Section 12
Busway
Powerbus™ Busway 12-2
Feeder Style
Power-Zone™ Busway 12-18
BUSWAY
exact fit of all components. Contact your local Schneider Electric sales office for exact
details.
• Emergency Service; we are on call 24 hours a day, 7 days a week, 365 days a year.
For emergencies, call 1-888-SquareD (1-888-778-2733).
• Quick Ship program provides product availability for time sensitive orders. The
program is available through the product selectors and offers a limited selection of I-
Line busway footage and fittings. Contact your local Schneider Electric sales office for
exact details.
12
Power-Zone Busway
11/10/2017
Powerbus™ Busway Powerbus™ Busway
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
Powerbus Busway
Construction
Powerbus busway construction consists of a light-weight electrical grade all-aluminum
housing with up to five (5) silver-plated copper conductor bars for maximum electrical
efficiency. The total product offer includes straight sections, fittings, accessories, and
plug-in units for a total installation. This busway is available in 400 A, 225 A and 100 A
ratings. A 50% integral ground is standard.
Straight Sections
Straight sections of busway are available in 10 ft. and 4 ft. lengths in a painted black
finish. The Enhanced busway offer includes 10 plug-in openings on each side of a 10 ft.
section and 3 plug-in openings on each side of a 4 ft. section.
Metering and Communications Options
Single phase systems and DC systems are also available. Contact your local Schneider Electric representative.
Powerbus busway tap boxes and plug-in units are available with optional metering and
communication capabilities, which include an integrated display and the ability to
remotely monitor the busway.
[1] Busway catalog numbers shown include a black painted finish. Contact your local Schneider Electric representative for a natural aluminum finish option.
[2] For 100 A busway only, add an (L), for top cable access, or a (U), for bottom cable access, before the last letter in the catalog no., which is (B).
[3] Replace the ( ) in the Tap Box w/Meter catalog number with the meter suffix number in Table 12.3 Meter Suffix Number, page 12-3. The meter will be configured based on the system
voltage.
12-2
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Powerbus Plug-In Units Powerbus™ Busway
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
BUSWAY
Table 12.7: Factory Assembled Units with FA Circuit Breakers—600 V max[9]
Circuit 3A Configuration 4A Configuration 5A Configuration 5B Configuration
Breaker [10]
Rating Catalog Number Catalog Number Catalog Number Catalog Number
15 PBPFA3A100A015 PBPFA4A100A015 PBPFA5A100A015 PBPFA5B100A015
20 PBPFA3A100A020 PBPFA4A100A020 PBPFA5A100A020 PBPFA5B100A020
30 PBPFA3A100A030 PBPFA4A100A030 PBPFA5A100A030 PBPFA5B100A030
40 PBPFA3A100A040 PBPFA4A100A040 PBPFA5A100A040 PBPFA5B100A040
50 PBPFA3A100A050 PBPFA4A100A050 PBPFA5A100A050 PBPFA5B100A050
60 PBPFA3A100A060 PBPFA4A100A060 PBPFA5A100A060 PBPFA5B100A060
70 PBPFA3A100A070 PBPFA4A100A070 PBPFA5A100A070 PBPFA5B100A070
80 PBPFA3A100A080 PBPFA4A100A080 PBPFA5A100A080 PBPFA5B100A080
90 PBPFA3A100A090 PBPFA4A100A090 PBPFA5A100A090 PBPFA5B100A090
12
100 PBPFA3A100A100 PBPFA4A100A100 PBPFA5A100A100 PBPFA5B100A100
[4] Busway catalog numbers shown include a black painted finish. Contact your local Schneider Electric representative for a natural aluminum finish option.
[4] Replace the ( ) in the Tap Box w/Meter catalog number with the meter suffix number in Table 12.3 Meter Suffix Number, page 12-3. The meter will be configured based on the system
voltage.
[5] For the NetShelter TM IT Rack-Mounting Bracket, refer to 5600CT9101.
[6] For single-pole operation on QO and ED circuit breakers.
[7] Certain NEMA receptacles can be field installed in this unit. Consult your local Schneider Electric representative.
[8] Plug-in tap box to be installed on 100 A and 225 A busways only.
[9] See Digest Section 7, Table 7.147 QB, QD, QG, QJ, Q4, FA, LA, Circuit Breakers, page 7-76 for FA circuit breaker information.
[10] The 4B configuration catalog numbers are also available.
12-3
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Powerbus™ Busway Powerbus Plug-In Units
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
Table 12.8: 120 V Factory Assembled Units: 1-pole QO/QOB circuit breakers with
NEMA 5-15R or 5-20R receptacles[11][12]
Circuit Breaker 4A Configuration 5A Configuration 5B Configuration
Rating Type Catalog Number Catalog Number Catalog Number
Type 1 (3 circuit breakers w. 3 duplex receptacles)
15 QO PBPQOR4A100M115 PBPQOR5A100M115 PBPQOR5B100M115
15 QOB PBPQOR4A100M115B PBPQOR5A100M115B PBPQOR5B100M115B
20 QO PBPQOR4A100M120 PBPQOR5A100M120 PBPQOR5B100M120
20 QOB PBPQOR4A100M120B PBPQOR5A100M120B PBPQOR5B100M120B
Type 2 (3 circuit breakers w. 2 duplex/1 locking recpt.)
