Professional Documents
Culture Documents
All RKV Series S Type Service Manual
All RKV Series S Type Service Manual
MODE
iAUTO-X
iA UTO-X
CS-S9RKV CU-S9RKV
NANOE-G
MODE
AUTO
COMFORT TEMP
AIR SWING
TIMER
ON SET
1 2 3
CS-S12RKV CU-S12RKV
AC RC
CS-S18RKV CU-S18RKV
i AUTO-X
CS-S24RKV CU-S24RKV
CS-S28RKV CU-S28RKV
Destination
Panama
Aruba
Dutch
Antilles
Trinidad & Tobago
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
WARNING This indication shows the possibility of causing death or serious injury.
CAUTION This indication shows the possibility of causing injury or damage to properties.
Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
WARNING
2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
Engage authorized dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause
4.
water leakage, electrical shock or fire.
5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage,
6.
fire or electrical shock.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
7.
done, the set will drop and cause injury.
For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single
8.
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
9.
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation
10. instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no
external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
11.
cause heat-up or fire at the connection point of terminal, fire or electrical shock.
When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration cycle
12.
(piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up
13.
to outdoor unit and cross over the handrail and causing accident.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
14.
telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
16.
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
17.
break and cause refrigerant gas leakage.
For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, flare
nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and
18. injury.
Thickness or copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.
It is desirable that the amount of residual oil less than 40 mg/10 m.
3
WARNING
During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration
19. piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury
etc.).
During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of refrigeration piping while
20. compressor is operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result
in explosion, injury etc.) .
After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant
21.
contacts with fire.
22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury
24. Must not use other parts except original parts describe in catalog and manual.
25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
CAUTION
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of
1.
the unit, it may cause fire.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
2.
furniture.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
3.
break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use
6. a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
CS-S9/12/18/24RKV CU-S9/12/18/24RKV
Power supply connection to the room air conditioner.
2 2
Use power supply cord 3 x 1.5 mm (1.0 ~ 1.5HP) or 3 x 2.5 mm (2.0 ~ 2.5HP) type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
7. In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1) Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0 ~ 1.5HP) or 16A (2.0HP) or 20A (2.5HP) power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with a
minimum 3.0 mm contact gap.
CS-S28RKV CU-S28RKV
Power supply connection to the room air conditioner.
2
Use power supply cord 3 x 4.0 mm type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
8. In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1) Power supply connection to the receptacle using power plug.
Use an approved 25A power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 25A circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact
gap.
Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take
9.
care of the liquid refrigerant, it may cause frostbite.
10. Installation or servicing work: It may need two people to carry out the installation or servicing work.
11. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
12. Do not sit or step on the unit, you may fall down accidentally.
4
2. Specification
Indoor CS-S9RKV CS-S12RKV
Model
Outdoor CU-S9RKV CU-S12RKV
Performance Test Condition JIS JIS
Phase, Hz Single, 60 Single, 60
Power Supply
V 220 220
Min. Mid. Max. Min. Mid. Max.
kW 0.84 2.65 3.20 0.92 3.23 4.00
Capacity BTU/h 2860 9040 10900 3140 11000 13600
kJ/h 3020 9540 11520 3310 11630 14400
Running Current A – 3.4 – – 4.1 –
Input Power W 225 695 870 260 855 1.14k
Cooling
Output Power W 40 40
QLo rpm 630 670
Lo rpm 700 740
Speed Me rpm 850 890
Hi rpm 1000 1050
SHi rpm 1120 1170
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
5
Indoor CS-S9RKV CS-S12RKV
Model
Outdoor CU-S9RKV CU-S12RKV
Control Device Capillary Tube Capillary Tube
Refrigeration 3
Refrigerant Oil cm FV50S (250) FV50S (320)
Cycle
Refrigerant Type g (oz) R410A, 820 (28.9) R410A, 690 (24.4)
Height (I/D / O/D) mm (inch) 296 (11-21/32) 511 (20-1/8) 296 (11-21/32) 542 (21-11/32)
Dimension Width (I/D / O/D) mm (inch) 870 (34-9/32) 650 (25-19/32) 870 (34-9/32) 780 (30-23/32)
Depth (I/D / O/D) mm (inch) 236 (9-5/16) 230 (9-1/16) 236 (9-5/16) 289 (11-13/32)
Weight Net (I/D / O/D) kg (lb) 9 (20) 21 (46) 9 (20) 27 (60)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 15 (49.2) 3 (9.8) ~ 15 (49.2)
Piping
I/D & O/D Height different m (ft) 5.0 (16.4) 5.0 (16.4)
Additional Gas Amount g/m (oz/ft) 15 (0.2) 15 (0.2)
Length for Additional Gas m (ft) 7.5 (24.6) 7.5 (24.6)
Inner Diameter mm 16.7 16.7
Drain Hose
Length mm 650 650
Fin Material Aluminium (Pre coated) Aluminium (Pre coated)
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
6
Indoor CS-S18RKV CS-S24RKV
Model
Outdoor CU-S18RKV CU-S24RKV
Performance Test Condition JIS JIS
Phase, Hz Single, 60 Single, 60
Power Supply
V 220 220
Min. Mid. Max. Min. Mid. Max.
kW 1.10 5.20 6.00 1.12 6.00 7.10
Capacity BTU/h 3750 17700 20500 3820 20500 24200
kJ/h 3960 18720 21600 4030 21600 25560
Running Current A – 6.4 – – 7.7 –
Input Power W 290 1.38k 1.68k 320 1.65k 2.00k
Cooling
Output Power W 40 40
QLo rpm 850 910
Lo rpm 930 1000
Speed Me rpm 1110 1220
Hi rpm 1300 1440
SHi rpm 1420 1560
Type Propeller Fan Propeller Fan
Material PP Resin PP Resin
Outdoor Fan
7
Indoor CS-S18RKV CS-S24RKV
Model
Outdoor CU-S18RKV CU-S24RKV
Height (I/D / O/D) mm (inch) 296 (11-21/32) 695 (27-3/8) 296 (11-21/32) 695 (27-3/8)
Dimension Width (I/D / O/D) mm (inch) 1070 (42-5/32) 875 (34-15/32) 1070 (42-5/32) 875 (34-15/32)
Depth (I/D / O/D) mm (inch) 241 (9-1/2) 320 (12-5/8) 241 (9-1/2) 320 (12-5/8)
Weight Net (I/D / O/D) kg (lb) 12 (26) 44 (97) 12 (26) 46 (101)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2) 6.35 (1/4) / 15.88 (5/8)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6) 3 (9.8) ~ 20 (65.6)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
8
Indoor CS-S28RKV
Model
Outdoor CU-S28RKV
Performance Test Condition JIS
Phase, Hz Single, 60
Power Supply
V 220
Min. Mid. Max.
kW 1.15 7.80 8.40
Capacity BTU/h 3920 26600 28600
kJ/h 4140 28080 30240
Running Current A – 12.6 –
Input Power W 350 2.70k 2.95k
Cooling
Output Power W 40
QLo rpm 910
Lo rpm 1000
Speed Me rpm 1270
Hi rpm 1540
SHi rpm 1600
Type Propeller Fan
Material PP Resin
Outdoor Fan
9
Indoor CS-S28RKV
Model
Outdoor CU-S28RKV
Height (I/D / O/D) mm (inch) 296 (11-21/32) 795 (31-5/16)
Dimension Width (I/D / O/D) mm (inch) 1070 (42-5/32) 875 (34-15/32)
Depth (I/D / O/D) mm (inch) 241 (9-1/2) 320 (12-5/8)
Weight Net (I/D / O/D) kg (lb) 12 (26) 57 (126)
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 15.88 (5/8)
Standard length m (ft) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 30 (98.4)
Piping
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
10
3. Location of Controls and Components
3.1 Indoor Unit
Auto OFF/ON button
Aluminium Fin • Use when remote control is misplaced or a malfunction occurs.
Air Filters Sunlight sensor and remote control receiver
Front Panel Indicator
(Green)
POWER (Green)
TIMER (Orange)
ER
POW
R
TIME
-X
i AUTO
OE-G
NON FORT
COM
i AUTO-X
AUTO
(Orange)
T
QUIE
Air outlet
AIR CONDITIONER
MODE
iAUTO-X
iA UTO-X
Remote control
display
OFF/ON
i AUTO-X OFF/ON ECONAVI
i AUTO-X operation ECONAVI operation
NANOE-G
Operation mode MODE Nanoe-G operation
AUTO
COMFORT TEMP Temperature setting
Auto Comfort operation
AIR SWING Airflow direction
Quiet operation
Fan Speed selection
QUIET FAN SPEED selection
TIMER
ON SET
1 2 3
Timer setting
OFF CANCEL
AC RC
Check
SET CHECK CLOCK RESET
Clock setting
11
4. Dimensions
4.1 Indoor Unit
4.1.1 CS-S9RKV CS-S12RKV
<Top View>
<Side View>
Air intake <Front View> <Side View>
direction
296
1-2 1-2
60.5
Air outlet
direction
15
Left piping 870 49
236
hole
AIR CONDITIONER
MODE
iAUTO-X
iA UTO-X
45.5
NANOE-G
160
MODE
AUTO
COMFORT TEMP
TIMER
ON SET
1 2 3
OFF CANCEL
AC RC
<Rear View>
Relative position between the indoor unit and the installation plate <Front View>
497.2 16.5
Installation
plate 439 432
Indoor unit
external Left Right
dimensions piping piping
264.2
Unit : mm
128 128
241.5 241.5
12
4.1.2 CS-S18RKV CS-S24RKV CS-S28RKV
<Top View>
296
61
Air outlet
direction
49
14.5
Left piping 1-2 1-2
hole 241
AIR CONDITIONER
MODE
iAUTO-X
iA UTO-X
44
44
i AUTO-X OFF/ON ECONAVI
NANOE-G
160
MODE
AUTO
COMFORT TEMP
TIMER
ON SET
1 2 3
OFF CANCEL
AC RC
<Rear View>
Relative position between the indoor unit and the installation plate <Front View>
748 16.5
Installation
plate 539 532
Indoor unit
128
external
Left Right
dimensions
264.3
piping piping
line
hole 219 hole
169
Unit : mm
128 128
241.5 241.5
13
4.2 Outdoor Unit
4.2.1 CU-S9RKV
<Top View>
18 (650)
Space necessary for 88 474 88
installation
79
100mm
134
261
293
100mm
1000mm
511
149
88
3-way valve at Gas side
(Low Pressure)
2-way valve at Liquid side
Unit : mm (High Pressure)
4.2.2 CU-S12RKV
<Top View>
Space necessary for
24.4 780 67.6
installation
34.5
100mm
1000mm
Unit : mm
14
4.2.3 CU-S18RKV CU-S24RKV
<Top View>
Space necessary for 875 70
installation
34.5 (131) 613 131
38
100mm
85
151
100mm
360.5
1000mm
<Side View>
695
75
(25)
70.4
3-way valve at Gas side
(Low Pressure)
2-way valve at Liquid side
Unit : mm (High Pressure)
4.2.4 CU-S28RKV
<Top View>
Space necessary for
installation 875 70
38
100mm
360.5
1000mm
<Side View>
64
70 75
(25)
15
5. Refrigeration Cycle Diagram
5.1 CS-S9RKV CU-S9RKV CS-S12RKV CU-S12RKV
INDOOR OUTDOOR
LIQUID
SIDE CAPILLARY TUBE STRAINER
PIPE
TEMP.
2-WAY SENSOR
VALVE
PIPE
TEMP.
SENSOR
INTAKE INTAKE
TEMP. TEMP.
SENSOR SENSOR
MUFFLER
GAS
SIDE
3-WAY
VALVE
COMPRESSOR
TEMP. SENSOR
COMPRESSOR
COOLING
16
5.2 CS-S18RKV CU-S18RKV CS-S24RKV CU-S24RKV
INDOOR OUTDOOR
LIQUID
SIDE CAPILLARY TUBE STRAINER
PIPE
TEMP.
2-WAY SENSOR
VALVE
PIPE
TEMP.
SENSOR
INTAKE INTAKE
TEMP. TEMP.
SENSOR SENSOR
GAS
SIDE
3-WAY RECEIVER
VALVE
COMPRESSOR
TEMP.
SENSOR
COMPRESSOR
COOLING
17
5.3 CS-S28RKV CU-S28RKV
INDOOR OUTDOOR
LIQUID EXPANSION
SIDE VALVE STRAINER RECEIVER
PIPE
TEMP.
2-WAY SENSOR
VALVE
PIPE
TEMP.
SENSOR
INTAKE INTAKE
TEMP. TEMP.
SENSOR SENSOR
GAS
SIDE
3-WAY
VALVE
COMPRESSOR
TEMP.
