Desig of Two Way & One Way Slab
Desig of Two Way & One Way Slab
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Actual span/depth ratio < Modified span/depth ratio 35.36 < 40.00 SAFE
DESIGN OF TWO WAY SLAB AT GF LVL Slab panel -S2 Rev : 0
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Actual span/depth ratio < Modified span/depth ratio 33.64 < 52.00 SAFE
DESIGN OF TWO WAY SLAB AT GF LVL Slab panel -S3 Rev : 0
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Actual span/depth ratio < Modified span/depth ratio 36.16 < 52.00 SAFE
DESIGN OF TWO WAY SLAB AT GF LVL Slab panel -S5 Rev : 0
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Actual span/depth ratio < Modified span/depth ratio 33.64 < 52.00 SAFE
DESIGN OF TWO WAY SLAB AT 5.10 M LVL Slab panel -S5 Rev : 0
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Actual span/depth ratio < Modified span/depth ratio 20.21 < 40.00 SAFE
DESIGN OF TWO WAY SLAB AT 5.10 M LVL Slab panel -S5 Rev : 0
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Actual span/depth ratio < Modified span/depth ratio 24.76 < 25.59 SAFE
DESIGN OF ONE WAY SLAB ATGF LVL Slab panel S5 Rev: 0
Simply Supported
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe415 fy = 415 N/mm²
Load Calculations:
Self weight of slab = 3.13 kN/m²
Finishing load(0.012+0.05)*21 = 2.13 kN/m²
Live load = 1.50 kN/m²
Actual span/depth ratio < Modified span/depth ratio 33.40 < 38.07 SAFE
DESIGN OF ONE WAY SLAB ATGF LVL Slab panel S5 Rev: 0
Simply Supported
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe415 fy = 415 N/mm²
Load Calculations:
Self weight of slab = 3.13 kN/m²
Finishing load(0.012+0.05)*21 = 1.10 kN/m²
Live load = 7.00 kN/m²
Actual span/depth ratio < Modified span/depth ratio 13.08 < 40.00 SAFE
DESIGN OF TWO WAY SLAB AT 4.2 M LVL
Slab panel -S3
Data:
Concrete M25 fck = 25 N/mm²
Steel Fe 500 fy = 500 N/mm²
Actual Shear Stress < Design Shear Stress 0.206 < 0.532 SAFE
CHECK FOR DEFLECTION
Allowable span / depth Ratio l/d = 26
% of Tension reinforcement provided pt(pro) = 0.327
% of Tension reinforcement req pt(req)) = 0.190
Actual span/depth ratio < Modified span/depth ratio 35.08 < 52.00 SAFE
DESIGN OF TWO WAY SLAB AT 4.50 M LVL
Actual Shear Stress < Design Shear Stress 0.163 < 0.532 SAFE
CHECK FOR DEFLECTION
Allowable span / depth Ratio l/d = 26
% of Tension reinforcement provided pt(pro) = 0.327
% of Tension reinforcement req pt(req)) = 0.162
Actual span/depth ratio < Modified span/depth ratio 34.33 < 52.00 SAFE
DESIGN OF TWO WAY SLAB AT 4.50 M LVL
Actual Shear Stress < Design Shear Stress 0.147 < 0.532 SAFE
CHECK FOR DEFLECTION
Allowable span / depth Ratio l/d = 26
% of Tension reinforcement provided pt(pro) = 0.327
% of Tension reinforcement req pt(req)) = 0.130
Actual span/depth ratio < Modified span/depth ratio 26.00 < 52.00 SAFE
DESIGN OF TWO WAY SLAB AT 4.50 M LVL
Actual Shear Stress < Design Shear Stress 0.139 < 0.532 SAFE
CHECK FOR DEFLECTION
Allowable span / depth Ratio l/d = 26
% of Tension reinforcement provided pt(pro) = 0.327
% of Tension reinforcement req pt(req)) = 0.120
Actual span/depth ratio < Modified span/depth ratio 25.67 < 52.00 SAFE
2 x 350MW CCPP AT PIPAVAV DOC NO.:PE-DC-292-635-C003
CLARIFIED SEA WATER PUMP HOUSE C-1.5
Data:
Concrete M20 fck = 20 N/mm²
Steel Fe 415 fy = 415 N/mm²
Load Calculations:
Self weight of slab = 3.75 kN/m²
Finishing load = 1.50 kN/m²
Pipe load = 0.00 kN/m²
Live load = 10.00 kN/m²
Equipment load = 0.00 kN/m²
file:///conversion/tmp/activity_task_scratch/752315448.xls JV 05/08/2024
752315448.xls
2 x 350MW CCPP AT PIPAVAV DOC NO.:PE-DC-292-635-C003
CLARIFIED SEA WATER PUMP HOUSE C-1.6
Reinforcement:
Required in Shorter Span Reinf Required Reinf Provided
Support #VALUE! - 10 dia @ 150 mm c/c
Mid span #VALUE! - 10 dia @ 150 mm c/c
Required in Longer Span
Support #VALUE! - 10 dia @ 200 mm c/c
Mid span #VALUE! - 10 dia @ 200 mm c/c
Actual Shear Stress < Design Shear Stress 0.246 < 0.579 SAFE
Modification factor for Tension reinf. F1 = 1.35 (From Fig 4 in IS 456 - 2000)
Modification factor for Comp. reinf. F2 = 1.00 (From Fig 5 in IS 456 - 2000)
Actual span/depth ratio < Modified span/depth ratio 31.00 < 35.19 SAFE
file:///conversion/tmp/activity_task_scratch/752315448.xls JV 05/08/2024