15 QO PBPQOR4A100M215 PBPQOR5A100M215 PBPQOR5B100M215
15 QOB PBPQOR4A100M215B PBPQOR5A100M215B PBPQOR5B100M215B
20 QO PBPQOR4A100M220 PBPQOR5A100M220 PBPQOR5B100M220
20 QOB PBPQOR4A100M220B PBPQOR5A100M220B PBPQOR5B100M220B
Type 3 (3 circuit breakers w. 1 duplex/2 locking recpt.)
15 QO PBPQOR4A100M315 PBPQOR5A100M315 PBPQOR5B100M315
15 QOB PBPQOR4A100M315B PBPQOR5A100M315B PBPQOR5B100M315B
20 QO PBPQOR4A100M320 PBPQOR5A100M320 PBPQOR5B100M320
20 QOB PBPQOR4A100M320B PBPQOR5A100M320B PBPQOR5B100M320B
Type 4 (3 circuit breakers w. 3 locking receptacles)
15 QO PBPQOR4A100M415 PBPQOR5A100M415 PBPQOR5B100M415
15 QOB PBPQOR4A100M415B PBPQOR5A100M415B PBPQOR5B100M415B
20 QO PBPQOR4A100M420 PBPQOR5A100M420 PBPQOR5B100M420
20 QOB PBPQOR4A100M420B PBPQOR5A100M420B PBPQOR5B100M420B
Table 12.9: Factory Assembled Units: One (1) QOU circuit breaker and one (1) drop cord with connector[13][14]
Circuit Breaker NEMA Drop Cord 4A Configuration 5A Configuration 5B Configuration
Rating Poles Connector Length (ft) Catalog Number Catalog Number Catalog Number
15 A 1 L5-15 3 PBPQOU4A100COOL515 PBPQOU5A100COOL515 PBPQOU5B100COOL515
20 A 1 L5-20 3 PBPQOU4A100COOL520 PBPQOU5A100COOL520 PBPQOU5B100COOL520
30 A 1 L5-30 3 PBPQOU4A100COOL530 PBPQOU5A100COOL530 PBPQOU5B100COOL530
15 A 2 L6-15 3 PBPQOU4A100COOL615 PBPQOU5A100COOL615 PBPQOU5B100COOL615
20 A 2 L6-20 3 PBPQOU4A100COOL620 PBPQOU5A100COOL620 PBPQOU5B100COOL620
12
[11] Many more factory assembled units are available using combinations of 1P/2P/3P circuit breakers with other NEMA receptacles. Maximum of 3 breaker spacess available. Consult your
local Schneider Electric representative.
[12] See Digest Section 7, QO and QOU Miniature Circuit Breakers, page for QOU circuit breaker information.
[13] Factory assembled units are available using combinations of 1P/2P/3P circuit breakers with other NEMA and IEC type receptacles. Maximum of three drop cords with six breaker spaces
available. Consult your local Schneider Electric representative.
[14] See Digest Section 7, QO and QOU Miniature Circuit Breakers, page for QOU circuit breaker information. Catalog numbers shown have the breaker in the top slot in the front cover and
the drop cord in the left position in the base of the unit. Other combinations are available.
12-4
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Powerbus Plug-In Units Powerbus™ Busway
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
Table 12.10: Factory Assembled Units with NEMA Connectors and Metering[15][16]
Circuit Breaker NEMA Drop Cord Catalog Number[17][18]
Rating Poles Connector Length (ft) 4A Configuration 5A Configuration 5B Configuration
15 A 1 L5-15 3 PBPEDU4A100COOL515M( ) PBPEDU5A100COOL515M( ) PBPEDU5B100COOL515M( )
20 A 1 L5-20 3 PBPEDU4A100COOL520M( ) PBPEDU5A100COOL520M( ) PBPEDU5B100COOL520M( )
30 A 1 L5-30 3 PBPEDU4A100COOL530M( ) PBPEDU5A100COOL530M( ) PBPEDU5B100COOL530M( )
15 A 2 L6-15 3 PBPEDU4A100COOL615M( ) PBPEDU5A100COOL615M( ) PBPEDU5B100COOL615M( )
20 A 2 L6-20 3 PBPEDU4A100COOL620M( ) PBPEDU5A100COOL620M( ) PBPEDU5B100COOL620M( )
30 A 2 L6-30 3 PBPEDU4A100COOL630M( ) PBPEDU5A100COOL630M( ) PBPEDU5B100COOL630M( )
20 A 3 L21-20 3 PBPEDU4A100COOL2120M( ) PBPEDU5A100COOL2120M( ) PBPEDU5B100COOL2120M( )
30 A 3 L21-30 3 PBPEDU4A100COOL2130M( ) PBPEDU5A100COOL2130M( ) PBPEDU5B100COOL2130M( )
15 A 1 L5-15 6 PBPEDU4A100FOOL515M( ) PBPEDU5A100FOOL515M( ) PBPEDU5B100FOOL515M( )
20 A 1 L5-20 6 PBPEDU4A100FOOL520M( ) PBPEDU5A100FOOL520M( ) PBPEDU5B100FOOL520M( )
30 A 1 L5-30 6 PBPEDU4A100FOOL530M( ) PBPEDU5A100FOOL530M( ) PBPEDU5B100FOOL530M( )
15 A 2 L6-15 6 PBPEDU4A100FOOL615M( ) PBPEDU5A100FOOL615M( ) PBPEDU5B100FOOL615M( )
20 A 2 L6-20 6 PBPEDU4A100FOOL620M( ) PBPEDU5A100FOOL620M( ) PBPEDU5B100FOOL620M( )
30 A 2 L6-30 6 PBPEDU4A100FOOL630M( ) PBPEDU5A100FOOL630M( ) PBPEDU5B100FOOL630M( )
20 A 3 L21-20 6 PBPEDU4A100FOOL2120M( ) PBPEDU5A100FOOL2120M( ) PBPEDU5B100FOOL2120M( )
30 A 3 L21-30 6 PBPEDU4A100FOOL2130M( ) PBPEDU5A100FOOL2130M( ) PBPEDU5B100FOOL2130M( )
