Professional Documents
Culture Documents
Im 6
Im 6
Im 6
College: Engineering
Campus: Bambang
Polyphase Systems
This lesson provides the students an Introduction to polyphase systems. This module discusses the
generation of three phase system, advantages of a three phase system over a single phase system,
phase notation of a three phase system, and three phase system configuration for current and voltage of
balanced three phase system.
V. LESSON CONTENT
Almost all electric power generation and most of the power transmission in the world is in the form of
three-phase AC circuits.
A poly-phase system consists of an arrangement of two or more similar single phase system in which the
maximum values of the independent voltage waves do not occur at the same instant of time.
The most common combination is the three phase system (interconnection of three single phase system)
with equal amplitude and frequency are displaced by exactly 120 electrical degrees.
the equation above is not applicable for 2 phase system for it is displaced by exactly 90 electrical degrees.
Note! Since each coil can be regarded as a single-phase generator by itself, the three-phase generator can supply power to
both single-phase and three-phase loads.
The three-phase sources, explained before, can be connected either wye (Y) or delta (∆) as shown
Consider the wye-connected voltages above, the voltages Van, Vbn, and Vcn are respectively between
lines a, b, and c, and the neutral line n. These voltages are called phase voltages. If the voltage sources
have the same amplitude and frequency and are out of phase with each other by 120 degrees, the
voltages are said to be balanced. This gives
𝑉𝑎𝑛 + 𝑉𝑏𝑛 + 𝑉𝑐𝑛 = 0 where |𝑉𝑎𝑛| = |𝑉𝑏𝑛| = |𝑉𝑐𝑛|
Phase sequence
There are two possible combinations, one possibility is called positive (abc) sequence. This sequence
is produced when the phasor diagram rotates clockwise. The other sequence is called negative (acb)
sequence and it is produced when the phasor diagram rotates counterclockwise. The phase sequence
is determined by the order in which the phasors pass through a fixed point in the phase diagram.
Positive sequence
Negative sequence
Exercise 1.1
Given a positive sequence 3 phase system, Find the phase voltages of 𝑉𝑎𝑛 = 120∠ − 30 𝑉.
Solution:
𝑉𝑎𝑛 = 120∠ − 30 𝑉
Note! Phase displacement between phase voltages is 120 degrees.
Exercise 1.2
Given 𝑉𝑏𝑛 = 220∠100 𝑉, determine Phase voltage Van and Vcn using negative sequence.
Solution:
Note! negative sequence- counter clockwise rotation
𝑉𝑏𝑛 = 220∠100 𝑉
𝑉𝑎𝑛 = 220∠(100 − 120) 𝑉 = 𝟐𝟐𝟎∠ − 𝟐𝟎 𝑽
Note! Y-connected load can be transformed into a delta-connected load, or vice versa.
Since both the three-phase source and the three-phase load can be either Y or ∆, we have four possible
connections:
Y-Y connection (Y-connected source with a Y-connected load)
Y-∆ connection (Y-connected source with a ∆-connected load)
∆-∆ connection (∆-connected source with a ∆-connected load)
∆-Y connection (∆-connected source with a Y-connected load)
The line-to-line voltages or simply line voltages Vab, Vbc, and Vca are related to the phase voltages
The relation between phase and line voltages can be proved vectorially
From the phasor diagram shown above, it is clear that the magnitude of the line voltages VL is √𝟑 times
the magnitude of the phase voltages Vp(Van, Vbn,Vcn).
Also the line voltages lead their corresponding phase voltages by 30◦.
Applying KVL to each phase, we obtain the phase current which is equal to the line current.
𝑽𝒂𝒏 𝑽𝒂𝒏 𝑽𝒄𝒏
𝑰𝒂 = 𝑰𝒃 = 𝑰𝒄 =
𝒁𝒂 𝒁𝒃 𝒁𝒄
The line current is the current in each line, and the phase current is the current in each
phase of the source or load. In Y-Y, the line current is the same as the phase current.
For a balanced three phase system, the line currents add up to zero.
