HIGH-SPEED

DC CIRCUIT BREAKERS
type UR26
RAIL VEHICLES

0.9 KV
1.8 KV
3.6 KV
GENERAL INFORMATION
The UR26 are DC high-speed, current-limiting, DC MODBOX® is a modular platform where the DC
circuit breakers with natural cooling. They are trip circuit breaker is integrated alone or with other
free, single pole, bi-directional and equipped with high and low voltage components (contactors,
electromagnetic blow-out, electric control circuits disconnectors, resistors, voltage and current
and direct over-current instantaneous release. sensors…) in a light and compact metal box. This
With its simple design and high insulation level, the way, rolling stock manufacturers can be supplied
UR range offers a very high reliability as well as an with a fully tested “Plug & Play” unit, easy to install
exceptionally long lifetime. and highly valuable for project management and
To guarantee a safe and optimized installation of its logistics.
circuit breakers in different environments, Sécheron With its proven worldwide experience and
offers a large range of standard and customized acceptance, Sécheron’s circuit breaker is the key
solutions. The circuit breaker of the UR range can product to guarantee the highest safety to rolling
be delivered with an insulating housing for indoor stock material and to the people operating or
installation, or for outdoor use, in DC MODBOX® using it.
or in a polyester protective enclosure.

APPLICATIONS
DC Traction vehicles to protect propulsion
UR26 BTE03.04 and auxiliary equipment. All equipment
DC circuit DC earthing indicated with a product name are in
breaker device Sécheron’s scope of supply.

BMS RS
Contactors Disconnector &
earthing
Surge Voltage sensor MMC
Arrester Master
controller
KM
Key multiplier

BSV
DL pantograph
door lock interlocking
® device
BOX
MOD
ge DC
volta tem
High ated sys
t e g r
In

Contactors
BMS

MAIN BENEFITS
D High insulation voltage.
D High rated short-circuit making and breaking capacity.
D Limited maximum arc voltage.
D Heavy duty with operational frequency C3.
D A large number of different options to match various application requirements.
D Available also for dual voltage 1.8/3.6 kVDC applications (UR26-DV).
D Optional integrated control module, to manage closing and holding sequences.
D Very low maintenance requirements.
D Proven design with worldwide experience and acceptance.

2 HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES


MAIN FEATURES
y Rated operational voltage 900 VDC ; 1,800 VDC ; 3,600 VDC and 1,800/3,600 VDC (dual voltage)
y Rated insulation voltage 3,000 VDC or 4,800 VDC
y Conventional free air thermal current: 2,300 A (UR26/UR26DV)
y Electro-magnetic closing with electric holding
y Five double contacts auxiliary switches
y Insulation material according to EN45545-2
y Reference standards: EN/IEC60077-3, IEC61373
y Certified according to Loc&Pas TSI for interoperability

BREAKING CURRENT PARAMETERS


IEC-60077
I T
A2 A2 = Peak of Short-circuit

0.63 A2 A0 = Setting of maximum current release


A4 = Cut-off current
di/d

di/dt = Initial current rate of rise


A4
t

T = Circuit time constant


A0 Ur = Rated operational voltage
t3 t
U V2 = Peak of the arc voltage
V2
t1 = Opening time
Ur t3 = Total break time

t1 t

OPENING TIME T1

t 1 20
[ms] Relationship between opening time t1 and the initial
18
rate of rise of current di/dt for direct instantaneous
16
over-current release.
14
12 Example for a di/dt of 3x106 A/s:
10
8
- for UR26: t1 ~ 4.3 ms.
UR26
6
4
2 Note: for a shorter opening time on low di/dt, the “indirect release”
(shunt trip) option can be used (refer to “Options” section page 7).
0
3.105 5 7 106 3 5 7 107 3
di/dt [A/s]

t l 10
[ms]
8
6
4
UR60/80
2
0
3.105 5 7 106 3 5 7 107 3
di/dt [A/s]

HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES 3


DATA FOR PRODUCT SELECTION
Symbol Unit UR26
Arch chute type 81 82 64 DV64
MAIN HIGH VOLTAGE CIRCUIT
Rated operational voltage Ur [VDC ] 900 1,800 3,600 1,800 3,600
Rated insulation voltage UNm [VDC ] 3,000 4,800
Conventional free air thermal current (1) Ith [A] 2,300
Rated operational current Ir [A] 2,300
Operational frequency C3
Power-frequency test voltage (50 Hz/1min) (2) Ua [kV] 9.2 15
Over-voltage category OV3
Rated impulse voltage (1.2/50 μs) (2) UNi [kVDC ] 20 30
Rated short-circuit making A2/T1 [kA]/ [ms] 100/0 80/0 40/0 100/0 70/0
& breaking capacity / Time constant (3) A2/T2 [kA]/ [ms] 100/15 80/15 35/15 80/15 35/15
A2/T3 [kA]/ [ms] 50/50 75/40 35/30 75/40 35/30
A2/T4 [kA]/ [ms] 13/150 20/100 35/50 20/100 35/30
Direct over-current instantaneous release [kA] 1.4 - 2.7
[kA] 2.0 - 5.0
Maximum arc voltage [kV] ≤ 2.5 ≤ 4.0 ≤ 8.0 ≤ 6.0 ≤ 8.0
(1)
At Tamb = +40°C and tested with high voltage connections according to standard IEC/EN 60943.
(2)
Values applicable for factory tests on serial products according to IEC60077-3:2019. (3) The values given refer for stand-alone circuit breaker (not in enclosure).
LOW VOLTAGE CIRCUIT
Control voltage
Nominal supply voltage Un [VDC] 24, 36, 48, 64, 72, 110 (4)
Range of voltage [0.7 - 1.25] Un
Nominal closing power (5) Po [W]/[s] 1,300/1
Nominal holding power for electrical holding (5) [W] 2.3
Mechanical opening time (5) (6) to [ms] 15 - 30
Mechanical closing time (5) (6) tc [ms] ~ 150
Mechanical switching power / time (5) (6) (7) Pc [W]/[s] 400/1 (6)
Mechanical switching time (not included pulse time) (7) [ms]
- From 1,800 VDC to 3,600 VDC ≤100
- From 3,600 VDC to 1,800 VDC ≤60
Power frequency test voltage Ua [kV] 2
(4) (5) (6)
24 VDC and 110 VDC available for dual voltage breakers UR26DV. For other voltages, please contact Sécheron. At Un and Tamb = +20°C • When signal is
received by the coil. (7) Voltage selector switch for dual voltage breaker UR26DV.
Auxiliary contacts
Type of contacts DC circuit breaker Potential free (PF)
Voltage selector switch change-over (CO)
Number of auxiliary contacts DC circuit breaker 5a + 5b (Potential free (PF))
Voltage selector switch (Dual Voltage breaker) 2a + 2b (Change-over (CO))
Rated voltage [VDC] 24 to 110
Conventional thermal current Ith [A] 10
Switching categories according to EN60947 [A] DC-13 110 VDC 0.5 A
Minimum let-through current at 24 Vdc (7) [mA] ≥ 10 (silver contacts) or 4 ≤ I < 10 (gold contacts)
(7)
For a dry and clean environment.

Low voltage interface


Connector type (8) Harting type Han® 32 EE or Han® 40 EE
(8)
Refer to page 5 for mobile connector information.
OPERATING CONDITIONS
Installation Indoor /outdoor (9)
Altitude (10) [m] ≤ 2,000
Working ambient temperature (11) Tamb [°C] - 25 to + 70
Relative Humidity 95 % at 40°C
Pollution degree PD3
Minimum mechanical durability N [Operations] 4x50,000

(9)
Outdoor with optional enclosure or DC MODBOX® (refer to page 9 to 11). (10) For altitude >2,000m, please contact Sécheron. (11) For -50°C ≤ Tamb < -25°C a special
configuration of DC circuit breaker can be delivered by Sécheron on request.

4 HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES


INFORMATION FOR PRODUCT INTEGRATION
MAIN FEATURES Dimensions without tolerances are
indicative. All dimensions are in mm. The
Weights (1) [Kg] maximum allowed flatness deviation of the
UR26 UR26-DV support frame is 0.5 mm.

arc chute 81 85 _
(1)
Approximate weight for standard
arc chute 82 95 _ circuit breakers without option, including
arc chute 64 159 167 maintenance arc chute lifting mechanism.