Table 12.11: Factory Assembled Units with IEC Connectors and Metering[15][16]
Circuit Breaker Drop Cord Catalog Number[18][20]
Rating Poles IEC 60309 Connector[19] Length (ft) 4A Configuration 5A Configuration 5B Configuration
20 2 2-Pole, 3-Wire Grounding 3 PBPEDU4A100COOS3420M( ) PBPEDU5A100COOS3420M( ) PBPEDU5B100COOS3420M( )
30 2 2-Pole, 3-Wire Grounding 3 PBPEDU4A100COOS3430M( ) PBPEDU5A100COOS3430M( ) PBPEDU5B100COOS3430M( )
60 2 2-Pole, 3-Wire Grounding 3 PBPEDU4A100COOS3460M( ) PBPEDU5A100COOS3460M( ) PBPEDU5B100COOS3460M( )
20 3 3-Pole, 4-Wire Grounding 3 PBPEDU4A100COOS4420M( ) PBPEDU5A100COOS4420M( ) PBPEDU5B100COOS4420M( )
30 3 3-Pole, 4-Wire Grounding 3 PBPEDU4A100COOS4430M( ) PBPEDU5A100COOS4430M( ) PBPEDU5B100COOS4430M( )
60 3 3-Pole, 4-Wire Grounding 3 PBPEDU4A100COOS4460M( ) PBPEDU5A100COOS4460M( ) PBPEDU5B100COOS4460M( )
20 3 4-Pole, 5-Wire Grounding 3 PBPEDU4A100COOS5420M( ) PBPEDU5A100COOS5420M( ) PBPEDU5B100COOS5420M( )
30 3 4-Pole, 5-Wire Grounding 3 PBPEDU4A100COOS5430M( ) PBPEDU5A100COOS5430M( ) PBPEDU5B100COOS5430M( )
60 3 4-Pole, 5-Wire Grounding 3 PBPEDU4A100COOS5460M( ) PBPEDU5A100COOS5460M( ) PBPEDU5B100COOS5460M( )
BUSWAY
Table 12.14: NEMA Receptacles and Connectors[23]
NEMA Non-Locking NEMA Locking
Wiring Voltage
15 A 20 A 30 A 15 A 20 A 30 A
2-pole, 3-wire grounding 120 5–15 5–20 5–30 L5–15 L5–20 L5–30
2-pole, 3-wire grounding 240 6–15 6–20 6–30 L6–15 L6–20 L6–20
3-pole, 4-wire grounding 120/240 14–15 14–20 14–30 — L14–20 L14–30
3-pole, 4-wire grounding 3Ø 240 15–15 15–20 15–30 — L15–20 L15–30
4-pole, 5-wire grounding 3ØY
120/208 — — — — L21–20 L21–30
12
Short-Circuit Current Rating
Product KA, RMS Symmetrical
UL 3–Cycle Test
100 A 14 kA
225 A 22 kA
400 A 35 kA
[15] See Digest Section 9, For NF Merchandised Panelboards, page 9-28 for ED circuit breaker information. Catalog numbers shown have the breaker in the top slot in the front cover and the
drop cord in the left position in the base of the unit. Other combinations are available. The Power Meter display will be located below the breaker space. For remote monitoring capabilities, a
gateway is required. The gateway is located in the tap box with metering or in a separate gateway plug-in unit listed below. The units with metering can be daisy-chained together back to the
gateway. A maximum of 30 units should be daisy-chained together to one gateway.
[16] Factory assembled units are available using combinations of 1P/2P/3P circuit breakers with other NEMA and IEC type receptacles. Maximum of three drop cords with three breaker spaces
available. Consult your local Schneider Electric representative.
[17] For IP54 splash resistant construction, add an "M54" suffix.
[18] For metering, replace ( ) in catalog number with the appropriate number in Table 12.12 Meter Suffix Number, page 12-5. Connectors must be rated for appropriate voltages.
[19] Other IEC Connectors are available.
[20] For the offer without metering, do not use the suffix “M” or any numbers following.
[21] Replace ( ) in above tables with the appropriate meter suffix number. Connectors must be rated for appropriate voltages.
[22] For remote monitoring capabilities, a gateway is required. The gateway is located in the tap box with metering or in a separate gateway plug-in unit listed above. Units with metering can be
daisy-chained together back to the gateway. A maximum of 30 units should be daisy-chained together to one gateway.
[23] Additional NEMA, IEC, and California Standard type receptacles and connectors are available.
[24] See 5600CT9101 for fuse and circuit breaker series connected ratings.
12-5
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
I-Line™ Busway Standard Components
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
[1] Add “I” for inside elbow; add “O” for outside elbow.
[2] For seismic applications, seismic hangers must be used with horizontal mount flatwise or edgewise busway. Vertical mount busway may use standard fixed or spring hangers.
