BACnet Gateway Owner's Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

MD13U-023FW

,
OWNER S MANUAL
CCM08
NW-BCN-CM

Thank you very much for purchasing our air conditioner, please read
this owner's manual carefully before using your air conditioner.
202055101030
CA TA LOGUE

1 Connecting diagram … … … … … … … … … … … … … … … 1
2 Function description …………………………………………2
3 Configuration illustration … … … … … … … … … … … … …3

4 Object table … … … … … … … … … … … … … … … … … … 5
1 Connecting diagram
1-1 Central ControllerO8 interfaces illus tration

Ethernet interface, connect with


BACnet/IP network
Four groups of 485 interfaces, each one connect
with a universal Midea centralized monitor controller
or Indoor/Outdoor air-conditioner.
1-2 System connecting il lustration

1) BACnet of CCM08(NW-BCN-CM) can connect with the indoor centralized controller CCM03/30
and outdoor centralized monitor CCM02, and the indoor CCM address must be set to zero (0) ,
the outdoor CCM address must be set to 16 .
2) BACnet of CCM08(NW-BCN-CM) series must connect with Building Control System at the same IP
subnet! Otherwise, the unit could not work normally.

1
4 Object tabel 2 Function description
1 0) P r o t ec t s t at es This unit shall be installed between in Building Management
R
Attribute Identifier Data mode Attribute value Read/write System (BMS) and air conditioning, which provide with BACnet interfaces,
Object Identifier BACnetObjectIdentifier Multistate-input 4 R
Object Name CharacterString AC _IOutprotect R
associating these two systems to realize the systems integration.It also can
Object Type BACnetObjectType Multistate-input R connect with Midea Multi-connected air-conditioner indepedently.
Discription CharacterString Protect State O
BMS is allowed to access any online air conditioning in central
Current value Unsigned R
Status Flags BACnetStatusFlags F F F F R air conditioning system for information collection and operation control,
Event states BACnet EventStates Normal R after proper installation of central air conditioning and this unit.
Take off service BOOLEAN F R 2-1 Information collection
States number Unsigned 17 R
This unit is provided a function that collecting information from
PF
PE the central air conditioning by BMS, which operation states’ data of
PD
PC
States text BACnet ARRAY[N] PB O indoor units and outdoor units within air conditioning system could be
PA
CharacterString P9
P8 obtained by accessing the specifically BACnet object. Refer to “Object
P7
P6 table” for detail object infromation.
P5
P4
P3
P2 2-2 Operation control
P1
P0 The unit provides BMS control central air conditioning, with
No P
Time delay Unsigned 1 O seven setting functions to control the indoor units in which of the
Publicly type Unsigned 1701 O system. Setting functions included “Operation mode setting”, “time-ON
Event enable BACnetEventTransitionBits T T T O
Affirm transform BACnetEventTransitionBits T T T O
setting”, “time-OFF setting”, “Auxiliary swing function setting”
Notify Type BACnetNotifyType alarm O and “electric heater setting”. By modify the corresponding BACnet object
The CURRENT VALUE attribute of the selected object reflects the current
Operation PROTECTION STATUS (it's read only). In case of the CURRENT VALUE variables to set the unit’s operation status. Refer to “Object table”
instruction shows as No P, that means the system without protection, while other
information displaying means the other relevant protection. For detail, for detail object information.
please refer to TROUBLESHOOT & MAINTENANCE BROCHURE, or
contact with After-sales agent. Provided that more than one protection
occurs simultaneously, only the minimal No. of the protection would be
showed. Thereinto, the CURRENT VALUE displays as 1 means P0; the
CURRENT VALUE displays as 2 means P1, analogously, the CURRENT
VALUE displays as 3 means P2; the CURRENT VALUE displays as 16
means PF; the CURRENT VALUE displays as 17 means No P. Do not operate the air-conditioner frequently, for avoiding the operating
status of the air-conditioner system would be different from the
expected status. The operation time interval between different objects
in the same air-conditioner should be over 10~20 seconds, to keep the
promptness and effectiveness of the status changing.
BACnet R which are the registered trademarks have been registered by America ASHARE
consortium in United State and other countries.

