AÞIRI ve DÜÞÜK GERÝLÝM KORUMA RÖLELERÝ TR OVER AND UNDER VOLTAGE PROTECTION RELAYS EN

DGRC-01, GKRC-01, GKRC-02, GKRC-02F, GKRC-02FA, GKRC-03, GKRC-03F, GKRC-M2 DGRC-01, GKRC-01, GKRC-02, GKRC-02F, GKRC-02FA, GKRC-03, GKRC-03F, GKRC-M2
General:
1 2 3 DGRC-01, GKRC-01/02/02F/02FA/03/03F relays are delay-off and delay-on capable
Baðlantý Þemalarý Relay Output NC C NO voltage protection relays which have adjustable over and under voltage limits. They
are used in 1-phase and 3-phase Air Conditioning systems, in electronical command
and control systems, for protection of capacitors in compensation systems and for
A1 1 2 3 1 2 3 1 2 3 1 2 3 protection of equipments like motors.
Utilization and Working Principle:
By using the Over Voltage(Max.) and Under Voltage(Min.) adjustment knobs on the
front side, the over and under voltage limits of the system that will be protected is
DGRC-01 Over Voltage Adjustment determined.
DGRC-01
GKRC-02FA GKRC-M2
DGRC-01 GKRC-03 GKRC-01 GKRC-01 Off The Delay knob on the front is used commonly for both the adjusted over voltage faults
GKRC-01
GKRC-02
GKRC-03F GKRC-02 GKRC-02 Under Voltage Adjustment Min. Max.
and adjusted under voltage faults.
GKRC-02F
Relay LED
(v) (v) The Reset Delay knob on the front is used commonly for all faults.
Off The over voltage and under voltage protection options can be deactivated separately(By
Supply LED adjusting the Max. and Min. knobs to OFF position).
A1 N L1 L2 L3 N L1 L2 L3 Under Voltage Warning LED Protection Functions:
Un A2 L1 L2 L3 N L N L1 L2 L3 L1 L2 L3 U< U> ON OUT
A2 a) Over Voltage Protection: GKRC-01 / 02 / 02F / 02FA /03 / 03F / M2
L1 L1 L1 Over Voltage Warning LED Reset If one or many of the measured voltage(Phase/Phase-Phase) values are over the limit
Delay Delay of the adjusted Over Voltage Value(Umax), the “U>” light turns on and the adjusted
L2 L2 Delay-ON Adjustment (s) (s)
Delay time starts to count. When the Delay time is up, the relay of the device breaks the
L3 N N connection and the “OUT” light turns off. When all of the measured voltages fall under
Tek fazlý sistemlerde Delay-OFF Adjustment
N Ýki fazlý sistemlerde the adjusted Over Voltage Value, “U>” light turns off and adjusted Reset Delay time
kullanýmý kullanýmý starts to count.When the Reset Delay time is up, the relay of the device makes contact
and “OUT” light turns on. If one or many of the measured voltage(Phase/Phase-Phase)
TEKNÝK ÖZELLÝKLER values go over the “1,5xUn” limit, “U>” light turns on, the relay of the device breaks the
Supply/Measurement Inputs N L1 L2 L3 connection and “OUT” light turns off. When the Over Voltage adjustment(Max.) knob
Ölçme ve Besleme Devresi is adjusted to the “OFF” position, the Over Voltage Protection function is disabled.