𝑰𝒂 + 𝑰𝒃 + 𝑰𝒄 = 𝟎
Example 1.3.
Given a three phase source with a phase voltage Van and a magnitude of 110 ∠0 𝑉.
Find the line voltages Vab, Vbc, and Vca. Assume a positive sequence.
Solution:
Example 1.4.
Refer to figure below, Find for the line voltages and line currents if 𝑉𝑎𝑛 = 120∠30 𝑉, and load impedance
𝑍𝑦 = 30∠25 𝑜ℎ𝑚𝑠.
Solution:
The balanced wye-delta system is shown in the figure below, where the source is Y-connected and the
load is delta-connected. There is no neutral connection from source to load for this case
Note! The line voltages are equal to the voltages across the load impedances for this system
configuration.
These currents have the same magnitude but are out of phase with each other by 120◦.
The line currents are obtained from the phase currents by applying KCL at nodes A, B, and C. Thus,
The relation between phase and line currents for delta-connected circuits is shown
From phasor diagram above, the magnitude IL of the line current is √𝟑 times the magnitude Ip of the
phase current, or
𝑰𝑳 = | 𝑰𝒂| = | 𝑰𝒃 | = | 𝑰𝒄|
And
𝑰𝑷 = | 𝑰𝒂𝒃| = | 𝑰𝒃𝒄 | = | 𝑰𝒄𝒂|
Also, the line currents lag the corresponding phase currents by 30◦.
Example 1.5
For wye- delta system, determine the line voltages, phase currents and line currents if Van=
120∠30 V and load impedance is equal to 20+15i ohms.
Solution:
𝑽𝒂𝒏 = 120∠30 𝑉
𝒁∆= 20 + 15𝑖 Ω = 25∠36.87 Ω
𝑉𝑎𝑏 207.846∠ 60
𝐼𝛷 = 𝐼𝑎𝑏 = = = 𝟖. 𝟑𝟏𝟒 ∠ 𝟐𝟑. 𝟏𝟑 𝑨
𝑍∆ 25∠36.87
𝑉𝑏𝑐 207.846∠ − 60
𝐼𝛷 = 𝐼𝑏𝑐 = = = 𝟖. 𝟑𝟏𝟒 ∠ − 𝟗𝟔. 𝟖𝟕 𝑨
𝑍∆ 25∠36.87
𝑉𝑐𝑎 207.846∠180
𝐼𝛷 = 𝐼𝑐𝑎 = = = 𝟖. 𝟑𝟏𝟒 ∠ 𝟏𝟒𝟑. 𝟏𝟑 𝑨
𝑍∆ 25∠36.87
Example 1.6
For the three-phase Y-∆ circuit shown calculate the line and phase currents of the load. Assume that
𝑍𝐿 = 12 + 𝑗2 Ω.
Solution:
𝑍∆ 12 + 𝑗2
𝑍𝑌 = = = 4.055∠9.462 𝑜ℎ𝑚𝑠.
3 3
In that case the transmission line impedance (Zline) will be in series with ZY
𝑉𝑎𝑛 100∠ 0 𝑉
𝐼𝑎 = = = 𝟏𝟕. 𝟔𝟒𝟕∠ − 𝟐𝟖. 𝟎𝟕𝟐𝟒 𝑨
𝑍𝑡𝑜𝑡𝑎𝑙 5.667∠28.0724 Ω
In wye-delta system line current is √𝟑 times the phase currents and it is always lagging by 30 degrees with
respect to phase currents.