29 2
3 Configuration illustration 4 Object tabel
Setting configuration before using this unit, whether can’t provide to 9 ) Er ro r s t at e s
preinstall function. User input IP address of this unit into the browser, Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Multistate-input 3 R
using WEB access function of this unit set air conditioning. Object Name CharacterString AC _IOutmalfunction R
3-1 Control setting Object Type BACnetObjectType Multistate-input R
Discription CharacterString Malfunction State O
Control of local network has only one control code in range between 0
Current value Unsigned R
and 63.Its name will auto-produce following address or has set by self that Status Flags BACnetStatusFlags F F F F R
convenient for remembrance. After the equipment has set and restart, then Event states BACnet EventStates Normal R
Take off service BOOLEAN F R
modifier will preform in the equipment.
States number Unsigned 17 R
The control code has set randomly before ex-factory, “*”means of EF
EE
control code in “CONTROL-UNIT-*”. ED
EC
States text BACnet ARRAY[N] EB O
3-2 Time and date setting CharacterString
EA
E9
Control provide real-time clock for saving date and time setting, E8
E7
E6
control also provide corresponding set function through network. After E5
E4
setting to control that will be preform at once and the equipment need’t E3
E2
E1
restart. E0
No E
3-3 Safe setting
Time delay Unsigned 1 O
Controller was reset function through administrator’s keyword provided Publicly type Unsigned 1701 O

by network. After setting will effect at once and need’t restart. Event enable BACnetEventTransitionBits T T T O
Affirm transform BACnetEventTransitionBits T T T O
The default administrator name is "admin" and the password is "12345". Notify Type BACnetNotifyType alarm O
The CURRENT VALUE attribute of the selected object reflects the current
Operation ERROR status (it's read only). In case of the CURRENT VALUE shows as
instruction No E, that means the system without protection, while other information
displaying means the other relevant protection. For detail, please refer to
TROUBLESHOOT & MAINTENANCE BROCHURE, or contact with After-
For the system safety, please change the password in time. sales agent. Provided that more the one protection occurs simultaneously,
only the minimal No. of the protection would be showed. Thereinto, the
CURRENT VALUE displays as 1 means E0; the CURRENT VALUE displays
as 2 means E1, analogously, the CURRENT VALUE displays as 3 means E2;
3-4 Network setting the CURRENT VALUE displays as 16 means EF; the CURRENT VALUE
displays as 17 means No E.
There is an Ethernet interfaces in the controller,it is Eth0.This deviece adapts
Ethernet as the network interface of BACnet/IP.
IP address of ethernet has been set“192.168.1.8”before ex-factory,
please modified to appropriate network address. Please contact with network
manager to know detailed infromation.

3 28
4 Object tabel 3 Configuration illustration
8 ) Co mp re ss o r 3 c ur r e nt
Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Analog-iutput 5 R
BACnet of CCM08(NW-BCN-CM) series must connect with Building
Object Name CharacterString AC_ ICom3Current R Control System at the same IP subnet! After IP configuration, must click
Object Type BACnetObjectType Analog-iutput R the "Apply” and "Reboot" key to restart the equipment.Otherwise, the
Current value REAL R unit could not work normally.
Discription CharacterString Compressor 3 current O
Status Flags BACnetStatusFlags F F F F R
3-5 BACnet setting
Event states BACnet EventStates Normal R
Take off service BOOLEAN F R The BACnet network code represents only one of the BACnet
Unit BACnetEngineering Units Amperes R Centralized Controller, at the range from 0 to 65535. Once set up
Minimum REAL 0 O the address, please restart the device to renew the modified
Maximum REAL 200 O settings to become effective.
Time delay Unsigned 1 O BACnet network No. is the BACnet network No. that belong to the
Publicly type Unsigned 1701 O
BACnet device of the MDV series air conditioner which under
Low valve value REAL 0 O
connect with the BACnet centralized controller. For different
centralized controller must be set in different BACnet network
High valve value REAL 200 O
NO., which is the unique number in the system could not be used
Width valve value REAL 1 O
for represent the other device or BACnet centralized controller.
Enable valve value BACnetLimitEnable F T O
The calculation formula of air-conditioner indoor and outdoor
Event enable BACnetEventTransitionBits T T T O
unit instance number is as follow:
Notify Type BACnetNotifyType alarm O
Device ID=BTXX;.
The CURRENT VALUE attribute of the selected object reflects the
Operation COMPRESSOR 1 ELECTRIC CURRENT (it's unsettable). The MINIMAL
B is the bus Number 0-3;
instruction VALUE stands for the minimum electric current, while the MAXMUN VALUE T means type 0-indoor unit,1-outdoor unit;
stands for the maximum electric current.
XX is the indoor unit Number 0-63 or outdoor unit 0-31;

