Professional Documents
Culture Documents
Motor & Generator OCR MSB Setting
Motor & Generator OCR MSB Setting
Overcurrent Protection
The term 'overcurrent' applies to a relatively small increase over the full load current (FLC)
rating (e.g., due to mechanical overloading of a motor), rather than the massive current
increase caused by a short-circuit fault.
Full load current (FLC) will flow through the coil wired in series with each phase of the load. This coil
heats up the bimetallic strip, which is used as a trip lever. The current increases and heat radiated by
the coil rises. This causes the bimetallic strip to bend, triggering the trip mechanism and the NC
contact opens.
The OCR and fuses/circuit breaker are coordinated so that the thermal overcurrent relay trips
contactor while the fuses/circuit breaker interrupt short-circuit fault currents. This contactor and
fuse arrangement is usually called backup protection.
To protect a modern continuous maximum rating (CMR) motor, the thermal OCR should be set at the
full load current (FLC) rating of the motor. This will ensure that tripping will not occur within two hours
at 105% FLC. At 120% FLC, tripping will occur within two hours.
Note that the current in winding V1-V2 is considerably higherthan that in the other two windings.Look
at the condition where the motor is at 60% of full load when single phasing occurs, the line currents
are 102 % of the full-load value, but the current in winding V1-V2 is 131% of its full-load value. The
102% line current will probably not activate a line connected OCR and the motor remains connected.
However, the local overheating in winding V1-V2 of the motor will quickly result in damage.
The effect of single phasing is to increase the current in the two remaining lines and cause the motor
to become very noisy due to the uneven torque produced in the rotor. Unbalanced rotor torque
causes shaft vibrating.
Motors can be protected against this condition by using a differential type relay that trips out with
unbalanced currents. Most modern thermal OCRs for motors have this protection against single
phasing incorporated as a normal feature. An increase in line current due to single phasing will be
detected by the protective OCR.
An electronic overcurrent relay usually converts the measured current into a proportional voltage.
This is then compared with a set voltage level within the monitoring unit, which may be digital or
analogue. In an analogue unit (see the Figure below) the time delay is obtained by the time taken to
charge up a capacitor.
This type of relay has separate adjustments for overcurrent and time settings, together with an
instantaneous trip. The electronic amplifiers within the relay require a low voltage DC power supply,
e.g., 24 V DC derived from a 220 V AC auxiliary supply.
An instantaneous trip operation is obtained by applying the output of the bridge rectifier directly to the
input of the amplifier with a voltage set by R4. Therefore, for higher values of fault current, the
inverse-time delay circuit is bypassed.
Continuous Amps (Ir) varies the level of current the circuit breaker will carry without tripping. Ir is a
percentage of the circuit breaker’s nominal rating (In). Continuous amps can be adjusted from 20 to
100 percent of the circuit breaker’s nominal rating. For example, a 1000 amp breaker can be changed
from 1000 amps to 800 amps by adjusting the breaker continuous amps setting to 80%.
2. Long-Time Delay
Long-time delay causes the breaker to wait a certain amount of time to allow temporary inrush
currents, such as those encountered when starting a motor, to pass without tripping. The adjustment
is from 2.2 to 27 seconds at six times the continuous amps (Ir) setting.
3. Short-Time Pickup
Short-time pickup is used for selective tripping. The short-time pickup function determines the amount
of current the breaker will carry for a short period of time, allowing downstream protective devices to
clear short-circuits without tripping the upstream device. Short-time pickup is adjustable from 1.5
to 10 times the trip unit ampere setting (Ir). For example, a 1000 ampere frame can be adjusted to trip
anywhere from 1500 to 10,000 amps. The switch also has an “OFF” position to eliminate short-time
pickup and short-time delay.
4. Short-Time Delay
Short-time delay, used in conjunction with short-time pickup, controls the time involved in postponing
a short-time pickup trip. Two modes: fixed time (from .05 to .5 seconds), or I2T ramp. The I2T ramp
mode is adjustable from .18 seconds to .45 seconds, providing a short inverse time ramp. It allows
better coordination with downstream thermal-magnetic circuit breakers and fuses.
Instantaneous pickup is used to trip the circuit breaker with no intentional delay at any current
between 2 and 40 times the breaker’s continuous ampere setting (Ir). In this example instantaneous
pickup has been set to 10 times the continuous amp setting, or 10,000 amps (10 x 1000) with a
continuous amp setting of 1000 amps.
Ground fault pickup controls the amount of ground fault current that will cause the breaker to interrupt
the circuit. The adjustment can be set from 20 to 70% of the maximum breaker rating. In compliance
with NEC® 230-95 (A), no trip point setting exceeds 1200 amps. The ground fault pickup is
divided into three sections; .1s, .2s, and .4s. This feature adds a time delay of .1, .2, or .4 seconds to
the breaker’s trip when a ground fault occurs.
Circuit breaker coordination
The ground fault pickup time delay feature is useful for circuit breaker coordination. In the following
scheme, upstream breaker “A” has been set to .2s and downstream breakers “B” and “C” have been
set to .1s. A ground fault occurring in the circuit supplied by “B” will trip the “B” breaker
without disturbing “A” or “C”.
The RP relay operation is easily checked during a generator changeover. The outgoing generator is
gradually throttled down so that it motors, causing the reverse power relay to trip its generator circuit
breaker.
All overcurrent relays can be tested by injecting calibrated test currents into them to check their
current trip levels and time delay settings.
Primary injection is where a calibrated test current is fed through the normal load circuit. This requires
a large current injection test set. The test set is a transformer and controller, rather like a welding set,
i.e., it gives a low voltage - high current output.
Small secondary injection currents (5-50A) are fed current directly into the overcurrent relay, usually
via a special test plug/socket wired into the relay. Secondary injection does not prove the CT
performance (as it is disconnected during the test), but is the usual method for testing an overcurrent
relay.
It is a method of connecting a secondary injection test set to a trip unit (trip device, over current
module, protection device, OCR, ETU etc.) on a circuit breaker and injecting a simulated current to
prove it works at different levels.
Main Switch Board Busbar Abnormal Protection (St-by generator must come in)
1. Overcurrent (Preferential Trip): @100% to 120% within 10 s (in case St-by generator not come in),
First Pref. Trip start, if load is not reduced Second Pref. Trip enters.
2. Busbar Frequency High (Low): 105% (95%) @ 5s (alarm)
3. Busbar Low Voltage: 97% @ 5s (alarm)
4. Busbar High Voltage: 103% @ 5s (alarm)