S500-Doc 02-12 DLHF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Jan.

-11 DL/HF modem


¾ Position: no. 1 to 7.

¾ Properties
9 Use a cable with a cross section of 0.203 mm2 (resistance of 100Ω per kilometer)
9 Connect the cable shielding to the Earth on one side

¾ DL/PL connection
DL surge protection Remote terminal unit
+ DL/HF board
Line test box

PL line

2 For further information, see the “Surge Protectors” §.

9 Multipoint PL topology
z "bus" type topology; no loopback nor start structure,
z Management of 4 LP-BOX units by DL/HF board,
z a maximum of 15 devices uniformly distributed over a maximum distance of
15 kilometers; network branches must be as short as possible,
z the two end devices must be configured as such
(cf. § "SERIAL / RADIO DL-PL Communications").
9 End of line 9 End of line
Maximum bus length = 15 km
(cable used: SYT+ AWG24 with cross section of 0.203 mm2)

¾ Radio connection:
9 The DL/HF modem can be connected to a MOTOROLA type Radio unit. See the
chapter corresponding to the type of radio to install.

¾ Diagnostics
9 The graphical display shows the input / output signals in order to ensure that the
communication occurs correctly.
DL/HF modem 3
Reception : 0 dB
Transmission :-10 dBm
CD | TX z RX |

S500-doc_02-12-DLHF