Boyutlar (mm)
Ýþletme Gerilimi (Un) : 220, 230V AC DGRC-01, GKRC-01/02/02F/02FA/M2 b) Under Voltage Protection: DGRC-01, GKRC-02 / 02F / 02FA/ 03 / 03F / M2
If one or many of the measured voltage(Phase/Phase-Phase) values are under the
: 400V AC GKRC-03/03F limit of the adjusted Under Voltage Value(Umin), the “U<” light turns on and the
: 150...300V AC DGRC-01, GKRC-01/02/02F/M2, adjusted Delay time starts to count. When the Delay time is up, the relay of the device
Ýþletme Gerilimi Aralýðý ( U) : 270...510V AC GKRC-03/03F U< U> On Out Meanings of the Device LEDs breaks the connection and the “OUT” light turns off. When all of the measured voltages
rise over the adjusted Under Voltage Value, “U<” light turns off and adjusted Reset
: 190...260V AC GKRC-02FA Voltage(s) are within the adjusted limits Delay time starts to count.When the Reset Delay time is up, the relay of the device
Ýþletme Frekansý : 48 ... 63 Hz. Temprorary Under Voltage Warning makes contact and “OUT” light turns on. If one or many of the measured voltage
: 50 / 60 Hz. (GKRC-02FA) (Phase/Phase-Phase) values go under the “0,5xUn” limit, “U<” light turns on, the relay
TÝP PK 28 Permanent Under Voltage Warning of the device breaks the connection and “OUT” light turns off.
Güç Tüketimi (max.) : 30 VA / 2 W (50 Hz.) When the Under Voltage adjustment (Min.) knob is adjusted to the “OFF” position, the
Ölçüm Yöntemi Temprorary Over Voltage Warning Over Voltage Protection function is disabled.
: True RMS
Ayarlar Permanenet Over Voltage Warning c) Phase Sequence Protection: GKRC-02F / 02FA / 03F
Aþýrý Gerilim Ayarý (Umax.) : 1,05...1,30 x Un (% Skala) Both Over and Under Voltage Warning L1, L2, L3 L3, L2, L1
: 240 ... 300 V AC (DGRC-01, GKRC-01/02/02F/M2) Unsufficient Supply Warning If there is a change in the
: 410 ... 510 V AC (GKRC-03/03F/02FA) phase sequence for
Phase Sequence Fault whatever the reason, only the
Düþük Gerilim Ayarý (Umin.) : 0,7...0,95 x Un (% Skala) ON
“ON” light turns on and the
: 150 ... 210 V AC (DGRC-01, GKRC-01/02/02F/M2) LED ON LED OFF FLASHING relay of the device breaks
U>
: 270 ... 370 V AC (GKRC-03/03F/02FA) the connection without any
delay.
Histeresis (Umax. ve Umin. için) : Un x %3 (Sabit) Function Table U<

Býrakma Gecikmesi (Delay) : 0.1 ... 20 sn. (Umax. ve Umin. için ortak) Protection Function 3-Phase 3-Phase OUT
4 Cable 3 Cable
Çekme Gecikmesi (Reset Delay) : 0.1 ... 20 sn. Type Over
Voltage
Under Phase
Voltage Sequence Star Delta 3
Gerilim Ayar Doðruluðu : ± %3 2
1
Tekrarlama Doðruluðu (Gerilim) : ± %0.5
Ayarlanan Zamanlarýn Doðruluðu Phase Sequence Fault Diagram
: ± %5 + 100 msn
Tekrarlama Doðruluðu (Zaman) : ± %3 Insufficient Supply Voltage: DGRC-01, GKRC-01 / 02 / 02F / 03 / 03F / M2
DGRC-01, GKRC-01 / 02 / 02F / 03 / 03F / M2 are supplied from a 3 Phase capacitive
Çýkýþ source. The supply voltage on these devices equals to the mean value of voltages
Çýkýþ Tipi : 1 Enversör, 8A, 250V, 2000VA (Cosj=1) from all three phases. If this mean value is less than half the supply voltage, the relay
Elektriksel Ömür : 105 gives an insufficient supply voltage warning (U< and U> LEDs flash in that order) and
the relay breaks contact without delay.
Mekanik Ömür : 107 Mono Phase DGRC-01,GKRC-01 / 02 / 02F With Neutral => (VL1+VL2+VL3)/3 < 115 VAC (F-N)
Çevresel Þartlar
* This option may be deactivated by making adjustments on the device GKRC-03 / 03F Without Neutral => (VL12+VL23+VL31)/3 < 200 VAC (F-F)
Çalýþma Sýcaklýðý : -5°C ... +55°C
Baðýl Nem : <%90 (Yoðunlaþma olmadan)
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Baðlantý BREAK OF THE NEUTRAL CONNECTION FOR DEVICES WITH NEUTRAL
Failure to follow those instructions will result in death or serious injury.
