Download as pdf or txt
Download as pdf or txt
You are on page 1of 38

SIEMENS

DESIGN INSTRUCTION SHEET


FOR 132/33kV TRAFO CONTROL PANEL - 1TCP
QT CORRECTED

CLIENT : APTRANSCO

SUBSTATION : APTRANSCO

LOI No : CE/Const/P& MM/E.32/PMM32-e-2(a)/2015/Lot-I/D.No.500/


2015,dt:20.06.2015

PROJECT: SUPPLY OF 132/33kV TRANSFORMER PANEL

DESIGN INSTRUCTION SHEET FOR


TITLE: 132/33kV TRAFO CONTROL PANEL
B 17.11.15 VA VA MS QT CORRECTED
A 10.07.15 MRG MRG MS AS PER CUST. DISCUSSION
SCALE SHEET REV.
0 29.06.15 VA VA MS FIRST SUBMISSION
Rev Date Prepared Checked Approved Revision
NTS B
2 3 4
P_Max Dimensions'!A11 2 3 4 5 6 7 8

Sr.No Description Feature Required details

1 Panel Construction
A A
a) Type of Panel Simplex
b) Type of Construction Fixed Front
c) Front Door Not Applicable
d) Rear Door Single Leaf door (up to 900mm W panel) up to IP54
e) Type of sheet steel All CRCA sheets
f) Unused cutouts All unused cutouts on fixed frame/U plates shall be covered with blanking plate
g) Dimensions of panel 1.Panel Width in mm 800
2.Total Height (incl Ant Pad and Base frame) in mm 2250
3.Panel Depth in mm 800
4.Anti-vibration Pad thickness in mm 15
B B
5.Base frame height in mm 50
h) Type of Locking Built in locking facility
i) Type of Hinges Concealed
j) Degree of Protection IP54
k) Sheet steel thickness 1.Equipment Holding sheets/Load bearing Columns in mm 3
2.Side/Rear/Top/Bottom cover in mm 2
3.Gland Plate in mm 3
4. Doors in mm 2
5. Base Frame in mm 3
l) Cable entry Bottom
C C
m) Type of gaskets Neoprene
n) Special Instructions

2 Painting
a) Colour 1.External Colour Shade Shade 631 of IS5
2.Internal Colour Shade White (RAL9003)
D 3.External Finish Structure Semi Glossy D
4.Internal Finish Structure Semi Glossy
5.Base Frame External Colour shade Black
b) Thickness of paint Average for Powder Coating 80 -100 Microns
c) Type of painting Powder Coating
d) Phospating Sheet steel shall be phosphated in accordance with IS 6005
e) Special instruction Small quantity of paint shall be supplied for minor touchup work required at site.

APPD MS CLIENT: APTRANSCO SALES REF: 3004397398 FILE:


CONTACTOR: --
B QT CORRECTED
17.11.15 VA CHKD VA FG9DC100
CIRCUIT: 132/33kV TRAFO. CONTROL PANEL Design Instruction Sheet
A CUST.DISCUS10.07.15 MRG PREP VA PROJECT: SUPPLY OF 132/33KV TRAFO CRP PANEL Sheet 1+
DRG REF: (4)-G719EA-FG9117-DC100
Ver. Remark Date Name Norm 29.06.15 Orig./Repl.f/Replby CONT:02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sr.No Description Feature Required details

3 Mimic Details
A A
a) Type Paint
b) Bus Width in mm 10
c) Branch Width in mm 7
d) Thickness in mm Not applicable
e) Colour Earth Symbol Black
400kV
220kV
132kV / 110kV French Blue (Shade 166 of IS5)
66kV B
33kV / 22kV Olive Green (shade 220 of IS5)
B
f) Special instruction

4 Name Plate Details


a) General instruction All equipment in front side and rear side and inside the panel shall be provided with individual name plate/Yellow
Sticker with equipment designation
b) Type/Colour of External name plate Black color Anodized Aluminium with White engravings .
c) Type/Colour of Internal name plate Yellow sticker with black colour lettering
d) Panel Name Plate Black color Anodized Aluminium with White engravings .
C C
e) Project Detail Name plate Black color Anodized Aluminium with White engravings .
f) Special Instruction

5 Panel wirirng
a) Inter Panel Wiring Interpanel wiring to be done through Bus wire Slots. Gaskets to be provided to bus wire slots
b) Type of wires 1100V grade Multistrands HRPVC
D c) Size of wires 1.For DC/230V AC Control circuits 1.5 Sqmm D
2.For CT circuits 2.5 Sqmm
3. For 110V PT Circuits 2.5 Sqmm
4. For Incoming AC/DC supply Circuits 1.5 Sqmm
5. Earthing Wires 2.5 Sqmm
6. For Automation signals : Not Applicable
d) Ferrules Printed Tubular ferrules as indicated in schemeatic drg
Ferrules shall fix tightly and shall not fall when wires are disconnected from terminal blocks.