12-6
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
800 A–5000 A Busway I-Line™ II Busway
Class 5615 / Refer to Catalog 5600CT9101
schneider-electric.us
Number Ampere
of Poles Rating
End Tap Box Edgewise Elbow Flatwise Elbow End Tap Box Edgewise Elbow Flatters Elbow
Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No.
800 AF2308GETBMB AF2308GLEM11 AF2308GLFM11 CF2308GETBMB CF2308GLEM11 CF2308GLFM11
1000 AF2310GETBMB AF2310GLEM11 AF2310GLFM12 CF2310GETBMB CF2310GLEM11 CF2310GLFM11
1200 AF2312GETBMB AF2312GLEM11 AF2312GLFM12 CF2312GETBMB CF2312GLEM11 CF2312GLFM12
BUSWAY
1350 AF2313GETBMB AF2313GLEM11 AF2313GLFM13 CF2313GETBMB CF2313GLEM11 CF2313GLFM12
3Ø3W 1600 AF2316GETBMB AF2316GLEM11 AF2316GLFM13 CF2316GETBMB CF2316GLEM11 CF2316GLFM12
with Integral 2000 AF2320GETBMB AF2320GLEM11 AF2320GLFM15 CF2320GETBMB CF2320GLEM11 CF2320GLFM13
Ground Bus 2500 AF2325GETBMB AF2325GLEM11 AF2325GLFM17 CF2325GETBMB CF2325GLEM11 CF2325GLFM15
3000 AF2330GETBMB AF2330GLEM11 AF2330GLFM18 CF2330GETBMB CF2330GLEM11 CF2330GLFM16
3200 — — — CF2332GETBMB CF2332GLEM11 CF2332GLFM17
4000 AF2340GETBMB AF2340GLEM11 AF2340GLFM22 CF2340GETBMB CF2340GLEM11 CF2340GLFM21
5000 — — — CF2350GETBMB CF2350GLEM11 CF2350GLFM21
800 AF2508GETBMB AF2508GLEM11 AF2508GLFM11 CF2508GETBMB CF2508GLEM11 CF2508GLFM11
1000 AF2510GETBMB AF2510GLEM11 AF2510GLFM12 CF2510GETBMB CF2510GLEM11 CF2510GLFM11
1200 AF2512GETBMB AF2512GLEM11 AF2512GLFM12 CF2512GETBMB CF2512GLEM11 CF2512GLFM12
1350 AF2513GETBMB AF2513GLEM11 AF2513GLFM13 CF2513GETBMB CF2513GLEM11 CF2513GLFM12
3Ø4W 1600 AF2516GETBMB AF2516GLEM11 AF2516GLFM13 CF2516GETBMB CF2516GLEM11 CF2516GLFM12
12
with Integral 2000 AF2520GETBMB AF2520GLEM11 AF2520GLFM15 CF2520GETBMB CF2520GLEM11 CF2520GLFM13
Ground Bus 2500 AF2525GETBMB AF2525GLEM11 AF2525GLFM17 CF2525GETBMB CF2525GLEM11 CF2525GLFM15
3000 AF2530GETBMB AF2530GLEM11 AF2530GLFM18 CF2530GETBMB CF2530GLEM11 CF2530GLFM16
3200 — — — CF2532GETBMB CF2532GLEM11 CF2532GLFM17
4000 AF2540GETBMB AF2540GLEM11 AF2540GLFM22 CF2540GETBMB CF2540GLEM11 CF2540GLFM21
5000 — — — CF2550GETBMB CF2550GLEM11 CF2550GLFM21
[1] To complete the catalog number, replace the blank with an “H” for the plug-in unit to be mounted on horizontally—oriented busway and “V” for the plug-in unit to be mounted on vertically-
oriented busway.
[2] Cannot be used for 800 A copper busway.
[3] Feeder style available in lengths from 16 to 120 inches.
[4] Plug-in style also available in 4, 6, and 8 foot lengths.
[5] For seismic applications, seismic hangers must be used with horizontal mount flatwise or edgewise busway. Vertical mount busway may use standard fixed or spring hangers.
12-7
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
I-Line™ II Busway 800 A–5000 A Busway
Class 5615 / Refer to Catalog 5600CT9101
schneider-electric.us
[6] For seismic applications, seismic hangers must be used with horizontal mount flatwise or edgewise busway. Vertical mount busway may use standard fixed or spring hangers.
12-8
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
800 A to 5000 A “Factory Assembled" I-Line™ II Busway
Busway Systems (or Components)
schneider-electric.us Class 5615 / Refer to Catalog 5600CT9101
BUSWAY
Unfused reducers are used to reduce from a higher amperage busway to a lower
amperage.
NOTE: The National Electric Code does not allow the use of unfused reducers in
vertical riser installations. Refer to the NEC for restrictions in industrial installations.
Fused or Circuit Breaker Cubicle
These are used as in-line overcurrent protection devices. They can be used in
conjunction with an unfused reducer to offer a device which reduces a run of busway in
ampacity and offers overcurrent protection.
I-Line to I-Line II Adapter
12
This adapter is used to join I-Line II busway (800 A–5000 A) to existing installations of
original I-Line busway. If connecting to an existing “slot end” of original I-Line, use a “bolt
end” adapter (-12B), and vice versa.
Expansion Fittings
The expansion fitting is built into a 3 ft. – 4 in. straight length for 800 A–5000 A and a 5
feet – 0 inch straight length for 225 A–600 A. Limit of expansion or contraction is ±1-1/2
inches. Not available in outdoor construction.
