Professional Documents
Culture Documents
(50-80-100) - He Plus
(50-80-100) - He Plus
Baxi 50 HE Plus
Baxi 80 HE Plus
Baxi 100/2 HE Plus
© Baxi Heating UK Ltd 2006 All rights reserved. No part of this publication may The flowchart opposite gives guidance for installers on the
be reproduced or transmitted in any form or by any means, or stored in any process necessary to ensure compliance with Building
retrieval system of any nature (including in any database), in each case whether
electronic, mechanical, recording or otherwise, without the prior written Regulations.
permission of the copyright owner, except for permitted fair dealing under
Copyrights, Designs and Patents Act 1988.
“Baxi” supports
Choose Building
Regulations Notification
Route
CORGI will record the data and LABC will record the data
will send a certificate of and will issue a
compliance to the property certificate of compliance
IMPORTANT - Installation, Commissioning, Service & Repair This company declare that no substances harmful to
health are contained in the appliance or used during
This appliance must be installed in accordance with the manufacturer’s instructions and appliance manufacture.
the regulations in force. Read the instructions fully before installing or using the
appliance. The appliance is suitable only for installation in GB and IE
and should be installed in accordance with the rules in
In GB, this must be carried out by a competent person as stated in the Gas Safety force, and only used in a suitably ventilated location.
(Installation & Use) Regulations.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance
Definition of competence: A person who works for a CORGI registered company and with the relevant requirements of the:
holding current certificates in the relevant ACS modules, is deemed competent. • Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Regulations (Northern Ireland).
Gas Installations”. • The Water Fittings Regulations or Water Byelaws in
Scotland.
NOTE: The addition of anything that may interfere with the normal operation of the • The Current I.E.E. Wiring Regulations.
appliance without express written permission from the manufacturer or his agent could
Where no specific instructions are given, reference should
invalidate the appliance warranty. In GB this could also infringe the Gas Safety
be made to the relevant British Standard Code of Practice.
(Installation and Use) Regulations.
In IE, the installation must be carried out by a competent
Warning - Check the information on the data plate is compatible with local supply Person and installed in accordance with the current edition
conditions. of I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current
ETCI rules for electrical installation.
All CORGI registered installers carry a CORGI identification card and have a
registration number. You can check your installer is registered by telephoning
Codes of Practice, most recent version should be used
0870 4012300 or writing to:-
1 Elmwood,
In GB the following Codes of Practice apply:
Chineham Business Park, Standard Scope
Crockford Lane, BS 6891 Gas Installation.
BS 5546 Installation of hot water supplies for domestic
Basingstoke. RG24 8WG purposes.
BS 5449 Forced circulation hot water systems.
BS 6798 Installation of gas fired hot water boilers.
or check online at www.corgi-gas-safety.com BS 5440 Part 1 Flues.
BS 5440 Part 2 Ventilation.
BS 7074 Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593 Treatment of water in domestic hot water
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) central heating systems.
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive In IE the following Codes of Practice apply:
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with Standard Scope
I.S. 813 Domestic Gas Installations.
liquid or gaseous fuels:- The following BS standards give valuable additional information;
BS 5546 Installation of hot water supplies for domestic
purposes.
Type test for purpose of Regulation 5 certified by: BS 5449 Forced circulation hot water systems.
Notified Body 0087. BS 7074 Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593 Treatment of water in domestic hot water
Product/Production certified by: central heating systems.
Notified Body 0086.
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.
Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care
on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the
‘Installation’ section of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
1.0 Introduction 7
8.0 Installation 23
9.0 Electrical 29
Benchmark Checklist 50
1.1 Description
Lower Door Panel 5. A label giving details of the model, serial number and
Gas Council number is situated on the rear of the lower
door panel (Fig. 1).
1. Wall Plate
2. Flue Elbow
3. Heat Exchanger
4. Burner
5. Air Box
6. Fan Protection Thermostat
13
Fig. 3
7
11
Fig. 4 Fig. 6
10
3.1
Flow NO
temperature less
than set point ?