APPD MS CLIENT: APTRANSCO SALES REF: 3004397398 FILE:


CONTACTOR: --
B QT CORRECTED
17.11.15 VA CHKD VA FG9DC100
CIRCUIT: 132/33kV TRAFO. CONTROL PANEL Design Instrction Sheet
A CUST.DISCUS10.07.15 MRG PREP VA PROJECT: SUPPLY OF 132/33KV TRAFO CRP PANEL Sheet 2+
DRG REF: (4)-G719EA-FG9117-DC100
Ver. Remark Date Name Norm 29.06.15 Orig./Repl.f/Replby CONT:03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sr.No Description Feature Required details

e) Termination Crimping for all the conductors for AC / DC/CT/PT circuits.


A A
Signal cables like RS232/485 etc to be screened cable which can be soldered.
f) Earthing wires All doors, gland plates and metallic parts shall be earthed.
g) Colour of Wires Current and Voltage Circuits Red,Yellow,Blue
CT / PT Neutral connection Black
AC control/ heater / lighting circiut White
DC Control circuits Grey
Signal / Automation cables : Black
Earth Wires Green
h) Special Instruction Black printed on white tubular ferrule , All wires associated with tripping ckts to be provided with 'T' marked red
B B
coloured ferrules. Insulated Sleeves to be provided at wire terminations

6 Terminal Blocks
a) Make Connectwell Melamine type
b) Grade 1100V / 10 A continuous
c) Type of Terminal blocks CT / PT Circuits Disconnecting Stud Type
AC & DC Control / Auxiliary circuits Non Disconnecting Stud Type
d) Spare Terminal Blocks 20% spare terminals in each panel with uniform distribution of all terminal blocks.
C C
e) Size of Terminal Blocks CT / PT Cicuits Suitable for 2*4 sqmm
DC & AC incoming Supply circuits. Suitable for 2*6 sqmm
DC & AC Auxiliary/Control Circuits Suitable for 2*1.5 sqmm
Automation : Digital / Analog signals --
f) Height of mounting of TBs Shall be atleast 250 mm above incoming cable gland plate.(wherever possible)
g) Distance between TB Channels More than 150 mm (Wherever possible)
h) Special instruction Transperant cover shall be provided for TB'S .TB's Type :CAT IV.

D D

7 Earthing and Earth Bus


a) Material Tinned Copper with threaded holes at a gap of 50mm with nut & bolt provision
b) Size 25 X 3 mm
c) Connection between panels Several panel mounted adjoining each other, the earth bus shall be made continuous and shall be connected to
main earth grid at both ends. Suitable stud/holes shall be left at each end of the bar.
d) Special Instructions All Equipments are to be connected to earth bus with individual wires. No looping of earthing wires is allowed.
Door and gland plate earthing to be done with 4 sqmm braded Cu wire

APPD MS CLIENT: APTRANSCO SALES REF: 3004397398 FILE:


CONTACTOR: --
B QT CORRECTED
17.11.15 VA CHKD VA FG9DC100
CIRCUIT: 132/33kV TRAFO. CONTROL PANEL Design Instrction Sheet
A CUST.DISCUS10.07.15 MRG PREP VA PROJECT: SUPPLY OF 132/33KV TRAFO CRP PANEL Sheet 3+
DRG REF: (4)-G719EA-FG9117-DC100
Ver. Remark Date Name Norm 29.06.15 Orig./Repl.f/Replby CONT:04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sr.No Description Feature Required details

8 Miscellaneous / Other Instructions


A A
a) Lifting arrangement & fasteners Necessary foundation anchor and foundation bolts and other parts of supporting and fastening of panel shall be
supplied with each panel separately. Lifting arrangement to be provided on top of the panel.

B B

C C

D D

APPD MS CLIENT: APTRANSCO SALES REF: 3004397398 FILE:


CONTACTOR: --
B QT CORRECTED
17.11.15 VA CHKD VA FG9DC100
CIRCUIT: 132/33kV TRAFO. CONTROL PANEL Design Instrction Sheet
A CUST.DISCUS10.07.15 MRG PREP VA PROJECT: SUPPLY OF 132/33KV TRAFO CRP PANEL Sheet 4+
DRG REF: (4)-G719EA-FG9117-DC100
Ver. Remark Date Name Norm 29.06.15 Orig./Repl.f/Replby CONT:-
1 2 3 4 5 6 7 8
SIEMENS
GENERAL ARRANGEMENT, EQUIPMENT LIST,
SCHEMATICS OF 132/33kV TRANSFORMER
CONTROL PANEL -1TCP
QT CORRECTED

CLIENT : APTRANSCO

SUBSTATION : APTRANSCO

LOI No : CE/Const/P& MM/E.32/PMM32-e-2(a)/2015/Lot-I/D.No.500/


2015,dt:20.06.2015

PROJECT: SUPPLY OF 132/33kV TRANSFORMER PANEL

TITLE: 132/33kV TRAFO. CONTROL PANEL


B 17.11.15 VA VA MS QT CORRECTED
A 10.07.15 MRG MRG MS AS PER CUST. DISCUSSION
SCALE SHEET REV.
0 29.06.15 VA VA MS FIRST SUBMISSION
Rev Date Prepared Checked Approved Revision
NTS B
2 3 4
NOTE :
CONTROL PANEL WILL KEPT IN A SEPARATE LOCATION FROM THE RELAY PANEL WITH IN THE CONTROL ROOM
FS1-DCF 2A
SPACE FOR PVC CASING LK1-DCF