SENSOR
COMPRESSOR
COOLING
18
6.1
6. Block Diagram
RY-PWR
FUSE301
FUSE3
FUSE301
POWER SUPPLY U M RY-FM
1Ø 220V 60Hz
SC C105
SC MS
FAN
19
MOTOR
3~
M
NOISE FILTER
TEMP. FUSE 1~
CR300
C-FM
CT1
2
3
6.2
PTC REACTOR
(INDOOR UNIT) (OUTDOOR UNIT) PTC1
FUSE104
1 RY-PWR FUSE103
RY-PWR
FUSE101
FUSE301
FUSE102
CS-S12RKV CU-S12RKV
SC
POWER SUPPLY U M
RY-FM
1Ø 220V 60Hz
SC MS
3~
20
TEMP. FUSE
NOISE FILTER
FAN MOTOR
M
CR1
1~
C-FM CT102
2
3
6.3
PTC2
PTC
PTC1
1 FUSE1
RY-PWR FUSE3 FUSE2
FUSE301
SC
CR6
RY-FM
POWER SUPPLY MS
21
U M
1Ø 220V 60Hz
SC 3~
CR4
RY-C
NOISE FILTER
M
TEMP. FUSE C205
1~
NTC
FUSE1
CT400 REACTOR
SINGLE PHASE P
POWER SUPPLY L
CS-S28RKV CU-S28RKV
FUSE3 DB1
FUSE2
+
N SSR1 M Q1
1~
TH1
NTC
U
+ M
V
RY-HL
DB2
+ 3~
W
FUSE301
+ DB3
+
SC RY-C
22
U M
CR5
NOISE FILTER
CR4
SC
N
TEMP.
FUSE RY-PWR2
1
2 PTC1
3
RY-AC
PTC2
7. Wiring Connection Diagram
7.1 Indoor Unit
7.1.1 CS-S9RKV CS-S12RKV CS-S18RKV CS-S24RKV
W
1 1 HIGH
W G
CN-CLN VOLTAGE GND MINUS ION
W POWER
(GRN) BL GENERATOR
W
AUTO SW 4 4 SUPPLY CN2
(SW01) CN1 (WHT)
1
CN-RMT
(WHT)
4
TERMINAL
BOARD RY-PWR 1
BL FUSE301
1
L
CN-CNT
TO T3.15A L250V (WHT)
2 BR
P
OUTDOOR NOISE 5
UNIT 3 FILTER BR
W AC303 (WHT) CIRCUIT 1 1
TEMP. R
FUSE CN-STM1 O M UP DOWN
R AC304 (RED) (WHT) Y LOUVER MOTOR
102°C
POWER SUPPLY (3A) 5 P 5
CORD B G G301 (GRN)
1 BR 1
R
CN-STM2 O M LEFT RIGHT
SINGLE PHASE (YLW) Y LOUVER MOTOR
POWER SUPPLY
Y/G P
5 5
GROUNDING
TERMINAL COMMUNICATION BR
CIRCUIT 1 1
R UP DOWN
Y/G CN-STM3 O M LOUVER MOTOR
(BLU) Y (INNER)
EVAPORATOR 5 P 5
RECTIFICATION
CIRCUIT SUCTION TEMP. SENSOR (THERMISTOR)
FAN MOTOR 1 0
t
CN-FM (WHT) CN-TH
Y 7
B (RED) 0
t
4
W PIPING TEMP. SENSOR (THERMISTOR)
M BL 4 CN-MSENS
GR 1
4 (BLU)
CN-SENS1 (YLW)
GR W
R CN-MSENS GR CN-SENS1 3 W
3 ELECTRONIC
1 (BLU) GR
ELECTRONIC CONTROLLER 1 4 (WHT) W CONTROLLER
1 1 (ECO SENSOR)
(MAIN) ELECTRONIC
CONTROLLER 4 CN-SENS2 (YLW)
(COMPARATOR) W
1 CN-DISP (YLW) 13 3
W ELECTRONIC
CN-SENS2 W
(YLW) 1 1 CONTROLLER
WWWWWWWWWWWW (ECO SENSOR)
BLACK (BL)
1
BLUE (B)
12 CN-DISP (WHT)
ELECTRONIC CONTROLLER
BROWN (BR)
(DISPLAY & RECEIVER) REMOTE GREEN (G)
CONTROLLER
LIGHT SENSOR ORANGE (O)
PINK (P)
RED (R)
WHITE (W)/(WHT)
YELLOW/GREEN (Y/G)
YELLOW (Y)/(YLW)
GRAY (GR)
23
7.1.2 CS-S28RKV
AC306
TERMINAL (GRN) POWER BL
(BLK)
W GENERATOR
BOARD
AUTO SW 4 4 SUPPLY CN2
BL FUSE301 (SW01) CN1 (WHT)
TO
1 T3.15A L250V
OUTDOOR 2 NOISE 1 BR 1
UNIT R AC304 (RED) R
3 FILTER CN-STM1 O M UP DOWN
W AC303 (WHT) CIRCUIT (WHT) Y LOUVER MOTOR
5 P 5
TEMP. FUSE
102°C (250V 3A) G G301 (GRN)
1 BR 1
R
CN-STM2 O M LEFT RIGHT
(YLW) Y LOUVER MOTOR
5 P 5
COMMUNICATION 1 BR 1
CIRCUIT R UP DOWN
CN-STM3 O M LOUVER MOTOR
(BLU) Y (INNER)
5 P 5
RECTIFICATION
CIRCUIT SUCTION TEMP. SENSOR (THERMISTOR)
1 0
t
CN-TH
(RED) 0
t
4
PIPING TEMP. SENSOR (THERMISTOR)
CN-SENS1 (YLW)
CN-MSENS
1 W
CN-RMT CN-SENS1 3 3 ELECTRONIC
(BLU)
W
(WHT) (WHT) CONTROLLER
4 W
1 1 (ECO SENSOR)
CN-FM (WHT) ELECTRONIC
FAN MOTOR
1 GR CONTROLLER CN-SENS2 (YLW)
R 4 1 (COMPARATOR) 4 W
GR 3
CN-MSENS GR W ELECTRONIC
BL 4 CN-SENS2
M W
(BLU)
1 GR
4 (YLW) 1
W
1 CONTROLLER
(ECO SENSOR)
B
Y 7 ELECTRONIC CONTROLLER BLACK (BL)
(MAIN)
BLUE (B)
BROWN (BR)
1 CN-DISP (YLW) 13
GREEN (G)
WWWWWWWWWWWW ORANGE (O)
PINK (P)
RED (R)
12 CN-DISP (WHT) 1 WHITE (W)/(WHT)
ELECTRONIC CONTROLLER YELLOW/GREEN (Y/G)
(DISPLAY & RECEIVER) REMOTE
CONTROLLER YELLOW (Y)/(YLW)
LIGHT SENSOR
GRAY (GR)
24
7.2 Outdoor Unit
7.2.1 CU-S9RKV
TO INDOOR UNIT
YELLOW
TERMINAL 1 2 3
BOARD (BLACK) (WHITE) (RED)
RED
BLUE RED
(TRADEMARK)
1 BLACK LLJP1 (BLK) DATA COMP. TERMINAL
CN301 (WHT) WHITE LLJP2 (WHT) (RED)
3
FUSE300 LLJP4
(20A) COMMUNICATION
BLACK L300 ORANGE (ORG) CIRCUIT OUTDOOR AIR TEMP.
SENSOR (THERMISTOR)
AC-BLK NOISE FILTER ACL300 1
WHITE (BLK) (ORG) RECTIFICATION t
0
AC-WHT 4
(WHT) ACN LLJP5 PIPING TEMP.
(GRY) (GRY) SENSOR (THERMISTOR)
GREEN GREEN
FG300 GND LLJP10
(GRN) (GRN) (GRN) CN-TANK 1 t
0
25
7.2.2 CU-S12RKV
TO INDOOR UNIT YELLOW (YLW)
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR
BLUE (BLU) RED (RED)
TRADEMARK
RED COMP. TERMINAL
GRY GRY
RAT2 RAT1
FUSE104 (GRY) (GRY)
DATA (15A 250V)
(RED)
WHT
SENSOR (THERMISTOR)
1 t
0
FG1 CN-TANK 1 t
0
26
7.2.3 CU-S18RKV CU-S24RKV
TO INDOOR UNIT YELLOW (YLW)
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR
BLUE (BLU) RED (RED)
TRADEMARK
RED COMP. TERMINAL
GRY GRY
L2-1 L2-0
COM3
(RED)
WHT
SENSOR (THERMISTOR)
1 t
0
CN-TH 2 SENSOR
NOISE FILTER COMPLETE
(WHT) 3 t
0
1
FUSE1
T2.50A L250V
BLU FAN MOTOR
M RED 5 CIRCUIT
1~ YLW P
(RED) RED
CN-ACFM U
(BLU) BLU MS
(WHT) V
FAN MOTOR (YLW) YLW 3~
BLU W
N
CAPACITOR
COMPRESSOR
ELECTRONIC CONTROLLER
27
7.2.4 CU-S28RKV
(T3.15A L250V)
4 4 RECTIFICATION V
CIRCUIT (YELLOW) W YLW YLW 3~
COMMUNICATION N W
CIRCUIT 1 1
GRN
FUSE2
CN-BLK AC-BLK
(BLACK) BLK (BLACK)
NOISE FILTER RECTIFICATION SWITCHING POWER
CIRCUIT CIRCUIT SUPPLY CIRCUIT
FG1 CN-WHT WHT AC-WHT FAN MOTOR
YLW/GRN (GREEN) (WHITE) RED 1 1
(WHITE)
1 YLW M
BLU 1~
3 ORG
FAN MOTOR
5 4 4
CIRCUIT
CABINET CN-ACFM
SIDE
ELECTRONIC CONTROLLER (WHITE) BLU FM CAPACITOR
(NOISE FILTER) CN-EV CN-TANK CN-TH1
PLATE (460V. 3.5µF)
6 (WHITE) 1 (WHITE) (WHITE) 1
3 1 4
° t° t°
t
28
8. Electronic Circuit Diagram
8.1 Indoor Unit
8.1.1 CS-S9RKV CS-S12RKV CS-S18RKV CS-S24RKV
RY-PWR
BOARD
50 BL FUSE301 3 14
1
L
*CN-STM2 12V
T3.15A L250V
Resistance (kΩ)