𝐼𝑎 17.647
𝐼𝑎𝑏 = = = 10.189∠ − 28.0724 + 30 = 𝟏𝟎. 𝟏𝟖𝟗 ∠𝟏. 𝟗𝟐𝟕𝟔 𝑨
√3 √3
𝐼𝑏 17.647
𝐼𝑏𝑐 = = = 10.189∠ − 148.0724 + 30 = 𝟏𝟎. 𝟏𝟖𝟗 ∠ − 𝟏𝟏𝟖. 𝟎𝟕𝟐 𝑨
√3 √3
𝐼𝑏 17.647
𝐼𝑐𝑎 = = = 10.189∠91.9276 + 30 = 𝟏𝟎. 𝟏𝟖𝟗 ∠ 𝟏𝟐𝟏. 𝟗𝟐𝟖 𝑨
√3 √3
The source as well as the load is delta-connected as shown. Assuming a positive sequence, the phase
voltages for a delta-connected source are:
𝑽𝑳 = 𝑽𝒑 𝑽𝒐𝒍𝒕𝒔
The line voltages are the same as the phase voltages. Assuming there is no line impedances, the phase
voltages of the delta connected source are equal to the voltages across the impedances. Hence, the
phase currents are
The line currents Ia, Ib and Ic are greater than the phase current by √𝟑 and lag the corresponding phase
current by 30°.
Example 1.6
A three-phase, positive sequence ∆- ∆ connected circuit with a load impedance of 30 ∠ 30 ohms. If the
line voltage Vab is 240 ∠ 0 V, calculate the line voltages, phase currents and line currents.
Solution:
𝑉𝑎𝑏 = 240 ∠ 0 𝑉
𝑉𝑏𝑐 = 240 ∠ − 120 𝑉
𝑉𝑐𝑎 = 240 ∠ 120 𝑉
𝑉𝑎𝑏 240 ∠ 0 𝑉
𝐼𝑎𝑏 = = = 𝟖∠ − 𝟑𝟎 𝑨
𝑍∆ 30 ∠ 30Ω
𝑉𝑏𝑐 240 ∠ − 120 𝑉
𝐼𝑏𝑐 = = = 𝟖∠ − 𝟏𝟓𝟎 𝑨
𝑍∆ 30 ∠ 30Ω
𝑉𝑐𝑎 240 ∠120 𝑉
𝐼𝑐𝑎 = = = 𝟖∠𝟗𝟎 𝑨
𝑍∆ 30 ∠ 30Ω
NVSU-FR-ICD-05-00 (081220) Page 10 of __
Republic of the Philippines
NUEVA VIZCAYA STATE UNIVERSITY
Bambang, Nueva Vizcaya
INSTRUCTIONAL MODULE
IM No6.:EE02-2S-2020-2021
At source side, the line voltages, given above, are also same as the phase voltages.
At load side the phase voltage Van is less than the line voltage Vab by √𝟑 and lags it by 30°, therefore,
the line current (which equals the phase current) Ia can be obtained as:
𝑉𝑎𝑏/√𝟑
𝐼𝑎 = ∠ − 30⁰
𝑍𝑦
Example 1.7
For the 3-phase, +ve sequence ∆-Y circuit , if 𝑉𝑎𝑏 = 440∠10° 𝑉 and 𝑍𝑦 = 10 − 𝑗8 𝑜ℎ𝑚𝑠. Calculate
the line voltages and line currents.
Solution:
𝑍𝑦 = 10 − 𝑗8 Ω = 12.806 ∠ − 38.66 Ω
𝑉𝑎𝑏 = 440∠10° 𝑉
𝑉𝑏𝑐 = 440∠ − 110° 𝑉
𝑉𝑐𝑎 = 440∠130° 𝑉
For a ∆-Y circuits it is easier to convert the Zy to its equivalent Zdelta then proceed with the process of
a ∆- ∆ circuit in finding the line currents.
1. a. Calculate the phase voltages, line voltages, and load currents if Vcn= 230∠ 80 V and Zy= 25+j25
ohms.
Draw the phasor diagram for voltages and currents
b. Assume there is a line impedance of 3+ j2 ohms and all other conditions remain the same, phase
voltages and line voltage before and after the line impedance.
2. a. For wye- delta system, determine the line voltages, phase currents and line currents if the
load impedance is equal to 15+j10 ohms.
b. Assume there is a line impedance of 3+ j2 ohms and all other conditions remain the same, phase
voltages and line voltage before and after the line impedance.
3. Refer to the figure below, with Vab= 230∠0 V, find for the load voltages and line currents.