1. Switched Live On: When the switched live switches
on if the flow temperature is less than the set point
then pump overrun occurs. When the switched live
YES switches on if the flow temperature is greater than the
set point then pump overrun occurs.
10 second
Pump On.
2. Pump On: The pump is on while the fan, spark
generator and gas valve are off. After 10 seconds if the
flow switch has made then fan pre-purge occurs. After
10 seconds if the flow switch has not made then anti-
NO
Flow switch made ? cycle occurs.
5 second
8. Anti-cycle: The pump, fan, spark generator and gas
Fan Post Purge.
valve are off. After 3 minutes if the flow temperature is
less than the set point then pump on occurs. After 3
minutes if the flow temperature is greater than the set
point then pump overrun occurs.
YES All TRVs
shut down ?
9. Ignition Lockout: The pump, fan, spark generator
and gas valve are off. The boiler can only be reset by
manually using the reset button.
NO
1 minute
Pump Overrun.
3 minute
Anti-cycle.
Appliance Type C13 C33 Injector (Natural Gas) Electrical Supply 230V~ 50Hz
6.5mm Diameter (Appliance must be connected to an
Appliance Category CAT I 2H earthed supply)
CO/CO2 Ratio Up to a maximum
Heat Input (Q)(Gross) Max Min of 0.004 Power Consumption 80W
50 HE Plus kW 16.88 10.2 CO Level 2
9% ± 1%
Btu/hr 57,600 34,840 External Fuse Rating 3A
180 75
160 66
SEDBUK Declaration
140 58
For 50 HE Plus - The efficiency is 91.3% 50
120
For 80 HE Plus - The efficiency is 90.9%
100 42
For 100/2 HE Plus - The efficiency is 90.9%
80 33
This value is used in the UK Government’s Standard 60 25
Assessment Procedure (SAP) for energy rating of 40 17
dwellings. The test data from which it has been 20 8
calculated has been certified by 0087.
0 10 20 30 40
Water Flow Rate (litres/min)
DIMENSIONS
E A 600mm
3°
(1 in 20) B 320mm
C 390mm
A
D 125mm Ø Min.
E 150mm
F 125mm
B
360° Orientation
D C
The 3° (1 in 20) fall provided by the
elbow is to allow condensate to run
back to the boiler, for disposal
Tube Ø 110mm through the condensate discharge
pipe.
Fig. 7
Y
SIDE FLUE (left and right)
X For every 1m of horizontal flue
length, the clearance above the top
3° of the flue elbow should be 55mm
(1 in 20) to incorporate the 3°
(1 in 20) fall in the flue from the
terminal to the elbow.
Return
6.4 Low Head Installation
Air
Separator
Boiler Pump
Flow
Return
Fig. 12
Alternative Low Head Installation
230V gr
50Hz 230V b
gr
L N E b Y Plan 50Hz
g/y L N E
w Diverter Motor Motor
b
Cylinder Valve br
Stat gr
S Plan o g/y S Plan
1 o Valve Valve
g/y
br Cylinder o
C 2
Stat
Boiler
L E N P/F Boiler
L E N P/F
Timer
Timer
L
N L
CH on NE L Pump N
CH on NE L Pump
HW on
HW off HW on
Y Plan, Fully TRV’d System, CH Interlocked By Boiler Flow Switch S Plan, Fully TRV’d System, CH Interlocked By Boiler Flow Switch
Room Thermostat should not be fitted Room Thermostat should not be fitted
Pump must be run from Boiler P/F connection for Part L1 compliance Pump must be run from Boiler P/F connection for Part L1 compliance
By-pass not permitted (must be valved) for Part L1 compliance By-pass not permitted (must be valved) for Part L1 compliance
Temporary
DHW CH
Hose
Mains Return
Fig. 14
Inlet
© Baxi Heating UK Ltd 2006 15
7.0 Site Requirements
7.1 Location
In Operation
Fig. 16
50mm
per me
tre of Holes in the soak-away must
pipe ru
n face away from the building
2.5° M
inimum
fall
Terminal Position with Minimum Distance (Fig. 17) (mm) 7.7 Flue
Aa Directly below an opening, air brick, opening
NOTE: Due to the high efficiency of the boiler a plume
windows, etc. 300
of water vapour will be discharged from the flue. This
Ba Above an opening, air brick, opening window etc. 300
Ca Horizontally to an opening, air brick, opening window etc. 300 should be taken into account when siting the flue
D Below gutters, soil pipes or drain pipes. 25 terminal.