3-5 Factory Reset


When the unit is electrified,short connect the terminal 1and 2 of
485.It will return to factory settings when finishing start-up
.(E.g.,Factory IP address)

27 4
4 Object tabel 4 Object tabel
This device provides with different objects tables for the different 7 ) Co mp re ss or 2 c ur r e nt
types of outdoor units which are in using for the MDV system.
Attribute Identifier Data mode Attribute value Read/write
System will automatically identify the in using outdoor unit and
Object Identifier BACnetObjectIdentifier Analog-iutput 4 R
generate the BACnet object.
Object Name CharacterString AC_ ICom2Current R
4-1 Indoor objects Object Type BACnetObjectType Analog-iutput R
Current value REAL R
This equipment provides with fourteen types of BACnet object,
Description CharacterString Compressor 2 current O
show as the following table, for connecting with indoor unit using
Status Flags BACnetStatusFlags F F F F R
in the Building Management System (BMS) or other system which
Event states BACnet EventStates Normal R
suitable for BACnet Protocol.
Take off service BOOLEAN F R
Number Content Unit BACnetEngineering Units Amperes R
Minimum REAL 0 O
1 Device Information
Maximum REAL 200 O
2 Operation mode Time delay Unsigned 1 O
Publicly type Unsigned 1701 O
3 Fan state
Low valve value REAL 0 O
4 Preset Temperature High valve value REAL 200 O
Width valve value REAL 1 O
5 Indoor temperature
Enable valve value BACnetLimitEnable T T O
6 Set on time Event enable BACnetEventTransitionBits T T T O
Notify Type BACnetNotifyType alarm O
7 Set off time
The CURRENT VALUE attribute of the selected object reflects the
Operation
8 Swing function COMPRESSOR 2 ELECTRIC CURRENT (it's unsettable). The MINIMAL
instruction VALUE stands for the minimum electric current, while the MAXMUN VALUE
stands for the maximum electric current.
9 Electric heater function

10 Malfunction state

11 Protection state

12 Mode query

13 Speed query

14 Temp set query

5 26
4 Object tabel 4 Object tabel
6 ) Co mp re ss o r 1 c ur r e nt Detailed infromation of corresponding objects refer to under-table
Attribute Identifier Data mode Attribute value Read/write
1) Device infromation
Object Identifier BACnetObjectIdentifier Analog-iutput 3 R
Object Name CharacterString AC_ ICom1Current R Attribute Identifier Data mode Attribute value Read/write

Object Type BACnetObjectType Analog-iutput R Object Identifier BACnetObjectIdentifier Device + Acnumber R

Current value REAL R Object Name CharacterString Indoor_*_* R

Description CharacterString Compressor 1 current O Object Type BACnetObjectType Device R

Status Flags BACnetStatusFlags F F F F R Device Status BACnetDeviceStatus Operational R


Producer Name CharacterString AC Inc R
Event states BACnet EventStates Normal R
Producer Identifier Unisgned16 111(Unsigned) R
Take off service BOOLEAN F R
Get one of these from
Unit BACnetEngineering Units Amperes R protocolanalysis:
Minimum REAL 0 O Wall Mounted Tpye
Floor Tpye R
Maximum REAL 200 O Embedded Tpye
Duct Tpye
Time delay Unsigned 1 O Model Name CharacterString Floor&ceiling Tpye
AC Auxiliary Machine Tpye
Publicly type Unsigned 1701 O Digital Mutil-connection Tpye
Frequency Conversion Tpye
Low valve value REAL 0 O Digital Rotation Tpye
High valve value REAL 200 O
Width valve value REAL 1 O Firmware Edition CharacterString 1.0 R
Enable valve value BACnetLimitEnable T T O Application Software Edition CharacterString 1.0 R
Event enable BACnetEventTransitionBits T T T O Protocol Edition Unsigned 1 R
Notify Type BACnetNotifyType alarm O Protocol Correspondency Type Unsigned 3 R
The CURRENT VALUE attribute of the selected object reflects the Protocol Service Support BACnetServiceSupport ReadProperty R
Operation COMPRESSOR 1 ELECTRIC CURRENT (it's unsettable). The MINIMAL
Protocol Object Types SupportBACnetObjectTypesSupport AnalogInput R
instruction VALUE stands for the MINIMUM ELECTRIC CURRENT, while the MAXMUN
VALUE stands for the MAXIMUM ELECTRIC CURRENT. Object Array BACnetArray[n] Array all object R
Max length of APDU support Unsigned 1476 R
Segmentation support BACnetSegmentation Segmented both(0) R
Local Time Time R/W
Local Date Date R/W
APDU Segmentation Timeover Unsigned 2000 O
APDU Timeover Unsigned 3000 R
APDU Resend Times Unsigned 3 R
Device Address Binding AddressBinding ASN.1 ‘’ R
Operation The OBJECT NAME attribute of this selected object stands for the
instruction MODEL INFORMATION which could not be set.