UR26 Dimensions [mm]


617
UR26-81/82 UR26
168
238 419
69
A 645
B 131

51
R4 C 131
80
D 20

784
HV connectors

D 95 100
HV 40 25
A A

20
386
B

176
24

50
160 C
4x Ø14
4x Ø11

25
240 194 320 B
300 A
B 40 25

UR26-64/-DV64

25
478 700
320

50
4x Ø14

25
Dimensions [mm]
UR26
1035

A 646
B 140
C 140
D 95 100

HV D 20
370

= =
180
13

4x Ø14

320 C
365 206 300 B
A

INSULATION
Arc chute 81/82 Arc chute 64
(1)
At maximum short-circuit breaking
430 81: 469 490 790
capacity. For other installation conditions,
82: 667
contact Sécheron.
1,534

1,165

Note: For insulating distances to earth,


contact Sécheron.

HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES 5


Rs

F2 E2

LOW VOLTAGE CONTROL SCHEME


UR26/40/46
S
UR26/36/40/46
UR26/36/40/46
V=
+
V=
V=
S
S E1 F1
Rp
ELECTRIC HOLDING
+
+ E1 F1
E1 Rp F1
Rp Rs
E-Type Rs
Rs

y The circuit breaker remains closed F with a reduced


E ‘’holding’’ 2 2
F E
current. To open the circuit breaker the holding current is cut off.
– 2 2
– F2 E2

y With E-type closing device, the circuit breaker cannot remain closed
UR60/80
UR60/80
V= S
S
if the
I
Alow voltage supply is lost.
A B C D V=
V=
S
S
V= Iee B C D +
+
+ UR26/40/46/60/80
100%
+ E1
E1 UR60/80
F 100% F1
F
A F1 S
E S B C D V=
B C GD V=
F, G FF : Iecontrol contacts
R1 Rs
G R1 Rs +
Note: The duration of the closingE1pulse as
2

t [s] + t [s] R1 100%


2

: EEholding resistor
t [s] 0 t [s] well as the opening pulse should be 0.5 - 1 s.
F
2


0
~ 20%
~ 20% 0

S– : automatic circuit breaker
2
F1
0,5 1 tc t +1
0 0,5 1 tc tc+0.5 tcc+1
tc+0.5

G R1 Rs
F2
Customer scope
t [s] t [s]
RUR Sécheron
0 scope E2
– ~ 20% –
0,5 1 Maintien magnétique pour UR60/80
Maintien magnétique pour UR60/80 A
(maintien électrique idem que UR26-36-40-46) A 0 0,5 1 tc tc+1
(maintien électrique idem que UR26-36-40-46) tc+0.5
B
B

TYPICAL VALUE FOR CLOSING CCCOILS


D
D
Coil characteristics
E Note: for components selection, the
E
Closing pulse following criteria shall apply:
Holding E-type
0.5 to 1s Maintien magnétique pour UR60/80 Unom = RxInom for Tamb = +20°C
Umin = RxImin forA Tamb = -5°C
Un Inom Imin E Imin M (maintien
Imax R1électrique
nom
Inom idem que UR26-36-40-46)
Imin Imax
Umax = Rx for Tamb = +40°C
Imax
(R = Resistance) B
[VDC] [A] [A] [A] [A] [Ω] [A] [A] [A]
Standard: xxxx 23
24 41.7 (WI) 22.5 25 70.9 11.4 2.0 1.4
(I>) (WI) 2.5 24 I
Standard: xxxx 23
C
36 32.7 27 25 17.7
(WI) 19.6 55.6 25 1.4 1.0
(I>)
31 29 251.7
(WI)
27 24
32
I 15 14 12 11 9 8 6 5 3 2

48 20.9 27 25 11.3 12.5 35.4 45.7 1.0 0.7


31 29 27 251.3
32
15 14 12 11 9 8 D6 5 3 2

64 17.6 9.5 10.6 29.9 79.4 0.8 0.5 1.0


19 17 15 13 11 9 7 5 3 1
72 16.4 28 26 8.8 9.8 27.8 100 0.7 0.5
32 30 28 260.9
31
13 10 7
E4 1
19 17 15 13 11 9 7 5 3 1
110 11.7 6.3 7.0 19.9 210 0.5 0.4 28 260.6
31
I>

HARTING
28 26 32 30 13 10 7 4 1

I>

LOW VOLTAGE WIRING DIAGRAMS


HARTIN
20 18 16 14 12 10 8 6 4 2
20 18 16 14 12 10 8 6 4 2 Legend of the schemes :

