Professional Documents
Culture Documents
Through-Faults and Slow Breakers Affecting The Transformers
Through-Faults and Slow Breakers Affecting The Transformers
1. Harmonics increased level of condition monitoring, frequency of fault occurrences. Faults are
from the aspect of the rate of insulation generally the result of a low impedance
The increasing implementation of renew- aging and accumulation of the harmonic path to the ground being introduced into
able energy resources connected (most of content, which is now available with some a circuit, such as dielectric failure of pro-
the time) into an existing distribution or online monitoring systems. tection equipment or tree limbs striking
sub-transmission network that was never overhead lines and causing the current to
designed to handle a two-way power flow exceed the transformer’s rated base.
2. Through-faults
presents an opportunity for accelerated
aging of the paper insulation surround- Potential generation of through-faults Underground systems are designed to
ing the conductors of the windings. These can vary greatly across short spans of any limit exposure to potential fault sources.
generation sources (which are often in- electrical grid, and factors such as circuit However, when these underground faults
verter-fed) together with geomagnetical- length, type (overhead, underground), do occur, they are usually persistent, caus-
ly induced currents (GIC), are two of the condition of protective equipment, de- ing a lockout of the protection system,
factors known to introduce undesirable grading infrastructure, and terrain must which requires a closer investigation be-
harmonic frequencies into the grid and be considered as factors that can affect the fore power can be restored. These faults
the equipment connected to it.
tend to happen more frequently in over- chanical and thermal stresses on the core The frequency at which these events occur
head systems and are often transient in and coil assembly of the affected trans- can have an aggregated effect (cumula-
nature, resulting in the fault being cleared former. However, due to the power-pro- tive I2T) on the transformer’s mechanical
in a few milliseconds by the power system tection system operating effectively, little structure, ultimately resulting in a de-
protection. consideration is given to the weakening of crease of the transformer’s fault withstand
the transformers clamping system or any capability. The presence of these cumula-
The amount of energy flowing through core deformation that may have occurred tive effects is problematic in that they are
the transformer (I2T) for the duration of because of the increased electromagnetic not easily detected using routine main-
these transient faults places excessive me- force. tenance testing such as power factor and
dissolved gas or furan analysis but would
require more in-depth testing procedures
such as sweep frequency response analysis
It is difficult to quantify the level of cumu- or winding induction testing.
lative I2T a specific transformer can sustain
Nor are existing vintage electro-mechan-
and remain fit for service due to the wide ical relays much help to understand the
range of variables that must be considered amount and duration of through faults.
They react as designed to disconnect a
when performing the assessment load (transformer, generator, etc.) in a pre-
set amount of time. They do not have the
capability of modern digital relays that
can capture the events. However, many
existing substations have not had these re-
lays replaced with digital type protection
relays, and even when the digital relays are
present, asset managers are often not able
to access the quantitative data required to
evaluate the damage.
4. Limiting through-fault
exposure to transformers and
other equipment
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 33
FAILURES
6. Conclusion
Measuring and tracking the harmon-
ic content of both voltage and current is
recommended for existing transformers
connected to DER where inverters are in
place. The Loading guide IEC 60076-1/
2012 includes the definition of normal
service conditions in section 4.2 [3].
The wave shape of the supply voltage:
Figure 5. Complete failure of transformer and breaker
A sinusoidal supply voltage with a total
harmonic content not exceeding 5 % and
Online circuit breaker monitoring has prov- an even harmonic content not exceeding
1 %.
en to be highly effective at detecting oper-
Load current harmonic content:
ational abnormalities that may often go un-
The total harmonic content of the load
observed through traditional maintenance current not exceeding 5 % of the rated
testing current.
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 35