25 6
4 Object tabel 4 Object tabel
2 ) Ru nn in g mo d e 5 ) In do or q ua n t it y
Attribute Identifier Data mode Attribute value Read/write Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Multistate-output 1 R Object Identifier BACnetObjectIdentifier Analog-iutput 2 R
Object Name CharacterString AC_OModeSetting R Object Name CharacterString AC_ ITotalACs R
Object Type BACnetObjectType Multistate-output R Object Type BACnetObjectType Analog-iutput R
Description CharacterString Operation mode setting O Current value REAL R
Current value Unsigned W Description CharacterString Indoor unit qty O
Status Flags BACnetStatusFlags F F F F R Status Flags BACnetStatusFlags F F F F R
Event states BACnet EventStates Normal R Event states BACnet EventStates Normal R
Take off service BOOLEAN F R Take off service BOOLEAN F R
States number Unsigned 6 R Unit BACnetEngineering Units R
Minimum REAL 0 O
Auto
Cool Maximum REAL 250 O
Heat
Dehumidify O Time delay Unsigned 1 O
States text BACnet ARRAY[N] FanOnly
CharacterString Stop Publicly type Unsigned 1701 O
Low valve value REAL 0 O
High valve value REAL 250 O
Width valve value REAL 1 O
Enable valve value BACnetLimitEnable F T O
Priority Array BACnetPriorityArra NULL R
Event enable BACnetEventTransitionBits T T T O
Release default Unsigned 0 R
Notify Type BACnetNotifyType alarm O
Time delay Unsigned 2 O
The CURRENT VALUE attribute of the selected object reflects the current
Publicly type Unsigned 1701 O Operation
INDOOR UNIT QUANTITY (it's read only).
Feedback value Unsigned 6 instruction

Event enable BACnetEventTransitionBits T T T O


Affirm transform BACnetEventTransitionBits T T T O
Notify Type BACnetNotifyType alarm O

The CURRENT VALUE attribute of the selected object reflects the current
Operation OPERATION MODE (it's writeable and settable). Thereinto, the
instruction CURRENT VALUE 1 means HEATING MODE; the CURRENT VALUE 2
means COOLING MODE; the CURRENT VALUE 3 means DEHUMIDIFIED
MODE; the CURRENT VALUE 4 means AIR SUPPLY; the CURRENT
VALUE 5 means AUTO MODE; the CURRENT VALUE 6 means SHUT OFF.

7 24
4 Object tabel 4 Object tabel
4 ) Ou td oo r te r m pe r a tu r e 3) F an s t a te s
Attribute Identifier Data mode Attribute value Read/write Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Analog-iutput 1 R Object Identifier BACnetObjectIdentifier Multistate-output 2 R
Object Name CharacterString AC_ITempOutoor R Object Name CharacterString AC _OFanSpeed R
Object Type BACnetObjectType Analog-iutput R Object Type BACnetObjectType Multistate-output R
Current value REAL R Description CharacterString Fan Speed Setting O
Description CharacterString Outdoor Temperature O Current value Unsigned W
Status Flags BACnetStatusFlags F F F R Status Flags BACnetStatusFlags F F F F R
Event states BACnet EventStates Normal R Event states BACnet EventStates Normal R
Take off service BOOLEAN F R Take off service BOOLEAN F R
Unit BACnetEngineering Units Degree-Celsius R States number Unsigned 5 R
Minimum REAL -20 O
Auto
Maximum REAL 100 O Low
Middle
Time delay Unsigned 1 O High O
States text BACnet ARRAY[N] Stop
Publicly type Unsigned 1701 O CharacterString
Low valve value REAL -20 O
High valve value REAL 100 O
Width valve value REAL 1 O
Enable valve value BACnetLimitEnable T T O
Priority Array BACnetPriorityArra NULL R
Event enable BACnetEventTransitionBits T T T O
Release default Unsigned 5 R
Notify Type BACnetNotifyType event O
Time delay Unsigned 1 O
The CURRENT VALUE attribute of the selected object reflects the current
Operation ROOM TEMPERATURE (it could not be set). The MINIMAL VALUE stands for Publicly type Unsigned 1701 O
instruction the minimum temperature, while the MAXMUN VALUE stands for the Feedback value Unsigned 5
maximum Temperature.
Event enable BACnetEventTransitionBits T T T O
Affirm transform BACnetEventTransitionBits T T T O
Notify Type BACnetNotifyType alarm O