HARTING
HART
HARTING TYPE HAN® 32 EE OR HARTING TYPE
I> HAN
I (I>) ® 40
(WI) EE

HARTIN
(WI) a b a b
(WI) I> I (I>) (WI) a b a b Circuit breaker

HARTING
main contact

HARTING
UR26
Brochure
Brochure Brochure
b b
19 17 15 13 11 9 7 5 3 1 Voltage selector switch

Brochure
HARTING
b b
22 24

HARTING
main contact
ARC CHUTE
a a

HART
a a 19 17 15 13 11 9 7 5 3 1
22 24
81, 82 OR 64 Closing
a b a coil
b (WI) I> I (I>) (WI)

HARTIN H
HA
21 23
(1) a b a b (WI) I> 8 6 I (I>) (WI)
Low voltage connector interface
20 18 16 14 12 10 4 2

Brochure Brochure
(male pin) b

HARTING
b

HARTIN
Standard: xxxx

HA
(1)

HA
21 23
20 18 16 14 12 10 8 6 a4 2b a b (WI) I>I> I a (I>) (WI)a
Overcurrent
I (I>) tripping

Brochure Brochure
a b a b (WI) (WI)
Standard: xxxx
b b

HAR
HAR
23 a a

HAH
I
Type : CO Brochure Brochure
1a+1b - Switch CO
b b
24 a b

Brochure Brochure
b b
23
I
Type : CO
a a

BrochureHAR
circuit-breaker

24 a a

32 34
19 17 15 13 11 9 a 7 b5a 3b 1 (WI) I> a I
1a+1b
b a(I>) b (WI) - Switch
(WI) I> PF I (I>) (WI)

UR26
circuit-breaker

HART
19 17 15 13 11 9 7 5 3 1

H
34
32 34
ARC CHUTE DV64 only
b for 24 V

Brochure Brochure
Brochure
breaker

b b b
a b a b
34 DC
34 a a a a
34 33 31 33
(1)
20 18 16 14 12 10 8 6 4 2
circuit

(1)
33 31 33
I> 20 18 16 14 12 10 8 6 4 2
DCDCDC

I>
selector

2136 24 27
Voltageselector
selector

2136 24 27
switch
switch
switch

Note: Low voltage connectors are delivered with


Voltage

(1)
2235 25 23 2826 all pins mounted. The voltage selector switch is
Voltage

2235
(1)
25 23 2826 represented in 3.6 kV position.
(1)
Double cable only for 24 VDC control voltage.

6 HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES19 17


22 24
(1)
15 13 11 9 7 5 3 1
(1)
22 24 19 17 15 13 11 9 7 5 3 1
OPTIONS (SUBJECT TO ADDITIONAL COST AND LONGER DELIVERY TIME)

ECO-DRIVE INTEGRATED CONTROL MODULE

ECO-Drive is a compact control module


ECO-Drive integrated with UR circuit breakers, to
manage closing-holding sequences. ECO-
Drive is installed on the UR breaker’s
closing device.

MAIN BENEFITS
D No more additional hardware to manage the closing-holding sequences.
D Reduction of the overall space necessary to operate the circuit breaker.
D Reduction of overall installation costs of the DC circuit breakers.
D Reduction of holding power consumption and operational costs.
D Reduction of the risks of damaging the closing coil during commissioning and service.

LOW VOLTAGE WIRING DIAGRAM

The UR breaker together with the ECO-Drive is fully compliant for elec-
tromagnetic compatibility with EN 50121-3-2 and with EN 50155: § 5.1.1.2
short (10 ms) interruptions class S2 and § 5.1.3: voltage dips / variation
(at 0.6 Un during 100 ms) class C1.

19 17 15 13 11 9 7 5 3 1
28
k0 Harting connector
26 Vbat P
+
Un
Vbat N 4
25 Sécheron’s scope
UR26

- C
27
k1
22 ORDP
D Customer’s scope
+ 3
U EF Only for 24 VDC
- 21 ORDN
20 18 16 14 12 10 8 6 4 2