X:CP-DC2 FS1-TC1-LV 6A
XCP:AC
X:AC X:DC1 X:DC2 X:CP-DC1 X:TC1-LV X:TC2-LV X:VT-LV XCP:TC1-LV XCP:TC2-LV FS2-TC1-LV 6A

FS1-TC2-LV 6A

1-3 1-3 1-3 1-3 1-3 1-3 1-10 1-10 1-3 1-3 FS2-TC2-LV 6A
1-5
FS1-METER 2A F-AC 10A

HT
SPACE FOR PVC CASING FS2-METER 2A 10A
F-DC1
X:CT-MET FS1-LV-CC 6A
X:ISA-LV X:CB-LV X:SP
6A F-DC2 10A
FS2-LV-CC

FS-LMETR1-M 2A
1-5 1-15 1-20 FS1-CFL 2A
1-20
FS-LMETY1-M 2A
LK1-CFL
FS-LMETB1-M 2A
1-5

FS1-HT 2A
CUSTOMER CABELS LK-LMETN1-M
XB:VT-LV

LK1-HT
FS-LMETR1-C 2A
FS1-PSS 6A
FS-LMETY1-C 2A LK1-PSS
FS-LMETB1-C 2A FS1-ANN. AC 2A
LK-LMETN1-C LK1-ANN. AC
1-4

FS1-IND. 2A
DIODE

FS2-IND. 2A

FSI-ANNUN 2A

FS2-ANNUN 2A

FS1-HV-CC 6A

FS2-HV-CC 6A
1-5

CUSTOMER CABELS FS1-TC1-HV 6A


1-3

FS2-TC1-HV 6A
X:DCS X:CP FS1-TC2-HV 6A
1-3

FS2-TC2-HV 6A
1-20 1-30 FS-HMETR1 2A
1-3
XB:VT-HV XB:DC1 XB:DC2 XB:AC

FS-HMETY1 2A
SPACE FOR PVC CASING
X:ISA-HV FS-HMETB1 2A
X:VT-HV X:TC1-HV X:TC2-HV XCP:TC1-HVXCP:TC2-HV X:CB-HV X:DCS1
LK-HMETN1
LK-T
1-10 1-10 1-3 1-3 1-5 1-15 1-5
1-5 LK-NT

SPACE FOR PVC CASING LK-AT

LK-BZ
1 2 3 4 5

FUN. REF DESCRIPTION SPECIFICATION DIS MAKE TYPE QTY/PANEL

A FA ANNUNCIATOR Supply Voltage :220V DC & 240V AC (STDBY A/C SUPPLY) 3 BHARANI MCAN 1 A
(24 WINDOW) No. of Windows :24, Size of Window : 35x50 mm,4 Row x 6 Column
Trip Facia: Red colour, Non Trip Facia: WHITE colour
With DC failure in last window , AC Failure feature in last before window

A-HV Ammeter for HV Side Model: 72/144 ACI 3 RISHAB Digital 1


CT Ratio : 200-300-500/1A
Size : 72x144mm , 4 1/2 Digit Display , Display Height 25mm,1Ph
Accuracy : 0.5, Aux. Supply : 220V DC
Input: 1A; Scale: (0-200A) (0-300A) (0-500A)
B Multiplication Factor for (0-300A) (0-500A)
B

ASS-HV Ammeter Selector Switch for HV Side 10A ,440 V AC 50HZ, No.Position : 6 3 SWITRON 1
Type : Stayput
Position : OFF-R-Y-B-N-E

V-HV Voltmeter for HV Side Model:72/144 ACV ,PT Ratio :132kV/ 3 / 110V/ 3 3 RISHAB Digital 1
Size : 72x144mm , 4 1/2 Digit Display , Display Height 25mm,1Ph
Accuracy : 0.5, Aux. Supply : 220V DC
Scale: (0-150kV)
C C
VSS-HV Volt meter Selector Switch for HV Side 10A ,440 V AC 50HZ, No.Position : 6 3 SWITRON 1
Type : Stayput
Position : RN-YN-BN-RY-YB-BR

MW-HV MEGA WATT Meter for HV Side Model:Power DPM ,Type : Transducer Driven 3 RISHAB Digital 1
Size : 72x144mm , 4 1/2 Digit Display , Display Height 25mm
Accuracy : 0.5, Aux. Supply : 220V DC
Input : 4 -12- 20mA
Scale : (55-0-55MW) (85-0-85MW) (140-0-140MW)
D D
Multiplication factor for (85-0-85MW) (140-0-140MW)

MVAR-HV MEGA VAR Meter for HV Side Model:Power DPM 3 RISHAB Digital 1
Type : Transducer Driven
Size : 72x144mm , 4 1/2 Digit Display , Display Height 25mm
Accuracy : 0.5, Aux. Supply : 220V DC
Input : 4 -12- 20mA
Scale : (55-0-55MVar) (85-0-85MVar) (140-0-140MVar)
Multiplication factor for (85-0-85MVar) (140-0-140MVar)
E E
PF-HV Power Factor meter for HV Side Model: PF DPM 3 RISHAB Digital 1
CT Ratio : 200-300-500/1A
PT Ratio :132kV/ 3 / 110V/ 3
Type : Digital , 3Ph - 4 wire
Size : 72x144mm , 4 Digit Display , Display Height 25mm
Accuracy : 2 deg, Aux. Supply : 220V DC
Scale : (0.5 Lag - 1.0 - 0.5 Lead )

