Professional Documents
Culture Documents
1TB02017 017C62 Acn MTS Me 0019 C0
1TB02017 017C62 Acn MTS Me 0019 C0
RSG-CN-FRM-0012
AMAALA
General Information
Project
Program Name Project Name Six Senses
Triple Bay Central Code 1TB02017
Contract No.
1.TB.02.017C62-2000
Contract Description
Contractor
Method Statement for Flushing and
Contractor Name Subject Chemical Disinfection of (Potable)
ASTRA Construction Company Domestic Water Piping Network
Other (please
Discipline Civil
specify)
Planned Date of Work Submitted For: ☐ Approval ☐ Information
Contractor Authorized Representative
Date
Name Signature Date
Engineer’s - Comments
Comments:
Date
Name Signature Date
Status Code
RSG-CN-FRM-0012
Rev. 00, 16 Nov 2022 Page 1 of 2
Engineer’s - Comments
RSG-CN-FRM-0012
Rev. 00, 16 Nov 2022 Page 2 of 2
Method Statement
Method Statement for Flushing and Chemical Disinfection of (Potable) Domestic Water Piping Network
Revision Control
Page 2 of 17
Method Statement for Flushing and Chemical Disinfection of Domestic
Water Piping Network
1 Scope of Work
The scope of work includes the flushing and chemical disinfection of the domestic water piping network to ensure
compliance with worldwide standards and specifications. This encompasses preliminary flushing, chlorination
using sodium hypochlorite solution, final flushing, bacteriological testing, and certification of disinfection.
Infrastructure construction for Six Senses-Plot 6
American Society for Testing and Materials (ASTM) standards for dewatering.
Occupational Safety and Health Administration (OSHA) regulations for construction sites.
Project Specification
SDW: 1TB02017-017C62-ACN-00-XX-SDW-UT-12710
Material Approvals/Submittal
2 Methodology
Page | 1
Test samples for total bacteria count in accordance with Standard Methods for the Examination of
Water and Wastewater.
Control values for bacteriological testing:
Free chlorine: 50 ppm (during disinfection)
Free chlorine: 0 - 1.0 ppm (after flushing/de-chlorination)
Total Bacteria: 0/ml
5. Certificate of Disinfection (Stage IV):
Upon completion of the flushing and disinfection process, submit a Certificate of Disinfection along with
laboratory and bacterial test results indicating satisfactory outcomes.
Ensure all documentation is provided to relevant authorities and stakeholders for approval and record-
keeping purposes.
6. Safety Precautions:
Adhere to safety protocols for handling chemicals and operating equipment.
Provide adequate ventilation and use appropriate PPE during the disinfection process.
Ensure proper disposal of chemicals and waste in accordance with environmental regulations.
7. Quality Assurance and Compliance:
Maintain accurate records of all activities, including flushing, disinfection, and testing procedures.
Ensure compliance with AWWA Standards and local regulations throughout the entire process.
Conduct regular inspections and monitoring to verify the effectiveness of the flushing and disinfection
procedures.
8. Handover and Training:
Provide training to maintenance personnel on the operation and maintenance of the water piping
network.
Hand over all relevant documentation, including operation manuals and maintenance schedules, to the
client or facility management team.
a. Project Manager:
It is the overall responsibility of PM to organize resources to perform construction activities as per
project specifications in compliance with quality, schedule and safety requirements.
b. Construction Manager:
It is the responsibility of CM that construction activities are being executed according to the
relevant project specifications, in compliance with quality, schedule and safety requirements of
Concrete Works in Construction Works. in Construction
c. Site Engineer:
shall monitor all the construction activities in accordance with project specifications, IFC drawings
by following the safe conditions under the contractor’s site safety plan.
d. MEP Engineer
will coordinate with the Construction Manager or Site Engineer in advance in all MEP installation
works interfacing in line with work schedules and progress. He will coordinate with MEP
subcontractor and ensure that all MEP services/openings identified and located are completed at
required areas.
e. QA / QC Manager:
will check/Involve a strict internal quality control and inspection to ensure that the work is executed
fully in accordance with the requirements of the contract specifications and drawings.
f. QA/QC Engineer:
Shall make sure the following items and carry out all field inspections. Under project specification
related to the quality control services:
• He will ensure the material shall conform to project specification and approved samples.
• Work should be carried out as per latest revision of drawings.
• He will confirm the storage and placing of the materials on site and other arrangements as
per IFC drawings.
Page | 2
• He will monitor the quality of works and in conformance with the IFC drawing as per
approved checklist.
• He will keep records of all inspections and testing related to the activity.
g. The Surveyor:
• Will ensure the location & levels of all the structures are as per approved drawings.
• After the concreting and before setting of concrete the foundations and other connection
points (especially but not limited to anchor bolts) are checked by surveyor to confirm them
location, orientation, elevation and condition.
h. Safety Officers:
• He will make sure that all construction activities would be carried out under approved RAMS.
• He will make sure that all workers have proper PPEs.
• He will make sure that proper certifications and inspections of equipment are updated prior to
start the work.
• He will inspect and confirm all steps for tiles installation defined under RAMS.
• He will make sure the provision of safety arrangements for work area and will carry out the
required inspections.
• He makes sure the presence of work permit and list of involved personal at site.
• He shall ensure placement of all signals, signs and barricades until work completion.
• He will produce the Job Risk Assessment prior to work commencement and will identify the hazards (if any)
before start of all construction activities.
4. Interface Requirements
Coordinate activities with other construction teams following ISO 31000 for Risk Management, ensuring
seamless integration and minimizing potential conflicts.
ASTRA Construction Manager/Project Manager to coordinate with AMAALA delivery tea regarding any site
interfaces with other CONTRACTORS. The CM/PM is responsible to share with AMAALA Engineer the work looks
ahead plan and coordinates with other work disciplines to avoid any site issues and work delays.
5. List of Sub-Contractors
VEOLIA
6. Permit and Licensing Requirements
• ASTRA Construction Manager and Health & Safety Manager will coordinate all the site work in advance, and
they will be responsible for securing all the required work permits for different site activities.
• Toolbox Talk (TBT) to be given to all site team twice a week and will explain the hazards
related to the work activity and permits with other required documents to be filled accordingly.
The required work permits are:
• AMA-HS-FRM-0024: Permit to Work Activity.
Construction Manager
Site Engineer
HSE Engineer
Civil supervisor
Tankers drivers
Labor
Ensure availability of resources including water, sodium hypochlorite solution, neutralizing agents,
sampling bottles, and testing equipment.
Page | 3
Utilize appropriate equipment and tools such as flushing hoses, dosing pumps, sampling pumps, and
safety gear.
Provide training to personnel on proper handling of chemicals, operation of equipment, and adherence
to safety protocols.
Environmental Requirements
Materials/substances to be used which are nonhazardous to health.
Proposed storage location of hazardous materials.
Proposed maximum volume of hazardous materials being stored onsite. The key risk(s) to
health associated with the materials/substances.
The key control measures and precautions to be implemented to control the risks to health and
safety. This is to include control measures relating to emergency spill/release.
Location onsite of COSHH assessment for each material/substance identified on hazardous materials
and substances register. Safety Data Sheets form part of the risk assessment and shall be provided.
Hazardous Materials and Substances Register is provided to assist you in complying with this
section, although you may use your own process/format in addressing this section.
Clearly identify your arrangements for controlling your waste products at the workplace.
Keeping the workplace clean and tidy.
Minimizing the volume of the waste created by your work activities.
Segregating ‘hazardous wastes (i.e. special waste) from ‘non-hazardous wastes’ for final disposal from
site
The project will implement a specific waste management system for the collection of waste materials
from the workplace to be taken to final disposal from the site clearly indicate any quality assurance or
control requirements.
Quality Requirements
In-depth on-site inspections, timely stopping of illegal operations, strengthening process
control, process rectification, and reducing rework afterward. And ensure the following
process is in control.
The QA/QC Department shall ensure that all piping installation and welding Works are
conducted in accordance with the approved Inspection Test Plan, Project specifications,
drawings, and prevailing engineering standards implemented at the site.
Upon completion of construction, an electrical engineer in coordination with QC shall submit
RFI to the owner to perform all required inspections to assure that all requirements are met
and approved.
The QC Engineer/Inspector shall carry out Planned Inspections, Surveillance Inspections and
release hold points by signing various Quality Records as proof of Inspection conforming to
Specifications.
Any comments found during the inspection will be recorded.
ASTRA QAQC Dept.
Will monitor all activities throughout the execution of work. If any special QAQC consideration
require will be followed as per Pain ISO 9001:2015.
Material Inspection Request Shall be raised by Quality Engineer upon the receiving of
Materials at ASTRA store/ Ware house prior to installation the following documents shall
be attached with MIR.
Delivery Note
Approved Material Submittal
Factory Test Certificates
All received materials shall be as per approved Project Quality Plan refer. (1TB02017-017C62-ACN-PLN-QM-
0001) store at ware house properly.
Page | 4
First Aid & Medical Requirements the Following Emergency numbers will be displayed on site:
In case of any incident we will comply and follow AMALA requirements. ASTRA will follow the following steps
in case of emergency.
Stay Calm: It is important to remain calm and composed during an emergency situation. Panicking can hinder
your ability to make rational decisions and potentially put yourself and others at further risk.
Assess the Situation: Quickly assess the nature and severity of the incident. Determine if there are any
immediate dangers, such as falling hazards, traffic risks, or exposure to hazardous materials. This initial
assessment will help you prioritize and take appropriate actions.
Alert Others: If necessary, immediately notify any nearby workers, supervisors, or emergency response
personnel about the incident. Use available communication devices to relay the information accurately and
clearly.
Provide First Aid: If there are any injuries, provide first aid to the best of your ability while waiting for
professional medical assistance to arrive. This may include assessing the injured person's condition,
controlling bleeding, or performing CPR if necessary and trained to do so.
Establish a Safe Zone: Create a safe zone around the incident area by setting up barriers, cones, or caution
signs to prevent access by unauthorized personnel or vehicles. This will help minimize the risk of further
accidents or injuries.
Follow Emergency Protocols: Follow the established emergency protocols specific to your company or
worksite. This may involve contacting emergency services, such as the local fire department, police, or
medical services, and providing them with all relevant information about the incident.
Document the Incident: It is essential to document the incident thoroughly. Take photographs or videos of
the scene, gather witness statements, and record any relevant details about the incident. This
documentation will be important for future investigations or insurance claims.
Conduct Incident Review: After the immediate situation is resolved and everyone is safe, review the
incident to identify the root cause and determine if any changes or improvements are needed to prevent
such incidents in the future. Learn from the experience and update safety procedures accordingly.
Page | 5
1. ASTRA Supervisor/Foreman shall Monitor the activity and ensure the Valid Permit
available at site prior to execute the activity.
2. ASTRA Safety Verify the Validation of Permit and all the tools and inspected and can be
use at site for the work.
3. ASTRA Supervisor and Safety officer shall ensure that all the person attained the safety
training/Induction and are available with proper PPE.
4. Safety Officer shall conduct the Toolbox meeting for awareness for Hazard/Risk during the
activity.
5. Environmental department ensure that there is no any impact at environment during the
execute the activity.
6. Quality Engineer will monitor that the work has been carryout as per Client Specification.
The term “heat stress” includes several different conditions that occur when the body is stressed because of
overheating.
• ASTRA shall implement the AMAALA Heat Stress Management, Document Ref. AMA-HSOCH-0003
AMAALA WBGT.
Page | 6
14. Risk Assessment
Risk Identification:
1. Chemical Exposure:
Risk: Exposure of workers to chemicals used for disinfection can cause skin irritation,
respiratory issues, or chemical burns.
2. Slip and Trip Hazards:
Risk: Wet surfaces during flushing and disinfection can increase the risk of slips, trips, and falls
for workers.
3. Equipment Malfunction:
Risk: Malfunction or failure of equipment such as dosing pumps or flushing hoses can disrupt
the flushing and disinfection process.
4. Heat Stress:
Risk: Working in hot and humid conditions during summer months can lead to heat-related
illnesses among workers.
5. Environmental Contamination:
Risk: Improper disposal of chemicals or contaminated water can lead to environmental
pollution and regulatory non-compliance.
Page | 7
Risk Evaluation:
1. Chemical Exposure:
Severity: Moderate
Likelihood: High
Risk Rating: High
2. Slip and Trip Hazards:
Severity: Low to Moderate
Likelihood: Moderate
Risk Rating: Moderate
3. Equipment Malfunction:
Severity: Moderate
Likelihood: Moderate
Risk Rating: Moderate
4. Heat Stress:
Severity: Low to Moderate
Likelihood: Moderate
Risk Rating: Moderate
5. Environmental Contamination:
Severity: High
Likelihood: Moderate
Risk Rating: High
Control Measures:
1. Chemical Exposure:
Provide appropriate PPE including gloves, goggles, and respiratory protection.
Conduct training on safe handling and storage of chemicals.
Ensure adequate ventilation in work areas.
2. Slip and Trip Hazards:
Implement signage to warn of wet floors.
Provide non-slip footwear.
Keep work areas clean and free of clutter.
3. Equipment Malfunction:
Conduct regular maintenance and inspections of equipment.
Have backup equipment available on site.
Train personnel on proper use and troubleshooting of equipment.
4. Heat Stress:
Schedule work during cooler times of the day where possible.
Provide shaded rest areas and encourage frequent breaks.
Provide access to cool drinking water.
5. Environmental Contamination:
Use environmentally safe chemicals and follow proper disposal procedures.
Implement spill containment measures.
Monitor disposal activities to ensure compliance with regulations.
Page | 8
1. Chemical Exposure:
Monitor workers for signs of chemical exposure and provide medical attention if necessary.
Conduct regular audits to ensure compliance with PPE and chemical handling procedures.
2. Slip and Trip Hazards:
Monitor work areas for potential hazards and address them promptly.
Encourage workers to report any unsafe conditions or near-misses.
3. Equipment Malfunction:
Maintain a log of equipment maintenance and repairs.
Conduct pre-use checks of equipment before each use.
Implement a reporting system for equipment issues and malfunctions.
4. Heat Stress:
Monitor weather conditions and adjust work schedules accordingly.
Train workers on recognizing symptoms of heat stress and how to respond.
Implement a buddy system for heat stress monitoring and support.
5. Environmental Contamination:
Conduct regular inspections of chemical storage and disposal areas.
Monitor water quality during and after flushing and disinfection activities.
Review and update disposal procedures based on regulatory requirements.
Documentation:
Page | 9
Reports documenting environmental monitoring activities conducted during and after flushing
and disinfection.
Includes results of water quality testing, observations of disposal activities, and any corrective
actions taken.
8. Bacteriological Testing Reports:
Reports documenting results of bacteriological testing conducted on water samples collected
from different points.
Includes details of sampling procedures, testing methods, and compliance with regulatory
standards.
9. Certificate of Disinfection:
Formal certificate issued upon completion of flushing and disinfection activities, indicating
satisfactory results of laboratory and bacterial tests.
Includes certification of compliance with international standards and specifications.
10. Incident and Near-Miss Reports:
Records of any incidents, accidents, or near-misses that occurred during the flushing and
disinfection process.
Includes details of the event, corrective actions taken, and recommendations for preventing
future occurrences.
11. Project Closeout Documentation:
Final documentation package submitted at the completion of the project, including all relevant
reports, records, and certificates.