31 34
38
Selector switch

k2
30
+
Un
- 29

37
32 33 35 36
UR26DV

19 17 15 13 11 9 7 5 3 1
28
k0
26 Vbat P
+
Un
DC circuit breaker

25 Vbat N 4
-
27
k1
22 ORDP 3
+
U EF
- 21 ORDN
20 18 16 14 12 10 8 6 4 2

HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES 7


CONTROL CIRCUIT TECHNICAL DATA

Control circuit

Nominal supply voltage (1) Un [VDC] 24; 64, 72; 110


Nominal control voltage (1) UEF [VDC] [24 - 110]
Range of voltage Un [ 0.7 - 1.25 ]
Idle (standby) power [W] <3
Nominal closing power (2) Pc [W]/ [s] 1,300/0.5

(1)
Control voltage UEF and supply voltage Un
Nominal holding power (2) [W] <8 can be different.
Nominal opening power (2) [W] <3
At Un and Tamb = +20°C.
(2)

Mechanical opening time on opening order (3)


[ms] 15-30
Starting when the signal is received by the coil.
(3)
Mechanical closing time on closing order (2) (3) To [ms] ~150

INDIRECT RELEASE BI24


The indirect release enables The indirect release BI24 is
to shorten the breaker’s triggered by the control unit
opening time t1 down to about type CID-3 (not included with the
4 ms, independent of the circuit breaker - to be ordered
di/dt conditions (see graph separately - refer to CID3
page 2), when required by specific brochure SG101783B...).
applications.

MOBILE CONNECTOR
Mobile connector (without cable)

Auxiliary switches Fixed Number of pin


Control (delivered with
connector connector) Cable Sécheron’s
voltage Connector
type gland number
Size Size
Device Number Type
2.5 mm² 1.5 mm²

UR26
24,36, 48, 64, Harting
(without 5a+5b PF 4 28 M32 SG104063R40400
72, 110 VDC HAN® 32 EE
ECO-Drive)

UR26
24, 64, 72, Harting
(with 5a+5b PF 4 28 M32 SG104063R40400
110 VDC HAN® 32 EE
ECO-Drive)

UR26-DV
5a+5b PF Harting
(without 24 VDC 4 36 M32 SG104063R40500
2a+2b CO HAN® 40 EE
ECO-Drive)

UR26-DV
5a+5b PF Harting
(without 110 VDC 4 28 M32 SG104063R40400
2a+2b CO HAN® 32 EE
ECO-Drive)

UR26-DV
5a+5b PF Harting
(with 24, 110 VDC 4 36 M32 SG104063R40500
2a+2b CO HAN® 40 EE
ECO-Drive)

8 HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES


CONCEPTS FOR INTEGRATION ON VEHICLES
Sécheron proposes 3 different concepts to integrate the UR26/40 circuit
breakers in vehicles:
y Complete Plug & Play roof or underframe-mounted polyester
enclosure, in which the DC circuit breaker is installed, and that
offers an IP54 protection index. It is intended for metros, DC EMUs
and trains.
y Insulation housing with protection index IP00, delivered as
an option separately from the breaker. It enables the car builder
to build its own metal enclosure and/or container with reduced
dimensions, in which the DC circuit breaker with its insulation
housing will be installed. This type is mostly used for locomotives
and trains.
y Complete Plug & Play metal enclosure (DC MODBOX® program),
in which the DC circuit breaker is installed with other functions,
such as current & voltage measurements, line and charging
contactors, charging resistors, disconnect and/or earthing switch.
DC MODBOX® offers an IP56 protection index for outdoor roof or
underframe mounting. This type is mostly used for trains and high-
speed trains, as well as for applications with severe operational
environments (cold and icy, dusty or sandy environments).

PLUG & PLAY ROOF-MOUNTED POLYESTER ENCLOSURE


UR26-82TCP These enclosures can be directly mounted
Roof mounting (IP54) on the vehicle’s roof.

Valid for UR26-82


Rated voltage 1,800 VDC
Free air thermal current 2,300 A
Enclosure material Insulation material
Enclosure colour Blue grey RAL 7031
Enclosure thickness 6 mm
Protection index IP IP54
Opening of the box cover On low voltage connector side
Maximum breaking capacity 100 kA (T1)
Insulation distance around the
Not needed
enclosure
555
High voltage cable interface 1 cable plate with 4 cable glands M32x1.5 17
68
Low voltage cable interface Harting HAN® 32 EE connector on enclosure 0
90