E Below eaves. 25
F Below balconies or car port roof. 25 1. The following guidelines indicate the general requirements
G From a vertical drain pipe or soil pipe. 25 for siting balanced flue terminals.
H From an internal (i) or external (ii) corner. (i) 25 (ii) 115
For GB recommendations are given in BS 5440 Pt.1.
I Above ground, roof or balcony level. 300
For IE recommendations are given in the current edition of
J From a surface or boundary line facing a terminal. 600
K From a terminal facing a terminal (Horizontal flue). 1200 I.S. 813 “Domestic Gas Installations”.
From a terminal facing a terminal (Vertical flue). 600
L From an opening in carport (e.g. door, window) 2. If the terminal discharges onto a pathway or passageway,
into the dwelling. 1200 check that combustion products will not cause a nuisance
M Vertically from a terminal on the same wall. 1500 and that the terminal will not obstruct the passageway.
N Horizontally from a terminal on the same wall. 300
Table. 2
a In addition, the terminal should be no nearer than 150 mm to an 4. Adjacent surfaces close to the flue terminal may need
opening in the building fabric formed for the purpose of accommodating protection from the effects of condensation. Alternatively a
a built-in element such as a window frame. See BS 5440 Pt. 1. flue deflector kit (part no. 248167) is available.
Property Boundary Line 9. If a terminal is less than 2 metres (783/4 in) above a
balcony, above ground or above a flat roof to which people
have access, then a suitable terminal guard must be provided.
IMPORTANT:
• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
Fig. 17
Concentric
The maximum equivalent lengths are 4m (horizontal) or
D (vertical). There lengths exclude the standard elbow and
flue/terminal assembly (horizontal) and terminal assembly
Q
(vertical).
Twin Flue
The total maximum equivalent flue length is 150m.
E NOTE: Each 1m of flue duct should be calculated as 2m.
Plume Displacement 70/110 dia Kit Twin Flue Pipe: 45° bend (air duct) 1.3 m
1M Extensions, 45° & 93° bends 45° bend (flue duct) 2.6 m
are also available - see literature 90° bend (air duct) 4.8 m
supplied with the kit for details 90° bend (flue duct) 9.6 m
50
26 7.9 Plume Displacement Kit
&8
24 NOTE: Please read this section in conjunction with
0
the instructions supplied in the kit. The table opposite
22 supplements information in the kit literature.
10
20 1. This kit is recommended for installations where the
0/2
condensate plume emitted from the flue may cause a
18 nuisance or affect the surroundings.
70Ø Exhaust (metres) X
12 3. Full fitting details are supplied with the kit. The table
and illustration opposite show the maximum permissible
10 lengths of each part of the flue (Fig 17a).
X
Plume
Displacement Kit
Y
Air Inlet
100mm
Fig. 17b MIN. Fig. 17c
Pictorial examples of flue runs where EQUIVALENT flue length equals 4m 1. Only a flue approved with the Baxi 50, 80 and 100/2
HE Plus can be used.
Fig. 19
Backfall to the Boiler, ie. 2m flue offset (V) position 110mm 3. Mark the position of the centre hole for the wall
Flue Duct Hole plate (Fig. 20).
Offset V (mm) 27 55 110 165 220 (mm)
Distance in metres from boiler to the wall. 5. Cut the hole for the flue (minimum diameter
For pipe lengths greater than 4m increase the off-set by 52mm 125mm, see table (Fig. 20) for wall thicknesses and flue
for every additional metre to maintain approx 3° inclination.
diameters).
Fig. 21
6. Drill and plug the wall as previously marked. Secure
the wall plate using the centre hole (Fig. 22).