F FREQUENCY METER Model: 72X144 Hz 3 RISHAB Digital 1


F PT Ratio :132kV/ 3 / 110V/ 3 F
Size : 72x144mm , 4 Digit Display , Display Height 25mm
Accuracy : 0.2% , Aux.supply : 220V DC
Scale : 45 - 55Hz

Dis: 1- W Stock, 2- W Non stock, 3- Boughtouts, 4- Project Supply, 5- Loose Supply


Date 29.06.15 PROJECT: SUPPLY OF 132kV TRANSFORMER PANEL SALES REF: 3004397398
B QT CORRECTED 17.11.15 VA Created VA CLIENT: APTRANSCO REV-A
EQUIPMENT LIST FOR 1TCP
A CUST. DISCUSSION 10.07.15 MRG Appr. MS CIRCUIT:132/33 Kv TRAFO CONTROL PANEL DOC NO: (4)-G719EA-FG9117- Sht 1+
Rev. Remarks Date Name Norm Orig./Repl.f/Replby EC101 6Sh.
1 2 3 4 5

Unrestricted
1 2 3 4 5

FUN. REF DESCRIPTION SPECIFICATION DIS MAKE TYPE QTY/PANEL


A-LV Ammeter for LV Side Model: 72/144 ACI ,CT Ratio : 800-1200-2000/1A 3 RISHAB Digital 1
A Size : 72x144mm , 4 1/2 Digit Display , Display Height 25mm,1Ph A
Accuracy : 0.5, Aux. Supply : 220V DC
Input: 1A; Scale: (0-800A) (0-1200A) (0-2000A)
Multiplication Factor for (0-1200A) (0-2000A)

ASS-LV Ammeter Selector Switch for LV Side 10A ,440 V AC 50HZ, No.Position : 6 3 SWITRON 1
Type : Stayput
Position : OFF-R-Y-B-N-E

V-LV Voltmeter for LV Side Model:72/144 ACV ,PT Ratio :33kV/ 3 / 110V/ 3 3 RISHAB Digital 1
B Size : 72x144mm , 4 1/2 Digit Display , Display Height 25mm
B
Accuracy : 0.5, Aux. Supply : 220V DC
Scale: (0- 45kV)

VSS-LV Volt meter Selector Switch for LV Side 10A ,440 V AC 50HZ, No.Position : 6 3 SWITRON 1
Type : Stayput
Position : RN-YN-BN-RY-YB-BR

TVM-M (MAIN) TRI VECTOR METER FOR LV SIDE MAIN CT Ratio : 800-1200-2000/1A 3 SECURE PREMIURE-300 1
PT Ratio :33kV/ 3 / 110V/ 3
C Class of Accuracy : 0.2s
C
Type : 3Phase, 4Wire, 3Element with ABT feature&MRI compatibility
With Import & Export of KWAH, KVARH
With Optical Port, RS232 or RS485 Port with Modbus protocol

TVM-C (CHECK) TRI VECTOR METER FOR LV SIDE CHECK CT Ratio : 800-1200-2000/1A 3 SECURE PREMIURE-300 1
PT Ratio :33kV/ 3 / 110V/ 3
Class of Accuracy : 0.2s
Type : 3Phase, 4Wire, 3Element with ABT feature&MRI compatibility
With Import & Export of KWAH, KVARH
D D
With Optical Port, RS232 or RS485 Port with Modbus protocol

TTB - M Test terminal Block for LV Side Main Meter 3-Phase, 4 wire, back connected 3 IMP 2
TTB - C Test terminal Block for LV SIde Check Meter Rear connection link type

SCB-HV SEMAPHORE INDICATOR FOR HV - CB AUX SUPPLY: 220V DC 3 DAV NTC-22L 2


SCB-LV SEMAPHORE INDICATOR FOR LV - CB TYPE: NTC-22L
DIA - 63MM

S1 SEMAPHORE INDICATOR FOR 89A-HV AUX SUPPLY: 220V DC 3 DAV NTC-22 2


E E
S2 SEMAPHORE INDICATOR FOR 89A-LV TYPE: NTC-22
DIA - 48MM

CS52-HV Breaker control switch for HV Side 3 Positions , 8 Ways; Rated current: 32A DC 3 SWITRON 2
CS52-LV Breaker control switch for LV Side Spring return to neutral, Pistol grip; Lockable
Pos: Trip-After Trip-Neutral-After Close-Close
Bezel size: 75mmX75mm
(Trip - 3, AT-1, AC-1, Close-2, Neutral - 1)

F PB01 Push button for Annun. Accept 220V DC, Black actuator with plastic front ring and holder 1 SIEMENS 3SB50000AB01 1 F
with 2NO+2NC contact block , Size - 22.5mm DIA +3SB54000A 2

Dis: 1- W Stock, 2- W Non stock, 3- Boughtouts, 4- Project Supply, 5- Loose Supply