UR26-64TCP
Roof mounting (IP54)
Valid for UR26-64 / UR26-DV64
Rated voltage 3,600 VDC / 1,800 VDC- & 3,600 VDC
Free air thermal current 2,300 A
Enclosure material Insulation material
Enclosure colour Blue grey RAL 7031
Enclosure thickness 6 mm
Protection index IP IP54
Opening of the box cover On low voltage connector side
Maximum breaking capacity 50 kA (T1) / available on request.
Insulation distance around the
Not needed
enclosure
496

High voltage cable interface 1 cable plate with 4 cable glands M32x1.5
15
Low voltage cable interface Harting HAN® 32 EE connector on enclosure 08
0
90

HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES 9


PLUG & PLAY UNDERFRAME-MOUNTED POLYESTER ENCLOSURE

UR26-80TCS
Underframe mounting (IP54)
Valid for UR26-80 (shorter version of arc chute 81)
Rated voltage 900 VDC
Free air thermal current 2,150 A
Enclosure material Insulation material
Enclosure colour Graphite grey RAL7024
Enclosure thickness 6 mm
Protection index IP IP54

525
Opening of the box cover From below the box
Maximum breaking capacity 50 kA (T1)
1,0 8
Insulation distance around the 50 99
Not needed
enclosure
High voltage cable interface 1 cable plate with 8 cable glands M32x1.5
Low voltage cable interface Harting HAN® 32 EE connector on enclosure

UR26-82LTCS
Underframe mounting (IP54)
Valid for UR26-82L (shorter version of arc chute 82)
Rated voltage 1,800 VDC
Free air thermal current 2,150 A
Enclosure material Insulation material
Enclosure colour Graphite grey RAL7024
Enclosure thickness 6 mm
Protection index IP IP54
Opening of the box cover From below the box

525
Maximum breaking capacity 50 kA (T1)
Insulation distance around the
Not needed 1,0 8
enclosure 50 99
High voltage cable interface 1 cable plate with 8 cable glands M32x1.5
Low voltage cable interface
INSULATION HOUSINGSHarting HAN 32 EE connector on enclosure
®

The insulation housings have to be ordered additionally to the DC circuit


breaker (see page 12).
FOR HORIZONTAL UNDERFRAME MOUNTING
UR26/26DV-64TCS This housing is designed to minimize the
Underframe mounting (IP00) necessary insulation clearance distances
against earth, when the circuit breaker is
Valid for UR26-64 / UR26-DV64 integrated in the car builder’s own metal
enclosure.
Rated voltage 3,600 VDC / 1,800 VDC & 3,600 VDC
Rated insulation voltage 4,800 VDC
Protection index IP IP00
Opening of the box cover Knurled knobs
Maximum breaking capacity Available on request
Insulation distance around the
Available on request
enclosure
Enclosure opening for cable connection
High voltage cable interface
to the circuit breaker
Direct connection on circuit breaker’s
Low voltage cable interface
connector
450

114
0
850

10 HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES


FOR VERTICAL INDOOR MOUNTING

The purpose of this housing is to minimize


UR26/26DV-64TDP the necessary insulation clearance distances
Indoor mounting (IP00) against earth, when the circuit breaker is
integrated in the car builder’s own metal
Valid for UR26-64 / UR26-DV64 enclosure/container.
Rated voltage 3,600 VDC / 1,800 VDC & 3,600 VDC
Free air thermal current 2,300 A
Enclosure material Insulation material
Enclosure colour Beige RAL 7016
Enclosure thickness 4 mm
Protection index IP IP00

1160
Opening of the box Knurled knobs
Maximum breaking capacity Available on request
Insulation distance around the
Available on request 80
enclosure 0 3
50
Enclosure opening for cable connection on
Interface for high voltage cable
circuit breaker
Direct connection on circuit breaker’s
Interface for low voltage cable
connect

DC MODBOX®
DC MODBOX® is a compact metal can be, to a certain extent, adapted solutions to solve constraints
clad, “plug and play’’, project-based to the application requirements. related to roof space, insulation
solution, featuring several high Typically electric schemes, integrat- and speed. Moreover it allows the
voltage DC components located ed components, as well as both high voltage DC components to
around the DC circuit breaker. high- and low-voltage interfaces operate protected from the most
Built on a standard platform can be customized. severe environmental conditions.
of rolling-stock-dedicated With its limited height DC MODBOX® simplifies project
aluminium enclosure and (535 mm) and a shape designed management, logistics, and
standard proven high voltage to match aerodynamic constraints, installation tasks for the car builder.
DC components, DC MODBOX® DC MODBOX ® brings efficient