Includes signed completion certificates, as-built drawings, and any other required deliverables
for project handover.
Page | 10
QVGOLIA
Statement of Compliance
Package
I, as the Authorized representative from the Supplier/ Manufacturer, acknowledge and certify the material
submission covered under this document Domestic Water Treatment Disinfection
☐
/ Compliance with Contract Drawings
☐
/ Compliance with Authority Requirements
Signature :
Stamp:
The intent of the program is to ensure compliance with the methods and procedures outlined in ASME/AWWA
Standard C651-14 and meet the bacteriological standards.
System Details:
2. INTRODUCTION
The disinfection process will be carried out in accordance with the latest standards as following:
American Water Works Association. 2014 ANSI/AWWA C651-14 - AWWA Standard for Disinfection
of Water Mains. Approved by American National Standards Institute.
American Water Works Association. 2005 ANSI/AWWA C652-05- AWWA Standard for Disinfection
of Water –Storage Facilities.
The construction, rehabilitation, and repair of water tanks & mains are extremely common activities
that occur on a regular basis in all water systems. The relative frequency and nature of these activities
represent a potential contamination risk to water distribution systems if proper procedures and
existing standards are not followed. Installation and repair of water mains provides the potential for
direct contamination of the distribution system.
PURPOSE :
This procedure is developed to assure the external and internal drinking water distribution network a are
properly disinfected and meet the American Water Works Association Standard forcommunity water
systems.
WATER TECHNOLOGIES
©
METHOD STATEMENT ( INTERNAL BUILDING PIPING NETWORK)
Before being chlorinated, potable water, drinking water Tanks ( If Available) & distribution piping
networks need to be flushed with fresh water to remove sedimentand other foreign matter.
The potable water, drinking water tanks (If Available)& distribution piping networks should be
completely filled withwater to eliminate air pockets and then flushed to purge the line of dirt and
debris. This is typically conducted after the completion of the leakage and pressure tests. Adequate
drainage must be provided during flushing.
Ineffective removal of dirt and debris from lines prior to disinfection often leads to failed bacterial tests,
requiring repeated disinfection.
The disinfection of the potable water, drinking water distribution piping networks on a stabilized
pH< 8.5 will be carried out with sodium Hypochlorite solution as defined in thedisinfection procedure
as per AWWA Standards (ASME / A.W.W.A. C651/C652) of Potable Water, Drinking Water Tanks
and allassociated distribution piping networks to maintain 50 ppm.
The injection to all associated distribution piping networks till chlorinated solution is observed and
tested to the all points. ( Chemicals will be charged directly the temporary storage tanks)
After confirmation of the chlorine residual as required for 24 hours exposure, neutralizing agent will be
dosed to neutralize the chlorinated water.( Environmentally Safe Dispose)
Once the chlorinated water is properly neutralized and discharged, the entire new main shall be flushed
with fresh water until it is clean and clear.
Continuously flush the entire system with clear potable water until the replacement water throughout
the new pipeline can be proved, by laboratory testing, comparable in quality to the incoming water.
WATER TECHNOLOGIES
BACTERIOLOGICAL TESTING
©
According to AWWA C651, after final flushing and before the new water main is connected to all associated
distribution piping networks, 3-5 water samples for each level floor will be taken from different points for
bacteriological tests.
All samples shall be tested for bacteriological in accordance with Standard Methods for the Examination of
Water and Wastewater.
Sampling Procedure — samples for bacteriological analysis will be collected in sterile bottles treated with
sodium thiosulfate, as required by Standard Methods of the Examination of Water and Wastewater. No hose or
fire hydrant shall be used in the collection of samples.
Control Values:
WATER TECHNOLOGIES
STAGE IV: CERTIFICATE OF DESINFECTION
©
At the moment of job completion VWS will submit a Certification of Disinfection along with laboratory and
bacterial tests shows Satisfaction results.
Day Description
Day 1 Flush the entire system (Potable water, Drinking Water Tanks &
distribution piping networks) need to be flushed with freshwater
toremove sediment and other foreign matter until clean and clear
( Should be done by the contractor).
Day 2 Inject chlorine solution to the water existing / external storage tanks and
start dumping all water to all associated distribution piping networks.
Paste stickers / notice at the end points and other important locations to
avoid the consumption of water during duration of disinfection job.
Day 3 Check chlorine residual after chlorine solution has remained in all
associated distribution piping networks and users point.
Neutralize residual
Flush chlorine solutions form all associated distribution piping networks
and user points until replacement water has a chlorine content not more
than 1.0 ppm.
WATER TECHNOLOGIES
MATRIX OF RESPONSIBILITY
d. Notwithstanding satisfactory completion of the water absorption test, any leakage visible on the
outside faces of the structure shall be stopped. Any caulking or making good of cracks in the
wall section shall, where practicable, be carried out from the inside face, and to the satisfaction
of the Employer’s Representative and Assistants.
e. Upon completion of the test, the Contractor shall empty the structure, dispose of the contents
and shall clean the structure and any equipment therein of all deposits left by the water.