Date 29.06.15 PROJECT: SUPPLY OF 132kV TRANSFORMER PANEL SALES REF: 3004397398
B QT CORRECTED 17.11.15 VA Created VA CLIENT: APTRANSCO REV-A
EQUIPMENT LIST FOR 1TCP
A CUST. DISCUSSION 10.07.15 MRG Appr. MS CIRCUIT:132/33 Kv TRAFO CONTROL PANEL DOC NO: (4)-G719EA-FG9117- Sht 2+
Rev. Remarks Date Name Norm Orig./Repl.f/Replby EC101 6Sh.
1 2 3 4 5

Unrestricted
1 2 3 4 5

FUN. REF DESCRIPTION SPECIFICATION DIS MAKE TYPE QTY/PANEL

A PB02 Push button for Annun. Reset 220V DC, Black actuator with plastic front ring and holder 1 SIEMENS 3SB50000AB01 1 A
with 2NO+2NC contact block, Size - 22.5mm DIA +3SB54000A 2

PB03 Push button for Annun. Test 220V DC, Black actuator with plastic front ring and holder 1 SIEMENS 3SB50000AB01 1
with 2NO+2NC contact block ,Size - 22.5mm DIA +3SB54000A 2

PB04 Push button for DC-Fail-1 Test 220V DC, Black actuator with plastic front ring and holder 1 SIEMENS 3SB50000AB01 1
with 2NO+2NC contact block, Size - 22.5mm DIA +3SB54000A 2

PB05 Push button for DC-Fail-2 Test 220V DC, Black actuator with plastic front ring and holder 1 SIEMENS 3SB50000AB01 1
B with 2NO+2NC contact block, Size - 22.5mm DIA +3SB54000A 2
B

PB06 Push button for DC Fail Accept 220V DC, Black actuator with plastic front ring and holder 1 SIEMENS 3SB50000AB01 1
with 2NO+2NC contact block, Size - 22.5mm DIA +3SB54000A 2

SL01 Indicating Lamp for HV CB Open 220V DC, LED type, GREEN indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HE14 1

SL02 Indicating Lamp for HV CB Close 220V DC, LED type, RED indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HC14 1

SL03 Indicating Lamp for HV CB Spring Charge 220V DC, LED type, BLUE indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HF14 1
C C
SL04 Indicating Lamp for HV CB Capacitor Trip 220V DC, LED type, RED indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HC14 1

SL05 Indicating Lamp for LV CB Open 220V DC, LED type, GREEN indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HE14 1

SL06 Indicating Lamp for LV CB Close 220V DC, LED type, RED indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HC14 1

SL07 Indicating Lamp for LV CB Spring Charge 220V DC, LED type, BLUE indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HF14 1

D SL08 Indicating Lamp for LV CB Capacitor Trip 220V DC, LED type, RED indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HC14 1 D

SL09 Indicating Lamp for HV CB TRIP CIRCUIT-1 HEALTHY 220V DC, LED type, White indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HG14 1

SL10 Indicating Lamp for HV CB TRIP CIRCUIT-2 HEALTHY 220V DC, LED type, White indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HG14 1

SL11 Indicating Lamp for LV CB TRIP CIRCUIT-1 HEALTHY 220V DC, LED type, White indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HG14 1

SL12 Indicating Lamp for LV CB TRIP CIRCUIT-2 HEALTHY 220V DC, LED type, White indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HG14 1
E E
SL13 Indicating Lamp for DC-1 Fail 240V AC, LED type, RED indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HC14 1

SL14 Indicating Lamp for DC-2 Fail 240V AC, LED type, RED indicating LED, Size - 22.5mm DIA 1 SIEMENS 3SB52356HC14 1

F F

Dis: 1- W Stock, 2- W Non stock, 3- Boughtouts, 4- Project Supply, 5- Loose Supply


Date 29.06.15 PROJECT: SUPPLY OF 132kV TRANSFORMER PANEL SALES REF: 3004397398
B QT CORRECTED 17.11.15 VA Created VA CLIENT: APTRANSCO REV-A
EQUIPMENT LIST FOR 1TCP
A CUST. DISCUSSION 10.07.15 MRG Appr. MS CIRCUIT:132/33 Kv TRAFO CONTROL PANEL DOC NO: (4)-G719EA-FG9117- Sht 3+
Rev. Remarks Date Name Norm Orig./Repl.f/Replby EC101 6Sh.
1 2 3 4 5

Unrestricted
1 2 3 4 5

FUN. REF DESCRIPTION SPECIFICATION DIS MAKE TYPE QTY/PANEL

195-HV TC-1 supervision relay for HV Model no: 7PJ1321-5AA21-0AA0 1 SIEMENS 7PJ 2
295-HV TC-2 supervision relay for HV Aux. Supply: 220V DC, Contacts: 2C/O SR
Flag: Led Indication, Case:-96X48mm: Mounting-Flush
A A
195-LV TC-1 supervision relay for LV Side Breaker Model no: 7PJ1321-5AA21-0AA0 1 SIEMENS 7PJ 2
295-LV TC-2 supervision relay for LV Side Breaker Aux. Supply: 220V DC, Contacts: 2C/O SR
Flag: Led Indication, Case:-96 x 48mm: Mounting-Flush

52X-HV CONTACT MULTI RELAY - HV BREAKER Model: RXPSU14-1MYN563646-EBA 3 ABB RXPSU14 2


52X-LV CONTACT MULTI RELAY - LV BREAKER Case: 2S 12C
Contacts: 7NO+7NC
Mounting: Flush
Aux supply : 220V DC

89AX-HV CONTACT MULTI RELAY - 89A-HV Model: RXPSU6-1MYN563623-EAF 3 ABB RXPSU6 2


B 89AX-LV CONTACT MULTI RELAY - 89A-LV Case: 2S 12C
B
Contacts: 3NO+3NC
Mounting: Flush
Aux supply : 220V DC

80A DC Supervision relay for DC source -1 Model no:TSR-IN 352-001- AS 3 ABB TSR 2
80B DC Supervision relay for DC source -2 Aux. Supply: 220V DC, Contacts: 2C/O SR
Flag: Led Indication, Case:-2S 6C: Mounting-Flush
C 80C DC Fail Accept relay Model no:RXMA1-RK211052-BS 3 ABB RXMA1 1
C
Aux. Supply: 230V AC with built in Rectifier,
Contacts: 2NO+2NC SR
Flag: No flag, Case:-2S 6C: Mounting-Flush

DCC01 DC change over relay Model no:RXME1-RK221 052-AS 3 ABB RXME1 2


DCC02 Aux. Supply: 220-250V DC, Contacts: 2NO+2NC self reset
Flag. No flag, Case:-2S 6C, Mounting -Flush
D D
30A/30B-HV HV CB TROUBLE RELAY Model: RXSF1-RK 271 018-AS 3 ABB RXSF1 2
30A/30B-LV LV CB TROUBLE RELAY Case: 2S 6C, 2 element
Contacts: 3NO Per element, Self Reset
Flag: Hand reset , Mounting: Flush
Aux supply : 220V DC

FRAME EQUIPMENT FRAME FOR ABB relays RELAY CASE - RHGX20 WITH BASE - 4S 60C 3 ABB 1
WITH DOOR - 1MYN560004-D

E E

F F

Dis: 1- W Stock, 2- W Non stock, 3- Boughtouts, 4- Project Supply, 5- Loose Supply


Date 29.06.15 PROJECT: SUPPLY OF 132kV TRANSFORMER PANEL SALES REF: 3004397398
B QT CORRECTED 17.11.15 VA Created VA CLIENT: APTRANSCO REV-A
EQUIPMENT LIST FOR 1TCP
A CUST. DISCUSSION 10.07.15 MRG Appr. MS CIRCUIT:132/33 Kv TRAFO CONTROL PANEL DOC NO: (4)-G719EA-FG9117- Sht 4+
Rev. Remarks Date Name Norm Orig./Repl.f/Replby EC101 6Sh.
1 2 3 4 5

Unrestricted
1 2 3 4 5

FUN. REF DESCRIPTION SPECIFICATION DIS MAKE TYPE QTY/PANEL

A INTERNALLY MOUNTED EQUIPMENTS A

HT Space Heater 100W,240V AC 1 APT control 1

HTS Heater ON /OFF Switech 15 A , 240V AC 1 Anchor 1

Ps andPSS Power Socket with ON/OFF switch 5/15A, 3Pin, 240V AC 1 Anchor 1

TH Thermostat 30-90 deg cent 1 APT Control 1


B CILS Cubicle door operated switch Limit Switch(1No+2NC) -3SE30230A 1 SIEMENS 1
B

CFL Compact Flourescent Lamp 240 V AC, 18W 1 Philips 1

F-DC-1 DCMCB - DOUBLE POLE 10A, 220V DC with 1NO+1NC aux contact 1 SIEMENS 2
F-DC-2 with Aux contact MLFB NO: 5SY52107+5ST3010

F-AC ACMCB - SINGLE POLE WITH NEUTRAL 10A, 240V AC with 1NO+1NC aux contact 1 SIEMENS 1
with Aux contact MLFB NO: 5SL42107RC+5ST3010
C C

TD-MW-HV Programmable Type Active Power Transducer Model: Rish ConP W/o display 3 RISHAB 1
for HV Side Active Power Transducer (DIN series)
3PH 4Wire 3 ELEMENT
Aux. Supply : 220V DC
O/P: 4-12-20mA, DUAL OUTPUT
CT Ratio : 200-300-500/1A
PT Ratio :132kV/ 3 / 110V/ 3
Class of Accuracy : 0.5
D D
Scale : (55-0-55MW) (85-0-85MW) (140-0-140MW)

TD-MVAR-HV Programmable Type Reactive Power Transducer Model: Rish ConP W/o display 3 RISHAB 1
for LV Side Reactive Power Transducer (DIN series)
3PH 4Wire 3 ELEMENT
Aux. Supply : 220V DC
O/P: 4-12-20mA, DUAL OUTPUT
CT Ratio : 200-300-500/1A
PT Ratio :132kV/ 3 / 110V/ 3
Class of Accuracy : 0.5
E E
Scale : (55-0-55MVar) (85-0-85MVar) (140-0-140MVar)

F F

Dis: 1- W Stock, 2- W Non stock, 3- Boughtouts, 4- Project Supply, 5- Loose Supply


