2021 - Advanced Distribution Protection

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

DISTRIBUTION PROTECTION

Advanced Distribution Protection


Increases System Resiliency
ComEd employs an advanced distribution protection scheme to reduce momentary outages
and speed up protection.
By SCOTT WETHY, JOHN PREHN III, STEVEN WALKER and DALE PLAYER, Commonwealth Edison Co.

A
s the electric distribution system transforms into a smarter enhances the efficiency of fault identification and isolation by
network, Commonwealth Edison Co.’s distribution auto- providing greater selectivity in device operation, allowing faster
mation team has embarked on a step-change journey that clearing times for fault energy removal and driving down un-
will transform distribution operations. Engineering per- necessary momentary outages.
sonnel with specialized skill sets are advancing distribution grid
capabilities through the expansion of distribution automation Limitations And Challenges
(DA) and next-generation equipment that supports communica- Historic DA practices rely on time-based protection coordina-
tion-assisted grid protection and restoration. This advancement tion between devices. Time-based coordination requires the DA
in distribution protection philosophy is key to ComEd’s focus on recloser time curve to coordinate with the station breaker relay-
providing a premier customer experience by improving power ing time curve. Time overcurrent protection typically has the
quality and limiting momentary outages. speed needed to isolate distribution faults with minimal damage.
Because of the limitations of existing communication systems, However, the problem lies in overcurrent coordination with other
DA systems traditionally have relied on time-based coordination downstream devices, which inherently slows down protection.
between distribution reclosers and substation devices for distri- To coordinate, the station breaker relay’s time curve typically is
bution grid protection functionality. However, DA continues to slowed from the pre-distribution automation settings that allow
gain widespread acceptance by moving to a low-latency, high- the DA devices to operate faster, isolating faults downstream
speed communication network, enabling the deployment of an before the station breaker clears the whole circuit. Although this
advanced communication-assisted protection philosophy. This accomplishes device coordination, it requires a slower trip curve
28 T&D World | June 2021
1,000

100

Above avalailable fault current


Time in seconds
10

1.0 With DA

No DA

0.1

0.01
1 10 100 1,000 10,000 100,000
Current in Amperes

Station relaying phase time overcurrent comparison requirements.

at the station, which creates undesired increased fault times and


stress on system components.
To effectively realize the full potential of communication-
assisted distribution protection schemes, a couple of essential
components are required:
• Protection speed communication network that is acces-
sible to link the DA and substation devices together. Power
quality, upstream conductor slap and equipment health
from fault stress are all factors to consider when determin-
ing a clearing time for faults, which has relay, communica-
tion and breaker speed components. For power quality of
industrial loads and equipment health,
a clearing time of 10 cycles would be ideal. Considering
distribution breaker operating times typically are five
cycles, this only leaves five cycles for the relaying and
communication scheme to operate for the identified fault.
SAFETY IN NUMBERS • Common communication protocol to use for communica-
Has a NEW MEANING tion between devices. The DA devices must be capable of
communicating through the selected protocol. The IEC
Give lone workers a virtual safety network 61850 generic object-oriented substation events (GOOSE)
messaging protocol is one of the more effective solutions.
that dispatches help the moment they need
A challenge the industry faces is not all manufactured DA
it. Get live location, status, and gas alarm devices currently support IEC 61850.
notifications from workers in remote locations
to eliminate manual check-in guessing games. Advanced Protection Scheme
Fiber communication enables DA devices to deploy an advanced
protection scheme incorporating the IEC 61850 communication
Connect your team at protocol. Use of the GOOSE messaging protocol enables the
indsci.com/lone-worker vendor-agnostic, low-latency transmission of digital data between
DA devices and station protection relays. The IEC 61850 standard
is a scalable and future-proof solution for DA schemes, which is
vital for a sustainable solution. The two focus areas in developing
an advanced protection scheme that will provide a significant
improvement to the system are as follows:
• Reduction in momentary outages
DISTRIBUTION PROTECTION