Klemens için Kablo Kesitleri : 4mm² (12AWG) stranded/örgülü rijit kablo
In devices with neutral, Phase-Neutral measurements are taken. Disconnect all power before working on equipment.
: 6mm² (10AWG) solid/som iletken kablo If the neutral cable breaks, the neutral point of the system shifts When the device is connected to the network, do not remove the front panel.
: 2x2.5mm² (14AWG) solid/som iletken kablo because of the asymmetrical phase loading. The device continues Do not try to clean the device with solvent or the like.
Vida Sýkma Kuvveti : 0.5 Nm (4.5in.lbs) the take measurements according to the shifted neutral system Only clean the device with a dried cloth.
point.
Gövde Verify correct terminal connections when wiring.
Montaj : Pano içine dikey veya klemens rayýna. Electrical equipment should be serviced only by your compedent seller.
Malzeme Cinsi : Plastik UL 94 V0 ’a uygun Over and Under Voltage Function Diagram Mount device to the panel
Koruma Sýnýfý : IP 20 (Terminaller), IP 40 (Ön panel) No responsibility is assured by the manufacturer or any of its subsidiaries
Boyutlar : Tip PK 28 Delay=20sn for any consequences arising out of the use of this material.
Aðýrlýk : 100 gr. (Sadece GKRC-02FA 200 gr. ) Reset Delay=20sn
(V) Delay Delay Reset Delay Reset Delay Delay Delay Reset Delay Reset Delay
Ýzolasyon
Umax.
Yalýtým Gerilimi (EN 60255-5) : 400 V
Hysteresis
Yalýtým Koordinasyonu : Aþma Gerilimi Kategorisi III L1
(EN 60255-5) Kirlilik Derecesi 3 L2
L3
Ani Darbe Gerilimi (EN 60255-5) : 4 kV 1.2 / 50 uS Hysteresis
Dielektrik Dayanýmý (EN 60255-5) : 2 kV AC 50 Hz. 1 dk. Umin.
Yalýtým Direnci (EN 60255-5) : >500 MOHM / 500 V DC
(t)
Uyulan Standartlar
EN-60255-6 : Ürün standardý ON
EN-61000-6-2 : Baðýþýklýk
EN-61000-6-3, EN-61000-6-4 : Emisyon
U>
Uyumlandýrýlacak Direktif / Yönetmelikler U<
73/23/EEC LVD
89/336/EEC EMC OUT
“Bu ürün, 30.05.2008 tarih ve 26891 sayýlý resmi gazetede yayýnlanan 3
A4818 / Rev.6 EEE Yönetmeliðinin Madde 2 ve Ek-1A madde 9 kapsamýndadýr.” 2
1
OVER AND UNDER VOLTAGE PROTECTION RELAYS EN AÞIRI ve DÜÞÜK GERÝLÝM KORUMA RÖLELERÝ TR
DGRC-01, GKRC-01, GKRC-02, GKRC-02F, GKRC-02FA, GKRC-03, GKRC-03F, GKRC-M2 DGRC-01, GKRC-01, GKRC-02, GKRC-02F, GKRC-02FA, GKRC-03, GKRC-03F, GKRC-M2
Genel:
1 2 3 DGRC-01, GKRC-01/02/02F/02FA/03/03F röleleri; üst ve alt gerilim sýnýrlarý ayarlanabilen,
Connection Diagram býrakmada ve çekmede gecikmeli gerilim koruma röleleridir. Üç fazlý ve tek fazlý klima
Röle çýkýþý NC C NO sistemlerinde, elektronik kumanda ve kontrol sistemlerinde, kompanzasyon panolarýnda
A1 1 2 3 1 2 3 1 2 3 1 2 3
kondansatör korunmasýnda ve motor gibi ekipmanlarýn korunmasýnda kullanýlýr.
