Project Note

Project: SGS PHILS INC

Notes: Equivalent length is calculated by coefficients:


1.2:System 1
The user is responsible for ensuring that all data entered is correct.
Equipment selections have been based on the Design Guidelines stated within the Toshiba SMMS∞/SMMS-u/SMMS-
e/SHRM-e/SMMS-7/MiNi-SMMS7/MiNi-SMMS-e/Side Blow VRF/MiNi-SMMS Installation Manual.
It is the responsibility of the consultant or contractor, to verify and confirm that the equipment selection and system
design is correct before installation.
Please note that in the event of future system expansion being allowed for in the system design or a change in
cooling/heating requirements, a re-evaluation of the air conditioning system must be made prior to final installation.

Project Name:SGS PHILS INC Version:2.0.69


Prepared By:NLR Revision: Page 1 of 6
Project Equipment List

SGS PHILS INC

Outdoor Units
Model Quantity Description
MMY-MUP1401T7P 2 Super Modular Multi System (SMMS∞)

DX Kit Item
Model Quantity Description
TCB-IFDMX01UP-E 2 DX Coil Controller
RBM-A201UPVA-E 2 DX Valve Kit

Y Joints
Model Quantity Description
RBM-BT24E 1 Outdoor Unit Branch Kit
RBM-BY305E 1 Y-Joint

Piping Length
Pipe Diameter Total Length Gas Side Discharge Side Liquid Side
15.9mm 0.00 m 0.00 m 0.00 m 0.00 m
19.1mm 0.00 m 0.00 m 0.00 m 0.00 m
28.6mm 0.00 m 0.00 m 0.00 m 0.00 m
34.9mm 0.00 m 0.00 m 0.00 m 0.00 m

Total Refrigerant Charge Amount


Refrigerant (R410A) Amount Description
Outdoor Unit 12.000 kg Refrigerant amount charged in factory
Additional Refrigerant 4.400 kg Amount needed for the pipes at the site
TOTAL: 16.400 kg

Outdoor Design Temperature


System Mode Description Temperature
System 1 Cooling Dry Bulb temperature 35.0 °C
Heating Wet Bulb temperature 6.0 °C

Project Name:SGS PHILS INC Version:2.0.69


Prepared By:NLR Revision: Page 2 of 6
System Equipment List

System 1

Outdoor Units
Model Quantity Description
MMY-UP2811T7P 1 Super Modular Multi System (SMMS∞)
MMY-MUP1401T7P Super Modular Multi System (SMMS∞)

DX Kit Item
Model Quantity Description
TCB-IFDMX01UP-E 2 DX Coil Controller
RBM-A201UPVA-E 2 DX Valve Kit

Y Joints
Model Quantity Description
RBM-BT24E 1 Outdoor Unit Branch Kit
RBM-BY305E 1 Y-Joint

Piping Length

Pipe Diameter Total Length Gas Side Discharge Side Liquid Side

15.9mm 0.00 m 0.00 m 0.00 m 0.00 m


19.1mm 0.00 m 0.00 m 0.00 m 0.00 m
28.6mm 0.00 m 0.00 m 0.00 m 0.00 m
34.9mm 0.00 m 0.00 m 0.00 m 0.00 m

Total Refrigerant Charge Amount


Refrigerant (R410A) Amount Description
Outdoor Unit 12.000 kg Refrigerant amount charged in factory
Additional Refrigerant 4.400 kg Amount needed for the pipes at the site
TOTAL: 16.400 kg

Outdoor Design Temperature


Mode Description Temperature
Cooling Dry Bulb temperature 35.0 °C
Heating Wet Bulb temperature 6.0 °C

Electrical Information(OutdoorUnits)
Property Value Description
MOCP(A) 64 Maximum Overcurrent Protection
MCA(A) 56 Minimum Circuit Amps
Protection Device Size(A) Follow applicable local standard as needed
Wire(cable size)(mm²) or AWG(#) Follow applicable local standard as needed

Electrical Information(IndoorUnits)
Property Value Description
Total MCA(A) 0.4
Protection Device Size(A) Follow applicable local standard as needed
Wire(cable size)(mm²) or AWG(#) Follow applicable local standard as needed

Project Name:SGS PHILS INC Version:2.0.69


Prepared By:NLR Revision: Page 3 of 6
Schematic Overview

System 1
System information MMY-UP2811T7P
Indoor Units 1 of 63 80.00 kW
Capacity Ratio 100.0% Cooling Only
Total Pipe Length 0.00 m
Indoor Cap. Tot./Sen. 80.00 kW/0.00 kW
Indoor Cap. Heat. n/a
Building diversity 0%

Outdoor/Indoor Legend
Unit Name
Model Name
Room Name
Rated Capacities Tot./Sens./ Heat.

Piping Legend
Actual Length
Liquid / Suction Gas diameters
Note: It is the responsibility of the consultant or
contractor, to verify and confirm that the equipment 19.1 / 34.9
selection and system design is correct before 28HP_2TCB-IFDMX01UP-E+
installation. 2RBM-A201UPVA-E
80.00 /0.00 kW
Cooling Only

Project Name:SGS PHILS INC Version:2.0.69


Prepared By:NLR Revision: Page 4 of 6
Dx kit Details

System 1
28HP_2TCB-IFDMX01UP-E+2RBM-A201UPVA-E

Size 14 HP 14 HP
DX Control TCB-IFDMX01UP-E TCB-IFDMX01UP-E
DX Valve RBM-A201UPVA-E RBM-A201UPVA-E
Elevation 0.00 m 0.00 m
Name

Project Name:SGS PHILS INC Version:2.0.69


Prepared By:NLR Revision: Page 5 of 6
Wiring Diagram

System 1
B
B

3N AC+Earth 380V 60Hz


MCA 56A / MOCP 64A
MMY-MUP1401T7P Super Modular Multi System (SMMS∞)
MMY-MUP1401T7P

Outdoor Unit

MMY-UP2811T7P
80.00 kW
Cooling Only

Uc:Control wiring between Outdoor Units(2 Core Shield Wire)


Uv:Control for Outdoor Unit-Indoor Unit(2 Core Shield Wire)
Uc

B
1N AC+Earth 220V 60Hz
MCA 0.4A / MOCP 15A Uv

28HP_2TCB-I
FDMX01UP-E
+2RBM-A201
UPVA-E
80.00 /0.00 kW
Cooling Only
Page 1 of 1

Project Name:SGS PHILS INC Version:2.0.69


Prepared By:NLR Revision: Page 6 of 6