The CURRENT VALUE attribute of the selected object reflects


Operation
the current FAN SPEED (It's writable and settable). Thereinto,
instruction the CURRENT VALUE 1 means HIGH SPEED; the CURRENT
VALUE 2 means MEDIUM SPEED; the CURRENT VALUE 3
means LOW SPEED; the CURRENT VALUE 4 means AUTO
SPEED; the CURRENT VALUE 5 means FAN STOP. The thing
is, during air conditioner operating, the CURRENT VALUE
would be set as to 5 (the order of stop the fan) for ensuring the
normal operate, however, this default setting would be omitted
by the system automatically.

23 8
4 Object tabel 4 Object tabel
4 ) Pr es et t em p e ra t u re 3) F an s t a te s
Attribute Identifier Data mode Attribute value Read/write Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Analog-output 1 R Object Identifier BACnetObjectIdentifier Multistate- iutput 2 R
Object Name CharacterString AC_OTempSetting R Object Name CharacterString AC_IFanSpeed R
Object Type BACnetObjectType Analog-output R Object Type BACnetObjectType Multistate- iutput R
Current value REAL W Current value Unsigned R
Description CharacterString Temperature Setting O Description CharacterString Fan speed O
Status Flags BACnetStatusFlags F F F F R Status Flags BACnetStatusFlags F F F F R
Event states BACnet EventStates Normal R Event states BACnet EventStates Normal R
Take off service BOOLEAN F R Take off serviceBOOLEAN F R
Unit BACnetEngineering Units Degree-Celsius R States number Unsigned 4 R
Minimum REAL 16 O Low
States text BACnet ARRAY[N] Middle
Maximum REAL 32 O High O
CharacterString
Stop
Priority array Value BACnetPriorityArra NULL R
Time delay Unsigned 1 O
Default release REAL 25 R
Publicly type Unsigned 1701 O
Distinguishability REAL 1 O
Event enable BACnetEventTransitionBits T T T O
COV increment REAL 1 O
Affirm transform BACnetEventTransitionBits T T T O
Low valve value REAL 16 O
Notify Type BACnetNotifyType alarm O
High valve value REAL 32 O
The CURRENT VALUE attribute of the selected object reflects the
Width valve value REAL 1 O Operation current FAN SPEED (It's read only). Thereinto, the CURRENT VALUE 1
Enable valve value BACnetLimitEnable T T O instruction means HIGH SPEED; the CURRENT VALUE 2 means MEDIUM SPEED;
the CURRENT VALUE 3 means LOW SPEED; the CURRENT VALUE 4
Event enable BACnetEventTransitionBits T T T O means FAN STOP.
Notify Type BACnetNotifyType alarm O
Publicly type Unsigned 1701 O
Time delay Unsigned 1 O
Affirm transform BACnetEventTransitionBits T T T O

Operation The CURRENT VALUE attribute of the selected object reflects the current
instruction SETTNG TEMPERATURE (it's writable and settable). The MINIMAL VALUE
stands for the min. temperature, while the MAXMUN VALUE stands for the
max. temperature. The setting temperature could not exceed than the range.