Fig. 22
© Baxi Heating UK Ltd 2006 23
8.0 Installation
Fig. 23
Wall Plate
Fig. 24
8.4 Making the Water Connections (Fig. 25)
Return Pipe Connection
1. The boiler has two side water connections which are
Suggested Lifting labelled FLOW and RETURN. The front connection is the
Points shown as flow pipe and the rear threaded connection is the return.
shaded area
2. It is essential that the flow and return pipes are
connected to the boiler correctly. The flow connection
Flue Products Exhaust incorporates the boiler thermostats and a flow switch.
HORIZONTAL FLUE
5. Take the flue and mark off (Z) from the terminal end
as indicated (Fig. 27).
Inner Flue Support Bracket 6. Ensure the inner flue support bracket is positioned in
the flue (Fig. 28).
7. Engage the flue into the flue elbow using soap solution
to ease the engagement ensuring the flue is assembled as
shown (Fig. 29).
Fig. 28
8. Place the gasket over the flue exit on the boiler.
Flue Elbow 11. Make good between the wall and air duct outside the
building ensuring the 3° drop between the terminal and
elbow.
Gasket
VERTICAL FLUEING
Fig. 30
Flue Trim
Fig. 29
Fig. 33
op
PCB g/y
w g br
b bk r w
r
gy r br b y bk
gy r Flow
Electrical
Overheat
Filter
g/y g/y Thermostat
br g/y Gas
Flow g/y Valve
Thermistor b w Flame
CH 325 Vdc
Flow Detection Spark
DC Fan bk
Switch Electrode Electrode
bk
L N Optional
Pump
Feed
Fan g/y
Overheat Condensate
Thermostat Trap
b - Blue r - Red
bk - Black g - Green
w - White g/y- Green/Yellow
br - Brown op - Opaque
gy - Grey y - Yellow
L
N Optional
Flow
Pump
Thermistor
Feed
g/y
r
g/y b
r br
CH
Flow Switch Electrical
y
Filter
br g/y
Spark
b Electrode
gy Flame
Detection
gy Electrode
br
Main g/y
PCB
w
Layout of PCB Pins
op Condensate Trap
w
br g
r bk
b
Gas Valve
w r
g/y bk
bk Fan Overheat
Thermostat
Fan bk
Flow Overheat
Thermostat
Wiring Key
b - Blue
bk - Black
br - Brown
r - Red
w - White
g/y - Green/Yellow
g - Green
gy - Grey
op - Opaque
y - Yellow
30 © Baxi Heating UK Ltd 2006
10.0 Commissioning the Boiler
8. With the system cold and all controls calling for heat
check the gas pressure at the inlet tapping of the gas valve
(Fig. 36). The pressure must be a minimum of 18.1 mbar
(Working Pressure). Check that the gas rate is no greater
than quoted in Section 4.0 Technical Data.
Fig. 36
Inlet Gas Pressure Test Point
Spark 6. Release the four 1/4 turn screws securing the air box
Sleeve door panel and remove the door (Fig. 39).
Sensing
7. Disconnect the leads from the centre and right hand
Fig. 40
terminals (earth and flame sensing probe) (Fig. 40).
Earth
Reconnect in reverse order.
a) Burner.
b) Heat exchanger fins.
c) Fan compartment (Check also for condensate leaks).
d) Insulation.
e) Door seals-Important: Pay particular attention to
the condition of the combustion box door seals.
f) Electrodes.
Fig. 41 g) The condensate trap.
Combustion Box
NOTE: Remove the trap drain plug and place a vessel
Door Panel
underneath to catch the condensate (care should be
taken as this could be hot). Clean the trap and refit
the drain plug. Check for leaks.
h) Top of heat exchanger.
Injector Pipe e) Remove the gas injector pipe from the gas valve
(push-fit) (Fig. 42).
Combustion Box Base 12. Complete the relevant Service Interval Record
Securing Screws
Burner Securing section of the Benchmark Commissioning Checklist at
Screws Fig. 44 the rear of this publication and then hand it back to the
user.
34 © Baxi Heating UK Ltd 2006
13.0 Changing Components
Safety
Thermostat The thermistor, safety thermostat, interface PCB and
the flow switch can be accessed after removal of the
outer case.