Date 29.06.15 PROJECT: SUPPLY OF 132kV TRANSFORMER PANEL SALES REF: 3004397398
B QT CORRECTED 17.11.15 VA Created VA CLIENT: APTRANSCO REV-A
EQUIPMENT LIST FOR 1TCP
A CUST. DISCUSSION 10.07.15 MRG Appr. MS CIRCUIT:132/33 Kv TRAFO CONTROL PANEL DOC NO: (4)-G719EA-FG9117- Sht 5+
Rev. Remarks Date Name Norm Orig./Repl.f/Replby EC101 6Sh.
1 2 3 4 5

Unrestricted
1 2 3 4 5

FUN. REF DESCRIPTION SPECIFICATION DIS MAKE TYPE QTY/PANEL

A INTERNALLY MOUNTED EQUIPMENTS A

D1-D4 DIODE VOLTAGE: 220V DC; IN4007,1A 3 CONNECTWELL CDL4UED3 4

EBZ AC BUZZER FOR DC FAIL INDICATION Type : Electronic , Multi tone, Aux. Supply : 240V AC 3 ALAN 1

EH DC HOOTER FOR NON TRIP ALARM Type : Electronic , Multi tone, Aux. Supply : 220V DC 3 ALAN 1

EB DC BELL FOR TRIP ALARM Type : Electronic , Multi tone, Aux. Supply : 220V DC 3 ALAN 1
B B

GLAND CABLE GLAND SINGLE COMPRESSION TYPE Size : 3/4" (19mm) Dia 3 DOWELLS 25

Size : 1" (25mm) Dia 3 DOWELLS 6

TB TERMINAL BLOCKS 1100V ,10A , TYPE : CAT - IV


DISCONNECTING TYPE - STUD - SCREW DRIVER OPERATED 3 CONNECTWEEL AS REQUIRED
NON DISCONNECTING TYPE - STUD - SCREW DRIVER OPERATED
C C

FUSE HOLDER+ 6A 1 SIEMENS HRC 13


FUSE 3NW20NNSF+3NWNS6

FUSE HOLDER+ 2A 1 SIEMENS HRC 19


FUSE 3NW20NNSF+3NWNS2

LINK HOLDER + 3NW20NNSF+3NWNNSL 1 SIEMENS 12


D D

E E

F F

Dis: 1- W Stock, 2- W Non stock, 3- Boughtouts, 4- Project Supply, 5- Loose Supply


Date 29.06.15 PROJECT: SUPPLY OF 132kV TRANSFORMER PANEL SALES REF: 3004397398
B QT CORRECTED 17.11.15 VA Created VA CLIENT: APTRANSCO REV-A
EQUIPMENT LIST FOR 1TCP
A CUST. DISCUSSION 10.07.15 MRG Appr. MS CIRCUIT:132/33 Kv TRAFO CONTROL PANEL DOC NO: (4)-G719EA-FG9117- Sht 6-
Rev. Remarks Date Name Norm Orig./Repl.f/Replby EC101 6Sh.
1 2 3 4 5

Unrestricted
TRAFO 3-PH TRIP RELAY-86-HV

TRAFO INTER TRIP RELAY-86IN

TRAFO 3-PH TRIP RELAY-86-LV

FREQUENCY TRIP RELAY-81

TC-1 OF 132KV TRAFO CB

TC-2 OF 132KV TRAFO CB

TO OLTC INTERLOCKING
LBB TRIP RELAY - 86-LBB

TC-1 OF 33KV TRAFO CB

TC-2 OF 33KV TRAFO CB

TO TRIP 33KV FEEDER


LBB INITIATION
DEVICE NO DESCRIPTION TYPE

87T MAIN DIFFERENTIAL PROTN 7SR242 X


67RYBN-HV DIR.O/C & E/F PROTN-HV 7SR22 X X
50LBB-HV LBB PROTN. FOR HV SIDE INBUILT-67RYBN-HV X
50/51RYBN-LV NON,DIR. O/C & E/F PROTN-LV 7SR21 X
99-HV OVER FLUX PROTN-HV 7RW8 X
81U/81R-LV UNDER FREQUENCY PROTN-LV 7SJ80
27-LV UNDER VOLTAGE PROTN-LV INBUILT-81U/81R-LV
30A WTI-HV TRIP RXSF1 X
30B OTI TRIP RXSF1 X
30C PRV TRIP RXSF1 X
30D BUCH TRIP RXSF1 X
30E OLTC BUCH TRIP RXSF1 X
30F WTI-LV TRIP RXSF1 X
86-HV TRAFO 3-PH TRIP RELAY-86-HV RXMVB2 X
86-IN TRAFO INTER TRIP RELAY-86IN RXMVB4 X
86-LBB LBB TRIP RELAY FOR HV SIDE RXMVB4 X
86-LV TRAFO 3-PH TRIP RELAY-86-LV RXMVB2 X
86-81 FREQUENCY TRIP RELAY-81 RXMVB4
SIEMENS 132/33kV APTRANSCO-CONTROL PANEL 132kVTRAFO