9 22
4 Object tabel 4 Object tabel
2 ) Ru nn in g mo d e 5 ) Ro om t em pr a t ur e
Attribute Identifier Data mode Attribute value Read/write Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Multistate-input 1 R Object Identifier BACnetObjectIdentifier Analog-iutput 1 R
Object Name CharacterString AC_IOperationMode R Object Name CharacterString AC _ITempIndoor R
Object Type BACnetObjectType Multistate-output R Object Type BACnetObjectType Analog-iutput R
Description CharacterString Operation mode O Current value REAL R
Current value Unsigned W Description CharacterString Indoor temperature O
Status Flags BACnetStatusFlags F F F F R Status Flags BACnetStatusFlags F F F F R
Event states BACnet EventStates Normal R Event states BACnet EventStates Normal R
Take off service BOOLEAN F R Reliability BACnetReliability NO-FAULT-DETECTED R
States number Unsigned 3 R Take off service BOOLEAN F R
States text BACnet ARRAY[N] Cool Unit BACnetEngineering Units Degree-Celsius R
Heat O
CharacterString Stop Minimum REAL -20 O
Maximum REAL 100 O
Time delay Unsigned 1 O
Distinguishability REAL 1 O
Publicly type Unsigned 1701 O
Time delay Unsigned 1 O
Event enable BACnetEventTransitionBits T T T O
Publicly type Unsigned 1701 O
Affirm transform BACnetEventTransitionBits T T T O
Low valve value REAL -20 O
Notify Type BACnetNotifyType alarm O
High valve value REAL 100 O
The CURRENT VALUE attribute of the selected object reflects
Operation t h e c u r r e n t O U T D O O R U N I T O P E R AT I O N M O D E ( i t ' s Width valve value REAL 1 O
instruction unsettable). Thereinto, the CURRENT VALUE 1 means Enable valve value BACnetLimitEnable T T O
HEATING MODE; the CURRENT VALUE 2 means COOLING Event enable BACnetEventTransitionBits T T T O
MODE; the CURRENT VALUE 3 means DEHUMIDIFIED MODE;
Notify Type BACnetNotifyType event O
The CURRENT VALUE attribute of the selected object reflects the
Operation
current ROOM TEMPERATURE (its read only, could not be set).
instruction
The MINIMAL VALUE stands for the min. temperature, while the
MAXMUN VALUE stands for the max. Temperature.

21 10
4 Object tabel 4 Object tabel
6 ) Se t on t i m e 1 ) De vi ce i nf r o ma t i on
Attribute Identifier Data mode Attribute value Read/write Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Analog-output 2 R Object Identifier BACnetObjectIdentifier Device + Acnumber R
Object Name CharacterString AC _ IOnTime R Object Name CharacterString Outdoor_*_*_* R
Object Type BACnetObjectType Analog-intput R Object Type BACnetObjectType Device R
Current value REAL W System Status BACnetDeviceStatus Operational R
Description CharacterString On Time Setting O Producer Name CharacterString AC Inc R
Status Flags BACnetStatusFlags F F F F R Producer Identifier Unisgned16 111(Reserve) R
Event states BACnet EventStates Normal R Model Name CharacterString Frequency Conversion AC R
Reliability BACnetReliability NO-FAULT-DETECTED R or Digital rotation AC
Take off service BOOLEAN F R Firmware Edition CharacterString 1.0 R
Unit BACnetEngineering Units Hours R Application Software Edition CharacterString 1.0 R
Minimum REAL 0 O Protocol Edition Unsigned 1 R
Maximum REAL 24 O Protocol Correspondency Type Unsigned 3 R
Distinguishability REAL 0.25 O Protocol Service Support BACnetServiceSupport ReadProperty etc. R
Priority Array BACnetPriorityArra NULL R Protocol Object Types Support BACnetObjectTypesSupport AnalogInput etc. R
Default release REAL 0 R Object Array BACnetArray[n] List all objects R
COV INCREMENT REAL 0.25 O Max length of APDU support Unsigned 1476 R
Low valve value REAL 0 O Segmentation support BACnetSegmentation Segmented both(0) R
High valve value REAL 24 O Local Time Time R/W
Width valve value REAL 0.5 O Local Date Date R/W
Enable valve value BACnetLimitEnable T T O APDU SEGMENTATION TIMEOVER Unsigned 2000 O
Event enable BACnetEventTransitionBits T T T O APDU TIMEOVER Unsigned 3000 R
Notify Type BACnetNotifyType alarm O APDU RESEND TIMES Unsigned 3 R
Publicly type Unsigned 1701 O Device Address Binding AddressBinding ASN.1 ‘’ R
Time delay Unsigned 1 O Operation
The OBJECT NAME attribute of this selected object reflects the
Affirm transform BACnetEventTransitionBits T T T O MODEL INFORMATION, which is not allowed to set, while the
instruction
specific MODEL NAME is defined by the relevant protocol.
The CURRENT VALUE attribute of the selected object reflects the
Operation
instruction current TIMING ON time (it is read only, could not be set). From 0
to 24 means during the 24 hours without timing has been set.

