Dear customer,
Safety advice
General information
Table of content
Chapter Page
1 Features 5
2 Safety advice 6
3 Specification 8
4 Applications 10
5 Operating elements
5.1 Installation 11
5.2 Power supply 11
5.3 Heater and TC connection 11
5.4 Alarm wiring 13
6 Operation
6.1 Operating elements and keys 16
6.2 Bringing into service 19
6.3 Operation menu levels 27
6.3.1 Configuration level—general settings 30
6.3.2 Configuration level—individual settings 38
6.3.3 Parameter level 43
6.3.4 Operation level 48
8 Error messages 52
9 Default settings 54
10 CE-Conformity declaration 55
1. Features
2 Safety advice
3. Specification
Mains voltage :
230/240V +/- 10%, 48...63 Hz
Fuses :
16A FF, 6,3x32mm, heating-loads
1,6A mT, 5x20mm, controller
Power control :
0...100% proportional,
zero-voltage switching
Automatic soft-start :
(factory defaults)
manipulated-value 50% / temperature 80°C /
time 5 min
LED-display :
Indicates actual values, set-points, configuration
parameters, load-current, alarms, tendencies
Sensor inputs :
Thermocouple Fe-CuNi, type J, 0...800°C
Internal zero point correction
Thermocouple is monitored for cable breakage,
short-circuit and polarity errors.
Standby / alarm-exit :
7-pin plug:
2 floating n.o. contacts (230VAC, max. 3A) for alarms.
One floating input to activate the 2nd (standby-)
temperature-value for all zones simultaneously, wired
in parallel with the internal “stand-by” switch.
Safety load-shedding :
Disconnection of all heating loads in case of process-
high alarm.
Sensor-/load-connectors :
16 or 24-pole standard-industry female plug 16A/400V
Accuracy :
0,25% FS
Insulation voltage :
2,5kV mains/sensor circuit
Dimensions :
570 x 180 x 340mm (w x h x d)
Colour :
Textured RAL7035 top/ground
RAL3020 side-parts
Weight :
ca. 12kg
4. Application :
5.1 Installation :
The installation site must provide easy access for
the operator without hazard. Sufficient mechanical
stability must be guaranteed, also secure the device
from slipping on the installation surface.
Protect from heat, radiation and allow free air circu-
lation. Protect power cable from heat and mechani-
cal stress. Do not place the device on hot surfaces.
VK 24 : VK 16 :
3 Alarm connector
4 Power cable
5 Mains masterswitch
6. Operation
Key description
Zone selection
Enter key
F1-Key
F2-Key
Up / Down-Keys
P.SPx :
P: Process value (actual) to be displayed
SP1: Set-point 1
SP2: Set-point 2 (2nd set-point, if activated by external
contact „SP2 enable“ or button on the front panel).
01.04:
Display of the chosen value for Zone 1… Zone 4
05.08:
Display of the chosen value for Zone 5… Zone 8
09.12:
Display of the chosen value for Zone 9… Zone 12
13.16:
Display of the chosen value for Zone 13… Zone 16
1: Alarm A1 active
2: Alarm A2 active
-: no alarm on this Zone
Tendency display
Element A :
Display = 1 , if Alarm exit 1 for this zone is active
Display = 2 , if Alarm exit 2 for this zone is active
Display = 3 , if Alarm exit 1 and 2 for this zone are active
Element C :
Display = 1 , if Alarm exit 1 for this zone is active
Display = 2 , if Alarm exit 2 for this zone is active
Display = 3 , if Alarm exit 1 and 2 for this zone are active
Example:
26
Operations manual NR5016
Attention:
Changes made in „Zone 0“ can lead to malfunctions
of the controller, as some parameters are directly
related to the hardware of the device (e.g. the
sensor inputs). Normally, the device is preset in the
factory ready for use and no changes have to be
made.
28
Operations manual NR5016
Co.A1 Configuration
Alarm 1 OFF alarm OFF, no
alarm signalisation
(ex works)
1 signal contact
off - on
2 limit contact
off - on
3 limit comparator
off - on - off
4 signal contact
on - off
5 limit contact
on - off
6 limit comparator
on - off - on
7 limit comp. with
start-up
suppression
off - on - off
8 Heater current
limit contact
off - on
9 Heater current
limit contact
off - on
30
Operations manual NR5016
Please note :
The individual temperature alarms A1 of all zones are
connected to the main, common contact A1 (switches
relay A1). The selected configuration is effective for all
control zones.
Care should be used to ensure, that the setpoints of the
alarm contacts are programmed within the selected
measuring range. If a setpoint ramp has been
programmed, the alarms that are relative to the setpoint
(signal contact, limit comparator) follow the setpoint up
the ramp.
In case of sensor error the alarms will react in the same
way as range override. The alarm contacts therefore do
not offer protection against all types of plant breakdown.
32
Operations manual NR5016
Current monitoring
Monitoring by relay A1 :
Alarmconfiguration
Co.A1 set on „8“ or „9“
Monitoring by relay A2 :
Alarmconfiguration
Co.A2 set on „8“ or „9“
dL = Zn x Cu.CY x F
with
dL = Alarm delay
Zn = Number of active zones
Cu.CY = Current monitoring
interval
F = fixed delay factor (internal)
34
Operations manual NR5016
36
Operations manual NR5016
38
Operations manual NR5016
40
Operations manual NR5016
Setting: Auto
In the case of a sensor break, the
controller automatically maintains the
last valid output ratio as the actuating
signal.
Displays „process“:
Error warning „Er.H“ or „Er.L“
Displays 1...8:
„H“ (heating-function) will be
displayed in the first digit,
followed by the actual output
ratio value.
H99 = 100% heating
Setting: Man
The controller now operates only as an
actuator. Within the operation level, an
output ratio can be entered instead of the
setpoint. In this case, the control action
(PID-function) is switched of.
Displays „process“:
Actual process temperature value
Displays 1...8:
„H“ (heating-function) will be
displayed in the first digit, followed
by the actual manual output ratio
value.
H99 = 100% heating
42
Operations manual NR5016
44
Operations manual NR5016
OFF; 0,1...80,0 °C
(factory default : 0,1)
46
Operations manual NR5016
48
Operations manual NR5016
50
Operations manual NR5016
Setpoint SP1
Synchronised
heating-up
Autotuning
Softstart
8. Error messages
52
Operations manual NR5016
8. Error messages
54
Operations manual NR5016