X:DCS WIRE NO. SHEET X:CT-MET WIRE NO. SHEET X:SP WIRE NO. SHT NO. XCP:TC1-HV WIRE NO. SHT NO. XCP:TC2-HV WIRE NO. SHT NO.
1 S1 1 D11 1 U1 1 1K21 1 1K51
11 12
2 S2 2 D79 2 U2 2 1K23 2 1K53
3 S3 3 D31 3 U3 3 SPARE 3 SPARE
4 S4 4 D79 4 U4
14 8 14
5 S5 5 D51 5 U5
6 S6 6 D79 6 U6
7 S7 7 D71 7 U7 XCP:TC1-LV WIRE NO. SHT NO. XCP:TC2-LV WIRE NO. SHT NO.
8 S8 8 D79 8 U8 1 2K21 1 2K51
12 12
9 S9 9 D21 9 U9 2 2K23 2 2K53
10 S10 10 D89 10 U10 3 SPARE 3 SPARE
11 S11 11 D41 11 U11
12 S12 12 D89 12 U12
15 9 15
13 S13 13 D61 13 U13
14 S14 14 D89 14 U14
15 S15 15 D81 15 U15
16 S16 16 D89 16 U16 X:CB-HV WIRE NO. SHEET X:CB-LV WIRE NO. SHEET
17 SPARE 17 SPARE 17 SPARE 1 1K1 1 2K1
18 SPARE 18 SPARE 18 SPARE 2 1K2 2 2K2
13 13
19 SPARE 19 SPARE 19 SPARE 3 1K1R 3 2K1R
20 SPARE 20 SPARE 20 SPARE 4 1K15 4 2K15
5 L1 5 L1
6 L35 14 6 L39 14
7 L37 7 L41
8 L1 8 L1
9 L11 16 9 L27 16
X:DC1 WIRE NO. SHEET XB:DC1 WIRE NO. SHEET X:DCS1 WIRE NO. SHEET 10 L17 10 L33
1 J101 1 J101 1 1S101 11 L101 11 L101
6 6
2 J102 2 J102 2 1S102 12 L171 19 12 L175 19
8
3 SPARE 3 SPARE 3 1S103 13 L173 13 L177
4 1S104 14 SPARE 14 SPARE
5 SPARE 15 SPARE 15 SPARE

X:DC2 WIRE NO. SHEET XB:DC2 WIRE NO. SHEET X:ISA-HV WIRE NO. SHEET X:VT-HV WIRE NO. SHEET XB:VT-HV WIRE NO. SHEET
1 J201 1 J101 1 L1 1 E11 1 E11
6 6
2 J202 2 J102 2 L43 15 2 E31 2 E31
5 5
3 SPARE 3 SPARE 3 L45 3 E51 3 E51
4 SPARE 4 E71 4 E71
5 SPARE 5 SPARE 5 SPARE

X:AC WIRE NO. SHEET XB:AC WIRE NO. SHEET X:ISA-LV WIRE NO. SHEET X:VT-LV WIRE NO. SHEET XB:VT-LV WIRE NO. SHEET
1 H1 1 H1 1 L1 1 E111 1 E111
7 7
2 H2 2 H2 2 L47 15 2 E131 2 E131
5 5
3 SPARE 3 SPARE 3 L49 3 E151 3 E151
4 SPARE 4 E171 4 E171
5 SPARE 5 SPARE 5 SPARE
Client: APTRANSCO
Appd By : MS
Checked: VA
Prep: DD
Date: 17.11.15
QT CORRECTED Description:-TB list Sales Ref: 3004397398
Page 1 of 2 Drg no:(4)G719EA-EG9117-TC101
SIEMENS 132/33kV APTRANSCO-CONTROL PANEL 132kVTRAFO

X:TC1-HV WIRE NO. SHT NO. X:TC2-HV WIRE NO. SHT NO. X:CP-DC1 WIRE NO. SHEET X:CP-DC2 WIRE NO. SHEET
1 1K21 1 1K51 1 J103A 1 J203A
6 6
2 1K22 2 1K52 2 J104A 2 J204A
3 1K23 11 3 1K53 11 3 SPARE 3 SPARE
4 1K29 4 1K59
5 1K27 5 1K57
6 1K21R 6 1K51R
13 13
7 1K25 7 1K55
8 SPARE 8 SPARE
9 SPARE 9 SPARE
10 SPARE 10 SPARE

X:TC1-LV WIRE NO. SHT NO. X:TC2-LV WIRE NO. SHT NO. XCP:AC WIRE NO. SHEET X:CP WIRE NO. SHEET
1 2K21 1 2K51 1 H3 1 1K1R
7
2 2K22 2 2K52 2 H4 2 1K7
13
3 2K23 12 3 2K53 12 3 SPARE 3 2K1R
4 2K29 4 2K59 4 2K9
5 2K27 5 2K57 5 L121
6 2K21R 6 2K51R 6 L123
13 13
7 2K25 7 2K55 7 L125
8 SPARE 8 SPARE 8 L127
9 SPARE 9 SPARE 9 L129
17
10 SPARE 10 SPARE 10 L131
11 L133
12 L135
13 L137
14 L149
15 L153
16 L155
17 L157
18 L159 18
19 L161
20 L163
21 L165
22 K101
19
23 K117
24 SPARE
25 SPARE
26 SPARE
27 SPARE
28 SPARE
29 SPARE
30 SPARE

Client: APTRANSCO
Appd By : MS
Checked: VA
Prep: DD
Date: 17.11.15
QT CORRECTED Description:-TB list Sales Ref: 3004397398
Page 2 of 2 Drg no:(4)G719EA-EG9117-TC101