Kullaným ve Çalýþma Prensibi:
Ön paneldeki Aþýrý Gerilim (Max.) ve Düþük Gerilim (Min.) ayar düðmeleri kullanýlarak,
korunacak olan sistemin üst ve alt çalýþma gerilimi sýnýrlarý belirlenir.
DGRC-01 DGRC-01 Ön paneldeki Býrakma Gecikmesi (Delay), ayarlanan aþýrý ve düþük gerilim hatalarý için
DGRC-01 GKRC-03 GKRC-01 GKRC-01 ortak kullanýlýr.
GKRC-02FA GKRC-M2 GKRC-01 GKRC-03F GKRC-02 GKRC-02 Aþýrý gerilim ayarý
GKRC-02 Ön paneldeki Çekme Gecikmesi (Reset Delay) tüm hatalar için ortak kullanýlýr.
GKRC-02F Off
Aþýrý ve Düþük Gerilim Koruma Fonksiyonlarý birbirinden baðýmsýz olarak devre dýþý
Düþük gerilim ayarý Min.
(v)
Max. býrakýlabilir (Max. ve Min. ayar düðmeleri “Off” konumuna getirilerek).
Röle ýþýðý (v)
KORUMA FONKSÝYONLARI:
A1 A2 L1 L2 L3 N L N L1 L2 L3 L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Off
a) Aþýrý Gerilim Korumasý: GKRC-01 / 02 / 02F / 02FA / 03 / 03F / M2
Un
A2
Besleme ýþýðý Ölçülen gerilimlerden (Faz/Faz-Faz) herhangi biri/birkaçý ayarlanan Aþýrý Gerilim deðerini
L1 L1 L1 Düþük gerilim uyarý ýþýðý U< U> ON OUT (Umax.) aþarsa; U> ýþýðý yanar ve ayarlanan Býrakma Gecikmesi (Delay) saymaya
L2 baþlar. Býrakma Gecikmesi (Delay) dolduðunda cihazýn rölesi býrakýr, OUT ýþýðý söner.
L2 Yüksek gerilim uyarý ýþýðý Reset Ölçülen tüm gerilimler, ayarlanan Aþýrý Gerilim deðerinin altýna indiðinde; U> ýþýðý söner
L3 N N Delay Delay
ve ayarlanan Çekme Gecikmesi (Reset Delay) saymaya baþlar. Çekme Gecikmesi
Two Phase Single Phase Çekme gecikmesi ayarý (s) (s)
N
Connection Diagram (Reset Delay) dolduðunda cihazýn rölesi çeker ve OUT ýþýðý yanar.
Connection Diagram
Býrakma gecikmesi ayarý Ölçülen gerilimlerden (Faz/Faz-Faz) herhangi biri/birkaçý “1.5xUn” deðerini aþarsa; U>
ýþýðý yanar, cihazýn rölesi gecikmesiz býrakýr ve OUT ýþýðý söner.
TECHNICAL PROPERTIES Aþýrý gerilim ayar düðmesi (Max.) “Off” konumuna getirildiðinde Aþýrý Gerilim Koruma
Fonksiyonu iptal edilmiþ olur.
Measurement and Supply Circuit b) Düþük Gerilim Korumasý: DGRC-01, GKRC-02 / 02F / 02FA / 03 / 03F / M2
Supply Voltage (Un) : 220, 230V AC DGRC-01, GKRC-01/02/02F/02FA/M2 Besleme / ölçme giriþleri N L1 L2 L3 Ölçülen gerilimlerden (Faz/Faz-Faz) herhangi biri/birkaçý ayarlanan Düþük Gerilim
Dimensions (mm)
: 400V AC GKRC-03/03F deðerinin (Umin.) altýna düþürse; U< ýþýðý yanar ve ayarlanan Býrakma Gecikmesi
(Delay) saymaya baþlar. Býrakma Gecikmesi (Delay) dolduðunda cihazýn rölesi býrakýr
: 150...300V AC DGRC-01, GKRC-01/02/02F/M2 ve OUT ýþýðý söner.