11 20
4 Object tabel 4 Object tabel
4-2 Outdoor Air Conditio ner Objects 7 ) Se t of f t im e
This equipment provides with ten types of BACnet object, show as Attribute Identifier Data mode Attribute value Read/write
the following table, for connecting with Inverter AC or Digital AC Object Identifier BACnetObjectIdentifier Analog-output 3 R
using in the Building Management System (BMS) or other system Object Name CharacterString AC _ OOffTime R
which suitable for BACnet Protocol. Object Type BACnetObjectType Analog-output R
Current value REAL W
Description CharacterString Off Time Setting O
Number Content
Status Flags BACnetStatusFlags F F F F R
1 Device Information Event states BACnet EventStates Normal R

2 Take off service BOOLEAN F R


Operation mode
Unit BACnetEngineering Units Hours R
3 Fan state Minimum REAL 0 O
Maximum REAL 24 O
4 Outdoor temperature
Distinguishability REAL 0.25 O
5 Indoo unit quantity Reliability BACnetReliability NO-FAULT-DETECTED O

6 Compressor 1 electric current Priority Array BACnetPriorityArra NULL R


Default release REAL 0 R
7 Compressor 2 electric current COV INCREMENT REAL 0.25 O

8 Compressor 3 electric current Low valve value REAL 0 O


High valve value REAL 24 O
9 Malfunction state Width valve value REAL 0.5 O
10 Protection state Enable valve value BACnetLimitEnable T T O
Event enable BACnetEventTransitionBits T T T O
Notify Type BACnetNotifyType alarm O
Publicly type Unsigned 1701 O
Time delay Unsigned 1 O
Affirm transform BACnetEventTransitionBits T T T O
Operation The CURRENT VALUE attribute of the selected object reflects the
instruction current TIMING OFF time (it is read only, could not be set). From 0
to 24 means during the 24 hours without timing has been set.

19 12
4 Object tabel 4 Object tabel
8 ) Sw in g f u nc t i on 14 ) Tem p er a t ur e s e tt in g qu er y
Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Binary-output 1 R Attribute Data type Attribute value Read/Write
Object Name CharacterString AC _OSwing R identifier
Object Type BACnetObjectType Binary-output R
Object BACnetObjectIdentifier Analog-input 4 R
Current value BACnetBinaryPV inactive W identifier
Discription CharacterString Swing Setting O
Object name CharacterString AC_QueryTempSetting R
Status Flags BACnetStatusFlags F F F F R
Event states BACnet EventStates Normal R
Object type BACnetObjectType Analog-input R
Take off service BOOLEAN F R
Polarity BACnetPolarity Normal R Current value REAL R
Inactive text CharacterString Turn off O
Active text CharacterString Turn on O Description CharacterString QueryTempSetting O
Time delay Unsigned 1 O
States change time BACnetDateTime O
Unit BACnetEngineering Units Degree-Celsius R
States change times Unsigned O
Change time to 0BACnetDateTime O
Publicly type Unsigned 1701 O
Feedback value BACnetBinaryPV inactive O
Event enable BACnetEventTransitionBits T T T R
Affirm transform BACnetEventTransitionBits T T T O
Priority Array BACnetPriorityArra NULL R
Default release BACnetBinaryPV inactive R
Notify Type BACnetNotifyType alarm O

Operation The CURRENT VALUE attribute of the selected object reflects the
instruction current SWING STATUS. INACTIVE means SWING OFF, while
ACTIVE means SWING ON.

13 18
4 Object tabel 4 Object tabel
12 ) Mo d e q ue ry 9 ) El ec tr ic h e a te r f u nc ti on
Attribute Identifier Data mode Attribute value Read/write
Attribute Data type Object Identifier BACnetObjectIdentifier Binary-output 2 R
Attribute value Read/Write
identifier
Object Name CharacterString AC _OElecHeat R
Object Object Type BACnetObjectType Binary-output R
BACnetObjectIdentifier Multistate-input 3 R
identifier
Current value BACnetBinaryPV Inactive W
Discription CharacterString Elecheat Setting O
Object name CharacterString AC_QueryMode R
Status Flags BACnetStatusFlags F F F F R