Bussed Transformer Connection
A bussed transformer connection is used when the busway physically attaches (other
than cable) to a three phase transformer. For power company vault termination
information, consult the factory.
Transformer Taps
Transformer taps are used to make cable connection to transformers. Lugs other than
standard Square D brand lugs are available. Note that taps need NOT be located directly
above transformers for cable connections.
Finger Protection to IP2X
This feature provides improved protection from accidental contact with live parts during
insertion and removal of plug-in units. This feature meets the IP2X rating as defined by
IEC529 standard.
12-9
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
I-Line™ II Busway Additions, Accessories, and Electrical Data
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
Table 12.22: Short Circuit Ratings: UL 3 Cycle Test (KA, RMS Symmetrical)[7]
Aluminum Copper
Ampere APH CPH
Rating AOF2 AOFH AP COF2 COFH CP
AP2/AR2 APH2/ CF2 CFH2 CP2/CR2 CPH2/
AF2 AFH2 CRH2
ARH2
225 — — 22 — — — 22 —
400 — — 22 42 — — 22 42
600 — — 22 42 — — 22 42
800 50 85 50 75 50 85 50 75
1000 50 100 50 100 50 85 50 75
1200 50 100 50 100 50 100 50 100
1350 50 100 50 100 50 100 50 100
1600 50 100 50 100 50 100 50 100
2000 100 150 125 150 50 100 65 100
2500 100 150 125 150 100 150 125 150
3000 100 150 125 150 100 150 125 150
3200 — — — — 100 150 125 150
4000 150 200 200 — 150 200 200 —
5000 — — — — 150 200 200 —
[7] 6–cycle and 30–cycle, and fuse/circuit breaker series connected ratings are available. Please reference 5600CT9101.
[8] For IP54 splash resistant construction, add an "M54" suffix.
[9] For use on vertical riser applications only.
[10] For vertical riser applications, order auxiliary mounting kit—Catalog Number PBQ4060RMK.
[11] This device uses bolt-on connection. It may be used only on plug-in busway with same number of poles. To complete the catalog number, replace the blank with an “H” for the plug-in unit to
be mounted on horizontally—oriented busway and “V” for the plug-in unit to be mounted on vertically-oriented busway. Not for use on 800 A copper busway.
[12] Kit must be field installed.
[13] Contains parts to convert two units.
12-10
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Plug-In Units I-Line™ II Busway
Class 5615, 5630 / Refer to Catalog 5600CT9101
schneider-electric.us
BUSWAY
12
Table 12.34: H- and J-Frame Circuit Breaker Plug-in Units with Electronic Trip—Standard (80%) Rated—3Ø4W
D Interrupting G Interrupting J Interrupting L Interrupting
Trip Rating Trip Trip Unit
Ampere Function [16] [17] Catalog Number[18][19][20] Catalog Number[18][19] Catalog Number[18][19][20] Catalog Number[18][19][20]
[20]
Micrologic Standard Trip Unit
3Ø4W + G, 600 Vac 50/60 Hz
60 PHD36060GNU31X PHG36060GNU31X PHJ36060GNU31X PHL36060GNU31X
100 PHD36100GNU31X PHG36100GNU31X PHJ36100GNU31X PHL36100GNU31X
LI 3.2
150 PHD36150GNU31X PHG36150GNU31X PHJ36150GNU31X PHL36150GNU31X
250 PJD36250GNU31X PJG36250GNU31X PJJ36250GNU31X PJL36250GNU31X
60 PHD36060GNU33X PHG36060GNU33X PHJ36060GNU33X PHL36060GNU33X
100 PHD36100GNU33X PHG36100GNU33X PHJ36100GNU33X PHL36100GNU33X
LSI 3.2 S
150 PHD36150GNU33X PHG36150GNU33X PHJ36150GNU33X PHL36150GNU33X
250 PJD36250GNU33X PJG36250GNU33X PJJ36250GNU33X PJL36250GNU33X
Micrologic Ammeter Trip Unit
3Ø4W + G, 600 Vac 50/60 Hz
60 PHD36060GNU43X PHG36060GNU43X PHJ36060GNU43X PHL36060GNU43X
100 PHD36100GNU43X PHG36100GNU43X PHJ36100GNU43X PHL36100GNU43X
LSI 5.2 A
150 PHD36150GNU43X PHG36150GNU43X PHJ36150GNU43X PHL36150GNU43X
250 PJD36250GNU43X PJG36250GNU43X PJJ36250GNU43X PJL36250GNU43X
60 PHD36060GNU44X PHG36060GNU44X PHJ36060GNU44X PHL36060GNU44X
100 PHD36100GNU44X PHG36100GNU44X PHJ36100GNU44X PHL36100GNU44X
LSIG 6.2 A
150 PHD36150GNU44X PHG36150GNU44X PHJ36150GNU44X PHL36150GNU44X
BUSWAY
250 PJD36250GNU44X PJG36250GNU44X PJJ36250GNU44X PJL36250GNU44X
Micrologic Energymeter Trip Unit
3Ø4W + G, 600 Vac 50/60 Hz
60 PHD36060GNU53X PHG36060GNU53X PHJ36060GNU53X PHL36060GNU53X
100 PHD36100GNU53X PHG36100GNU53X PHJ36100GNU53X PHL36100GNU53X
LSI 5.2 E
150 PHD36150GNU53X PHG36150GNU53X PHJ36150GNU53X PHL36150GNU53X
250 PJD36250GNU53X PJG36250GNU53X PJJ36250GNU53X PJL36250GNU53X
60 PHD36060GNU54X PHG36060GNU54X PHJ36060GNU54X PHL36060GNU54X
100 PHD36100GNU54X PHG36100GNU54X PHJ36100GNU54X PHL36100GNU54X
LSIG 6.2 E
150 PHD36150GNU54X PHG36150GNU54X PHJ36150GNU54X PHL36150GNU54X
250 PJD36250GNU54X PJG36250GNU54X PJJ36250GNU54X PJL36250GNU54X
12
[16] If alternate trip functions are required, contact your local Schneider Electric field office for pricing.