Fig. 46
13.2 Flow Temperature Thermistor and
Safety Thermostat (Fig. 46)
Support Bracket 3. Remove the clip securing the flow pipe to the
flowswitch.
Fig. 47
Clip
1. Pull the control knob off the spindle and remove the
Plastic plastic button cover. Refit them onto the new PCB
Button (Fig. 48).
Cover
Hinge down
PCB Housing
Injector Pipe 5. If changing the fan remove the screws securing the
Injector venturi and fan protection sensor bracket, noting the
Screw Opening positions of the injector opening and sensor bracket, fix
them to the new fan.
Gasket
Fan
6. Fit the new fan and reassemble in reverse order.
Fig. 52
Electrical Connection
Wing Nuts
Case Pressure Pipe 4. Disconnect the electrical plug from the gas valve.
Combustion Box
The burner and heat exchanger can be changed after
Door Panel
removal of the combustion box door. To change the
heat exchanger, the fan and burner must be removed
first (see section 13.6 and 13.10).
Fig. 55
1. Remove the two screws securing the burner to the
Support base of the combustion box.
Bracket Return
Burner
Connection
2. Remove the burner carefully from the combustion
box base.
Heat Exchanger
Assembly
Fig. 59
40 © Baxi Heating UK Ltd 2006
13.0 Changing Components
Lower Insulation
Pad Fig. 60 13.13 Heat Exchanger Upper Insulation Pad
(Fig. 60)
Burner
1. Remove all components in the base of the airbox.
Combustion
3. Remove the heat exchanger (see section 13.11).
Box Base
A B C
Key G.C. Description Manufacturers
No. No. Part No.
D PCB 5110991
E Fan 5109925
E
F Gas Valve 241900
L
42 © Baxi Heating UK Ltd 2006
High
15.0 Fault Finding
Reset
Lockout Boiler On Mains On General Fault Finding should only be carried out by
LED Light LED Light LED Light someone who is appropriately qualified.
(Red) (Green) (Green)
Lights
Off Off Off Go to Electrical Supply
YES
section of the fault finding
instructions. Lights
ON
On Flash On YES Go to Thermistor section
of the fault finding
instructions.
ON
Lights
On Off Flash Live & Neutral Reversed
YES
Incoming Live and Neutral
Low Electrical Supply
reversed. Lights
ON Incoming Voltage less than
Flash Off Flash YES 180V. Check System
Controls & System Wiring.
ON Otherwise contact Electricity
Lights
Go to Dry-Fire Provider.
On Flash Flash
YES
section of the fault finding
instructions.
ON Lights
LV Wiring Harness Ensure 8-
On On On YES way PCB connector securely
pushed in. If fault persists
Lights ON replace LV wiring harness.
On Off On YES Go to Ignition Lockout section
of the fault finding instructions.
ON Lights
Flash On Flash YES PCB Fault
Replace PCB.
Lights ON
Flash Off On Go to Overheat Lockout
YES
section of the fault finding
instructions.
ON Lights
On On Flash YES PCB Fault
Replace PCB.
Lights ON
Flash Flash On Go to Fan Lockout
YES
section of the fault finding
instructions.
ON Lights
Flash On On YES PCB Fault
Replace PCB.
ON
ON
No Switched Live to
NO boiler. Check Systems
240V at A ?
Controls and System
Wiring.
YES
NO A
Check wiring from
240V at B ?
terminal block to PCB.
YES
L N Optional
Pump
Live
Check for shorts on
NO
pump, fan & gas valve.
PCB fuse OK ?
Replace if shorted &
replace fuse.
YES
Replace PCB.
B
Fuse
ON
Are NO
Flow & Return reversed ? Swop Flow & Return.
Is the NO
Fill system with water and
system full of water ?
bleed out all air.
L N Optional
Pump Replace PCB.
Live
YES
YES
Turn Turn
NO NO mains off, unplug
Is the mains off & on. After 5 sec, is 7-way connector to PCB.
pump running ? there 240V Is there continuity between
F and G ?
at E?
YES NO
Unplug
5-way PCB
YES
connector. Is there continuity
Replace PCB.
between H (run pump from
switched live) ?