1 TO BR 4 13 YELLOW
40 2 1
P
1
2 OUTDOOR NOISE 61 2 2 100μH
30
UNIT 3 FILTER
5 12 64
70
3
4
3 100μH
4 100μH
W AC303 (WHT) CIRCUIT 6 11
74 5 5 100μH
20 TEMP.
FUSE AC304 (RED) 7 10
102°C R LEFT RIGHT LOUVER MOTOR
GND
10 8 *CN-STM3 12V
POWER SUPPLY (3A) BLUE
CORD B G G301 (GRN) 1 1
0 103 2 2 100μH
-10 0 10 20 30 40 50 12V 110 3 3 100μH
111 4 4 100μH
Temperature (ºC) VCC
9
IC05 121 5 5 100μH
1 16
SINGLE PHASE COMMUNICATION
POWER SUPPLY CIRCUIT 2 15 UP DOWN LOUVER MOTOR (INNER)
Y/G
144 143 CN-STM1
ELECTRONIC 5V_3 ELECTRONIC 5V_3 GROUNDING
3 14
WHITE
12V
CONTROLLER CN-SENS1 CONTROLLER CN-SENS2 R47 1/2W R46 1/2W 1 1
(ECO SENSOR) TERMINAL 4 13 68 68 134 2 2 100μH
(ECO SENSOR) YELLOW YELLOW
SENSOR 1 13 1 SENSOR 2 13 1 RECTIFICATION 136 3 3 100μH
14 138 4 4 100μH
14 2 2
Y/G CIRCUIT 5 12 139 5
3 3 5 100μH
C410 C410 CN-FM (WHT)
1000p 1000p FAN MOTOR 6 11
50V 50V EVAPORATOR R 1 UP DOWN LOUVER MOTOR (OUTER)
7 10
G2 G2 GND
BL 4
M W
8
CN2
B 12V
*CN-CLN
Y 7 *F301
GREEN
CN1 (WHT)
2 135 0.5A 32V ON 4
HIGH
1
4 4 MONITOR 3 VOLTAGE -6.0kV
5 3 ALARM 2 POWER
e
c
5V 8 2 GND 1
5V_3 6 IC402 5V 1 SUPPLY
7 5V_3 ELECTRONIC CONTROLLER
(COMPARATOR) *R2
b
CN-SENS2 5
3 *R12 *R10
YELLOW VCC *Q01 *R14 GND
1
2 8 c *Q04
1
2 408 4.7k b
3 3 4
GND C404 *C23 *C24
4 413
0.1μ 5V_3 47k *C29
25V PCB401 e 5V
G2 R401
27.0k *CN-TH
G2 405 1% 5V 12V RED
169 1
SUCTION TEMP. SENSOR
R402 2
NTC
(THERMISTOR)
5V_3 170 3
10.0k
1%
4
NTC PIPING TEMP. SENSOR 1
406 *R77 (THERMISTOR)
*CN-MSENS R62 C25 R61 C27
6 IC401 BLUE *R74
7 R403 15.0k 1μ 20.0k 1μ
13.0k 409 1 215 1% 16V 1% 16V
CN-SENS1 5 1% 403 4 2 195
2 VCC
8
5V_3 402 3 3 193
1 1 401 2 4 194
*R75
2 407 1k
3 4 1
3
GND
CN-MSENS
G2 BLUE
C403
0.1μ
G2 25V
*C40 *C41
G2
5V_ G2 12V
REMOTE CONTROLLER ELECTRONIC CONTROLLER 5V
R209 (DISPLAY & RECEIVER)
IC201 47 5V F302 5V
AIR CONDITIONER 15 R90 R82
Vout 1 10k 10k L6
*CN-DISP L5
*CN-DISP
MODE Vcc 2
GND 3 YELLOW *R89
iAUTO-X
iA UTO-X (Mild/dry) 1 KB KB
16 R201 C52
GND GND Day/Night Sensor 2 147 C51
4 5 GREEN 1k GND 3 157 1000p 1000p C56 C57
LED201 12 Remote Out 4 159 50V 50V
11 12 5V 5 155 1
17 10 11 Power LED 6 2
C201 C202 R202 9 10 DE-ICE 7 3
47μ 0.01μ ORANGE 2k 8 9 Timer LED 8 4
6.3V 16V *R214 LED202 7 8 ECONAVI 9 5
6 7 Auto Comfort 10
*LED203 12V 11 165
133
i AUTO-X ECONAVI 18 *R203 5 6
*CN-CNT
OFF/ON NANOE-G 12
4 5
3 4 Powerful LED 13
R91 R92 WHITE
PCB201
186
2 3 Quite LED 14
NANOE-G 1 2
1/8W 1/8W
*LED204 1 100 100 c *Q09
MODE
c 19 *R204 CN-DISP
AUTO
TEMP YELLOW 4.7k b
COMFORT 14
12V C3 C1 10k
e *SEN201 *R227 0.1μ 0.1μ
AIR SWING *R210 *R225 *JP205 *R58 e
QUIET FAN SPEED
16V 16V 1M
232k *JP201 1% 5V
TIMER 1% 20
ON SET *R211
*LED205 *R205 *R37
1 2 3 261k *JP202 10k
OFF CANCEL 1%
21 *R206 *R54
AC RC
*R212
270
SET CHECK CLOCK RESET 357k *JP203 *LED206
1% *R226 *JP206
*R213 22 ELECTRONIC CONTROLLER
(MAIN) *C45 *C49
475k *JP204 0.1μ
*LED207 *R207
210
209
208
207
1%
GND-A
*CN-RMT
4
3
2
1
29
8.1.2 CS-S28RKV
GROUNDING Y/G
TERMINAL EVAPORATOR
AUTO SW
AC306
Sensor (Thermistor) TERMINAL (SW01) 12V
(BLK)
Characteristics BOARD VCC
9
IC03
70 BL FUSE301 1 16
CN2
B 12V
*CN-CLN
Y 7 *F301
GREEN
CN1 (WHT)
2 135 0.5A 32V ON 4
HIGH
1
4 4 MONITOR 3 VOLTAGE -6.0kV
e 5 3 ALARM 2 POWER
c
5V 8 2 GND 1
5V_3 6 IC402 5V 1 SUPPLY
7 5V_3 ELECTRONIC CONTROLLER
(COMPARATOR) *R2
b
CN-SENS2 5
3 *R12 *R10
YELLOW VCC *Q01 *R14 GND
1
2 8 c *Q04
1
2 408 4.7k b
3 3 4
GND C404 *C23 *C24
4 413
0.1μ 5V_3 47k *C29
25V PCB401 e 5V
G2 R401
27.0k *CN-TH
G2 405 1% 5V 12V RED
169 1
SUCTION TEMP. SENSOR
R402 2
NTC
(THERMISTOR)
5V_3 170 3
10.0k
1%
4
NTC PIPING TEMP. SENSOR 1
406 *R77 (THERMISTOR)
*CN-MSENS R62 C25 R61 C27
6 IC401 BLUE *R74
7 R403 15.0k 1μ 20.0k 1μ
13.0k 409 1 215 1% 16V 1% 16V
CN-SENS1 5 1% 403 4 2 195
2 VCC
8
5V_3 402 3 3 193
1 1 401 2 4 194
*R75
2 407 1k
3 4 1
3
GND
CN-MSENS
G2 BLUE
C403
0.1μ
G2 25V
*C40 *C41
G2
5V_ G2 12V
REMOTE CONTROLLER ELECTRONIC CONTROLLER 5V
R209 (DISPLAY & RECEIVER)
IC201 47 5V F302 5V
AIR CONDITIONER 15 R90 R82
Vout 1 10k 10k L6
*CN-DISP L5
*CN-DISP
MODE Vcc 2
GND 3 YELLOW *R89
iAUTO-X
iA UTO-X (Mild/dry) 1 KB KB
16 R201 C52
GND GND Day/Night Sensor 2 147 C51
4 5 GREEN 1k GND 3 157 1000p 1000p C56 C57
LED201 12 Remote Out 4 159 50V 50V
11 12 5V 5 155 1
17 10 11 Power LED 6 2
C201 C202 R202 9 10 DE-ICE 7 3
47μ 0.01μ ORANGE 2k 8 9 Timer LED 8 4
6.3V 16V *R214 LED202 7 8 ECONAVI 9 5
6 7 Auto Comfort 10
*LED203 12V 11 165
133
i AUTO-X ECONAVI 18 *R203 5 6
*CN-CNT
OFF/ON NANOE-G 12
4 5
3 4 Powerful LED 13
R91 R92 WHITE
PCB201
186
2 3 Quite LED 14
NANOE-G 1 2
1/8W 1/8W
*LED204 1 100 100 c *Q09
MODE
c 19 *R204 CN-DISP
AUTO
TEMP YELLOW 4.7k b
COMFORT 14
12V C3 C1 10k
e *SEN201 *R227 0.1μ 0.1μ
AIR SWING *R210 *R225 *JP205 *R58 e
QUIET FAN SPEED
16V 16V 1M
232k *JP201 1% 5V
TIMER 1% 20
ON SET *R211
*LED205 *R205 *R37
1 2 3 261k *JP202 10k
OFF CANCEL 1%
21 *R206 *R54
AC RC
*R212
270
SET CHECK CLOCK RESET 357k *JP203 *LED206
1% *R226 *JP206
*R213 22 ELECTRONIC CONTROLLER
(MAIN) *C45 *C49
475k *JP204 0.1μ
*LED207 *R207
210
209
208
207
1%
GND-A
*CN-RMT
4
3
2
1
30
8.2 Outdoor Unit
8.2.1 CU-S9RKV
TO INDOOR UNIT
TERMINAL 1 2 3
BOARD (BLACK) (WHITE) (RED)
RED
333
GREEN CT1 R215
WHITE R216 15.0k
FG301 15.8k 1%
(GRN) AC-WHT301 1% 334 560
(WHT) AC-WHT01
C115 C116
BLUE (WHT) 1μ 1μ
10V 10V OUTDOOR TEMP. SENSOR
FUSE301 AC-WHT302 AC-WHT02 (15kΩ 3950)
586
T3.15A L250V (BLU) (BLU) G6 1
2
G6 G6 3
1 BLU FM301 (BLU) 4
YELLOW
M 2 RED FM302 (RED) FAN MOTOR CN-TH PIPE TEMP. SENSOR
1~ 3 YLW FM303 (YLW) CIRCUIT ACL301 LLJP6 (WHT) (4.96kΩ 3800)
(YLW) (YLW) Q4
15V
FAN MOTOR P
*RY-AC U (RED) RED
U
355
15V 3 WHITE 3
D41 D44
D300 G2 G2
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
o
Temperature ( C) Temperature (oC)
31
8.2.2 CU-S12RKV
TO INDOOR UNIT
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
REACTOR
COMMUNICATION
CIRCUIT 5V
NOISE FILTER
AC-BLK CIRCUIT 1
t
0
(BLK) 3
C113 R213 CN-TANK COMP. TEMP. SENSOR
FUSE101 1μ 4.99k (WHT)
10V (50kΩ 3950)
(20A 250V) FUSE102 1%
T3.15A L250V G6 G6
5V
AC-WHT 5V
(WHT)
333
R215
R216 15.0k
FG1 15.8k 1%
GRN (GRN) 1% 334 560
C115 C116
FG2 1μ 1μ
10V 10V OUTDOOR TEMP. SENSOR
GRN (GRN) (15kΩ 3950)
586
G6 1
t
0
2
G6 G6 3
t
0
4
CN-TH PIPE TEMP. SENSOR
(WHT) (4.96kΩ 3800)
SWITCHING POWER
SUPPLY CIRCUIT
PFC RECTIFICATION
CIRCUIT FUSE103
CIRCUIT T3.15A L250V
BLU FM1 (BLU)
M RED FM2 (RED) FAN MOTOR
1~ YLW FM3 (YLW) CIRCUIT P
(RED) RED
U
(BLU) BLU MS
V
FAN MOTOR (YLW) YLW 3~
W
N
ELECTRONIC CONTROLLER
COMPRESSOR
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
32
8.2.3 CU-S18RKV CU-S24RKV
TO INDOOR UNIT
REACTOR
1 2 3 TERMINAL
(BLACK) (WHITE) (RED) BOARD
GRY GRY
L2-1 L2-0 5V
RED 90
R101 R100
COM3 15.8k 15.0k
(RED) OUTDOOR AIR TEMP.
WHT
1μ 1μ
6.3V 6.3V (15kΩ 3950)
97 1
t
0
98 2
NOISE FILTER
99 3
AC-BLK CIRCUIT 4 t
0
(BLK)
CN-TH1 PIPE TEMP. SENSOR
(THERMISTOR)
FUSE3 (4.96kΩ 3800)
(20A 250V) FUSE2 COMMUNICATION
T3.15A L250V CIRCUIT
AC-WHT
(WHT)
SWITCHING
POWER 5V
FG01 CN-TANK
SUPPLY
GRN (GRN) 1
CIRCUIT 102 3 t
0
1
FUSE1
T3.15A L250V
BLU FAN MOTOR
M RED 5 CIRCUIT
1~ YLW P
(RED) RED
CN-ACFM U
(WHT) (BLU) BLU MS
V
FAN MOTOR (YLW) YLW 3~
BLU W
CAPACITOR N
COMPRESSOR
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
o
Temperature ( C) Temperature (oC)
33
8.2.4 CU-S28RKV
POWER SUPPLY TO INDOOR UNIT
(T3.15A L250V)
1/10W RECTIFICATION V
c CN-COM CN-COM G5 (YELLOW) W YLW YLW 3~
COMMUNICATION CIRCUIT N
Q25 4.7k b (YELLOW) (YELLOW) W
CIRCUIT
0.1A 1 1
GRN 50V 10k
FUSE2
RT1N432C
e CN-BLK AC-BLK
G1 (BLACK) BLK (BLACK)
NOISE FILTER RECTIFICATION SWITCHING POWER
CIRCUIT CIRCUIT SUPPLY CIRCUIT
FG1 CN-WHT WHT AC-WHT FAN MOTOR
YLW/GRN (GREEN) (WHITE) (WHITE) RED 1 1
1 YLW M
BLU 1~
3 ORG
FAN MOTOR
5 4 4
5V CIRCUIT
KB CN-ACFM
CABINET C49
SIDE
ELECTRONIC CONTROLLER 1u
R410 (WHITE) BLU FM CAPACITOR
4.99k 5V
PLATE (NOISE FILTER) 6.3V 1/10W 1% (460V. 3.5µF)
G5 G5
R100 R101
D33 15.0k 15.8k
1/10W 1% 1/10W 1%
13V D34
D35 KB KB
C45 C46
D36 1u 1u
C84 6.3V 6.3V
G2 G5 G5
G2 G5
CN-EV CN-TANK CN-TH1
6 1 (WHITE) 3 1 (WHITE) 4 1 (WHITE)
t° t°
t°
50 50
Resistance (kΩ)
Resistance (kΩ)
40 40
1
30 30
2
20 20
10 10
0 0
-10 0 10 20 30 40 50 20 40 60 80 100 120 140
34
9. Printed Circuit Board
9.1 Indoor Unit
9.1.1 Main Printed Circuit Board
AC304 AC303
G301
RY-PWR
SW01
CN-FM
CN-RMT
CN-CNT
CN-STM1
CN-STM3
CN-STM2
CN-DISP
CN-MSENS
CN-TH
CN-CLN
35
9.1.2 Indicator Printed Circuit Board
CN-DISP
GND
36
9.1.4 Comparator Printed Circuit Board
CN-SENS1 CN-SENS2
CN-MSENS
37
9.2 Outdoor Unit
9.2.1 Main Printed Circuit Board
9.2.1.1 CU-S9RKV
POWER
TRANSISTOR
(IPM)
CURRENT CN-TH
TRANSFORMER
CN-TANK
(CT)
DATA
38
9.2.1.2 CU-S12RKV
POWER
TRANSISTOR
(IPM)
CN-TH
CN-TANK
CURRENT
TRANSFORMER
(CT)
AC-BLK
AC-WHT
DATA
39
9.2.1.3 CU-S18RKV CU-S24RKV
POWER
TRANSISTOR
(IPM)
CURRENT
TRANSFORMER
(CT)
CN-ACFM
COM3
CN-TANK
CN-TH1
AC-WHT
AC-BLK
40
9.2.1.4 CU-S28RKV
POWER
TRANSISTOR
(IPM)
CURRENT
TRANSFORMER
(CT)
AC-WHT
AC-BLK
CN-ACFM
CN-COM
CN-TANK
CN-EV
CN-TH1
41
9.2.2 Noise Filter Printed Circuit Board
9.2.2.1 CU-S9RKV
42
9.2.2.2 CU-S28RKV
CN-COM
COM3
ACL1 CN-BLK
ACN1
CN-WHT
FG1
43
10. Installation Instruction
(For CS/CU-S9/12/18/24RKV only)
or more
50 mm
should purchase ( )
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration. Installation plate 1
Recommended installation height for indoor unit (Left and right are identical)
Bend the pipe as
closely on the wall as
shall be at least 2.5 m. possible, but be careful
that it doesn’t break.
Insulation of piping connections Power supply cord ( )
10.1.2 Outdoor Unit • Carry out insulation after checking
for gas leaks and secure with
Vinyl tape (wide) ( )
vinyl tape.