[17] For Trip Unit information, refer to Micrologic Trip Units, page 7-65.
[18] For communication capabilities, add the communication suffix as shown in Communication Suffix, page . The communication package will be configured based on the system voltage
specified by the communication suffix.
[19] For availability on 100% rated, see 5600CT9101.
[20] For IP54 splash resistant construction, add an "M54" suffix.
12-13
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
I-Line™ II Busway PowerPactTM H-, J-, and L-Frame Plug-in
Units with Electronic Trip
Class 5600 / Refer to Catalog 5600CT9101 schneider-electric.us
Table 12.35: L-Frame Circuit Breaker Plug-in Units with Electronic Trip—Standard (80%) Rated—3Ø3W
D Interrupting G Interrupting J Interrupting L Interrupting R Interrupting
Trip Rating Trip
Trip Unit[22] Catalog Number[23][24] Catalog Number[23][24] Catalog Number[23] Catalog Number[23][24] Catalog Number[23][24]
Ampere Function[21]
[25][26] [25][26] [24][25][26] [25][26] [25][26]
Micrologic Standard Trip Unit
3Ø3W + G, 600 Vac 50/60 Hz
250 PBLD36250GU31X PBLG36250GU31X PBLJ36250GU31X PBLL36250GU31X PBLR36250GU31X
400 LI 3.3 PBLD36400GU31X PBLG36400GU31X PBLJ36400GU31X PBLL36400GU31X PBLR36400GU31X
600 PBLD36600GU31X PBLG36600GU31X PBLJ36600GU31X PBLL36600GU31X PBLR36600GU31X
250 PBLD36250GU33X PBLG36250GU33X PBLJ36250GU33X PBLL36250GU33X PBLR36250GU33X
400 PBLD36400GU33X PBLG36400GU33X PBLJ36400GU33X PBLL36400GU33X PBLR36400GU33X
LSI 3.3 S
600 PBLD36600GU33X PBLG36600GU33X PBLJ36600GU33X PBLL36600GU33X PBLR36600GU33X
Micrologic Ammeter Trip Unit
3Ø3W + G, 600 Vac 50/60 Hz
400 PBLD36400GU43X PBLG36400GU43X PBLJ36400GU43X PBLL36400GU43X PBLR36400GU43X
LSI 5.3 A
600 PBLD36600GU43X PBLG36600GU43X PBLJ36600GU43X PBLL36600GU43X PBLR36600GU43X
Micrologic Energymeter Trip Unit
3Ø3W + G, 600 Vac 50/60 Hz
400 PBLD36400GU53X PBLG36400GU53X PBLJ36400GU53X PBLL36400GU53X PBLR36400GU53X
LSI 5.3 E
600 PBLD36600GU53X PBLG36600GU53X PBLJ36600GU53X PBLL36600GU53X PBLR36600GU53X
Table 12.36: L-Frame Circuit Breaker Plug-in Units with Electronic Trip—Standard (80%) Rated—3Ø4W
D Interrupting G Interrupting J Interrupting L Interrupting R Interrupting
Trip Rating Trip Trip Unit[22]
Ampere Function[21] Catalog Number[23][24] Catalog Number[23][24] Catalog Number[23][24] Catalog Number[23][24] Catalog Number[23][24]
[25][26] [25][26] [25][26] [25][26] [25][26]
Micrologic Standard Trip Unit
3Ø4W + G, 600 Vac 50/60 Hz
250 PBLD36250GNU31X PBLG36250GNU31X PBLJ36250GNU31X PBLL36250GNU31X PBLR36250GNU31X
400 PBLD36400GNU31X PBLG36400GNU31X PBLJ36400GNU31X PBLL36400GNU31X PBLR36400GNU31X
LI 3.3
600 PBLD36600GNU31X PBLG36600GNU31X PBLJ36600GNU31X PBLL36600GNU31X PBLR36600GNU31X
250 PBLD36250GNU33X PBLG36250GNU33X PBLJ36250GNU33X PBLL36250GNU33X PBLR36250GNU33X
400 PBLD36400GNU33X PBLG36400GNU33X PBLJ36400GNU33X PBLL36400GNU33X PBLR36400GNU33X
LSI 3.3 S
600 PBLD36600GNU33X PBLG36600GNU33X PBLJ36600GNU33X PBLL36600GNU33X PBLR36600GNU33X
Micrologic Ammeter Trip Unit
3Ø4W + G, 600 Vac 50/60 Hz
400 PBLD36400GNU43X PBLG36400GNU43X PBLJ36400GNU43X PBLL36400GNU43X PBLR36400GNU43X
LSI 5.3 A
600 PBLD36600GNU43X PBLG36600GNU43X PBLJ36600GNU43X PBLL36600GNU43X PBLR36600GNU43X
400 PBLD36400GNU44X PBLG36400GNU44X PBLJ36400GNU44X PBLL36400GNU44X PBLR36400GNU44X
LSIG 6.3 A
600 PBLD36600GNU44X PBLG36600GNU44X PBLJ36600GNU44X PBLL36600GNU44X PBLR36600GNU44X
Micrologic Energymeter Trip Unit
3Ø4W + G, 600 Vac 50/60 Hz
400 PBLD36400GNU53X PBLG36400GNU53X PBLJ36400GNU53X PBLL36400GNU53X PBLR36400GNU53X
LSI 5.3 E
600 PBLD36600GNU53X PBLG36600GNU53X PBLJ36600GNU53X PBLL36600GNU53X PBLR36600GNU53X
400 PBLD36400GNU54X PBLG36400GNU54X PBLJ36400GNU54X PBLL36400GNU54X PBLR36400GNU54X
LSIG 6.3 E
600 PBLD36600GNU54X PBLG36600GNU54X PBLJ36600GNU54X PBLL36600GNU54X PBLR36600GNU54X
12
BUSWAY
[21] If alternate trip functions are required, contact your local Schneider Electric field office for pricing.