H
G
Viewed from
Wire Entry end
NO
7-way Connector
F
Disconnect YES
Flow Switch Inline
connector. With pump running is
Wires from inline
there continuity across flow connector to PCB faulty.
switch ?
L N Optional
NO Pump
Live
Remove NO
flow switch from boiler. Is there a NO
Is there a physical blockage to blockage in the system ? Replace Flow Switch.
the paddle within the
flow switch ?
YES YES
ON
I
NO
Check isolation valve and
Is there gas at gas valve inlet
gas supply. J
?
5-way Connector
YES
Remove
Reset Lockout. NO 5-way connector YES
Is there gas flow from gas valve. Is there 240 Replace Gas Valve.
(check at meter) ? Vdc between I & J
during ignition ?
YES NO
Remove
the larger or the
Is NO Lead from PCB to Gas
Remove Gas Valve & check two 6-way PCB connectors.
there at least NO Is there continuity from I to L
inlet filter for blockage. Valve faulty.
18mbar dynamic at gas valve Otherwise incorrect gas supply & from J to K ?
inlet ? to boiler.
YES
Replace PCB.
YES
Is
Condensate Trap
YES
Clear blockage and dry
blocked or water on sensors. K
terminals ?
L
NO
6-way Connector
Is
YES Replace spark or flame
spark or flame detection detection probe and
probe damaged ? gaskets.
NO
Is NO
spark gap between 3 and Set spark gap to 3.5mm.
4mm ?
YES
Is
wiring from PCB YES Is the NO
to spark probe & flame burner blocked or Replace PCB.
detection probe OK ? damaged ?
NO YES
ON
Disconnect
NO
black stat on flow pipe.
When flow < 60° C is there Replace Stat.
continuity across stat ?
YES
Reconnect stat. NO
Disconnect fan stat.
When fan temp < 60° C Replace Stat.
is there continuity
across stat ?
YES
Reconnect stat.
NO M
Disconnect the larger of Wiring from PCB to
the 6-way PCB connectors.
thermostats faulty.
Is there continuity
across M ?
Disconnect
thermistor NO
(red sensor on flow pipe). Replace thermistor.
Is resistance between
0.5kΩ & 20kΩ ?
YES
Is
combustion chamber YES Replace combustion
door seal damaged or not in chamber door seal & trim
seal.
place ?
NO
Replace PCB.
Fan PCB
Connection Connection
Unplug
3-way PCB connector NO
N O
& unplug fan. Is there Rectify wiring.
continuity from N to O &
Q
from P to Q ?
P
YES
Fan PCB
Connection Connection
Unplug
the smaller of the NO
6-way PCB connector. Is there
Rectify wiring.
continuity from R to S & from T
R
to U & from
T S
V to W ? V U
W
YES
Viewed from
Wire Entry end
Replace fan.
ON
Unplug
thermistor, NO
Is thermistor resistance between Replace thermistor.
0.5kΩ & 20kΩ ?
D
YES
Plug in
thermistor, leave NO
8-way connector unplugged. Wiring from PCB to
Is resistance at D between thermistor faulty. Viewed from
0.5kΩ & 20kΩ ? Wire Entry end
YES
Replace PCB.
COLLECTIVE MARK
GAS BOILER COMMISSIONING CHECKLIST
BOILER SERIAL No. NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/STAT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER COMBI BOILER
HEATING ZONE VALVES FITTED NOT REQUIRED
HOT WATER ZONE VALVES FITTED NOT REQUIRED
THERMOSTATIC RADIATOR VALVES FITTED
AUTOMATIC BYPASS TO SYSTEM FITTED NOT REQUIRED
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SIGNATURE SIGNATURE
SIGNATURE SIGNATURE
SIGNATURE SIGNATURE
SIGNATURE SIGNATURE
SIGNATURE SIGNATURE
51
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained in
this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
BAXI
A Tr a din g D i v i s i o n of B a x i Heat i ng U K Lt d
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 08700 60 30 60 Technical Enquiries 08706 049 049
Website www.baxi.co.uk
e&oe