ارتفاعات اجهزة الانذار على الحائط
ارتفاعات اجهزة الانذار على الحائط
ارتفاعات اجهزة الانذار على الحائط
The graphic below shows installation requirements for fire alarm equipment such as pull stations, smoke and heat detectors, notification
appliances, and control equipment. This quick reference can help you determine the minimum and maximum heights for wall-mounted fire
alarm equipment as found in the 2022 edition of NFPA 72®, National Fire Alarm and Signaling Code®. Scan the QR code to use NFPA LiNK® to
navigate to the code requirements and related content to learn more or visit nfpa.org/LiNK.
6 in.
12 in.
(150 mm) 4 in. (100 mm) min
6 in. (150 mm) (300 mm)
EXIT
min 12 in. (300 mm) max
min for max
low ceilings
FIRE
5 ft
(1.5 m)
max 90 in.
(229 mm)
80 in. (2.03 m) min
FIRE ALARM
min
96 in. (2.44 m) max
PULL DOWN
This information is provided to help users navigate NFPA codes and standards. It is not intended to be a comprehensive list of requirements. Check with the local jurisdictions for specific
requirements. This quick reference guide does not represent the official position of the NFPA or its technical committees on any referenced topic, which is represented solely by the NFPA
documents in their entirety. For free access to the complete complete and most current version of all NFPA documents, please go to nfpa.org/docinfo. The NFPA disclaims liability for any
personal injury, property, or other damages of any nature whatsoever resulting from the use of this information. In using this information, you should rely on your independent judgment,
and when appropriate, consult a competent professional..