6. Flushing and Disinfection of Water Mains
a. Procedure: To AWWA C651-92.
b. The Contractor shall provide equipment, gauges, temporary connections and chlorine needed
for flushing and disinfection and arrange with the Employer to draw water from existing sources.
c. Sections: The Contractor shall flush and disinfect mains in sections as directed by the Em-
ployer’s Representative and Assistants.
d. Draining: The Contractor shall use washout valves and fire hydrants to drain flushing and disin-
fecting water.
e. First Flushing: Before commencing disinfection, the Contractor shall flush mains until effluent is
clean and then clean as directed. 1 to 2 times volume of pipe is usually required for such flush-
ing.
f. Type of Chlorine: The Contractor shall disinfect with chlorine gas or solutions of calcium hypo-
chlorite or sodium hypochlorite and agree with the Employer’s Representative and Assistants
on method of application.
g. Initial dosing shall be 40-50 ppm.
h. Contact period shall be 24 hours.
i. Residual Chlorine: The Contractor shall measure residual chlorine by Orthotolidin test. Residual
chlorine shall not to be less than 5 ppm or the test shall be repeated as directed.
j. Final Flushing: After disinfection, the Contractor shall reflush the network until chlorine concen-
tration in water leaving main is less than 1 ppm.
k. Tests: The Contractor shall perform bacteriological tests to AWWA C651-92, Section 9. Number
of samples shall be one per 1 km of main feeders and one per 0.25 km of distribution lines.
l. Procedure after Cutting into Existing Main: To AWWA C651, Section 11.
7. Field Protection and Coating
a. Iron Pipes: Polyethylene sleeves shall be to ANSI/AWWA C105, Section 4.1 or ISO 8180 or in
accordance with the manufacturer's instructions. Sleeves shall be heavy duty blue colour poly-
ethylene with a minimum thickness of 225 microns.
b. Patented Detachable and Flexible Joints and Flanged Connections: The Contractor shall protect
metal joints with mastic compound and protective tape in accordance with the manufacturer's
instructions. Minimum overlap shall be 55% and the Contractor shall press out firmly all folds
and irregularities.
8. Anti-Corrosion Tape
a. The tape shall consist of a PVC backing bonded to a self-adhesive bituminous rubber compound
with a total thickness of approximately 1.65 mm.
b. The plastic backing shall be extruded PVC and shall have an approximate thickness 0.35 mm.
c. When the tape is to be applied with a 50-55 % overlap the tape shall have a “guide- line” printed
down the centre of the tape to ensure accurate overlapping is achieved.
Page: 96 of 144
STANDARD SPECIFICATIONS DIVISION 33 0000 - UTILITIES
WSP SECTION 33 1411 – WATER UTILITY TRANSMISSION PIPING
d. Notwithstanding satisfactory completion of the water absorption test, any leakage visible on the
outside faces of the structure shall be stopped. Any caulking or making good of cracks in the
wall section shall, where practicable, be carried out from the inside face, and to the satisfaction
of the Employer’s Representative and Assistants.
e. Upon completion of the test, the Contractor shall empty the structure, dispose of the contents
and shall clean the structure and any equipment therein of all deposits left by the water.
6. Flushing and Disinfection of Water Mains
a. Procedure: To AWWA C651-92.
b. The Contractor shall provide equipment, gauges, temporary connections and chlorine needed
for flushing and disinfection and arrange with the Employer to draw water from existing sources.
c. Sections: The Contractor shall flush and disinfect mains in sections as directed by the Em-
ployer’s Representative and Assistants.
d. Draining: The Contractor shall use washout valves and fire hydrants to drain flushing and disin-
fecting water.
e. First Flushing: Before commencing disinfection, the Contractor shall flush mains until effluent is
clean and then clean as directed. 1 to 2 times volume of pipe is usually required for such flush-
ing.
f. Type of Chlorine: The Contractor shall disinfect with chlorine gas or solutions of calcium hypo-
chlorite or sodium hypochlorite and agree with the Employer’s Representative and Assistants
on method of application.
g. Initial dosing shall be 40-50 ppm.
h. Contact period shall be 24 hours.
i. Residual Chlorine: The Contractor shall measure residual chlorine by Orthotolidin test. Residual
chlorine shall not to be less than 5 ppm or the test shall be repeated as directed.
j. Final Flushing: After disinfection, the Contractor shall reflush the network until chlorine concen-
tration in water leaving main is less than 1 ppm.
k. Tests: The Contractor shall perform bacteriological tests to AWWA C651-92, Section 9. Number
of samples shall be one per 1 km of main feeders and one per 0.25 km of distribution lines.
l. Procedure after Cutting into Existing Main: To AWWA C651, Section 11.
7. Field Protection and Coating
a. Iron Pipes: Polyethylene sleeves shall be to ANSI/AWWA C105, Section 4.1 or ISO 8180 or in
accordance with the manufacturer's instructions. Sleeves shall be heavy duty blue colour poly-
ethylene with a minimum thickness of 225 microns.
b. Patented Detachable and Flexible Joints and Flanged Connections: The Contractor shall protect
metal joints with mastic compound and protective tape in accordance with the manufacturer's
instructions. Minimum overlap shall be 55% and the Contractor shall press out firmly all folds
and irregularities.