latency requirement of 10 msec as the


Avoid Momentary Outage maximum allowable latency between
devices. This communication speed
Trip enables an IEC 61850 GOOSE peer-
to-peer messaging scheme to be used
for improving both protection and res-
toration efforts. The initial protection
Station DA DA DA DA tie
breaker device device device device use case entailed momentary outage
1 2 3
reduction and faster clearing times.
During a fault condition, the ex-
pected outcome from the scheme is
to isolate the faulted segment with
the closest interrupting device and
IEC 61850 protection scheme one-line diagram.
avoid operation of all upstream de-
• Ability to speed up protection set points to remove fault vices. This avoidance of upstream DA device operations is not
energy from the system faster. accomplished if all reclosers have the same overcurrent curve
settings without communication. An IEC 61850 advanced com-
Reduce Momentary Outages munication-assisted protection scheme results in an avoided
The configuration of distribution protection systems does not momentary outage for customers fed within those segments.
allow enough margin to stack multiple distribution recloser Through IEC 61850, GOOSE messages are transmitted and
time current curves, which is needed for proper coordination. received in near-real time to ensure proper coordination be-
Normally closed reclosers are programmed to operate on the tween the devices. On detection of abnormal current on the
same overcurrent set points, resulting in distribution reclosers line, the devices publish a GOOSE message onto the network
overtripping for a fault that ultimately is outside its zone of protec- to inform subscribers it experienced an overcurrent event.
tion. This creates unnecessary momentary outages for customer The scheme is set up so that only neighboring devices sub-
segments that are avoidable if these intelligent devices could scribe to the published message in the normal configuration.
communicate, in protection speed, with each other. This enables the source direction to change, but the scheme
In developing its communication network, ComEd set a remains functional. If an overcurrent condition is detected,

32 T&D World | June 2021


DISTRIBUTION PROTECTION

the device publishes a block to signal, they restrain operation of


its adjacent devices: the fast overcurrent element. This
For all devices except the configuration ensures protection
station breaker: is always enabled, independent of
• If two block signals are the communication network. For
received, then do not trip. fault-on-fault scenarios, it also en-
• If one block signal is sures an upstream DA device can
received, then trip. operate during the fault prior to
For the station breaker: the substation breaker.
• If one block signal is
received, then do not trip. Speed Up Protection
• If no block signals are The second focus area in an ad-
received, then trip. vanced protection scheme is the
For a normally open tie: ability to speed up protection.
• If the device is open at the As DA devices are installed on
time of fault, then no action the system, it results in having
is required. to slow down the protective ele-
• If the device is abnormally ments at the substation to ensure
closed: proper coordination. This is not
• And two block signals are ideal but necessary, given the ex-
received, then do not trip. isting communication constraints.
• And one block signal is With an IEC 61850 communica-
received, then trip. tion scheme, it is now possible to
The device settings are created communicate directly into the
to enable multiple overcurrent ComEd’s lab setup. substation, providing the ability
elements: one is a communication-supervised fast overcur- to speed up protection.
rent element and the other a non-supervised slow overcur- With GOOSE messages, the fast, supervised element at the
rent element. When the subscribing devices receive a block substation does not have to follow typical coordination margin

June 2021 | T&D World 33


DISTRIBUTION PROTECTION

Existing Coordination Enhanced Coordination


1,000 1,000
140 k 140 k

DA Substation DA Substation
100 100

Above avalailable fault current


Above avalailable fault current

Time in seconds
Time in seconds

10 10
3,000 amp fault clears 3,000 amp fault clears
in 1.059 seconds • 1. Relayed circuit breaker - phase in 0.45 seconds
Amps: 3028.952
Seconds: 1.059
• 1. Relayed circ
circuit
rc
cuuit br
u breaker
reake
er - phase
e
1.0 1.0 Amps: 3028
A 3028.952
9522
Seconds: 0.45
S

0.1 0.1

0.01 0.01
1 10 100 1,000 10,000 100,000 1 10 100 1,000 10,000 100,000
Current in Amperes Current in Amperes

Protection comparison of existing coordination (left) vs. enhanced coordination (right).

principles, because of the substation relay subscribing to its This results in fault energy being removed from the system
neighboring DA device. On receipt of a block message, the fast 57% faster, which reduces material failures as cable insulation,
element is restrained from operating, which results in significant transformer windings, conductors, switchgear and other related
improvement in speeding up protection on the circuit. For ex- equipment experience shorter periods of fault current, reduc-
ample, a 3000-A fault is cleared 57% faster than with the current ing the stress on that equipment. Communication between the
communication infrastructure. substation DA devices provides additional benefits, specifically
regarding advanced restoration efforts.

Next Steps
ComEd’s next steps in deploying an ad-
vanced protection scheme is to continue
implementing and increasing in-service
recloser exposure to gain additional ben-
efits. As devices are operated under fault
condition and system conditions provide
additional information, schemes will con-
tinue to be improved and incorporate
lessons learned. In parallel, ComEd will
continue to leverage the fiber network for
recloser scheme advancement beyond its
initial use cases.

SCOTT WETHY (scott.wethy@comed.com), serves on the


distribution automation team at Commonwealth Edison.

JOHN PREHN III (john.prehniii@comed.com), serves


on the distribution automation team at Commonwealth
Edison.

STEVEN WALKER (steven.walker@comed.com),


serves on the distribution automation team at
Commonwealth Edison.

DALE PLAYER (dale.player@comed.com), serves on the


distribution automation team at Commonwealth Edison.

34 T&D World | June 2021

You might also like