If an awning is built over the unit to prevent direct Vinyl tape • Apply after carrying
out a drainage test.
sunlight or rain, be careful that heat radiation from Attaching the remote control holder to the wall
• To carry out the
drainage test,
the condenser is not obstructed. remove the air filters
Remote control holder fixing screws 6
and pour water into
There should not be any animal or plant which Remote
the heat exchanger.
Keep the spaces indicated by arrows from wall, Remote control holder 5
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air. 10
or m0 mm
or 0 mm
ore
mo 10
re
If piping length is over the [piping length for It is advisable to
avoid more than 2
Connection cable ( )
44
10.2 Indoor Unit
10.2.1 How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent it from the vibration.
Wall
Wall Wall
More than 1 More than 1
Indoor unit
More
2 screw than 2
3 4
128 mm
6
241.5 mm 241.5 mm
Measuring 5
Tape Installation plate 1
Dimension
Model
1 2 3 4 5 6
S9***, S12*** or 490 mm 82 mm 439 mm 432 mm 43 mm 95 mm
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate center to unit’s left side is 3.
From installation plate center to unit’s right side is 4.
B : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1 Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2 Drill the piping plate hole with ø70 mm hole-core drill.
o Line according to the left and right side of the installation plate. The meeting point of the extended line is
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively.
o Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to 10.2.2)
45
10.2.3 Indoor Unit Installation
• Do not turn over the unit without it’s shock absorber during pull out the piping.
It may cause intake grille damage.
• Use shock absorber during pull out the piping to protect the intake grille from damage.
pull o
ut t
h ep
pull o ipi
ut t ng
h ep
i pi
ng
Piping
Piping
PUSH PUSH
PUSH PUSH
Shock absorber
Intake grille
• If indoor power supply, excess length of power supply must arrange accordingly,
please refer “Power supply cord arrangement” before secure the indoor unit.
How to keep the cover
Cover for piping
In case of the cover is cut, keep the cover at the rear
Step-4 Insert the connection cable of chassis as shown in the illustration for future
reinstallation.
Piping
Cover for
Step-2 Install the Indoor Unit Cover for Cover for the left
Drain hose the right the bottom piping
piping piping
Step-3 Insert the connection cable Install the indoor unit Hooks at
installation
Hook the indoor unit onto the upper portion of installation plate
plate. (Engage the indoor unit with the upper edge of the
installation plate). Ensure the hooks are properly Sleeve for
Step-4 Secure the Indoor Unit seated on the installation plate by moving it in left piping hole
• If indoor power supply, excess length of power supply must arrange accordingly, and right. Piping
please refer “Power supply cord arrangement” before secure the indoor unit.
Indoor unit Drain hose
Step-4 Cut and flare the embedded piping Do not tie up power supply
• When determining the dimensions of the piping, slide the unit all the way to the cord into a bundle by band.
Insert the connection cable It may generate heat and
left on the installation plate.
cause fire.
• Refer to the section “Cutting and flaring the piping”.
Connection cable
Step-5 Install the Indoor Unit 70 Ab
o Gas side
–
80 ut piping
m
m Liquid side
piping
Step-6 Connect the piping Guide
Connection cable Drain hose
surface
To take out the unit, push the marking at the bottom unit,
Step-8 Secure the Indoor Unit and pull it slightly towards you to disengage the hooks from the unit.
46
Replace the drain hose
Rear view for left piping installation
Connection cable
Piping
More than 950 mm
Drain hose Drain hose (1.0 ~ 1.75HP) or
Drain hose Connection cable
More than 1150 mm
Drain cap (2.0 ~ 2.5HP)
Sleeve for piping hole
• How to pull the piping and drain hose out, in case • In case of left piping how to insert
of the embedded piping. the connection cable and drain hose.
Apply putty or n
tha
caulking material re m
Mo 50 m
to seal the wall 11 Connection
opening
cable
More than 700 mm
Piping
WARNING
This equipment must be properly earthed.
Note:
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.
47
10.2.4.1 Wire Stripping and Connecting Requirement
10 ± 1 mm
terminal board
5 mm
No loose strand or more
when inserted (gap between wires) ACCEPT PROHIBITED PROHIBITED
RISK OF FIRE
JOINING
OF WIRES
MAY CAUSE
WARNING OVERHEATING OR
AND FIRE.
OR OR
Improper flaring
Pipe Handle
Reamer 0 – 0.5 mm
Bar Bar
Yoke Inclined Surface Cracked Uneven
Core damaged thickness
When properly flared, the internal surface of the
Point down Red arrow mark Copper
Clamp handle flare will evenly shine and be of even thickness.
pipe
Since the flare part comes into contact with the
1. To cut 2. To remove burrs 3. To flare connections, carefully check the flare finish.
48
10.3 Outdoor Unit
10.3.1 Install the Outdoor Unit
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.
A B
C
Model A B C D
S9*** 474 mm 87 mm 18.5 mm 261 mm
S12*** 570 mm 105 mm 18.5 mm 320 mm
S18***, S24*** 613 mm 130 mm 24 mm 360.5 mm
49
10.3.3 Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND
PIPES in the following procedure.
Close
Gas side
Close
Vacuum CLOSE
pump
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
50
10.3.4 Connect the cable to the Outdoor Unit
1 Remove the control board cover from the unit
by loosening the screw. Terminal
2 Connection cable between indoor unit and Board
outdoor unit shall be approved
polychloroprene sheathed 4 × 1.5 mm2 1 2 3
(1.0 ~ 1.5HP) or 4 x 2.5 mm2 (2.0 ~ 2.5HP) Earth Wire
flexible cord, type designation 60245 IEC 57 longer than
or heavier cord. Do not use joint connection others AC
cable. Replace the wire if the existing wire wires for
(from concealed wiring, or otherwise) is too safety reason
short.
51
11. Installation Instruction
(For CS/CU-S28RKV only)
Right
There should not be any heat source or steam Rear
Left
Right Left
near the unit. bottom Rear Left bottom
or more
50 mm
A place where drainage can be easily done.
A place where noise prevention is taken into
Installation plate 1
consideration. Bushing-Sleeve ( )
Do not install the unit near the door way. Sleeve ( )
Keep the spaces indicated by arrows from wall, Remote control holder 5
mo m
10
Do not place any obstacles which may cause a
re
or 0 m
or 0 m
mo m
10
re
short circuit of the discharged air. It is advisable to
avoid more than 2 Connection cable ( )
If piping length is over the [piping length for blockage directions.
For better ventilation Liquid side piping ( )
mm
additional gas], additional refrigerant should be & multiple-outdoor
installation, please 00 ore
10 r m
Gas side piping ( )
consult authorized o
added as shown in the table. dealer/specialist.
3
Additional drain hose ( )
or 00 m Control Board cover
m m
or
e
Addi-
Min. Max. Piping
Horse Piping size Std. Max tional
Piping Piping Length
Model Power Length Eleva- Refri-
Length Length for add.
(HP) Gas Liquid (m) tion (m)
(m) (m)
gerant
gas (m) This illustration is for explanation purposes only.
(g/m)
The indoor unit will actually face a different way.
15.88 6.35
S28*** 3.0HP mm mm 5 20 3 30 30 10
(5/8") (1/4")
52
11.2 Indoor Unit
11.2.1 How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent it from the vibration.
Wall
Wall Wall
More than 1 More than 1
3 4
128 mm
6
241.5 mm 241.5 mm
Measuring 5
Tape Installation plate 1
Dimension
Model
1 2 3 4 5 6
S28*** 590 mm 82 mm 539 mm 532 mm 169 mm 219 mm
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate center to unit’s left side is 3.
From installation plate center to unit’s right side is 4.
B : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1 Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2 Drill the piping plate hole with ø70 mm hole-core drill.
o Putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively. Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
o Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to 11.2.2)
53
11.2.3 Indoor Unit Installation
• Do not turn over the unit without it’s shock absorber during pull out the piping.
It may cause intake grille damage.
• Use shock absorber during pull out the piping to protect the intake grille from damage.
pull o
ut t
h ep
pull o ipi
ut t ng
h ep
i pi
ng
Piping
Piping
PUSH PUSH
PUSH PUSH
Shock absorber
Intake grille
Cover for
Cover for the the left
Cover for
Drain bottom piping piping
the right Cover for the
hose
Step-3 Secure the Indoor Unit piping bottom piping
Sleeve for
and right. piping hole
Step-1 Replace the drain hose
Piping
54
Replace the drain hose
Rear view for left piping installation
Connection cable
Drain hose Piping
More than 1150 mm
Connection cable Drain hose
Drain hose
Drain cap
Adjust the piping
slightly downwards. Sleeve for piping hole
• How to pull the piping and drain hose out, in case of the • In case of left piping how to insert the
embedded piping. connection cable and drain hose.
Apply putty or n
tha
caulking material o re mm
M 50
to seal the wall 11 Connection
opening.
cable
More than 700 mm
Piping
72 mm
55
11.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connection cable can be connected without removing the front grille.
2 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
4 x 1.5 mm2 flexible cord, type designation 60245 IEC 57 or heavier cord.
3 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the
escapement.
4 Remove the tapes and connect the connection cable between indoor unit and outdoor unit according to the
diagram below.
Terminal
Tape Board
Earth Wire
longer than
Recommended others
Connection cable
length (mm) AC wires
Indoor & outdoor for safety
Connection cable reason
Escapement Holder
Recommended a b c d
length (mm) 35 35 35 55 Indoor & outdoor
Connection cable
Outdoor unit
WARNING
This equipment must be properly earthed.
Note:
Secure the connection cable onto the control board with the holder.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
56
11.2.4.1 Wire Stripping and Connecting Requirement
10 ± 1 mm
terminal board
5 mm
No loose strand or more
when inserted (gap between wires) ACCEPT PROHIBITED PROHIBITED
RISK OF FIRE
JOINING OF WIRES
MAY CAUSE
OR
WARNING OVERHEATING
AND FIRE.
OR OR
Improper flaring
Pipe Handle
Reamer 0 – 0.5 mm
Bar Bar
Yoke Inclined Surface Cracked Uneven
Core damaged thickness
When properly flared, the internal surface of the
Point down Red arrow mark Copper
Clamp handle flare will evenly shine and be of even thickness.
pipe
Since the flare part comes into contact with the
1. To cut 2. To remove burrs 3. To flare connections, carefully check the flare finish.
57
11.3 Outdoor Unit
11.3.1 Install the Outdoor Unit
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.
A B
C
Model A B C D
S28*** 613 mm 130 mm 24 mm 360.5 mm
58
11.3.3 Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND
PIPES in the following procedure.
Close
Gas side
Close
Lo Hi
Vacuum CLOSE
pump
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
59
11.3.4 Connect the cable to the Outdoor Unit
1 Remove the control board cover from the unit 5 Secure the power supply cord and connection
by loosening the screw. cable onto the control board with the holder.
2 Cable connection to the power supply through 6 Attach the control board cover back to the
Isolating Devices (Disconnecting means). original position with screw.
o Connect approved type polychloroprene 7 For wire stripping and connection requirement,
sheathed power supply cord refer to instruction 11.2.4 of indoor unit.
3 x 4.0 mm2 type designation 60245 IEC
57 or heavier cord to the terminal board,
and connect the others end of the cord to Terminal
Isolating Devices (Disconnecting means). Board
o Do not use joint power supply cord. L N 1 2 3
Replace the wire if the existing wire (from Earth wire
concealed wiring, or otherwise) is too longer than
others Earth wire
short. longer than
o In unavoidable case, joining of power AC wires
for safety others
supply cord between isolating devices AC wires
and terminal board of air conditioner shall reason
for safety
be done by using approved socket and reason
plug rated 25A. Wiring work to both
socket and plug must follow to national Holder
wiring standard.
3 Connection cable between indoor unit and
Power Indoor &
outdoor unit shall be approved outdoor
supply
polychloroprene sheathed 4 x 1.5 mm2 connection
cord
flexible cord, type designation 60245 IEC 57 cable
or heavier cord. Do not use joint connection
cable. Replace the wire if the existing wire
Isolating Indoor unit
(from concealed wiring, or otherwise) is too
Devices
short.
4 Connect the power supply cord and
connection cable between indoor unit and WARNING
outdoor unit according to the diagram below. This equipment must be properly earthed.
60
12. Operation Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operation
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
61
12.2 Indoor Fan Motor Operation
12.2.1 Basic Rotation Speed
Manual Fan Speed
o Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab Hi Me+ Me Me- Lo
Fan Speed a b c d e f g h a b
Higher
Medium
Lower
[1 pattern : 10s]
Feedback control
o Immediately after the fan motor is started, feedback control is performed once every second.
o During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continuously for 10 seconds, the fan
motor error counter increased; fan motor is then stopped and restarted. If the fan motor error counter
increased to 7, then H19 – fan motor error is detected. Operation stopped and could not be restarted.
ON ON
Compressor OFF
ON Fan Speed ON
Outdoor Fan 30 sec OFF
62
12.4 Airflow Direction
There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
CS-S18/24/28RKV
Inner Vane Angle (°) Outer Vane Angle (°)
Operation Mode Airflow Direction
1 2 3 4 5 1 2 3 4 5
Auto 125 ~ 65 60 ~ 90
Cooling
Manual 125 120 100 82 65 60 70 77 83 90
Auto 125 ~ 65 60 ~ 90
Soft Dry
Manual 125 120 100 82 65 60 70 77 83 90
Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. It does not swing during fan motor stop. When the air conditioner is stopped using
remote control, the vane will shift to close position.
Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as figure below. When the air conditioner is stopped using remote control, the vane
will shift to close position.
Side View (Inner Vane)
12.26º
Reference point
137º
Step 1
Stopper
Step 2
Step 3 Closed
Position
Step 4
Step 5
63
Side View (Outer Vane)
Closed Stopper
Position
34.11º
127.28º
Step 1
Step 2
Step 3
Step 4
Step 5
Manual airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as figure below:
Top View
2 5
3 4
1
CS-S9/12RKV
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°) 90 65 77.5 102.5 115
CS-S18/24/28RKV
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°) 90 70 80 100 110
64
12.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)
Purpose
o To provide quiet cooling operation compare to normal operation.
Control condition
o Quiet operation start condition
When Quiet button at remote control is pressed Quiet INDICATOR illuminates.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
ECONAVI button is pressed.
iAUTO-X button is pressed.
AUTO COMFORT button is pressed.
Stop by OFF/ON button.
OFF Timer activates.
Quiet button is pressed again.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if ON timer activates, quiet operation maintains.
After off, when on back, quiet operation is not memorized.
Control content
o Fan speed is changed from normal setting to quiet setting of respective fan speed.
o Fan speed for quiet operation is reduced from setting fan speed.
60 minutes before the set ON time, indoor (at fan speed of Lo-) and outdoor fan motor start operation for 30 seconds
to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operation earlier than the set time as shown below.
Indoor intake air
temperature (°C)
15 min
30
10 min
25
5 min
Outdoor air
30 35 temperature (°C)
65
12.7 Random Auto Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes. There are 10 patterns to be selected randomly after power supply resumes.
This control is not applicable during OFF/ON Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
Note:
If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer sampling.
If TIMER LED blinks, there is an abnormal operation occurs.
66
12.9 nanoe-G Operation
This operation provides clean air by producing great amount of negative ions and distribute through the
discharge airflow to capture or deactivate molds, bacteria or viruses.
Timer control
o When ON Timer activates when unit stops, previous operation resumes and restored last saved nanoe-G
operation status.
o When ON Timer activates during any operation, no change on current operation.
o When OFF Timer activates during any operation, all operation stops and the latest nanoe-G operation status
is saved.
Indicator
o When nanoe-G starts, nanoe-G indicator ON.
Power failure
o During nanoe-G individual operation, if power failure occurs, after power resumes, nanoe-G individual
operation resumes immediately.
o During combination operation, if power failure occurs, after power resumes, combination operation resume
immediately.
67
nanoe-G check mode
o To enable nanoe-G check mode, during nanoe-G operation ON:
SET
Press continously for 5s
SET
TEMP
SET
TEMP
SET
Transmit check code
and after 30 seconds return to normal
mode.
Troubleshooting method
Connect the connector or stop operation to cancel the blinking.
Switch off the power supply and unplug before cleaning.
Clean the dirty nanoe-G generator with cotton bud.
Troubleshooting method
Press nanoe-G button or OFF/ON button to stop the operation and check the nanoe-G connector at
PCB.
After that, press nanoe-G button again to confirm the nanoe-G indicator do not blinks.
The 24 timer counter will be clear after 10 minutes of normal operation or when operation stops.
68
Error reset method
Press “OFF/ON” button to OFF the operation.
Press AUTO OFF/ON button at indoor unit to OFF the operation.
OFF Timer activates.
Power supply reset.
Troubleshooting method
Press nanoe-G button or OFF/ON button to stop the operation.
Change nanoe-G high voltage power supply or main PCB.
When Lo-feedback voltage supplied to nanoe-G system during nanoe-G operation ON, nanoe-G
indicator and Timer indicator stop blinking.
Control contents:
o When the unit operate in Cool or Dry mode before turned off.
1. The unit will operate fan operation, fan motor will operate at 500 rpm for 30 minutes then stop.
2. During fan operation, horizontal vane will fixed at 30° (outer vane) and 63° (inner vane) for 30 minutes
then close.
3. After 30 minutes the unit will continue with common control.
o Common control.
- nanoe-G generator will operate for 120 minutes.
Timer control
o When ON Timer activates during in filter deactivation operation, in-filter deactivation operation stops.
o When OFF Timer activates during in filter deactivation operation, in-filter operation will continue.
Indicator
o nanoe-G indicator ON.
o Power indicator OFF.
Power failure
o During in-filter operation, if power failure occurs, after power resumes in-filter deactivation operation will not
resume.
69
12.11 AUTO COMFORT and ECONAVI Operation
Area of human availability, activity level and absent is judged based on pulses by using 2 infrared sensors. The
internal setting temperature shift, fan speed and horizontal airflow direction are adjusted in order to provide
comfort environment while maintain the energy saving level.
Signal Detection
Information Log
70
12.11.1.1 Signal Detection
7m
A C
2m
B
7m
120º
Human Activity sensor will turns on according to infrared sensors signal detection.
71
12.11.1.7 Setting Position Judgment
According to installation position when there is only one activity area detected, the horizontal airflow direction
louver position is fixed according to chart below:
When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow
louver steps at the targeted activity areas is judged.
When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right.
ECONAVI ; Detecting human presence and activity, the unit controls room temperature to save energy.
Mode Human Low activity Normal activity High activity Absent
+2 °C
+1 °C
Set
COOL/DRY
temperature
AUTO COMFORT
AUTO COMFORT ; Detecting human presence and activity, the unit controls room temperature to keep human
comfortable consistently.
Mode Human Low activity Normal activity High activity Absent
+2 °C
+1 °C
Set
temperature -1 °C
COOL/DRY
* During low activity, fan speed 1 tap up for first 15 minutes or until set temperature is reached.
** During human absence, maximum fan speed for COOL/DRY mode is medium fan.
72
12.11.1.9 Rhythmic Temperature Wave Operation
To further maximize the energy saving during ECONAVI or AUTO COMFORT operates at low activity level.
Start condition
o The unit is operates in Cool or Dry mode under ECONAVI or AUTO COMFORT operation, and
o Human activity sensor detects low activity level continuously for 60 minutes, and
o ON Timer is not activated.
Stop condition
o Unit is off, or
o ECONAVI or AUTO COMFORT is off, or
o Human activity sensor detects high activity level or absent, or
o ON Timer is activated.
Control contents
o When all start conditions complied, set temperature will shift accordingly as following:
ECONAVI
Mode Human Low activity Normal activity High activity Absent
+2 °C
+1 °C
Set
COOL/DRY
temperature
AUTO COMFORT
Mode Human Low activity Normal activity High activity Absent
+2 °C
+1 °C
Set
temperature -1 °C
COOL/DRY
Set
COOL/DRY
temperature
73
12.11.1.10 ECONAVI and AUTO COMFORT Demo Mode
To enable ECO DEMO mode, during unit is OFF (power standby):
SET
Press continously for 5s
SET
TEMP
SET
TEMP
SET
Transmit check code
and after 30 seconds return to normal
mode.
Operation details
Infrared Sensor
Vane Position Fan Speed
Sensor 1 Sensor 2
1 0 5 HI
1 1 Auto Swing HI
0 1 2 HI
0 0 Auto Swing LO
The target area will maintain for 5 seconds before changeover to next detection.
If no activity detection, the last action will maintain for 30 seconds before changeover to human absence status.
74
12.11.1.11 Human Activity Sensor Abnormality
Abnormality detection:
Connector disconnection / Wire cut abnormality
o Sensor judge Hi level continuously for 25 seconds
Circuit abnormality
o 70 seconds after power ON, if human activity sensor judge Lo level continuously for 25 seconds
When error code happened, the unit is able to operate without AUTO COMFORT / ECONAVI.
SET
TEMP
TEMP
SET
TEMP
TEMP
SET
Transmit check code
and after 30 seconds return to normal
mode.
During ECONAVI is ON, when CHECK signal received, if either sensors has abnormality, the 4 times abnormality
counter is ignored, ECONAVI Indicator will blink immediately and error code is memorized.
The unit could operate without ECONAVI or AUTO COMFORT.
The ECONAVI indicator blinking could be cancelled by pressing ECONAVI button again.
If the human activity sensor has no abnormality, the CHECK process will end and continue with normal operation.
75
12.11.2 Sunlight Sensor
During ECONAVI operation, the sunlight sensor detects sunlight intensity coming through windows and
differentiates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature.
Sunlight judgment is as following
Temperature shift
76
12.11.2.2 Judge Sunlight Intensity
Based on sunlight sensor output voltage, the sunlight intensity value will be computed and logged to sunlight
intensity database.
The sunlight sensor sensitivity could be adjusted:
Set to Level. 4
Press Transmit
Timer solar radiation
SET level
Set to Level. 5 &
after *30 secs
go back to
normal mode
Set to Level. 1
Set to Level. 2
77
12.11.2.3 Judge Ambient Condition
According to sunlight intensity over a period of time, the system will analyze the ambient condition is sunny,
cloudy or night.
In a room without window or with thick curtain, the sunlight sensor will judge as cloudy/night.
78
12.11.2.5 Sunlight Sensor Check Mode
To enable sunlight sensor check mode, during unit is OFF (power standby):
SET
TEMP
TEMP
SET
TEMP
TEMP
SET
Transmit check code
and after 30 seconds return to normal
mode.
Operation details
o The sunlight sensor check mode will be operated for 5 minutes.
o During check mode, the ON and OFF timer will be memorized but it operation be ignored.
o During check mode, if the sunlight sensor check code is retransmitted, the 5 minutes counter will be reset.
o During check mode, if sunlight sensor detected the sunlight intensity value above minimum level, the
ECONAVI indicator turns ON. Else if sunlight sensor detected sunlight intensity value below minimum level,
the ECONAVI indicator is OFF.
To disable sunlight sensor check mode
o After check mode is ended (5 minutes counter elapsed), press AUTO OFF/ON button at indoor unit.
o If the sunlight sensor detected sunlight intensity is at abnormal range, the check mode will be ended.
Please check for error code.
79
13. Protection Control
13.1 Restart Control (Time Delay Safety Control)
The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
(B)
39°C
(A) 38°C
80
13.5 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor temperature. The changes of
frequency are as below.
If compressor temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes, timer
LED will be blinking. “F97” is indicated.
Compressor=OFF
107°C
92°C
Compressor Frequency
103°C Reduced
91°C
Compressor Frequency
100°C Maintain
90°C
Free
Comp Tank temperature
81
13.9 Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust based on outdoor air temperature.
Free
38°C
37°C
Limited Frequency
82
13.14 Odor Cut Control
To reduce the odor released from the unit.
o Start condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o Control content
Depends on compressor conditions:
1. Compressor OFF → Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 50 seconds.
2. Compressor ON → Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
83
14. Servicing Mode
14.1 Auto Off/On Button
Auto OFF/ON Auto OFF/ON
Button Pressed Button Pressed
5 sec
iAUTO-X Operation Test Run Operation Stop
(Forced Cooling Operation)
Beep
The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air
conditioner operation.
Auto OFF/ON Main unit always continue Test Run (forced cooling) operation.
Button Pressed
5 sec 8 sec 11 sec 16 sec
iAUTO-X Test Run Operation Remote Control Number Remote Control Receiving
Operation (Forced Cooling Operation) Switch Mode Sound OFF/ON
There are 4 types of remote control transmission code could be selected. The indoor unit will only operate
when received signal with same transmission code from remote control. This could prevent signal
interference when there are 2 or more units installed nearby together.
To change remote control transmission code, short or open jumpers at the remote control printed circuit
board.
After Auto OFF/ON button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON
Mode is restarted.
84
14.2 Remote Control Button
14.2.1 SET Button
To check remote control transmission code and store the transmission code to EEPROM.
o Press “Set” button by using pointer.
o Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code change.
o LCD returns to original display if remote control does not operate for 30 seconds.
To limit set temperature range for iAUTO-X, COOL & DRY mode.
o Press “Set” button by using pointer.
o Press TEMP increment or decrement button to choose No. 3.
o Press Timer increment or decrement button to select desired temperature low limit of set temperature for
iAUTO-X, COOL & DRY mode.
o Press Timer Set button to confirm low limit selection.
o Press TEMP increment or decrement button to choose No. 4.
o Press Timer decrement or increment button to select desired temperature high limit of set temperature for
iAUTO-X, COOL & DRY mode.
o Press Timer Set button to confirm high limit selection.
o LCD returns to original display if remote control does not operate for 30 seconds or press Timer Cancel
button.
14.2.4 TIMER ▲
To change indoor unit indicators’ intensity:
o Press continuously for 5 seconds.
14.2.5 TIMER ▼
To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F).
o Press continuously for 10 seconds.
14.2.6 TEMP
To change remote control set temperature range from 16°C ~ 30°C (60°F ~ 86°F) to 20°C ~ 30°C (68°F ~ 86°F).
o Press continuously for 15 seconds.
85
15. Troubleshooting Guide
15.1 Refrigeration Cycle System
In order to diagnose malfunctions, ensure the air conditioner is free Normal Pressure and Outlet Air Temperature (Standard)
from electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air
MPa Temperature
Such problems include insufficient insulation, problem with the 2
(kg/cm G) (°C)
power source, malfunction of a compressor and a fan. The normal
outlet air temperature and pressure of the refrigeration cycle Cooling Mode 0.9 ~ 1.2 (9 ~ 12) 12 ~ 16
depends on various conditions, the standard values for them are Condition: Indoor fan speed = High
shown in the table to the right. Outdoor temperature = 35°C at cooling mode.