8. Anti-Corrosion Tape
a. The tape shall consist of a PVC backing bonded to a self-adhesive bituminous rubber compound
with a total thickness of approximately 1.65 mm.
b. The plastic backing shall be extruded PVC and shall have an approximate thickness 0.35 mm.
c. When the tape is to be applied with a 50-55 % overlap the tape shall have a “guide- line” printed
down the centre of the tape to ensure accurate overlapping is achieved.
Page: 96 of 144
QVEOUA
● Project Title :Amaala Six Senses Project
● Project : The Red Sea
● Location : KINGDOM OF SAUDI ARABIA
● Description Flushing and Disinfection of Water Mains
VEOLIA WATER
CONSULTANT SPECIFICATION CLARIFICATION/CONFIRMATION
D Draining: The Contractor shall use washout valves and fire hydrants to drain
flushing and disin- fecting water. Comply
E First Flushing: Before commencing disinfection, the Contractor shall flush mains
until effluent is clean and then clean as directed. 1 to 2 times volume of pipe is Comply
usually required for such flush- ing.
F Type of Chlorine: The Contractor shall disinfect with chlorine gas or solutions of
calcium hypo- chlorite or sodium hypochlorite and agree with the Employer’s Comply, Sodium Hypo will be used
Representative and Assistants on method of application.
1
QVEOUA
VEOLIA WATER CLARIFICATION/CONFIRMATION
CONSULTANT SPECIFICATION
G Comply
Initial dosing shall be 40-50 ppm.
H Contact period shall be 24 hours.
Comply
I Residual Chlorine: The Contractor shall measure residual chlorine by Orthotolidin
test. Residual chlorine shall not to be less than 5 ppm or the test shall be repeated Comply
as directed.
J Final Flushing: After disinfection, the Contractor shall reflush the network until
chlorine concen- tration in water leaving main is less than 1 ppm.
Comply
K
Tests: The Contractor shall perform bacteriological tests to AWWA C651-92,
Section 9. Number of samples shall be one per 1 km of main feeders and one per Comply
0.25 km of distribution lines.
2
HYDREX 4301
Product information
Reducer Agent
Advantages
• Food grade quality , free of any impurities.
• Cost - effective concentrate
• Easy to use liquid formulation.
Application Information 08
/
12
When RO or NF membrane is used in the RO/NF process, the feed must be dechlorinated to prevent oxidation
of the membrane. Dosage rate will be dependent upon the level of free chlorine present in the water system.
-
The suitable dose is 10 ppm of Flydrex 4301 for each ppm of active chlorine. O
-
I
§
Although the dechlorination itself is rapid, good mixing is required to ensure completion. Static mixers are
1
recommended. The recommended injection point is downstream of the cartridge filters in order to protect the £
filters by chlorine. In this case, Flydrex 4301 solution should be filtered through a separate cartridge before
being injected to the RO feed.
The absence of chlorine should be monitored using and oxidation - reduction potential (ORP) electrode
I
downstream of the mixing line.
Please consult your VWS representative for detailed instructions regarding the application of the product.
f
£
Reducer Agent
Specifications
Appearance : Colourless to yellowish liquid
Specific Gravity @ 25°C : 1.31
pH ( as supplied) : 3.0 - 4.0
Flash Point : ND
Solubility in Water : Completely miscible
Materials Compatibility
Compatible store materials are: stainless steel, polyethylene, polypropylene, PVC, glass and rubber.
08
/
12
Packaging -
O
Hydrex 4301 is supplied in 25 kg polyethylene drums. -
Shelf life of Hydrex 4301 is 6 months form production date under normal handling and storage conditions.
I
§
1
£
Safety Information
This product is corrosive to body tissue and must be handled with great care. Eye contact should be avoided I
and persons with sensitive skin who are repeatedly handling the concentrated product should wear gloves. I
o
Ensure that the operator is fully informed and familiar with the use of the product. D>
3
Keep in a cool dry place. Avoid contact with oxidising agents. 5
o
Please refer to the Material Safety Data Sheet for more detailed information.
QVEOUA
WATER
Veolia Water Solutions & Technologies
Headquarters
"L'aquarene" 1, Place Montgolfier - 94417
Saint-Maurice Cedex - France
Solutions «• Technologies Tel. +33 1 45 11 55 55
Website : www.veoliawaterst.com
Product Name: Hydrex 4301
QVEOLIA WATER
MSDS Code: HYS4301
3 - HAZARDS IDENTIFICATION
As a general rule, in case of doubt or if symptoms persist , always call a doctor . NEVER induce swallowing in an unconscious
person.
If in eyes Flush eyes with water.
If on skin Promptly wash with mild soap and water.
Move subject to fresh air . Give artificial respiration if breathing has stopped.
If inhaled
If swallowed: If conscious , give large quantities of water . IMMEDIATELY get medical attention. Never give anything by
mouth to an unconscious person .
Revision No.: 04
Revision Date: 01 -01- 2016 Page 1 of 4
Product Name: Hydrex 4301
QVEOLIA WATER
MSDS Code: HYS4301
Spill Clean up Methods: Contain large spills with dikes and transfer the material to appropriate containers for
reclamation or disposal. Absorb remaining material or small spills with an inert material and
then place in a chemical waste container . Flush spill area with water .
Handling:
Observe precautions stated on label and also industrial safety regulations . Avoid contact of product with the skin and eyes .
