S STAMP

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

Roof Floor at Level +8.50 Beams Schedule


G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

Size Top Reinforcement Bottom Reinforcement Stirrups


F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
Extra Over Cont.
Label
Width (mm) Depth (mm) Straight Left Sup. Right Sup. Straight Extra at Mid Span Skin bars Up to L/3 from Support Mid Span Remarks E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.


DB1 300 600 3T16 - - 3T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

DB2 300 600 3T16 2T14 2T14 3T16 2T14 - T10 @ 200mm T10 @ 200mm 2 Legs
B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

DB4 300 600 3T20 3T20 3T20 3T20 2T16 - T12 @ 150mm T10 @ 200mm 2 Legs A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED


DB5 400 700 4T25 2T16 2T16 4T20 4T16 - T10 @ 150mm T10 @ 200mm 2 Legs

OWNER
DB6 300 700 4T16 - - 4T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

DB7 300 700 4T16 2T20 2T20 4T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

DB8 300 700 4T16 4T20 4T20 4T16 - - T10 @ 200mm T10 @ 200mm 2 Legs

CONSULTANT
DB9 600 1500 5T20 5T20 5T20 10T20 2T16 2T12@300 T10 @ 200mm T10 @ 200mm 2 Legs

ILF CONSULTING ENGINEERING FOR


DB10 600 1500 5T20 5T20 5T20 10T20 2T14 2T12@300 T10 @ 200mm T10 @ 200mm 2 Legs ENGINEERING CONSULTANCY

DB11 600 1500 5T20 5T20 5T20 12T20 6T20 2T12@300 T10 @200mm T10 @ 200mm 2 Legs

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING REINFORCEMENT DRAWINGS
SHEET 06 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00047 06 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


FOUNDATION SECTIONS AND R.C. DETAILS
g
i

F1 p

KEY PLAN
HEA 180 300
3T16
G.L G.L
G.L
DETAIL 1 Anchors 20/400
T10@150 STIR.
N.G.L N.G.L

500
N.G.L
-1.00 T12@100 TOP -0.80 T12@150 TOP
T12@150 TOP -3.60 -1.00 T12@150 TOP T.O.C. Tie Beam T.O.C.
T.O.C T.O.C. Tie Beam 800
-1.00
Tie Beam T.O.C.
100 300 300 100 300 300

FULL TANKING 3T16

108
200

200
-1.50
MEMBRANE

800

800
200

200
-4.10 -1.50 B.O.C.

185

185
B.O.C. B.O.C.

108
-1.50
B.O.C.
2 LAYERS BITUMEN 800

Base Plate
2 LAYERS BITUMEN BP1:400*400*15mm
2 LAYERS BITUMEN
100mm BLINDING CONCRETE
PLAN
ANCHOR BOLTS 20mm
HOLES.DIA.22mm
100mm BLINDING CONCRETE
100mm BLINDING CONCRETE T14@150 BOTTOM 100mm BLINDING CONCRETE 2 LAYERS BITUMEN
T16@100 BOTTOM
T14@150 BOTTOM 100mm BLINDING CONCRETE
FULL TANKING MEMBRANE T16@150 BOTTOM Detail 1
FULL TANKING MEMBRANE FULL TANKING MEMBRANE
FULL TANKING MEMBRANE

FOUNDATION F3 - SECTION 4 TB 1 -SECTION


1 FOUNDATION F1 - SECTION 2 FOUNDATION F2 - SECTION 3 000-000 SCALE 1:25
000-000 000-000
000-000 1:50 60 FOUNDATION F4 - SECTION
1:50 1:50 000-000 1:50

NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
3. REFER TO GENERAL NOTES GENERAL DETAILS
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
RETAINING WALL 6. COVER (mm):
COLUMNS=40 , SLAB & SLAB BEAMS = 25
2T16 E.F. ALL STRUCTURES IN CONTACT WITH SOIL=75
TYP. ALL AROUND
ALL STRUCTURES IN CONTACT WITH WATER=50

1500 2230 1000


LINK SEAL
( PRESSURE PLATES
INDUCING 2T16 E.F., E.W. AND BOLTS )
T16@150
-2.70
ABBREVIATIONS AND LEGEND -
EACH SIDE ARROUND THE T.O.C.
OPENING
TENSION BELT
ABBREVIATIONS:
50 T.O.C: Top of Concrete
-3.20 B.O.C: Bottom of Conrete

900
50

T.O.C.
T.O.B: Top of Beam
50

T16@150 T16@150
T16@150
T12@150 T12@150 T12@150 B.O.B: Bottom of Beam

400
300 50
T16@150
TYP. -3.60 178 50 200 -3.60 P.F.L: Pavement Floor Level
T.O.C. T.O.C.
INSULATION LAYERS LEGEND:

350

350
350
POLYURETHANE FOAM Reinforced Concrete
250 T12@150
250 T12@150
PIPE SLEEVE ( GALVANIZED ) Blinding Concrete

950
T12@150 T12@150
T12@150 T12@150 T12@150
250 Full Tanking Membrane
PUDDLE FLANGE T12@150
T16@150 +0.00 = +140.45
-4.55 Protection Board

250
T.O.C.
OPENING IN A REINFORCED CONCRETE WALL -SIDE VIEW WALL OPENING WITH LINK SEAL DETAIL
5 6 T12@150 T16@150
REFERENCE DRAWINGS

250
000-000 000-000 1:20
SCALE 1:25
100mm BLINDING CONCRETE
FULL TANKING MEMBRANE
T12@150
DRAWING TITLE DRAWING NUMBER
INSULATION ANTIVIBRATION
(THICKNESS AS PER MANUFACTURER) 300
TYP. Formwork Drawings 02200016411-H3-CWC -010GEN-STR-SH-00046
100mm BLINDING CONCRETE
T12@200
OPENING FOR PIPE Φ90 FULL TANKING MEMBRANE
T16@150
TOP OF PIPE AT LEVEL -0.30 SECTION A Reinforcement Drawings
7 02200016411-H3-CWC -010GEN-STR-RD-00047
000-000
T16@150 TYPICAL RAMP SECTION 1:25
T12@200

INTERNAL WATERSTOP
INTERNAL WATERSTOP
ENGINEER'S STAMP CONTRACTOR'S STAMP
1000 350 1000 350 TYP.
TYP. CONSTRUCTION JOINT
CONSTRUCTION JOINT
T14@150 T14@150 T14@150 T14@150
300 300
750 -3.60
400 TYP. TYP.
T.O.C.

LEVEL
450

350

T.O.C.
500

500
500

T14@150

T12@150 H GENERAL REVISION 02-05-24 D.K. M.K. L.S.


T14@150
100
500

T16@150 T16@150
T16@150
G GENERAL REVISION 15-03-24
1200

T16@150 T14@150 T14@150 D.K. M.K. L.S.

T14@150
+0.20 50 150 +0.20 F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
T16@150 T.O.C. T.O.C.

200

200
100mm BLINDING CONCRETE 2 LAYERS
E GENERAL REVISION 15-01-24 D.K. M.K. L.S.
FULL TANKING MEMBRANE 4 PVC DUCTS Ø 150MM T12@200
500

DB1

600

700
T12@125 T10@200
D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
550 400 550

-0.50
T.O.C.
C GENERAL REVISION 23-11-23 D.K. M.K. L.S.
200
T16@150

200
B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
100mm BLINDING CONCRETE
FULL TANKING MEMBRANE T12@200
SECTION B 20MM E.J. T16@150
8 -1.00
T.O.C.
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.
000-000 1:25

500 750 500 REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

500
OWNER

9 SECTION C

5700
000-000
T14@150
1:25
100mm BLINDING CONCRETE
FULL TANKING MEMBRANE

4550

2600
T16@150 CONSULTANT
T12@200

ILF CONSULTING ENGINEERING FOR


350
ENGINEERING CONSULTANCY
INTERNAL WATERSTOP
TYP.
CONSTRUCTION JOINT
750
T12@150 300
-3.60 TYP. T14@150 CONTRACTOR
T.O.C.
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
350

500
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733
950

350
T16@150 T14@150 T16@150

T16@150
T14@150
-4.55
850 DESIGN OFFICE
T.O.C.
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae
T16@150

100mm BLINDING CONCRETE


PROJECT NAME
FULL TANKING MEMBRANE

250 3778 Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE

10 SECTION D PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


000-000 1:25 AND GENERATORS BUILDING SECTIONS AND R.C DETAILS
SHEET 01 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00049 01 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


FOUNDATION SECTIONS AND R.C. DETAILS 212
+1.15
T.O.C.

g
i

950
1000 p

+0.20 T12@125
+0.15 TRENCH TRENCH +0.15
TRENCH T.O.C.
F.P.L F.P.L
m

DOOR CUT-OUT 75 2 LAYERS 40


4 PVC DUCTS Ø 150MM

600
p

700

700
700
DB1 T12@125

75 2 LAYERS
2 LAYERS 4 PVC DUCTS Ø 150MM
-0.50 -0.50 4 PVC DUCTS Ø 150MM -0.50
T.O.C. T.O.C. T.O.C.
200

KEY PLAN

4750

3600
NOTES:
T16@150 T16@150 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
T12@200 T12@200
350 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
4030
350 3. REFER TO GENERAL NOTES GENERAL DETAILS
INTERNAL WATERSTOP TYP. INTERNAL WATERSTOP TYP.
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
1000 CONSTRUCTION JOINT CONSTRUCTION JOINT 1000
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
T14@150 500 500 3110 500 900 500 3030 500 900 500 1260 500 900 500 835 500 500 T14@150
T14@150 T14@150
6. COVER (mm):
50 450 -3.60 T14@150 50 -3.60 T14@150 50 450 -3.60 -3.60
-3.60 -3.60
T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. COLUMNS=40 , SLAB & SLAB BEAMS = 25
ALL STRUCTURES IN CONTACT WITH SOIL=75
T14@150 T14@150 ALL STRUCTURES IN CONTACT WITH WATER=50

450
450

500
500

500
500

500
T14@150 T14@150 T14@150 T14@150 T14@150 T14@150

900

900
900
T14@150 T14@150 T14@150

500
500

T16@150 T16@150 T16@150 T16@150 T16@150 T16@150


-4.55 -4.55 -4.55
Protection Board
T.O.C. T.O.C. T.O.C.
100mm BLINDING CONCRETE
FULL TANKING MEMBRANE
Protection Board

500

500
500
T16@150 300 300 Protection Board T16@150

100mm BLINDING CONCRETE


TYP. TYP.
100mm BLINDING CONCRETE ABBREVIATIONS AND LEGEND -
FULL TANKING MEMBRANE FULL TANKING MEMBRANE

500 500 500 T16@150 T16@150 T16@150 500 500 500 ABBREVIATIONS:
300
TYP.
T.O.C: Top of Concrete
100mm BLINDING CONCRETE 100mm BLINDING CONCRETE 100mm BLINDING CONCRETE
SECTION E B.O.C: Bottom of Conrete
FULL TANKING MEMBRANE 11 FULL TANKING MEMBRANE FULL TANKING MEMBRANE
000-000 1:25 T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level
LEGEND:
Reinforced Concrete
Blinding Concrete
-2.016
T.O.C. Full Tanking Membrane
1600

+0.00 = +140.45

REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Formwork Drawings 02200016411-H3-CWC -010GEN-STR-SH-00046

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047


T12@200 2020 250 900 250

T12@200 T12@150 T12@150

-3.60 200 50 50 200 -3.60


1775

T16@150 T.O.C. T.O.C. ENGINEER'S STAMP CONTRACTOR'S STAMP


T16@150

350

350
700

500
T14@150 TOP 700
1000 TYP. TYP. T12@150 T12@150
T12@150 TOP 1000

950
T16@150 T14@150 TOP T12@150 TOP T12@150 T12@150
400

-3.60 T16@150
T14@150 T12@150
T.O.C. -3.60
-4.55 Protection Board
T.O.C. T.O.C.
350

H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

250
500

350
500

G GENERAL REVISION 15-03-24 D.K. M.K. L.S.


T12@150
300
TYP. F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
100mm BLINDING CONCRETE
3200
FULL TANKING MEMBRANE
100mm BLINDING CONCRETE T12@150 BOT. 3200 E GENERAL REVISION 15-01-24 D.K. M.K. L.S.
T16@150 BOT. T12@150 BOT.
100mm BLINDING CONCRETE
800 FULL TANKING T16@150 BOT. D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
TYP.
800 FULL TANKING
TYP. 14 SECTION R-R
000-000 SCALE 1:25
C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

12 SECTION F
000-000 1:25
13 SECTION G B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
000-000 1:25
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

1500 2245 1000 228 900 250 2051 500 850

T16@150
-2.70
1000 228 900 250 T.O.C. T16@150
T12@200

-3.20 -3.20 INTERNAL WATERSTOP CONSULTANT


900

T.O.C. T.O.C. 350


TYP.
T16@150 T16@150 CONSTRUCTION JOINT
T16@150 T16@150
T12@150 T12@150 T12@150 T14@150 ILF CONSULTING ENGINEERING FOR

400
400

T16@150 300 T12@150 T16@150 300


50 50 200 50 50 200 -3.60
178
TYP.
300 178 T.O.C. TYP. ENGINEERING CONSULTANCY
200
350
350

500
T12@150 T12@150 T12@150 T12@150 T12@150
250

T12@150
250
CONTRACTOR
950

950
950

T12@150 T12@150
T12@150
T16@150
T12@150 T12@150
T14@150 T14@150 CIVIL WORKS COMPANY

100
250 T12@150 T16@150 T16@150
T12@150 T12@150 T12@150
cWc P.O.BOX 7012, DAMMAM - 34162

1200
T16@150 T16@150
-4.55 -4.55 -4.55
Protection Board Protection Board KINGDOM OF SAUDI ARABIA
250

T.O.C. T.O.C. T.O.C. T14@150


T12@150 T16@150 T.P. 03 8572205 FAX. 03 8574733
250

250
250

100mm BLINDING CONCRETE


FULL TANKING MEMBRANE

500
T12@150 T12@150 T12@150
DESIGN OFFICE
300
TYP.
300
TYP.
300
TYP.
P.O. Box. 126579, Abu Dhabi, U.A.E.
100mm BLINDING CONCRETE 100mm BLINDING CONCRETE
100mm BLINDING CONCRETE
FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE TEL: +971-2-6339940,
T16@150 FAX: +971-2-6339946,
100mm BLINDING CONCRETE
ENGINEERING & MANAGEMENT
email: info@salfo.ae
FULL TANKING MEMBRANE

15 SECTION M 16 SECTION N
PROJECT NAME
000-000 1:25 000-000 1:25 500 850 500

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE

PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE


AND GENERATORS BUILDING SECTIONS AND R.C DETAILS
SHEET 02 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00049 02 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


GROUND FLOOR SECTIONS AND R.C. DETAILS

g
i

3T14 T14@150 124


3T16 3T16 3T16 3T20 3T16 3T16
200 250 200 2754 200 250 200 200 500 200 p

200
2T14 at sup. only 3T20 at sup. only +0.5

200

200

200
200

200
200
T.O.C.

600
m

T10@200

500

500

500
l
500

500
500
T10@200 T10@200 T10@200 T10@200 T12@200 T12@200 TYP. T12@200 T10@200
2T14 at mid. only T10@200 T10@200

150

150

150
T10@200 FULL TANKING T10@200 3T20 at mid. only FULL TANKING 2T14 at mid. only FULL TANKING FULL TANKING +0.20 TYP. TYP. TYP. +0.20 p

FULL TANKING FULL TANKING T.O.C. T.O.C.


MEMBRANE MEMBRANE MEMBRANE MEMBRANE MEMBRANE MEMBRANE
3T20 3T14

200

200
3T16 3T25
+0.05 +0.05 +0.05
3T16 3T16 3T16 200 T.O.C. T.O.C. T.O.C.
300 300 300 300 300 300
50mm BLINDING 50mm BLINDING 50mm BLINDING 50mm BLINDING 50mm BLINDING 50mm BLINDING
CONCRETE CONCRETE CONCRETE CONCRETE CONCRETE CONCRETE

GB1 19 GB3 GB4 21 GB5 22 GB6 23 DB1


17 18 GB2 20 000-000
T12@200
T12@200 T12@200 KEY PLAN
000-000 1:25 000-000 1:25
000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25 1:25

24 SECTION H
000-000 1:25

710
200 500 300 250 200 5970
705 T16@150
T14@150 3000 200 1875 200
+0.50
200 900 200 T14@150 200 250 200 T.O.C.
655 200 757 200 250 T10@200 300
50
150

300
150
T10@200 T10@200
T10@200 50 50 50 50 T10@200 T10@200 150 50 150
+0.20 150 50 50 150 +0.20 +0.20

200
+0.20 +0.20 T.O.C. T.O.C.
T.O.C. T.O.C. T.O.C.

500

500

200
T12@200 T12@200
200

200
+0.05 +0.05
T.O.C. T.O.C.

400
T12@200 T12@200

700
INTERNAL WATERSTOP
T12@200 T12@200 T14@150 -0.20
T.O.C. TYP.
NOTES:
TYP. T14@150 100mm BLINDING CONCRETE CONSTRUCTION JOINT 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
700

T12@200

200
T12@200 T12@200 300 FULL TANKING MEMBRANE
-0.50
INTERNAL WATERSTOP
TYP.
50mm BLINDING CONCRETE
TYP.
-0.50
T.O.C.
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
T.O.C. FULL TANKING MEMBRANE
CONSTRUCTION JOINT 3. REFER TO GENERAL NOTES GENERAL DETAILS

200
Protection Board
200

Protection Board
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
2 COATS OF BITUMEN PAINT
T12@200 50mm P.C.C T12@200 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
27 SECTION J
000-000 1:25 6. COVER (mm):
COLUMNS=40 , SLAB & SLAB BEAMS = 25
26 SECTION K
000-000
TYPICAL RAMP SECTION 1:25 ALL STRUCTURES IN CONTACT WITH SOIL=75
25 SECTION I ALL STRUCTURES IN CONTACT WITH WATER=50
000-000 1:25

200 1100 200


+0.05
T.O.C.

T16@150.
ABBREVIATIONS AND LEGEND -
PIPE SUPPORT DIMENSIONS
ABBREVIATIONS:
(SEE PLAN)
STEEL WIRE MESH T.O.C: Top of Concrete

1400
50mm GRAVEL B.O.C: Bottom of Conrete
SLAB ON GRADE REINF.
1000 SLAB ON GRADE T.O.B: Top of Beam
400

FOUNDATION
SLAB ON GRADE

LEVEL LEVEL B.O.B: Bottom of Beam


THICKNESS

300mm THICK

T16@150 TRANSFORMER PAD

T10@200 P.F.L: Pavement Floor Level


FOUNDATION
THICKNESS

+0.20
T.O.C.

300 20mm E.J. T12@200 T12@200 T12@200


-1.35
T.O.C. LEGEND:
T12@200
TYP.

200
-0.50
Reinforced Concrete
-0.50
T.O.C. T.O.C.

T10@200 Blinding Concrete


3" PIPE CONNECTED 100mm BLINDING CONCRETE T12@200
T12@200
100mm BLINDING CONCRETE
Full Tanking Membrane
100mm BLINDING CONCRETE TO THE END OIL FULL TANKING MEMBRANE
FOUNDATION 30 SECTION Q FULL TANKING MEMBRANE
CONNECTION PIT +0.00 = +140.45
REINF. FULL TANKING MEMBRANE 000-000 1:50
31 SECTION S
000-000 SCALE 1:25

28 TYPICAL CONCRETE PIPE SUPPORT 29 TYPICAL OIL CATCHMENT BASIN DETAIL REFERENCE DRAWINGS
000-000 SCALE 1:25 000-000 SCALE 1:25

DRAWING TITLE DRAWING NUMBER


Formwork Drawings 02200016411-H3-CWC -010GEN-STR-SH-00046

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

300 5035 200 1250 200 4215 200 1250 200 209 3244
3453
300
ENGINEER'S STAMP CONTRACTOR'S STAMP
10mm ISOLATION JOINT 10mm ISOLATION JOINT 10mm ISOLATION JOINT
50 50
T10@200 T10@200 150 50 150 T10@200 150 50 150 T10@200 T10@200

T12@200 T12@200 T12@200 T12@200

700
700

INTERNAL WATERSTOP
TYP.
CONSTRUCTION JOINT
-0.50 -0.50
T.O.C. T.O.C. H GENERAL REVISION 02-05-24 D.K. M.K. L.S.
50mm BLINDING CONCRETE

200
200

Protection Board
FULL TANKING MEMBRANE
G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

T12@200 T12@200
F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

32 SECTION P
000-000 1:25 E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED


200 1300 200
200 1000 200 200 1000 200 200 1000 200
SLAB SLAB SLAB SLAB
OWNER
REINF. REINF. REINF. REINF.
50 50
150 100 150 100 150 100 150

73 150 100 150 100 150 100 150 100 150 75


700

700

700

700
50 50
300 150 100 150 300 150 100 150 100 150 100 150
SMOKE AND FIRESTOPPING FOAM
28 100

SMOKE AND FIRESTOPPING FOAM SMOKE AND FIRESTOPPING FOAM SMOKE AND FIRESTOPPING FOAM
FOR WALL AND FLOOR PENETRATIONS
26

33

33
FOR WALL AND FLOOR PENETRATIONS FOR WALL AND FLOOR PENETRATIONS FOR WALL AND FLOOR PENETRATIONS
CONSULTANT
250

250

250

250
UPVC DUCT FOR LOW VOLTAGE ELEC. UPVC DUCT FOR LOW VOLTAGE ELEC. UPVC DUCT FOR LOW VOLTAGE ELEC. UPVC DUCT FOR LOW VOLTAGE ELEC.
SERVICE 150mm SERVICE 150mm SERVICE 150mm SERVICE 150mm ILF CONSULTING ENGINEERING FOR
100mm BLINDING CONCRETE 100mm BLINDING CONCRETE 100mm BLINDING CONCRETE 100mm BLINDING CONCRETE ENGINEERING CONSULTANCY
FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE

Detail 1 Detail 2 Detail 3 Detail 4 CONTRACTOR


CIVIL WORKS COMPANY
SLAB
REINF.
200 800 200
SLAB
REINF.
200 800 200
SLAB
REINF.
200 1350 200
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733
100 50 50 50 50 50 100
150 150 150 150 150 150
50 50 50 50 50 50 50
50 50 50 50 50 50

700
75 75 75 75 75 75 DESIGN OFFICE
700
700

50
P.O. Box. 126579, Abu Dhabi, U.A.E.

50
75 75 75 75 75 75
75

SMOKE AND FIRESTOPPING FOAM SMOKE AND FIRESTOPPING FOAM TEL: +971-2-6339940,
25

SMOKE AND FIRESTOPPING FOAM

50
FOR WALL AND FLOOR PENETRATIONS FOR WALL AND FLOOR PENETRATIONS FOR WALL AND FLOOR PENETRATIONS
FAX: +971-2-6339946,
20
50

250
250
250

UPVC DUCT FOR CONTROL CABLES 75mm UPVC DUCT FOR CONTROL CABLES 75mm UPVC DUCT FOR LOW VOLTAGE ELEC. ENGINEERING & MANAGEMENT
email: info@salfo.ae
SERVICE 150mm
100mm BLINDING CONCRETE 100mm BLINDING CONCRETE 100mm BLINDING CONCRETE
PROJECT NAME
FULL TANKING MEMBRANE FULL TANKING MEMBRANE FULL TANKING MEMBRANE
Water Quality Improvement project strategic Network and
Detail 5 Detail 6 Detail 7 Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING SECTIONS AND R.C DETAILS
SHEET 03 OF 06
33 TYPICAL ELECTRICAL RESERVATION DETAILS
000-000 SCALE 1:25
DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00049 03 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


LEVEL +5.00 SECTIONS AND R.C DETAILS LEVEL +5.672 SECTIONS AND R.C DETAILS
g
i

3T16 3T20 600


2T14 at sup. only 3T16 2T20 at sup. only 700
3T16
3T14 at sup. only
300 p

T12@150mm.
200

200

200

200
300
T12@150mm. (Vertical stirrup)
(Vertical stirrup) CRANE RAIL HE360B 350 350

600

600

600

600
600 Steel plate thk=40mm M20 Gr8.8
CRANE RAIL HE280A m

T10@200 T10@200 T10@200


l

T10@200 600 50 80 80 80 60
M20 Gr8.8
2T14 at mid. only

80 51
p

T16 Anchor Bar M20 Gr8.8 HEB 360 M20 Gr8.8

261
T16 Anchor Bar Steel plate thk=20mm
M22 Gr8.8

50 80
3T16 3T16 3T16 3T20 60 90 90 90 70 70 90 90 90 60
M22 Gr8.8

500
300 300 300 300

630 (Distribution distance


for horizontal stirrup)
41 70 75 41
500
2T16

630 (Distribution distance


HEA 280 HEA 280 HEB 360 60 80 79 131

for horizontal stirrup)

227
2T16 4T12 Steel plate thk=25mm 350
4T12
400 400
HEA 280
34 DB1 35 DB2 36 DB3 37 DB4 KEY PLAN
000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25

500
45 Lap splice detail for HEB 360

500
10T12 Closed 000-000 SCALE 1:25
10T12 Closed Horizontal stirrups(Ah)
Horizontal stirrups(Ah) 43 Lap splice detail for HEA 280 6T20(As Primary
000-000 SCALE 1:25 tension reinforcement) 1T12
3T20 3T20 3T16 1T12
2T14 at sup. only 2T20 at sup. only 3T16 2T14 at sup. only

MIN.1000
3T14 at sup. only

MIN.1000
200
200

200

200
7T20(As Primary
tension reinforcement)

600
600

600

600
T10@200 T10@150 T12@100 T10@200
2T14 at mid. only 2T14 at mid. only

3T20 3T20 3T16 3T16


300 300 300 200

NOTES:
38 DB5 39 DB6 40 DB7 45 DB8 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25 44 TYPICAL CORBEL DETAIL IN 2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
42 TYPICAL CORBEL DETAIL IN PUMP 000-000
GENERATOR ROOM 1:25
000-000 STATION ROOM 1:25 3. REFER TO GENERAL NOTES GENERAL DETAILS
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
3T16 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
3T14 at sup. only 6. COVER (mm):
3T16 COLUMNS=40 , SLAB & SLAB BEAMS = 25
200

3T14 at sup. only ALL STRUCTURES IN CONTACT WITH SOIL=75


ALL STRUCTURES IN CONTACT WITH WATER=50
600

200
T10@200
2T14 at mid. only

600
3T16 T10@200
200 2T14 at mid. only

3T16
300
41 DB8
000-000 1:25

46
000-000
DB1
1:25
ABBREVIATIONS AND LEGEND -

ABBREVIATIONS:
T.O.C: Top of Concrete
B.O.C: Bottom of Conrete
T.O.B: Top of Beam
B.O.B: Bottom of Beam
P.F.L: Pavement Floor Level
LEGEND:
Reinforced Concrete
ROOF FLOOR AT LEVEL +8.5 SECTIONS AND R.C DETAILS
Blinding Concrete
4T25 Full Tanking Membrane
3T16 3T20 2T16 at sup. only 4T16 4T16
2T14 at sup. only 3T20 at sup. only 2T20 at sup. only +0.00 = +140.45
3T16

REFERENCE DRAWINGS
200

200

200
200

200

200

DRAWING TITLE DRAWING NUMBER


700

700

700
600

600

600

T10@200 T10@200 T10@150 T10@150


T10@200 T10@200 Formwork Drawings 02200016411-H3-CWC -010GEN-STR-SH-00046
3T16 2T14 at mid. only 2T16 at mid. only 4T16 at mid. only
300 300 300 400 4T16 4T16
300 300 Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047
3T16 3T20 4T20 150
+9.78
T.O.P.

47 DB1 48 DB2 49 DB4 50 DB5


51 DB6 52 DB7
ENGINEER'S STAMP
000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25 CONTRACTOR'S STAMP
AS PER EQUIPEMENT MANUFACTURER REQUIREMENT

1280
200 FOR PAD DIMENSIONS 200
5T20 at sup. only 5T20 5T20 at sup. only 5T20 5T20 at sup. only 5T20
T12@200 T12@200
+8.93 +8.93
T10@200 T.O.P.
T14@200 T10@200 T.O.P.
200

200

200

T10@150

-
T12@150 +8.50
T.O.C.
T10@150 +8.50
T.O.C.
H GENERAL REVISION 02-05-24 D.K. M.K. L.S.

200
2T12@300 2T12@300 2T12@300

50
4T16 T10@200 T10@200 T10@200 T12@150 G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

700
4T20 at sup. only
1500

1500

1500

2T12@300 2T12@300 2T12@300


DB6 SLAB REINFORCEMENT F GENERAL REVISION 31-01-24 D.K. M.K. L.S.
200

2T12@300 2T12@300 2T12@300 INSULATION ANTIVIBRATION


(THICKNESS AS PER MANUFACTURER) E GENERAL REVISION 15-01-24 D.K. M.K. L.S.
700

300
6T20 at mid. only
2T16 at mid. only 2T14 at mid. only
T10@200 D GENERAL REVISION 07-12-23 D.K. M.K. L.S.
58 SECTION L 59 TYPICAL PAD DETAIL
000-000 1:25
000-000 1:25
4T16 300 10T20 600 10T20 600 12T20 600 TYPICAL PARAPET DETAI L C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.

53 DB8 54 DB9 55 DB10 56 DB11


000-000 1:25 000-000 1:25 000-000 1:25 000-000 1:25 A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY

CONTRACTOR
CIVIL WORKS COMPANY
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
ENGINEERING & MANAGEMENT
email: info@salfo.ae

PROJECT NAME

Water Quality Improvement project strategic Network and


Reservoirs AlHasa- project 3

DRAWING TITLE
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING SECTIONS AND R.C DETAILS
SHEET 04 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00049 04 H

SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411


0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

g
i

+8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 +8.93 m

T12@200 l

T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. T.O.C.


REFER TO TYPICAL
+8.5 REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL
p

PAD DETAIL (63) T.O.C. PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63)

T12@200 T12@200 T12@200 T12@200 T12@200 T12@200 T12@200 T12@200 T12@200

KEY PLAN

+4.938
T.O.C.

CRANE CAPACITY 6.00 TON

NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED
3. REFER TO GENERAL NOTES GENERAL DETAILS
4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
6. COVER (mm):
COLUMNS=40 , SLAB & SLAB BEAMS = 25
+1.15 ALL STRUCTURES IN CONTACT WITH SOIL=75
T.O.C.
ALL STRUCTURES IN CONTACT WITH WATER=50

+0.15
P.F.L.

T16@150 ABBREVIATIONS AND LEGEND -

T12@200 T12@300 T12@300 T12@300 T12@300 T12@300 T12@300 T12@300 ABBREVIATIONS:


T.O.C: Top of Concrete
INTERNAL WATERSTOP T16@150 T16@150 T16@150 T16@150 T16@150 T16@150 B.O.C: Bottom of Conrete
TYP. T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T.O.B: Top of Beam
B.O.B: Bottom of Beam
CONSTRUCTION P.F.L: Pavement Floor Level
JOINT
T12@150 LEGEND:
-3.6 -3.6 T16@150 T16@150 T16@150 T16@150 T16@150 T16@150 Reinforced Concrete
T.O.C. T.O.C.

T14@150 Blinding Concrete


Full Tanking Membrane
T16@150 +0.00 = +140.45
T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150 T12@150
REFERENCE DRAWINGS
T12@150 T12@150 T12@150 T12@150 T12@150
INSULATION ANTIVIBRATION
(THICKNESS AS PER MANUFACTURER)
DRAWING TITLE DRAWING NUMBER
Formwork Drawings 02200016411-H3-CWC -010GEN-STR-SH-00046

Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

0000 0000 0000 0000 0000 0000 0000

ENGINEER'S STAMP CONTRACTOR'S STAMP

+8.93 +8.93 +8.93 +8.93 +8.93


T.O.C. T.O.C. T.O.C. T.O.C. T.O.C. H GENERAL REVISION 02-05-24 D.K. M.K. L.S.
REFER TO TYPICAL REFER TO TYPICAL REFER TO TYPICAL
+8.5 REFER TO TYPICAL REFER TO TYPICAL
+8.50 +8.5
PAD DETAIL (63) PAD DETAIL (63) PAD DETAIL (63) T.O.C. PAD DETAIL (63) PAD DETAIL (63)
T.O.C. T.O.C.
G GENERAL REVISION 15-03-24 D.K. M.K. L.S.