Compressor operate at rated frequency
Excessive amount
of refrigerant
Cooling
Gas side Mode High
Inefficient compressor Measuring gas side
pressure pressure
Low
Insufficient refrigerant
86
15.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and
Electric Current
Inefficient compression
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
87
15.2 Breakdown Self Diagnosis Function
15.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)
Once error occurred during operation, the unit will stop its operation, and Timer LED blinks.
Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown
condition, the LED will ON again.
In operation after breakdown repair, the Timer LED will not blink. The last error code (abnormality) will be stored
in IC memory.
operation. iAU
iA UTTO
MODE
O--X
2 Press the CHECK button on the remote control continuously for
X
5 seconds.
3 “- -“ will be displayed on the remote control display.
Note: Display only for “- -“ (No signal transmission, no receiving i AUTO
4 Press the TIMER ▲ or ▼ button on the remote control. The MODE NANO
E-G
code “H00” (no abnormality) will be displayed and signal will be AUTO
COMFO
TEMP RT
ON
6 When the latest abnormality code on the main unit and code Check 1
2
SET
transmitted from the remote control are matched, Power LED button OFF 3
CANCEL
LED will light up for 0.5 seconds and no sound will be heard.
7 The breakdown diagnosis mode will be canceled unless
pressing the CHECK button continuously for 5 seconds or
operating the unit for 30 seconds.
8 The LED will be off if the unit is turned off or the RESET button on the main unit is pressed.
88
15.3 Error Code Table
Diagnosis Emergency
Abnormality / Protection control Abnormality Judgment Primary location to verify
display Operation
H00 No abnormality detected - Normal operation
Indoor / Outdoor abnormal > 1 min after starting Indoor fan operation Internal / external cable connection
H11
communication operation only Indoor / outdoor PCB
Continuously for 90 sec
H12 Connection capability rank abnormality - -
after power supplied
Indoor intake air temperature sensor Intake air temperature sensor
H14 Continue for 5 sec. -
abnormality (defective or disconnected)
Outdoor compressor temperature sensor Compressor temperature sensor
H15 Continue for 5 sec. -
abnormality (defective or disconnected)
Outdoor PCB
H16 Outdoor current transformer open circuit - -
IPM (Power transistor) module
7 occurrences Indoor PCB
H19 Indoor fan motor mechanism locked -
continuously Fan motor
Indoor heat exchanger temperature ○ Heat exchanger temperature sensor
H23 Continue for 5 sec.
sensor abnormality (defective or disconnected)
○ Indoor PCB
H25 nanoe-G abnormality -
nanoe-G PCB
Outdoor air temperature sensor ○ Outdoor temperature sensor
H27 Continue for 5 sec.
abnormality (defective or disconnected)
Outdoor heat exchanger
Outdoor heat exchanger temperature ○
H28 Continue for 5 sec. temperature sensor (defective or
sensor abnormality
disconnected)
Discharge temperature sensor Outdoor discharge temperature
H30 Continue for 5 sec.
abnormality sensor (defective or disconnected)
H33 Indoor / outdoor wrong connection - - Indoor / outdoor supply voltage
H38 Indoor / outdoor mismatch (brand code) - - -
ECONAVI sensor (defective or
○
H59 ECONAVI sensor abnormality Continue for 25 sec. disconnected)
ECONAVI PCB
Low output continue for Light sensor (defective or
H70 Light sensor abnormal -
24hours, 15days disconnected)
2 occurrences within 30
H97 Outdoor fan lock abnormality Outdoor fan motor locked
minutes
Air filter dirty
H98 Indoor temperature rise abnormality - -
Air circulation short circuit
Indoor heat exchanger freeze prevention Insufficient refrigerant
H99 - -
protection Air filter dirty
4 occurrences within 30 4-way valve
F11 4 way valve switching failure * -
minutes v-coil
System and compressor microcomputer 2 occurrences within 5 Compressor
F90 -
communication error(for S10*** only) seconds Outdoor PCB
4 occurrences within 20
F90 Power factor correction abnormality - Outdoor PCB
minutes
2 occurrences within 20 No refrigerant ( 3-way valve is
F91 Refrigerant cycle abnormal -
minutes closed)
4 occurrences within 20
F93 Outdoor compressor abnormal revolution - Outdoor compressor
minutes
4 occurrences within 20
F95 Cooling high pressure protection - Outdoor refrigerant circuit
minutes
Excess refrigerant
Intelligent power transistor overheating
F96 - - Improper heat radiation
protection
IPM (Power transistor)
Compressor temperature rise protection 4 times occurrence within Insufficient refrigerant
F97 -
control 20 minutes Compressor
3 times occurrence within Excess refrigerant
F98 Total running current protection -
20 minutes Improper heat radiation
Outdoor PCB
Outdoor direct current (DC) peak 7 times occurrence
F99 - IPM (Power transistor)
detection continuously
Compressor
Note:
“○” – Frequency measured and fan speed fixed
“ * ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one “beep” to four “beep” sounds.
89
15.4 Troubleshooting Flowchart
15.4.1 H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
During startup and operation of cooling, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused
Faulty indoor unit PCB.
Faulty outdoor unit PCB.
Indoor unit-outdoor unit signal transmission error due to wrong wiring.
Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the
indoor and outdoor units.
Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting
90
15.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit or outdoor unit PCBs mounted.
Indoor unit or outdoor unit PCBs defective.
Indoor-outdoor unit signal transmission error due to wrong wiring.
Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor
and outdoor units.
Troubleshooting
91
15.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling, the temperatures detected by the indoor intake air temperature sensor
are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
92
15.4.4 H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling, the temperatures detected by the outdoor compressor temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
93
15.4.5 H16 (Outdoor Current Transformer Open Circuit)
Malfunction Decision Conditions
A current transformer (CT) is detected by checking the compressor running frequency (≥ rated frequency) and
CT detected input current (less than 1.14A) for continuously 20 seconds.
Malfunction Caused
CT defective
Outdoor PCB defective
Compressor defective (low compression)
Troubleshooting
94
15.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor
(feedback of rotation > 2550rpm or < 50rpm)
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty indoor unit PCB.
Troubleshooting
95
15.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling, the temperatures detected by the indoor heat exchanger temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
96
15.4.8 H25 (nanoe-G Air Purifying System Abnormal)
Malfunction Decision Conditions
During standby of cooling operation, nanoe-G breakdown occurs and air conditioner stops operation.
Malfunction Caused
Faulty indoor main PCB.
Faulty indoor nanoe-G power module.
Troubleshooting
97
15.4.9 H27 (Outdoor Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling, the temperatures detected by the outdoor air temperature sensor are
used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
98
15.4.10 H28 (Outdoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling, the temperatures detected by the outdoor pipe temperature sensor are
used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
99
15.4.11 H30 (Compressor Discharge Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling, the temperatures detected by the outdoor discharge pipe temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
100
15.4.12 H33 (Unspecified Voltage between Indoor and Outdoor)
Malfunction Decision Conditions
The supply power is detected for its requirement by the indoor/outdoor transmission.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit and outdoor unit PCBs used.
Indoor unit or outdoor unit PCB defective.
Troubleshooting
101
15.4.13 H59 (Human Activity Sensor Abnormality)
Malfunction Decision Conditions
Feedback signal of human activity sensor.
Malfunction Caused
Feedback signal is fixed at 0VDc or 5VDc continuously for 25 seconds during ECONAVI or AUTO COMFORT
operation.
Feedback signal is detected during ECONAVI or AUTO COMFORT off.
Troubleshooting
102
15.4.14 H70 (Light Sensor Abnormality)
Malfunction Decision Conditions
Feedback signal of light sensor.
Malfunction Caused
Feedback value is 0VDC continuously.
Troubleshooting
103
15.4.15 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor.
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty outdoor unit PCB.
Troubleshooting
104
15.4.16 H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Caused
Clogged air filter of the indoor unit
Dust accumulation on the indoor unit heat exchanger
Air short circuit
Detection error due to faulty indoor pipe temperature sensor
Detection error due to faulty indoor unit PCB
Troubleshooting
105
15.4.17 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
Clogged air filter of the indoor unit
Dust accumulation on the indoor unit heat exchanger
Air short circuit
Detection error due to faulty indoor pipe temperature sensor
Detection error due to faulty indoor unit PCB
Troubleshooting
106
15.4.18 F11 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
When cooling operation, when indoor pipe temperature or indoor heat exchanger temperature sensor is above
45°C.
Malfunction Caused
Faulty connector connection.
Faulty indoor pipe temperature sensor.
Faulty indoor main PCB.
Troubleshooting
107
15.4.19 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
During startup and operation of cooling, when Power Factor Correction (PFC) protection circuitry at the outdoor
unit main PCB senses abnormal high DC voltage level.
Malfunction Caused
DC voltage peak due to power supply surge.
DC voltage peak due to compressor windings not uniform.
Faulty outdoor PCB.
Troubleshooting
108
15.4.20 F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
During cooling, compressor frequency = Fcmax.
During cooling and heating operation, running current: 0.65A < I < 1.65A.
During cooling, indoor intake - indoor pipe < 4°C.
Malfunction Caused
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor.
2/3 way valve closed.
Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
109
15.4.21 F93 (Compressor Rotation Failure)
Malfunction Decision Conditions
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
Malfunction Caused
Compressor terminal disconnect
Outdoor PCB malfunction
Troubleshooting
110
15.4.22 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
Outdoor pipe temperature rise due to defective of outdoor fan motor.
Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting
111
15.4.23 F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling, when IPM temperature data (100°C) is detected by the IPM temperature sensor.
Malfunction Caused
IPM overheats due to short circuit of hot discharge air flow.
IPM overheats due to defective of outdoor fan motor.
IPM overheats due to defective of internal circuitry of IPM.
IPM overheats due to defective IPM temperature sensor.
Troubleshooting
112
15.4.24 F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling, when compressor tank temperature data (112°C) is detected by the compressor tank
temperature sensor.
Malfunction Caused
Refrigerant shortage (refrigerant leakage).
2/3 way valve closed.
Detection error due to faulty compressor tank temperature sensor.
Troubleshooting
113
15.4.25 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During cooling operation, when an input over-current is detected by checking the input current value being detected
by current transformer (CT) with the compressor running.
Malfunction Caused
Over-current due to compressor failure.
Over-current due to defective outdoor unit PCB.
Over-current due to defective inverter main circuit electrolytic capacitor.
Over-current due to excessive refrigerant.
Troubleshooting
114
15.4.26 F99 (DC Peak Detection)
Malfunction Decision Conditions
During startup and operation of cooling, when inverter DC peak data is received by the outdoor internal DC peak
sensing circuitry.
Malfunction Caused
DC current peak due to compressor failure.
DC current peak due to defective power transistor (IPM).
DC current peak due to defective outdoor unit PCB.
DC current peak due to short circuit.
Troubleshooting
115
16. Disassembly and Assembly Instructions
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding
with repair work. Failure to heed this caution may result in electric shocks.
Figure 1
CAUTION
a. Use a manual screw driver with at least 150 mm shaft
length. Do not use a hand drill type.
b. Slightly tilt the screw driver handle downward so that the
shaft does not touch the flap. Be careful not to scratch the
flap while undoing the screws.
116
16.1.1.2 To Remove Electronic Controller
Figure 2
8. Remove screw to
remove terminal board
complete. RY-PWR
CN-TH
Figure 3 Figure 4
117
16.1.1.3 To Remove Discharge Grille
Figure 6
118
16. Remove the bearing by pulling it
out gently
Figure 8
17. Push the holdfast to the left and lift up the evaporator.
Evaporator
119
Cross Flow Fan
120
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding
with repair work. Failure to heed this caution may result in electric shocks.
Figure 11
CAUTION
a. Use a manual screw driver with at least 150 mm shaft
length. Do not use a hand drill type.
b. Slightly tilt the screw driver handle downward so that the
shaft does not touch the flap. Be careful not to scratch the
flap while undoing the screws.
121
16.2.1.2 To Remove Horizontal Vane
Figure 13
122
8. Detach the terminal wire (Brown),
terminal wire (Black), terminal wire (Red)
and earth wire screw. 13. Detach all the connectors as labeled from
12. Pull put the main
electronic controller the electronic controller. Then pull out main
halfway. controller gently.
AC303
CN-STM1
9. Detach the CN-DISP CN-STM3
connector then remove
the indicator complete. CN-STM2
CN-MSENS
CN-CLN
CN-TH
Figure 14 Figure 15
123
16.2.1.5 To Remove Control Board
Figure 17
Figure 19
124
20. Push the holdfast to the left and lift up the evaporator.
125
16.3 Outdoor Electronic Controller Removal Procedure
16.3.1 CU-S9RKV
Caution! When handling electronic controller, be careful of electrostatic discharge.
1. Remove the 4 screws of the Top Panel. 5. Remove the Control Board as follows.
Fig.1
Fig.4
2. Remove the 7 screws of the Front Panel.
Fig.2
Fig.5
3. Remove the screw of the Terminal Board Cover.
4. Remove the Top Cover of the Control Board by 2
hooks.
Fig.6
Fig.3
126
Fig.9
Fig.7
Fig.8
127
16.3.2 CU-S12RKV
Caution! When handling electronic controller, be careful of electrostatic discharge.
1. Remove the 3 screws of the Top Panel. 5. Remove the Control Board as follows.
Fig.1 Fig.4
Fig.2
Fig.6
Fig.3
128
16.3.3 CU-S18RKV CU-S24RKV
Caution! When handling electronic controller, be careful of electrostatic discharge.