Smoking, eating and drinking are prohibited in premises where the preparation is used.
Emptied containers retain vapour and product residue . Observe all recommended safety precautions until container is cleaned ,
reconditioned or destroyed. The reuse of this material' s container for non industrial purposes is prohibited and any reuse must
be in consideration of the data provided in this material safety data sheet .
Storage:
Keep the container tightly closed in a dry place .
O0
Protective Equipment:
Eye Protection: Wear safety goggles . Provide eye washes in workshops where the product is constantly handled.
Hand protection: Protective gloves must be worn.
Body Protection: Wear apron.
Respiratory Protection: Avoid breathing vapour or mist .
Use approved respiratory protection equipment when airborne exposure is excessive. Consult the
respirator manufacturer to determine the appropriate type of equipment for a given application.
The respirator use limitations specified by the manufacturer must be observed .
Ventilation: Provide natural or mechanical ventilation to minimize exposure.
If practical, use local mechanical exhaust ventilation at sources of air contamination such as
processing equipment .
Appearance Clear
State Liquid
Color Colourless to yellowish
Odor Characteristic Characteristic
pH of concentrate 3.0 - 4.0
Specific Gravity @ 25°C 1.3 - 1.4
Viscosity, cps Not Applicable
Melting Point , ( Deg. Celsius) Not Specified
Boiling Point , ( Deg. Celsius) Not Specified
Percentage Volatility, (%) Not Applicable
Solubility in Water Complete
11 - TOXICOLOGICAL INFORMATION
Revision No.: 04
Revision Date: 01 -01- 2016 Page 2 of 4
Product Name: Hydrex 4301
QVEOLIA WATER
MSDS Code: HYS4301
12 - ECOLOGICAL INFORMATION
13 - DISPOSAL CONSIDERATIONS
Waste Management:
Do not pour into drains or waterways .
Disposal Methods:
Local, state , provincial, and national disposal regulations may be more or less stringent. Consult your attorney or appropriate
regulatory officials for information on such disposal. This product should not be dumped , spilled, rinsed or washed into sewers
or public waterways.
14 - TRANSPORT INFORMATION
15 - REGULATORY INFORMATION
This preparation was classified in compliance with the directive known as < AII preparations > 1999/45/EC and its adaptations
In addition directive 2004/73/EC with the 29 “ adaptation of directive 67/548/EEC ( Hazardous substances) have been taken into
account .
X
16 - OTHER INFORMATION
HEALTH 1
FLAMMABILITY 0
PHYSICAL HAZARD 0
Health
PERSONAL PROTECTION B
Specific
Revision No.: 04
Revision Date: 01-01-2016 Page 3 of 4
Product Name: Hydrex 4301
QVEOLIA WATER
MSDS Code: HYS 4301
Since the user's working conditions are not known by us, the information supplied on this safety data sheet is based on our current level of
knowledge and on national and community regulations.
The product must not be used for any purposes other than those specified under heading 1 without first obtaining written handling
instructions.
It is at all times the responsibility of the user to take all necessary measures to comply with legal requirements and local regulations.
The information given on this safety data sheet must be regarded as a description of the safety requirements relating to our product and not
a guarantee of its properties
Revision No.: 04
Revision Date: 01 -01- 2016 Page 4 of 4
Product Name: Sodium Hypochlorite
QveouA WATER
MSDS Code:S - NaOCI
Eye contact : May cause severe irritation such as bums, and eye damage.
Skin contact : May cause moderate skin irritation and reddening of the skin. Prolonged exposure may cause
bums, blistering.
Inhalation: May cause burns, cough, pulmonary edema , up to 48 hours after exposure.
Ingestion: May cause irritation of the membranes of the mouth and throat, stomach pain, and possible
ulceration.
.
As a genera rule, in case of doubt or if symptoms persist, always call a doctor NEVER induce swallowing in an unconscious
'
person.
If in eyes Rush with plenty of water for 15 minutes, lifting the lower and upper lids occasionally. GET MEDICAL
ATTENTION IMMEDIATELY. Contact lenses should not be worn when working with this chemical .
If on skin : Immediately flush contaminated areas with plenty of water. Remove contaminated clothing, jewelry, and
.
shoes immediately. Wash contaminated areas with soap and water Thoroughly clean and dry contaminated
clothing and shoes before reuse. GET MEDICAL ATTENTION IMMEDIATELY.
If inhaled: .
II adverse effects occur, remove to fresh air. Give artificial respiration if not breathing If breathing is difficult,
oxygen should be administered by qualified personnel. If respiration or pulse has stopped, have a trained
person administer Basic Life Support (Cardio-Pulmonary Resuscitation) and GET MEDICAL ATTENTION
IMMEDIATELY .
If swallowed Do not give any liquid to an unconscious person. Drink large quantities o( gelatin solution or milk. If these
.
are not available, drink large quantities of water Do NOT give vinegar, baking soda or acidic antidotes. GET
MEDICAL ATTENTION IMMEDIATELY.
Revision No 02
Revision Date 04 05-2009 Page 1 of 4
Product Name: Sod um Hypochlo te
QVEOLIA WATER
MSOS Code:S- NaOCI *
tightly lor proper disposal. This material is altaline and may raise the pH of surface waters
with low buffering capacity.
Handling
Observe precautions stated on label and also industrial safety regulations Avoid conlacl of product with the skin and eyes.
Smoking, ealing and drhiking are prohibited in premises where the preparation is used.
Emptied containers retain vapour and produd residue. Observe all recommended safety precautions until container Is deaned .
reconditioned or destroyed The reuse of this material's container lor non industrial purposes is prohibited and any reuse must
be in consideration ol the data provided in this material safety data sheet.
Storage
Store in a cool, dry, well-ventilated place.
Keep in original container .
Keep container dosed when not in use .
Keep away from heal, sparks, flames, direct sunlight, and other sources of heal including lighted tobacco produds.
Use only a clean, dry scoop made of metal or plastic each time product is taken from the container.
Protective Equipment;
Eye Protection:
Hand protection:
o © @
Wear safely goggles. Provide eye washes in workshops where the product is constantly handled.
Protective gloves must be worn.
8ody Protection: Wear apron while handling dosing this product.
Respiratory Protection: Not required under normal use conditions. In the case of a lire use self -coniained breathing
apparatus. A NIOSH approved respirator with N95 (dust, fume, mist) Alters may be permissible
under certain circumstances where airborne concentralions are expected to exceed exposure
limits, or when symptoms have been observed that are indicative of overexposure.
When decomposition products exist, add gas cartridges are also required. A half -piece air-purifying
respirator may be used in concentrations up to 10X the acceptable exposure level and a full
facepiece air-purifying respiralor may be used in concentralions up to 50X the acceptable exposure
level.
Supplied air should be used when the level is expected to above 50X the acceptable level, or when
there is a potential lor uncontrolled release. A respiratory program that meets 29 CFR 1910.134
must be followed whenever workplace conditions warrant use ol a respiralor.
Ventilation: .
No special ventilation is required unless bleach is exposed to decomposition conditions, i e. heat or
acidic conditions.
Revsion No 02
Rev -slon Date: 04-05- 2009 Page 2 of 4
Product Name: Sodium Hypochlorite
QVGOLIA WATER
MSDS Code:S- NaOCI
Appearance Clear
Stale Liquid
Color Greenish -yellowish
Odor Characteristic Pungent chlorine like odor
pH of concentrate -
11.4 12.4
Specific Gravity at 20 Deg.C . -
1.14 1.24
Viscosity, cps NA
.
Melting Point, (Deg Celsius) NA
.
Bolling Point (Deg. Celsius) NA
Percentage Volatility, (%) NA
Solubility in Water Complete
Stability: .
Rapidly decomposes on exposure to air May decompose violently if exposed to heat
. .
or direct sunlight Thermally unstable
Conditions to avoid: .
Heat, flame, moisture, dusting, sources of Ignition and shock, and incompatibles
Material to avoid: This product is a strong oxidzer. Reacts with water and adds giving off chlorine gas
Forms explosive compounds with ammonia and amines, incompatible with organic
materials, nitrogen compounds and combustible materials.
Hazardous decomposition products: Gives off oxygen, chlorine and chlorine monoxide.
No LD50/LC50 Information found relating to normal routes of occupational exposure. Investigated as a tumorigen and mutagen.
Irritation data: eye, rabbit, 10 mg - Moderate
12 - ECOLOGICAL INFORMATION
13 - DISPOSAL CONSIDERATIONS
Disposal Methods:
Dilute with water and flush to sewer If local ordinances alow, otherwise, whatever cannot be saved for recovery or recycling
.
should be managed in an appropriate and approved wasle disposal facility Processing, use or contamination of this product
may change the wasle management options. State and local disposal regulations may efiffer from federal disposal regulations .
Dispose ol container and unused conlenls in accordance wilh federal, stale and local requirements.
Can be neutralized wilh weak reducing agenls such as sodium sulfite, bisulfite, or thiosulfrte (DO NOT USE SULFATES OR
BISULFATES)
14 - TRANSPORT INFORMATION
UN Number : 1791
Proper Shipping Name: Hypochlorite solution
IMOG Class : 8
Packing Group:
15 - REGULATORY INFORMATION
This preparaiion was classified in compliance with the directive known as <Ail preparations;* 1999/45/EC and ils adaptations
In addition directive 2004/73/EC with the 29" adaplation ol directive 67 /548/EEC (Hazardous subslances) have been laken into
account.
Revision No : 02
Revision Oats 04 - 05-2009 Page 3 of 4
Product Name: Sodium Hypochlorite
QVGOLIA WATER
M$DS CoOe S - KlaOCI
6
-
IB OTHER INFORMATION
FLAMMABILITY
9 t
PHYSICAL HAZARD 1
PERSONAL PROTECTION G
Health 1 Instability
OX
Specific
Since the user 's working conditions are not known by us, the information supplied on this safety data sheet ts based on our current level of
knowledge end on national and community regulations .
The product must not be used for any purposes other than those specified under heading 1 without first obtaining written handling
Instructons
It is at all times the responsibility of the user to lake all necessary measures to comply with legal raqulrementa and local regulations
The nformaton given on this safety data sheet must be regarded as a description of the safety requirements relating to our product and not
a guarantee of Is properties
Revison No 02
Rovsion Date 04-05-2009 Page 4 of 4