T12@200 T12@200 T12@200 F GENERAL REVISION 31-01-24 D.K. M.K. L.S.


T12@150

E GENERAL REVISION 15-01-24 D.K. M.K. L.S.

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.

KONECRANES 10t
C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

B GENERAL REVISION 03-11-23 D.K. M.K. L.S.


+5.672
T.O.C.

A GENERAL REVISION 23-10-23 D.K. M.K. L.S.


+5.00
CRANE CAPACITY 10.00 TON +5.00
T.O.C. T.O.C.
REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

T12@150 T12@150 T12@150


OWNER

20mm E.J.

CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY
T14@150

+0.5
T.O.C.
T10@200
+0.2 +0.2 T10@200 +0.2 T10@200
+0.20
T12@200 T12@200 TYP. T12@200 T10@200
+0.20
+0.15 CONTRACTOR
T.O.C. T.O.C. T.O.C.
CIVIL WORKS COMPANY
TYP. TYP. TYP.
T.O.C. T.O.C. P.F.L.
+0.05 +0.05 +0.05
T.O.C. T.O.C. T.O.C.

cWc
T12@200 T12@200 T12@200 T12@200 T12@200 T12@200

T10@200 T10@200 T12@200


T12@200 T12@200
P.O.BOX 7012, DAMMAM - 34162
-0.50 -0.50 -0.50
T.O.C. T.O.C. T.O.C.
KINGDOM OF SAUDI ARABIA
T16@150 T12@150 T12@100 25 SECTION H T12@100
T16@150 T12@200 T12@200 T12@200 -1.0 -1.0
000-000 1:25
-1.0 T.P. 03 8572205 FAX. 03 8574733
T.O.C. T.O.C. T.O.C.

T12@300 T12@300 T12@200


DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
T16@150 T16@150 T14@150 T14@150 T16@100 T16@100
TEL: +971-2-6339940,
T12@150
FAX: +971-2-6339946,
T12@150 ENGINEERING & MANAGEMENT
email: info@salfo.ae
T12@150
-3.6
T16@150 T16@150 T.O.C. PROJECT NAME
T14@150
Water Quality Improvement project strategic Network and
-4.55
T.O.C. T16@150
Reservoirs AlHasa- project 3
T12@150 T12@150
DRAWING TITLE
T12@150 T12@150
PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
AND GENERATORS BUILDING SECTIONS AND R.C DETAILS
SHEET 05 OF 06

DRAWING NUMBER: SHEET REV

67 CROSS SECTION THROUGH "X" DIRECTION


02200016411-H3-CWC -010GEN-STR-RD-00049 05 H
000-000 1:50
SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411
0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000 0000

17385 17385
g

4585 2915 1085 4000 1215 3585 4585 2915 1085 4000 1215 3585
i

150 150 p

T12@200
T12@200 +8.93

1480
1480

4T16 Embedded in column 4T16 4T16 4T16 4T16 4T16


T.O.C.
T12@200 Lap min. 800mm T10@200mm T10@200mm T10@200mm T10@200mm +8.50
+8.5 T12@200 T12@200 +8.50 REFER TO TYPICAL
T12@200 +8.50 2500 Lap min. 800mm
T.O.C. m

T.O.C. T.O.C. PAD DETAIL (63) T.O.C. l

700
700
p

DB6 (300x700)
650 DB6 T12@200
200 DB6 T12@200 DB6
T12@200 DB6
T12@200 DB6
650

1500
3535 3300 3300 4T16
3790
6T20 E.F. 6T20 E.F.
KEY PLAN

3500
700 700 700 700

KONECRANES 6t
KONECRANES 6t

+4.938
+4.938
+5.00 CRANE CAPACITY 6 TON T.O.C.
T.O.C. T.O.C.
1000

3T16 3T16
T10@200mm T10@200mm T10@200mm T10@200mm +4.00
500

+4.00
+4.00 T.O.C.
T.O.C. T.O.C.

DB1 (300x600)

NOTES:

600
600

600

600

600
3T16 3T16 6T20 E.F. 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED

12100
6T20 E.F. 6T25 E.F.
6T25 E.F. 6T25 E.F.

11900
3. REFER TO GENERAL NOTES GENERAL DETAILS
700 4. CONCRETE F'c=35MPa, BLINDING CONCRETE F'c=11MPa
700 5. REINFORCEMENT Fy=420MPA, STEEL GRADE: S275
6. COVER (mm):
+1.15 +1.15 T10@200mm T10@200mm T10@200mm T10@200mm T10@200mm
COLUMNS=40 , SLAB & SLAB BEAMS = 25
T.O.C. T.O.C. ALL STRUCTURES IN CONTACT WITH SOIL=75
100 ALL STRUCTURES IN CONTACT WITH WATER=50
350 350
+0.15 +0.15 +0.15 +0.15
P.F.L. P.F.L. P.F.L. P.F.L.
700 700 700

ABBREVIATIONS AND LEGEND -


T16@150 T16@150
ABBREVIATIONS:
T12@200
-2.7
T12@200 T.O.C: Top of Concrete
T16@150
B.O.C: Bottom of Conrete

400

400
T.O.C.
400

1800 1800

395
INTERNAL WATERSTOP

1000 1800 TYP.


1000
T.O.B: Top of Beam
T12@300
750
900

T16@150 T16@150
CONSTRUCTION JOINT
-3.6
T14@150 TOP 650 -3.6 B.O.B: Bottom of Beam
400

750 T14@150 T14@150


-3.60 T12@150 -3.60 T12@150 -3.60
T14@150 T14@150
650 T.O.C. T14@150 TOP T.O.C. P.F.L: Pavement Floor Level
T.O.C. T.O.C. T.O.C.

T14@150 T14@150
LEGEND:

450
450

T12@150
T14@150
Reinforced Concrete
950

T12@150 T12@150 T12@150

500
MEMBRANE
T12@150
T12@150 T12@150
T14@150 -4.55
T.O.C. Protection Board T16@150 BOTTOM T16@150 BOTTOM Blinding Concrete
250

T12@150
550 INSULATION
T16@150
Full Tanking Membrane
550
T16@150
T16@150
ANTIVIBRATION T12@150
(THICKNESS AS PER
MANUFACTURER) 50mm BLINDING CONCRETE +0.00 = +140.45
50mm BLINDING CONCRETE FULL TANKING MEMBRANE

250 1500 250 FULL TANKING MEMBRANE


REFERENCE DRAWINGS
DRAWING TITLE DRAWING NUMBER
Formwork Drawings 02200016411-H3-CWC -010GEN-STR-SH-00046
65 FRAME AT AXIS 1 DETAILS
64 CROSS SECTION THROUGH "Y" DIRECTION 000-000 1:50
000-000 1:50 Reinforcement Drawings 02200016411-H3-CWC -010GEN-STR-RD-00047

0000 0000 0000 0000 0000 0000 0000


ENGINEER'S STAMP CONTRACTOR'S STAMP

17385
4585 2915 1085 4000 1215 3585

5T20 Embedded in column


5T20 5T20 5T20
6000 Lap min. 800mm
Lap min. 800mm Add. 5T20 Add. 5T20
(Column Reinforcement)
H GENERAL REVISION 02-05-24 D.K. M.K. L.S.
(Column Reinforcement)
T10@200mm T10@200mm T10@200mm +8.50 G GENERAL REVISION 15-03-24 D.K. M.K. L.S.
T.O.C.
Add. 5T20 Embedded in column F GENERAL REVISION 31-01-24 D.K. M.K. L.S.

6000
E GENERAL REVISION 15-01-24 D.K. M.K. L.S.
DB11 (600x1500)
3500

D GENERAL REVISION 07-12-23 D.K. M.K. L.S.


6T25 E.F. 6T25 E.F.
1500

Skin Reinforcement 2T12 @300 Add. 6T20 C GENERAL REVISION 23-11-23 D.K. M.K. L.S.

6T20 700
6T20
B GENERAL REVISION 03-11-23 D.K. M.K. L.S.
3500

KONECRANES 6t
A GENERAL REVISION 23-10-23 D.K. M.K. L.S.

REV. DESCRIPTION DATE PREPARED CHECKED APPROVED

OWNER

6T25 E.F.
12100

6T25 E.F.
CONSULTANT

ILF CONSULTING ENGINEERING FOR


ENGINEERING CONSULTANCY
T10@200mm T10@200mm

CONTRACTOR
+0.15 +0.15 CIVIL WORKS COMPANY
P.F.L. P.F.L.
cWc P.O.BOX 7012, DAMMAM - 34162
KINGDOM OF SAUDI ARABIA
T.P. 03 8572205 FAX. 03 8574733

700 700
DESIGN OFFICE
P.O. Box. 126579, Abu Dhabi, U.A.E.
TEL: +971-2-6339940,
FAX: +971-2-6339946,
-2.7
T.O.C.
T16@150
ENGINEERING & MANAGEMENT
email: info@salfo.ae
400

395

1800 T12@300
900

T16@150 T16@150 -3.6


400

750 T14@150 T14@150


-3.60 T12@150 T12@150 -3.60 T12@150 -3.60
T14@150 T14@150
650 T.O.C.
PROJECT NAME
T.O.C. T.O.C. T.O.C.

T14@150 T14@150
Water Quality Improvement project strategic Network and
450
450

T12@150
Reservoirs AlHasa- project 3
950

T12@150 T12@150 T12@150


T12@150
T12@150 T12@150
T14@150 -4.55 T14@150
T.O.C. Protection Board
250

T12@150
550 INSULATION
T16@150
DRAWING TITLE
550
T14@150
T16@150
ANTIVIBRATION T12@150
(THICKNESS AS PER PUMP STATION, TRANSFORMER, MEDUIM VOLTAGE
MANUFACTURER) 50mm BLINDING CONCRETE
50mm BLINDING CONCRETE FULL TANKING MEMBRANE AND GENERATORS BUILDING SECTIONS AND R.C DETAILS
250 1500 250 FULL TANKING MEMBRANE SHEET 06 OF 06

DRAWING NUMBER: SHEET REV

02200016411-H3-CWC -010GEN-STR-RD-00049 06 H

66 FRAME AT AXIS 4 DETAILS


000-000 1:50 SCALE: AS SHOWN DATE: May 2024 PROJECT NO.: 02200016411