Functional scope
1.5 kV DC or 3 kV DC To evaluate DC MODBOX® solution that best
suits your project, please contact Sécheron.
(refer to brochure SG580044BEN for more
details).
BSV : Pantograph interlocking box
RS RS UR Imes PCC Rpc SA : Surge arrester
RS : Disconnector & Earthing
Air supply LC Umes : Voltage measurement
Imes : Current measurement
Imes Umes
BSV UR : High speed DC circuit breaker
BTE : Earthing switch
PCC Rpc
BTE MED-M : Manual earthing device
SA

PCC : Precharging contactor


LC LC : Line contactor BMS
Rpc : Precharging resistor

MED-M DC MODBOX®
Let us analyse your traction scheme and
To traction prepare a proposal for a MODBOX ®
equipment adapted to your application and to a safe
To next operation of the integrated components.
safety device

HIGH-SPEED DC CIRCUIT BREAKERS, TYPE UR26 / RAIL VEHICLES 11


DESIGNATION CODE FOR ORDERING
y  e sure to establish the designation code from our latest version of the brochure by downloading it from our website “www.secheron.com”.
B
y Be careful to write down the complete alphanumerical designation code with 17 characters when placing your order.
y The customer shall write down the setting of maximum current release value (Id) in its order form.
y For technical reasons some variants and options indicated in the designation code might not be combined.
y The bold part of this designation code defines the device type, and the complete designation defines the identification number of the product,
as displayed on the identification plate attached to the product.

Example of customer’s choice: UR 26 64 T D Ø E Ø B Ø A C Ø A


Line: 10 11 12 13 14 15 16 17 18 19 20 21 22 23

DESIGNATION CODE* (*)


Options are subject to additional costs

Customer’s
Line Description Designation standard Options
choice
10 Product type UR UR UR
11 Conventional free air thermal current 2,300 A 26
12 Rated operational voltage 900 VDC 81

Signature:
1,800 VDC 82
3,600 VDC 64
1,800 VDC /3,600 VDC DV64
13 Application Rolling stock T T
14 Mounting position Vertical D
Horizontal C
15 Breaker execution Vertical indoor mounting (1) Ø
Horizontal roof mounting with polyester enclosure P
Horizontal underframe mounting (2) S
16 Nominal supply voltage 24 VDC* A
36 VDC B
48 VDC C
64 VDC G
72 VDC D
110 VDC* E

Name:
17 Varistor in coil (3) No Ø
Yes (battery voltage) 1
18 Direct over-current release (bi-directional)
UR26 1.4 - 2.7 kA A
UR26 2.0 - 5.0 kA B
19 Indirect release No Ø
BI24 1
20 Auxiliary contacts (4) 5a + 5b (switch PF) / 2a + 2b (switch CO)-Silver type A
5a + 5b (switch PF) / 2a + 2b (switch CO)-Gold type C
21 LV connector type on circuit breaker (ref. p. 8) Harting type HAN® 32 EE C
Harting type HAN® 40 EE F Place and date:
22 ECO-Drive control module No Ø
Yes (5) 4
23 Digit for Sécheron internal purpose A A

(1)
For execution ordered with additional insulation housing, the housing must be ordered separately (section below) • (2) The insulation housing for the breaker’s
execution UR26-64TCS must be ordered separately (section below) • (3) In case control type “ECO-Drive” is selected (line 22), select “No” for varistor on coil (line 17)
• Based on the selected breaker’s configuration, the number of available auxiliary switches might be reduced • (5) For Nominal supply voltage 24, 64, 72 and 110
(4)

Vdc• * Available for DV64

Value of the setting of maximum current release value (A0): . . . . . . . . . . . . . . [A]


Material to be ordered separetely:
-Insulation housing (refer to page 10): Insulation housing for vertical indoor mounting: SG104420R00002
Insulation housing for UR26-64TCS: HSBT031031R00007
-Low voltage mobile connector (refer to page 8): None SG104063R40400
SG104063R40500
SG105306BEN_A09-03.23

Sécheron SA www.secheron.com
Rue du Pré-Bouvier 25 Tel: +41 22 739 41 11
1242 Satigny - Geneva Fax: +41 22 739 48 11
CH-Switzerland ess@secheron.com

Copyright© • 2023 • Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose