I56-1521-005

Model TC809A1059 Monitor Module


Installation Instructions
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.0mA (LED on)
Average Operating Current: 400µA, 1 communication every 5 seconds, 47k EOL resistor
EOL Resistance: 47K Ohms
Maximum IDC wiring resistance: 40 Ohms
Maximum IDC Voltage: 11.6 Volts
Maximum IDC Current: 240µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H x 4˝ W x 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box

BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system
will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The TC809A1059 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is
selected using the built-in rotary decade switches. It provides either a 2-wire or 4-wire fault tolerant initiating circuit for normally open
contact fire alarm, supervisory, or security devices. The module has a panel controlled LED indicator. TC809A1059 is also UL listed as
a commercial proprietary burglar alarm accessory.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed compatible system control panels only.
MOUNTING
The TC809A1059 mounts directly to 4″ square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8″. Surface
mounted electrical boxes (SMB500) are available.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances,
and regulations. This module is intended for power limited wiring
Figure 2A. Module mounting:
only.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as
shown in Figure 2A.

Figure 1. Controls and indicators: Figure 2B:

9
8 9
8
6
7
7
0 5
4 3 0 6
1 2 1S
N 8
TE 67
9
5
2
S

5
9
S

3 4 3
E

2 10
R
D
D

8
A

4
S
E
N

4 5 6 78
7
O

3
LO 6 TEN 2
S 1
9
0
OP 5 4 5 6 78
0
1
9 0
3
ON 2
ES 1
9 2
3
6789
0
4
5
AD
DR
ES
S
4
8 3 1
2
7 10
TENS
2
6789
6 5
4 3
3
5 2
10
4 C0157-00
ONES
LOOP ADDRESS

C0155-00

C0156-00

H500-13-00 1 I56-1521-005
Honeywell, 1985 Douglas Drive North, Golden Valley, MN 55422
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
)–( )–(
TO NEXT FROM PANEL OR
)+( )+( PREVIOUS DEVICE
DEVICE

MONITOR
ANY NUMBER OF UL LISTED CONTACT CLOSURE MODULE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING OR SUPERVISORY CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
DEVICES ON THE SAME MODULE.

9 0
5
6789 )–(
4
8 3 1
7
2
10 2 )+(
TENS
47 K EOL 6 4
5
6789
3
RESISTOR 5
3
2 4
SIGNAL LINE CIRCUIT (SLC)
10
14501600-027 LOOP
ONES
ADDRESS 32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED

INSTALL CONTACT CLOSURE DEVICES PER


MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
C0446-01

Figure 4. Typical 4-wire fault tolerant initiating circuit configuration, NFPA Style D:
)–( )-(
TO NEXT FROM PANEL OR
DEVICE )+( )+(
PREVIOUS DEVICE

ANY NUMBER OF UL LISTED CONTACT CLOSURE


MONITOR
DEVICES MAY BE USED. DO NOT MIX FIRE
MODULE
ALARM INITIATING OR SUPERVISORY
DEVICES ON THE SAME MODULE. CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
9 0
5
6789 )–(
4
8 3 1
7
2
10 2 )+(
TENS
6789
6 5
4 3
3
5 2 4
EOL RESISTOR ONES
10
ADDRESS SIGNAL LINE CIRCUIT (SLC)
LOOP
IS INTERNAL AT
32 VDC MAX
TERMINALS 8 & 9.
TWISTED PAIR
IS RECOMMENDED

INSTALL CONTACT CLOSURE DEVICES PER ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED C0447-01
MANUFACTURER'S INSTALLATION INSTRUCTIONS.