[22] For Trip Unit information, refer to Micrologic Trip Units, page 7-65.
[23] For communication capabilities, add the communication suffix as shown in Communication Suffix, page . The communication package will be configured based on the system voltage
specified by the communication suffix.
[24] For availability on 100% rated, see 5600CT9101.
[25] For IP54 splash resistant construction, add an "M54" suffix.
[26] For vertical riser applications, order auxiliary mounting kit—Catalog Number PBQ4060RMK.
12-14
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
PowerPactTM M-Frame Plug-in Units with I-Line™ II Busway
Basic Electronic Trip
schneider-electric.us Class 5600 / Refer to Catalog 5600CT9101
H- , J-, and L-Frame Plug-In Units with Electronic Trip and
Communication
Hardware communication packages are now available on Powerpact H-, J-, and
L-Frame Plug-in Units with Electronic Trip. These hardware communication packages
will provide you the capability to access and monitor circuit breaker data from these plug-
in units. The packages are available in Modbus and Ethernet.
Add the appropriate communication system voltage suffix to the end of the associated
H-, J-, or L-Frame breaker with electronic trip, for example: PHD36060GNU31XIFE4.
Table 12.39: M-Frame Circuit Breaker Plug-in Units with Basic Electronic Trip Unit
(ET 1.0)—3Ø4W[28][29]
G Interrupting J Interrupting
Trip Rating Ampere
Catalog Number[30] Catalog Number[30]
3Ø4W + G, 600 Vac 50/60 Hz
300 PTMG36300GN( ) PTMJ36300GN( )
350 PTMG36350GN( ) PTMJ36350GN( )
400 PTMG36400GN( ) PTMJ36400GN( )
450 PTMG36450GN( ) PTMJ36450GN( )
500 PTMG36500GN( ) PTMJ36500GN( )
600 PTMG36600GN( ) PTMJ36600GN( )
700 PTMG36700GN( ) PTMJ36700GN( )
800 PTMG36800GN( ) PTMJ36800GN( )
BUSWAY
12
[27] Communication packages are housed in a separate enclosure mounted adjacent to the plug-in units.
[28] The ET 1.0 trip unit cannot be field replaced or have the long-time trip point setting adjusted.
[29] All these devices use bolt-on connection. It may be used only on busway with same number of poles. Not for use on 800 A copper busway. To complete the catalog number, replace the
blank with an “H” for horizontal applications and “V” for vertical applications.
[30] For IP54 splash resistant construction, add an "M54" suffix.
12-15
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
I-Line™ II Busway PowerPactTM P-Frame Plug-in Units
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
[31] The 250 A is available as a special device. Contact your local Schneider Electric field office for ordering information.
[32] If alternate trip functions are required, contact your local Schneider Electric field office for pricing.
[33] For Trip Unit information, refer to Micrologic Trip Units, page 7-65.
[34] Listed catalog numbers are for 80% rated circuit breakers. For 100% rated circuit breakers, replace the blank with an “HC” for horizontal applications and “VC” for vertical applications. For
example, the catalog number for a 100% standard trip unit with standard LI trip functions at 800 A 3Ø3W for a horizontal application would be PTPG36080GHCU31A.
[35] The standard rating plug supplied with a trip unit will be the "A" rating plug. To specify an alternative rating plug, replace the "A" at the end of the catalog number with the applicable suffix
letter. See Table 7.132 Rating Plugs, page 7-69 for rating plug catalog suffix letters.
[36] All these devices use bolt-on connection. It may be used only on busway with same number of poles. Not for use on 800 A copper busway. To complete the catalog number, replace the
blank with an “H” for horizontal applications and “V” for vertical applications.
[37] For IP54 splash resistant construction, add an "M54" suffix.