Object type Event states BACnet EventStates Normal R


BACnetObjectType Multistate-input R
Take off service BOOLEAN F R
Description CharacterString QueryMode O Polarity BACnetPolarity Normal R
Inactive text CharacterString Turn off O
BACnet ARRAY[N] {"Heat","Cool","Dehumidify",
Status text O Active text CharacterString Turn on O
CharacterString "Fanonly","Auto","Stop"}
Time delay Unsigned 1 O
States change time BACnetDateTime O
States change times Unsigned O
13) Fan speed query
Change time to 0 BACnetDateTime O
Publicly type Unsigned 1701 O
Attribute Data type Attribute value Read/Write Feedback value BACnetBinaryPV inactive O
identifier
Event enable BACnetEventTransitionBits T T T R
Object
BACnetObjectIdentifier Multistate-input 4 R Affirm transform BACnetEventTransitionBits T T T O
identifier
Priority Array BACnetPriorityArra NULL R
Object name CharacterString AC_QueryFanSpeed R Default release BACnetBinaryPV inactive R
Notify Type BACnetNotifyType alarm O
Object type BACnetObjectType Multistate-input R The CURRENT VALUE attribute of this selected object reflects the current
Operation ELECTRIC HEATER working status. INACTIVE means ELECTRIC HEATER
Description CharacterString QueryFanSpeed O instruction OFF, while ACTIVE means ELECTRIC HEATER ON. The thing is, when air
conditioner in the COOLING MODE or other mode, the CURRENT VALUE
BACnet ARRAY[N] {"High","Middle","Low","Auto", would be set as ELECTRIC HEATER ON for ensuring the normal operate,
Status text "Stop"} O
CharacterString however, this default setting would be omitted by the system automatically.

17 14
4 Object tabel 4 Object tabel
1 0) M al fu nc t io n st a te s 11 ) Pr e t ec t io n sta t es
Attribute Identifier Data mode Attribute value Read/write Attribute Identifier Data mode Attribute value Read/write
Object Identifier BACnetObjectIdentifier Multistate-input 1 R Object Identifier BACnetObjectIdentifier Multistate-input 2 R
Object Name CharacterString AC _IMalfunction R Object Name CharacterString AC _IProtect R
Object Type BACnetObjectType Multistate-input R Object Type ACnetObjectType Multistate-input R
discription CharacterString Malfunction State O Discription CharacterString Protect State O
current value Unsigned R Current value Unsigned R
Status Flags BACnetStatusFlags F F F F R Status Flags BACnetStatusFlags F F F F R
Event states BACnet EventStates Normal R Event states BACnet EventStates Normal R
Take off service BOOLEAN F R Take off service BOOLEAN F R
States number Unsigned 17 R States number Unsigned 11 R
EF PF
EE P8
ED P7
EC P6
States text BACnet ARRAY[N] EB O States text BACnet ARRAY[N] P5 O
EA P4
CharacterString E9 CharacterString P3
E8 P2
E7 P1
E6 P0
E5 No P
E4
E3
E2
E1
E0
No E
Time delay Unsigned 1 O Time delay Unsigned 1 O
Publicly type Unsigned 1701 O Publicly type Unsigned 1701 O
Event enable BACnetEventTransitionBits T T T O Event enable BACnetEventTransitionBits T T T O
Affirm transform BACnetEventTransitionBits T T T O Affirm transform BACnetEventTransitionBits T T T O
Notify Type BACnetNotifyType alarm O Notify Type BACnetNotifyType alarm O
The CURRENT VALUE attribute of the selected object reflects the current
Operation The CURRENT VALUE attribute of the selected object reflects Operation PROTECTION status (it's read only). In case of the CURRENT VALUE
the current MALFUNCTION (it's read only). In case of the shows as No P, that means the system without protection, while other
instruction instruction
CURRENT VALUE shows as No E, that means without information displaying means the other relevant protection. For detail,
malfunction, while other information displaying means the please refer to TROUBLESHOOT & MAINTENANCE BROCHURE, or
relevant malfunction. For detail, please refer to contact with After-sales agent. Provided that more than one protection
TROUBLESHOOT & MAINTENANCE BROCHURE, or contact occurs simultaneously, only the minimal No. of the protection would be
with After-sales agent. Provided that more the one malfunction showed. Thereinto, the CURRENT VALUE displays as 1 means P0; the
CURRENT VALUE displays as 2 means P1, analogously, the CURRENT
occurs simultaneously, only the minimal No. of the error would VALUE displays as 3 means P2; the CURRENT VALUE displays as 10
be showed. means PF; the CURRENT VALUE displays as 11 means No P.

15 16