1. Remove the 4 screws of the Top Panel. 4. Remove the Control Board.
Fig.4
Fig.2
Fig.3
129
16.3.4 CU-S28RKV
Caution! When handling electronic controller, be careful of electrostatic discharge.
1. Remove the 4 screws of the Top Panel. 4. Remove the Control Board.
Fig.4
Fig.1
Fig.2 Fig.5
Fig.3
130
17. Technical Data
17.1 Operation Characteristics
17.1.1 CS-S9RKV CU-S9RKV
Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 7.5 m
o Compressor Frequency = Fc
220V
15.700
15.500
15.300
Outlet Air(℃)
15.100
14.900
14.700
14.500
14.300
14.100
13.900
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
2.900
2.800
Capacity(kW)
2.700
2.600
2.500
2.400
2.300
2.200
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
1.050
Piping Pressure (MPa)
1.040
Gas Side
1.030
1.020
1.010
1.000
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
4.100
3.900
Current(A)
3.700
3.500
3.300
3.100
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
131
Piping Length Characteristic Cooling
o Room temperature: 27°C (DBT), 19°C (WBT)
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Operation condition: High fan speed
o Compressor Frequency = Fc
220V
14.900
14.800
Outlet Air(℃)
14.700
14.600
14.500
14.400
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
220V
2.800
2.750
Capacity(kW)
2.700
2.650
2.600
2.550
2.500
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
220V
1.035
Piping Pressure(MPa)
1.030
Gas Side
1.025
1.020
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
220V
3.430
3.420
3.410
Current(A)
3.400
3.390
3.380
3.370
3.360
3.350
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
132
17.1.2 CS-S12RKV CU-S12RKV
Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5.0 m
o Compressor Frequency = Fc
220V
15.800
15.600
15.400
Outlet Air(℃)
15.200
15.000
14.800
14.600
14.400
14.200
14.000
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
3.500
3.400
Capacity(kW)
3.300
3.200
3.100
3.000
2.900
2.800
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
1.020
Piping Pressure (MPa)
1.010
Gas Side
1.000
0.990
0.980
0.970
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
4.800
4.600
Current(A)
4.400
4.200
4.000
3.800
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
133
Piping Length Characteristic Cooling
o Room temperature: 27°C (DBT), 19°C (WBT)
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Operation condition: High fan speed
o Compressor Frequency = Fc
220V
15.200
15.100
Outlet Air(℃)
15.000
14.900
14.800
14.700
14.600
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
220V
3.300
3.250
Capacity(kW)
3.200
3.150
3.100
3.050
3.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
220V
1.004
Piping Pressure(MPa)
1.002
1.000
Gas Side
0.998
0.996
0.994
0.992
0.990
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
220V
4.150
Current(A)
4.100
4.050
4.000
3 4 5 6 7 8 9 10 11 12 13 14 15
Piping Length (m)
134
17.1.3 CS-S18RKV CU-S18RKV
Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5.0 m
o Compressor Frequency = Fc
220V
15.900
15.700
Outlet Air(℃)
15.500
15.300
15.100
14.900
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
5.500
5.400
5.300
Capacity(kW)
5.200
5.100
5.000
4.900
4.800
4.700
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
1.010
Piping Pressure (MPa)
1.000
0.990
Gas Side
0.980
0.970
0.960
0.950
0.940
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
7.500
7.300
7.100
Current(A)
6.900
6.700
6.500
6.300
6.100
5.900
5.700
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
135
Piping Length Characteristic Cooling
o Room temperature: 27°C (DBT), 19°C (WBT)
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Operation condition: High fan speed
o Compressor Frequency = Fc
220V
15.700
15.600
Outlet Air(℃)
15.500
15.400
15.300
15.200
15.100
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
220V
5.250
5.200
Capacity(kW)
5.150
5.100
5.050
5.000
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
220V
0.970
Piping Pressure(MPa)
0.960
Gas Side
0.950
0.940
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
220V
6.500
6.400
Current(A)
6.300
6.200
6.100
6.000
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
136
17.1.4 CS-S24RKV CU-S24RKV
Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5.0 m
o Compressor Frequency = Fc
220V
14.600
14.400
Outlet Air(℃)
14.200
14.000
13.800
13.600
13.400
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
6.300
6.200
6.100
Capacity(kW)
6.000
5.900
5.800
5.700
5.600
5.500
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
0.990
Piping Pressure (MPa)
0.980
0.970
Gas Side
0.960
0.950
0.940
0.930
0.920
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
220V
8.800
8.600
8.400
Current(A)
8.200
8.000
7.800
7.600
7.400
7.200
7.000
30 31 32 33 34 35 36 37 38 39 40 41 42 43
Outdoor Temperature(℃)
137
Piping Length Characteristic Cooling
o Room temperature: 27°C (DBT), 19°C (WBT)
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Operation condition: High fan speed
o Compressor Frequency = Fc
220V
14.300
14.200
Outlet Air(℃)
14.100
14.000
13.900
13.800
13.700
13.600
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
220V
6.050
6.000
Capacity(kW)
5.950
5.900
5.850
5.800
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
220V
0.955
Piping Pressure(MPa)
0.950
Gas Side
0.945
0.940
0.935
0.930
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
220V
7.800
7.700
Current(A)
7.600
7.500
7.400
7.300
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Piping Length (m)
138
17.1.5 CS-S28RKV CU-S28RKV
Cooling Characteristic
o Room temperature: 27°C (DBT), 19°C (WBT)
o Operation condition: High fan speed
o Piping length: 5.0 m
o Compressor Frequency = Fc
220V
14.000
13.500
Outlet Air(℃)
13.000
12.500
12.000
11.500
11.000
10.500
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Temperature(℃)
220V
8.700
8.500
8.300
Capacity(kW)
8.100
7.900
7.700
7.500
7.300
7.100
6.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Temperature(℃)
220V
0.890
Piping Pressure (MPa)
0.870
0.850
Gas Side
0.830
0.810
0.790
0.770
0.750
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Temperature(℃)
220V
13.400
12.900
12.400
Current(A)
11.900
11.400
10.900
10.400
9.900
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
Outdoor Temperature(℃)
139
Piping Length Characteristic Cooling
o Room temperature: 27°C (DBT), 19°C (WBT)
o Outdoor temperature: 35°C (DBT), 24°C (WBT)
o Operation condition: High fan speed
o Compressor Frequency = Fc
220V
13.400
13.300
13.200
Outlet Air(℃)
13.100
13.000
12.900
12.800
12.700
12.600
12.500
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
220V
7.850
7.800
Capacity(kW)
7.750
7.700
7.650
7.600
7.550
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
220V
0.840
Piping Pressure(MPa)
0.790
0.740
Gas Side
0.690
0.640
0.590
0.540
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
220V
12.700
12.600
12.500
Current(A)
12.400
12.300
12.200
12.100
12.000
11.900
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
Piping Length (m)
140
18. Exploded View and Replacement Parts List
18.1 Indoor Unit
18.1.1 CS-S9RKV CS-S12RKV
43 CWH55025J
O/I 50 I/I 51 I/I 52
49
4 CWH55051J
3
47
17
2
5
20
1
23
18 22 8 28
21 9
19 7
40
10 24
16
48 11
41
42 13
12
44 26
45
14
15
25
AIR
CON
DITIO
NER
iAUTO-
iA MOD
UTO-X
X E
i AUTO
-X
OFF/O
N
ECON
MOD
AVI
AUTOE
COM
FORT NAN
46
TEM OE-G
P
QUIE
T
TIME FAN AIR
R
SPEED SWIN
ON G
1
OFF
2 SET
SET
3
CHECK
CANCE
L
CLOCK AC
RC
RESET
35 39
38
30
29
32
31
34
33
37
36
27
53
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
141
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-S9RKV CS-S12RKV REMARK
1 CHASSIS COMPLETE 1 CWD50C1605 ←
2 FAN MOTOR 1 L6CBYYYL0037 ← O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1076 ←
4 BEARING ASSY 1 CWH64K007 ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ←
6 GENERATOR COMPLETE 1 CWH94C0063 ←
7 EVAPORATOR 1 CWB30C4941 CWB30C4942
8 FLARE NUT (LIQUID) 1 CWT251030 ←
9 FLARE NUT (GAS) 1 CWT251031 CWT251073
10 CLIP FOR SENSOR 1 CWH32142 ←
11 CONTROL BOARD CASING 1 CWH102449 ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2435 CWA28C2357
13 ELECTRONIC CONTROLLER - MAIN 1 CWA73C8826 CWA73C8827 O
14 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000007 ← O
15 ELECTRONIC CONTROLLER - INDICATOR 1 CWA747894 ← O
16 SENSOR COMPLETE 1 CWA50C2401 ← O
17 SENSOR COMPLETE (ECO) 1 CWA50C3265 ← O
18 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA745791 ← O
19 ELECTRONIC CONTROLLER (ECO SENSOR) 1 CWA746206 ← O
20 ELECTRONIC CONTROLLER (COMPARATOR) 1 CWA747891 ← O
21 LEAD WIRE - PCB ECO 1 CWA68C1926 ←
22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933929 ←
23 CONTROL BOARD CASING FOR PCB ECO 1 CWD933930 ←
24 CONTROL BOARD TOP COVER 1 CWH131467 ←
25 INDICATOR HOLDER 1 CWD933928 ←
26 CONTROL BOARD FRONT COVER CO. 1 CWH13C1247 ←
27 DISCHARGE GRILLE COMPLETE 1 CWE20C3544 ←
28 BACK COVER CHASSIS 1 CWD933233A ←
29 FULCRUM 1 CWH621166 ←
30 VERTICAL VANE 8 CWE241457 ←
31 CONNECTING BAR 1 CWE261314 ←
32 AIR SWING MOTOR 1 CWA98K1025 ← O
33 AIR SWING MOTOR 1 CWA981241 ← O
34 AIR SWING MOTOR 1 CWA981299 ← O
35 CAP - DRAIN TRAY 1 CWH521259 ←
36 HORIZONTAL VANE COMPLETE 1 CWE24C1555 ←
37 HORIZONTAL VANE COMPLETE 1 CWE24C1514 ←
38 REMOTE CONTROL COMPLETE 1 CWA75C4543 ← O
39 REMOTE CONTROL HOLDER 1 CWH361162 ←
40 FRONT GRILLE COMPLETE 1 CWE11C6133 ← O
41 INTAKE GRILLE COMPLETE 1 CWE22K1670 ←
42 GRILLE DOOR COMPLETE 1 CWE14C1091 ←
43 AIR FILTER 2 CWD001389 ← O
44 SCREW - FRONT GRILLE 2 XTT4+16CFJ ←
45 CAP - FRONT GRILLE 2 CWH521294A ←
46 DRAIN HOSE 1 CWH851173 ←
47 INSTALLATION PLATE 1 CWH361134 ←
48 PARTICULAR PIECE - TERMINAL 1 CWD933137 ←
49 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C1705 ←
50 OPERATING INSTRUCTION 1 CWF569797 ←
142
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-S9RKV CS-S12RKV REMARK
51 INSTALLATION INSTRUCTION 1 CWF616620 ←
52 INSTALLATION INSTRUCTION 1 CWF616621 ←
53 POWER SUPPLY CORD - COMPLETE 1 CWA20C3054 ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
143
18.1.2 CS-S18RKV CS-S24RKV CS-S28RKV
45 CWH55025J
O/I 51 I/I 52
50
4 CWH55051J
3
I/I 53
49
18
2
21 5
1
24
19 23 8 29
22 9
20 7
42
10 17 25
11
13
43 44 14
12
46 27
47 15
16
26
AIR
CON
DITIO
NER
iAUTO
iA MOD
UTO-X
-X E
i AUTO
-X
OFF/O
N
ECO
MOD NAV
AUTOE
COM
I
FORT NAN
48
TEM OE-G
P
QUI
ET
TIME FAN AIR
R
SPEED SWIN
ON G
1
OFF
2 SET
SET
3
CHECK
CANCE
L
CLOCK AC
RC
RESET
37 41
40
31
33
34
30 35
32
36
39
38
28
54
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
144
REF.
SAFETY PART NAME & DESCRIPTION QTY. CS-S18RKV CS-S24RKV CS-S28RKV REMARK
NO.