: 270...510V AC GKRC-03/03F Ölçülen tüm gerilimler, ayarlanan Düþük Gerilim deðerinin üzerine çýktýðýnda; U< ýþýðý
Supply Voltage Gap ( U) : 190...260V AC GKRC-02FA söner ve ayarlanan Çekme Gecikmesi (Reset Delay) saymaya baþlar. Çekme Gecikmesi
(Reset Delay) dolduðunda cihazýn rölesi çeker ve OUT ýþýðý yanar.
Supply Frequency : 48 ... 63 Hz. U< U> On Out Cihaz Iþýklarýnýn anlamlarý Ölçülen gerilimlerden (Faz/Faz-Faz) herhangi biri/birkaçý “0,5xUn” altýna düþürse; U<
: 50 / 60 Hz. (GKRC-02FA) ýþýðý yanar, cihazýn rölesi gecikmesiz býrakýr ve OUT ýþýðý söner.
Gerilim(ler) ayarlanan sýnýrlarýn içinde
Power Consumption (max.) : 30 VA / 2 W (50 Hz.) Düþük gerilim ayar düðmesi (Min.) “Off” konumuna getirildiðinde Düþük Gerilim Koruma
TYPE PK 28 Geçici düþük gerilim uyarýsý Fonksiyonu iptal edilmiþ olur.
Measurement Method : True RMS
Sürekli düþük gerilim uyarýsý c) Faz Sýrasý Korumasý: GKRC-02F / 02FA / 03F
Settings
Over Voltage Setup (Umax.) : 1,05...1,30 x Un (% Scale) Geçici aþýrý gerilim uyarýsý L1, L2, L3 L3, L2, L1

: 240 ... 300 V AC (GKRC-01/02/02F/M2) Sürekli aþýrý gerilim uyarýsý Herhangi bir sebeple faz
: 410 ... 510 V AC (GKRC-03/03F/02FA) Hem aþýrý hem düþük gerilim uyarýsý sýrasýnda deðiþme tesbit
ON edilirse; sadece “On” ýþýðý
Under Voltage Setup (Umin.) : 0,7...0,95 x Un (% Scale) Yetersiz besleme uyarýsý yanar ve cihazýn rolesi
: 150 ... 210 V AC (DGRC-01, GKRC-02/02F/M2) U> gecikmesiz býrakýr.
Faz sýrasý hatasý uyarýsý
: 270 ... 370 V AC (GKRC-03/03F/02FA) U<
Hysteresis(for Umax and Umin) : Un x %3 (constant) IÞIK YANIK IÞIK SÖNÜK FLAÞÖR
Delay-Off(Delay) : 0.1 ... 20 sec. (common for Umax and Umin) OUT

Delay-On(Reset Delay) : 0.1 ... 20 sec. Fonksiyon Tablosu 2


3
Voltage Adjustment Accuracy : ± %3 Koruma Fonksiyonu 3 faz 3 faz 1
Repetition Accuracy(Voltage) : ± %0.5 TÝP Aþýrý Düþük Faz 4 kablo 3 kablo
Gerilim Gerilim Sýrasý Yýldýz Üçgen
Accuracy of the Set Times : ± %5 + 100 msn Yetersiz Besleme Voltajý: DGRC-01, GKRC-01 / 02 / 02F / 03 / 03F / M2
DGRC-01, GKRC-01 / 02 / 02F / 03 / 03F / M2 3 Fazdan kapasitif beslemelidir. Bu
Repetition Accuracy(Time) : ± %3 cihazlarda besleme voltajý 3 fazdan gelen gerilimin ortalamasýna eþittir. Eðer 3 fazdan
Output gelen gerilimin ortalamasý iþletme geriliminin yarýsýndan az olursa cihaz yetersiz besleme
uyarýsý verir (U< ve U> ledleri sýrasý ile yanýp sönerek flaþör yapar) ve röle gecikmesiz
Output Type : 1 inverter, 8A, 250V, 2000VA (Cosj=1) býrakýlýr.