12-16
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
PowerPactTM R-Frame Plug-in Units I-Line™ II Busway
Class 5600 / Refer to Catalog 5600CT9101
schneider-electric.us
BUSWAY
800 PTRG36080GN( )U41A PTRJ36080GN( )U41A PTRL36080GN( )U41A
1000 PTRG36100GN( )U41A PTRJ36100GN( )U41A PTRL36100GN( )U41A
LI 3.0 A
1200 PTRG36120GN( )U41A PTRJ36120GN( )U41A PTRL36120GN( )U41A
1600 PTRG36160GN( )U41A PTRJ36160GN( )U41A PTRL36160GN( )U41A
800 PTRG36080GN( )U43A PTRJ36080GN( )U43A PTRL36080GN( )U43A
1000 PTRG36100GN( )U43A PTRJ36100GN( )U43A PTRL36100GN( )U43A
LSI 5.0 A
1200 PTRG36120GN( )U43A PTRJ36120GN( )U43A PTRL36120GN( )U43A
1600 PTRG36160GN( )U43A PTRJ36160GN( )U43A PTRL36160GN( )U43A
800 PTRG36080GN( )U44A PTRJ36080GN( )U44A PTRL36080GN( )U44A
1000 PTRG36100GN( )U44A PTRJ36100GN( )U44A PTRL36100GN( )U44A
LSIG 6.0 A
1200 PTRG36120GN( )U44A PTRJ36120GN( )U44A PTRL36120GN( )U44A
1600 PTRG36160GN( )U44A PTRJ36160GN( )U44A PTRL36160GN( )U44A
12
[38] The 600 A is available as a special device. Contact your local Schneider Electric field office for ordering information.
[39] Listed catalog numbers are for 80% rated circuit breakers. For 100% rated circuit breakers, replace the blank with an “HC” for horizontal applications and “VC” for vertical applications. For
example, the catalog number for a 100% standard trip unit with standard LI trip functions at 800 A 3Ø3W for a horizontal application would be PTPG36080GHCU31A.
[40] The standard rating plug supplied with a trip unit will be the "A" rating plug. To specify an alternative rating plug, replace the "A" at the end of the catalog number with the applicable suffix
letter. See Table 7.132 Rating Plugs, page 7-69 for rating plug catalog suffix letters.
[41] All these devices use bolt-on connection. It may be used only on busway with same number of poles. Not for use on 800 A copper busway. To complete the catalog number, replace the
blank with an “H” for horizontal applications and “V” for vertical applications.
[42] For IP54 splash resistant construction, add an "M54" suffix.
12-17
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Power-Zone™ Busway Non-Segregated Bus
Class 6090 / Refer to Catalog 5600CT9101
schneider-electric.us
Non-Segregated Bus
• Non-segregated phase bus
• 600 V through 38 kV (1200 A–6000 A)
• Aluminum, steel or stainless steel housing
• Aluminum or copper bus bars
• Insulated with fluidized bed epoxy (5 kV–38 kV)
• Complete line of fittings provides for any configuration
• Indoor trapeze and outdoor column supports
• For use in utilities, industrial and commercial facilities
Power-Zone bus is custom designed, manufactured and tested per ANSI C37.23
standards to meet customer specifications. The 600 V product is also UL Listed. It is a
completely coordinated package of equipment with all the auxiliary material and supports
for connecting transformers, switchgear, MCCs, and motors, in all types of utility,
industrial, and commercial facilities.
Bus Options
Some available options are special momentary rating, special housing material and/or
finish, special conductor supports, heaters and thermostats, and ground bus.
Weatherproof Bus
12
All weatherproof runs must be equipped with strip heaters to eliminate condensation and,
if applicable, a thermostat. A heater should be used for every seven (7) foot of bus and
no more than 20 heaters can be controlled by one thermostat. Also, each bus run should
have its own thermostat. The heaters are rated 240 V, 500 watts and operate at 120 V,
125 watts.
Flanged Ends
A flanged end is used to terminate the bus into switchgear, motor control centers,
BUSWAY
Transformer/Generator Connection
This type of termination should be used whenever the bus is connecting to a transformer,
generator, motor, switch or any connection where the bus bars are connecting to
porcelain mounted equipment terminals. It will include the same components as a
flanged end plus one set of flexible braid type connectors and a terminal box (if required).
12-18
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Non-Segregated Bus Power-Zone™ Busway
Class 6090 / Refer to Catalog 5600CT9101
schneider-electric.us
Ground Bus
The bus housing is designed and constructed to provide an electrically continuous
ground path. The side rails of the bus housings are capable of carrying the full rated
phase current continuously and, under short circuit conditions, are capable of carrying up
to 60 kA RMS asymmetrical fault current for 3 seconds. Consequently, a separate
ground bus is not necessary unless specified.
Expansion Fittings
An expansion fitting is used to counteract the strain placed on the bus due to the
expansion and contraction of the building or the bus itself. One should be used whenever
the bus run crosses a building expansion joint and whenever a straight run of bus
exceeds 60 feet.
BUSWAY
Table 12.45: Hangers/Supports
Support Description Maximum Height Options
Indoor Trapeze Hanger —
Outdoor, Single
Column Support 12 feet
Outdoor, Double
Column Support 22 feet
12
12-19
© 2017 Schneider Electric
All Rights Reserved
11/10/2017
Power-Zone™ Busway Non-Segregated Bus
Class 6090 / Refer to Catalog 5600CT9101
schneider-electric.us
Standard Construction
Standard construction is as follows:
• Conductor (plating): Copper (silver) or Aluminum (tin)
• Conductor Insulation (5 kV through 38 kV only): epoxy
• Conductor
kV)
Supports: Glass reinforced polyester blocks (5 kV and 15 kV); porcelain (38
12-20
© 2017 Schneider Electric
All Rights Reserved
11/10/2017