1 CHASSIS COMPLETE 1 CWD50C1604 ← ←
2 FAN MOTOR 1 L6CBYYYL0037 L6CBYYYL0039 ← O
3 CROSS-FLOW FAN COMPLETE 1 CWH02C1077 ← ←
4 BEARING ASSY 1 CWH64K007 ← ←
5 SCREW - CROSS-FLOW FAN 1 CWH551146 ← ←
6 GENERATOR COMPLETE 1 CWH94C0063 ← ←
7 EVAPORATOR 1 CWB30C4905 CWB30C4911 CWB30C4913
8 FLARE NUT (LIQUID) 1 CWT251030 ← ←
9 FLARE NUT (GAS) 1 CWT251032 CWT251033 ←
10 CLIP FOR SENSOR 1 CWH32142 ← ←
11 CONTROL BOARD CASING 1 CWH102449 ← ←
12 TERMINAL BOARD COMPLETE 1 CWA28C2439 CWA28C2357 CWA28C2305 O
13 PARTICULAR PIECE - TERMINAL 1 CWD933137 ← ←
14 ELECTRONIC CONTROLLER - MAIN 1 CWA73C8828 CWA73C8829 CWA73C8830 O
15 ELECTRONIC CONTROLLER - HVU 1 N0GE1F000007 ← ← O
ELECTRONIC CONTROLLER -
16 1 CWA747894 ← ← O
INDICATOR
17 SENSOR COMPLETE 1 CWA50C2401 ← CWA50C2782 O
18 SENSOR COMPLETE (ECO) 1 CWA50C3292 ← ← O
ELECTRONIC CONTROLLER (ECO
19 1 CWA745791 ← ← O
SENSOR)
ELECTRONIC CONTROLLER (ECO
20 1 CWA746206 ← ← O
SENSOR)
ELECTRONIC CONTROLLER
21 1 CWA747891 ← ← O
(COMPARATOR)
22 LEAD WIRE - PCB ECO 1 CWA68C1985 ← ←
CONTROL BOARD CASING FOR PCB
23 1 CWD933929 ← ←
ECO
CONTROL BOARD CASING FOR PCB
24 1 CWD933930 ← ←
ECO
25 CONTROL BOARD TOP COVER 1 CWH131467 ← ←
26 INDICATOR HOLDER 1 CWD933928 ← ←
CONTROL BOARD FRONT COVER
27 1 CWH13C1247 ← ←
CO.
28 DISCHARGE GRILLE COMPLETE 1 CWE20C3545 ← ←
29 BACK COVER CHASSIS 1 CWD933031A ← ←
30 FULCRUM 2 CWH621166 ← ←
31 VERTICAL VANE 11 CWE241457 ← ←
32 CONNECTING BAR (RIGHT) 1 CWE261322 ← ←
33 CONNECTING BAR (LEFT) 1 CWE261316 ← ←
34 AIR SWING MOTOR 1 CWA98K1027 ← ← O
35 AIR SWING MOTOR 1 CWA981304 ← ← O
36 AIR SWING MOTOR 1 CWA981299 ← ← O
37 CAP - DRAIN TRAY 1 CWH521259 ← ←
38 HORIZONTAL VANE COMPLETE 1 CWE24C1556 ← ←
39 HORIZONTAL VANE COMPLETE 1 CWE24C1520 ← ←
40 REMOTE CONTROL COMPLETE 1 CWA75C4543 ← ← O
41 REMOTE CONTROL HOLDER 1 CWH361162 ← ←
42 FRONT GRILLE COMPLETE 1 CWE11C6134 ← CWE11C6135 O
43 INTAKE GRILLE COMPLETE 1 CWE22K1671 ← ←
44 GRILLE DOOR COMPLETE 1 CWE14C1091 ← ←
45 AIR FILTER 2 CWD001393 ← ← O
145
REF.
SAFETY PART NAME & DESCRIPTION QTY. CS-S18RKV CS-S24RKV CS-S28RKV REMARK
NO.
46 SCREW - FRONT GRILLE 3 XTT4+16CFJ ← ←
47 CAP - FRONT GRILLE 3 CWH521294A ← ←
48 DRAIN HOSE 1 CWH851173 ← ←
49 INSTALLATION PLATE 1 CWH361098 ← ←
BAG COMPLETE - INSTALLATION
50 1 CWH82C1705 ← ←
SCREW
51 OPERATING INSTRUCTION 1 CWF569797 ← ←
52 INSTALLATION INSTRUCTION 1 CWF616620 ← CWF616622
53 INSTALLATION INSTRUCTION 1 CWF616621 ← CWF616623
54 POWER SUPPLY CORD - COMPLETE 1 CWA20C2851 CWA20C2853 ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
146
18.2 Outdoor Unit
18.2.1 CU-S9RKV
31
42
29
28
11
25
4
5 19
23
6
27
24
41
12
7
17
35
32
26
22
18 15
13
10
30
9
16
14
33
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
147
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-S9RKV REMARK
1 CHASSIS ASSY 1 CWD50K2240
2 FAN MOTOR BRACKET 1 CWD541235
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951734 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55252J
6 PROPELLER FAN ASSY 1 CWH03K1020
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5SS072XGA21 O
9 ANTI - VIBRATION BUSHING 3 CWH501038
10 NUT - COMPRESSOR MOUNT 3 CWH561096
11 CONDENSER 1 CWB32C4227
12 CAPILLARY TUBE ASSY 1 CWB15K1488
13 DISCHARGE MUFFLER 1 CWB121010
14 HOLDER COUPLING 1 CWH351222
15 2-WAYS VALVE (LIQUID) 1 CWB021422 O
16 3-WAY VALVE (GAS) 1 CWB011343 O
17 TERMINAL COVER 1 CWH171041
18 SOUND PROOF NATERIAL 1 CWG302700
19 SOUND PROOF BOARD 1 CWH151389
22 SENSOR CO - COMP TEMP 1 CWA50C3062 O
23 CONTROL BOARD COVER - TOP 1 CWH131637
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C8789R O
25 ELECTRONIC CONTROLLER - NF 1 CWH16C0945 O
26 TERMINAL BOARD ASSY 1 CWA28K1036J
27 CABINET SIDE PLATE CO. 1 CWE04C1404
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2502 O
29 CABINET SIDE PLATE (LEFT) 1 CWE041778A
30 CABINET FRONT PLATE CO. 1 CWE06K1106
31 CABINET TOP PLATE 1 CWE031041A
32 CONTROL BOARD COVER 1 CWH131325
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1186
35 STRAINER 1 CWB11025
41 PLATE SPRING 1 CWH71044
42 WIRE NET 1 CWD041057A
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
148
18.2.2 CU-S12RKV
31 42
34
28
29
11
19
4
5 23
24
6 27
36
7
12
26
35
18
32
21 17
22
13
15
30
10
16
9 14
33
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
149
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-S12RKV REMARK
1 CHASSIS ASSY 1 CWD50K2071
2 FAN MOTOR BRACKET 1 CWD541030
3 SCREW - FAN MOTOR BRACKET 2 CWH551217
4 FAN MOTOR 1 CWA951466 O
5 SCREW - FAN MOTOR MOUNT 4 CWH55406J
6 PROPELLER FAN ASSY 1 CWH03K1010
7 NUT - PROPELLER FAN 1 CWH56053J
8 COMPRESSOR 1 5RS092XJA21 O
9 ANTI - VIBRATION BUSHING 3 CWH50077
10 NUT - COMPRESSOR MOUNT 3 CWH561096
11 CONDENSER 1 CWB32C4214
12 CAPILLARY TUBE ASSY 1 CWB15K1521
13 DISCHARGE MUFFLER 1 CWB121010
14 HOLDER COUPLING 1 CWH351233
15 2-WAYS VALVE (LIQUID) 1 CWB021564 O
16 3-WAY VALVE (GAS) 1 CWB011663 O
17 TERMINAL COVER 1 CWH171039A
18 NUT - TERMINAL COVER 1 CWH7080300J
19 SOUND PROOF BOARD 1 CWH151172
21 SOUND PROOF MATERIAL 1 CWG302431
22 SENSOR CO - COMP TEMP 1 CWA50C2205 O
23 CONTROL BOARD COVER - TOP 1 CWH131264
24 ELECTRONIC CONTROLLER - MAIN 1 CWA73C8986R O
26 TERMINAL BOARD ASSY 1 CWA28K1036J O
27 CABINET SIDE PLATE CO. 1 CWE04C1116
28 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2764 O
29 CABINET SIDE PLATE (LEFT) 1 CWE041248A
30 CABINET FRONT PLATE CO. 1 CWE06C1039
31 CABINET TOP PLATE 1 CWE031014A
32 CONTROL BOARD COVER 1 CWH131301
33 CONTROL BOARD COVER - COMPLETE 1 CWH13C1211
34 HANDLE 1 CWE161010
35 STRAINER 1 CWB11025
36 REACTOR 1 G0C752K00001
42 WIRE NET 1 CWD041111A
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
150
18.2.3 CU-S18RKV CU-S24RKV
36
33
42
34
5
6
7 26
31 12
11 15
9
10
19 30
29
40
37
35 32
21
20
3 28
4
14
38
22
41 2
39
8 16
1 18
17
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
151
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-S18RKV CU-S24RKV REMARK
1 CHASSIS ASSY 1 CWD52K1249 ←
2 ANTI - VIBRATION BUSHING 3 CWH50077 ←
3 COMPRESSOR 1 5RD132XHA21 ← O
4 NUT - COMPRESSOR MOUNT 3 CWH561096 ←
5 SOUND PROOF MATERIAL 1 CWG302600 ←
6 FAN MOTOR BRACKET 1 CWD541154 ←
7 FAN MOTOR 1 CWA951762 ← O
8 SCREW - FAN MOTOR BRACKET 3 CWH551217 ←
9 SCREW - FAN MOTOR MOUNT 4 CWH55252J ←
10 PROPELLER FAN ASSY 1 CWH03K1017 ←
11 NUT - PROPELLER FAN 1 CWH561092 ←
12 CONDENSER 1 CWB32C3085 CWB32C3089
14 CAPILLARY TUBE ASSY 1 CWB15K1362 CWB15K1363
15 STRAINER 1 CWB11025 ←
16 HOLDER COUPLING 1 CWH351225 ←
17 3-WAY VALVE (GAS) 1 CWB011670 CWB011656 O
18 2-WAYS VALVE (LIQUID) 1 CWB021462 ← O
19 SOUND PROOF BOARD 1 CWH151257 ←
20 TERMINAL COVER 1 CWH171039A ←
21 NUT - TERMINAL COVER 1 CWH7080300J ←
22 SENSOR CO - COMP TEMP 1 CWA50C2185 ← O
26 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2517 ← O
28 REACTOR 1 G0C153J00005 ← O
29 TERMINAL BOARD ASSY 1 CWA28K1036J ←
30 ELECTRONIC CONTROLLER - MAIN 1 CWA73C8987R CWA73C8988R O
31 CONTROL BOARD COVER - TOP 1 CWH131333 ←
32 CABINET SIDE PLATE 1 CWE041555A ←
33 HANDLE 1 CWE161010 ←
34 CABINET SIDE PLATE CO. 1 CWE041520A ←
35 CABINET FRONT PLATE CO. 1 CWE06K1077 ←
36 CABINET TOP PLATE 1 CWE031083A ←
37 CONTROL BOARD COVER 1 CWH131409A ←
38 CONTROL BOARD COVER - COMPLETE 1 CWH13C1238 ←
39 RECEIVER 1 CWB14011 ←
40 CAPACITOR 1 DS461305QP-A ← O
41 SOUND PROOF MATERIAL 1 CWG302292 ←
42 WIRE NET 1 CWD041155A ←
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
152
18.2.4 CU-S28RKV
45
40 51
41
31
6
38 12
11 19
9
10
23 37
34
35
53
33
43 39
25 54
24
32 4
5
52
46
50
30
49 2
14
13
8 20
1 22
21
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
153
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-S28RKV REMARK
1 CHASSIS ASSY 1 CWD52K1230
2 ANTI - VIBRATION BUSHING 3 CWH50055
3 PACKING 1 CWB81043
4 COMPRESSOR 1 5KD240XAF21 O
5 NUT - COMPRESSOR MOUNT 3 CWH561049
6 FAN MOTOR BRACKET 1 CWD541126
7 FAN MOTOR 1 CWA951712 O
8 SCREW - FAN MOTOR BRACKET 3 CWH551217
9 SCREW - FAN MOTOR MOUNT 4 CWH551040J
10 PROPELLER FAN ASSY 1 CWH001019
11 NUT - PROPELLER FAN 1 CWH561092
12 CONDENSER 1 CWB32C3508
13 EXPANSION VALVE 1 CWB051018J
14 V-COIL COMPLETE 1 CWA43C2258
19 STRAINER 1 CWB111032
20 HOLDER COUPLING 1 CWH351228
21 3-WAY VALVE (GAS) 1 CWB011363 O
22 2-WAYS VALVE (LIQUID) 1 CWB021464 O
23 SOUND PROOF BOARD 1 CWH151197
24 TERMINAL COVER 1 CWH171039A
25 NUT - TERMINAL COVER 1 CWH7080300J
30 SENSOR CO - COMP TEMP 1 CWA50C2185 O
31 SENSOR CO - AIR TEMP AND PIPE TEMP 1 CWA50C2517 O
32 REACTOR 1 G0C452J00002
33 CONTROL BOARD COVER 1 CWH131332
34 TERMINAL BOARD ASSY 1 CWA28K1076J
35 TERMINAL BOARD ASSY 1 CWA28K1162
37 ELECTRONIC CONTROLLER - MAIN 1 CWA73C8989R O
38 CONTROL BOARD COVER-TOP 1 CWH131333
39 CABINET SIDE PLATE (RIGHT) 1 CWE041319A
40 HANDLE 1 CWE161010
41 CABINET SIDE PLATE CO. (LEFT) 1 CWE041317A
43 CABINET FRONT PLATE CO. 1 CWE06K1063
45 CABINET TOP PLATE 1 CWE031083A
46 CONTROL BOARD COVER - COMPLETE 1 CWH13C1185
49 SOUND PROOF MATERIAL 1 CWG302951
50 SOUND PROOF MATERIAL 1 CWG302246
51 WIRE NET 1 CWD041128A
52 RECEIVER 1 CWB14017
53 CAPACITOR 1 DS461355QP-A O
54 ELECTRONIC CONTROLLER - NF 1 CWA746924 O
(Note)
All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
“O” marked parts are recommended to be kept in stock.
Printed in Malaysia
YB0315-0
154