Electrical Life : 105 DGRC-01,GKRC-01 / 02 / 02F Nötrlü => (VL1+VL2+VL3)/3 < 115 VAC (F-N)
Mechanical Life : 107 GKRC-03 / 03F Nötrsüz => (VL12+VL23+VL31)/3 < 200 VAC (F-F)
Ambiant Conditions
Operating Temperature : -5°C ... +55°C Tek Faz Faz sýrasý hatasý fonksiyon diagramý
Relative Humidity : <%90 (without condensation) * Bu fonksiyon, cihaz üzerinden ayarlanarak devre dýþý býrakýlabilir.
Güvenli Kullaným ve Kurulum Ýçin Uyarýlar
Connection Aþaðýdaki talimatlara uyulmamasý halinde yaralanma veya ölümle sonuçlanabilecek
Cable Cross-sections for Terminals : 4mm² (12AWG) stranded rigid cable NÖTRLÜ ÜRÜNLERDE NÖTR BAÐLANTISININ KOPMASI : durumlar ortaya çýkabilir.
: 6mm² (10AWG) solid conductor cable Nötrlü ürünlerde Faz-Nötr arasý ölçüm yapýlmaktadýr. Nötr Cihaz üzerindeki herhangi bir iþlemden önce tüm besleme gerilimlerini kesiniz.
: 2x2.5mm² (14AWG) solid conductor cable kablosu koparsa; asimetrik faz yüklenmesi sonucu oluþan Cihaz þebekeye baðlý iken ön paneli çýkarmayýnýz.
nötr noktasýnda bir kayma meydana gelir. Cihaz ölçümlerini Cihazý solvent veya benzeri maddelerle temizlemeyiniz. Cihazý temizlemek için
Screw-On Force : 0.5 Nm (4.5in.lbs) kaymýþ olan nötr noktasýna göre yapmaya devam eder. sadece kuru bez kullanýnýz.
Body Cihazý çalýþtýrmadan önce baðlantýlarýnýn doðru olduðunu kontrol ediniz.
Installation : Inside the panel vertically or on to the rail Cihazý panoya monte ediniz.
Aþýrý ve düþük gerilim fonksiyon diagramý Cihazýnýzdaki herhangi bir sorunda yetkili satýcýnýzla temas kurunuz.
Material Type : Plastic Consistent with UL 94 VO
Protection Class : IP 20 (Terminals), IP 40 (Front Panel) Yukarýdaki önlemlerin uygulanmamasý sonucu doðabilecek istenmeyen
Delay=20sn durumlardan üretici firma hiç bir þekilde sorumlu tutulamaz.
Dimensions : Type PK 28 Reset Delay=20sn
Weight : 100 gr. (Only GKRC-02FA 200 gr.) (V) Delay Delay Reset Delay Reset Delay Delay Delay Reset Delay Reset Delay
Isolation Umax.
Isolation Voltage (EN 60255-5) : 400 V Hysteresis
L1
Isolation Coordination : Exceeding Voltage Category III, L2
(EN 60255-5) Pollution Degree 3 L3
Hysteresis
Instant Burst Voltage (EN 60255-5) : 4 kV 1.2 / 50 uS Umin.
Dielectric Resistance (EN 60255-5) : 2 kV AC 50 Hz. 1 minute.
Isolation Resistance (EN 60255-5) : >500 MOHM / 500 V DC (t)
Followed Standards ON
EN-60255-6 : Product Standard
EN-61000-6-2 : Immunity U>
EN-61000-6-3, EN-61000-6-4 : Emission U<
Directives/Regulations To Be Followed
73/23/EEC LVD OUT
89/336/EEC EMC 3
A4818 / Rev.6 2
1