Protection and Control

Universal earth leakage Technical features


current monitoring (type B) Monitoring Class
Sensitivity, IΔn
B (IEC 60755)
0.1 … 3 A

RGU-10B
Delay, t Δ 0.1 … 10 s
Earth leakage transformer External, WGC TB series

Preventive control Test and Reset


Remote control
Using buttons T and R
Remote Test and Reset

Electronic earth leakage


ready
Control of the display/con- With 2 switched output
trol element relays, NO/NC
Electrical Auxiliary power supply 230 Vac ±20% 50/60 Hz, protection and monitoring relay
Easy leakage diagnostics features 6 VA
Output contacts
Operating temperature
250 Vac, 6 A
-10...+50 ºC
Type B
Mechanical Attachment DIN Rail 46277 (EN 50022)
features Dimensions
Weight
3 modules
256 g
Full protection and monitoring
Protection degree IP 20 terminals,
IP 41 cross-grid within your reach
Standards IEC 62020, IEC 60755
Application
For monitoring and controlling:
References
Type Code Sensitivity, I∆N Delay, t Δ

RGU-10B P11951 0.03 ... 3 A 0.1 s ... 10 s

Computer units (UPS)


Associated Transformers
Type Code Useful section I∆n minimum Weight (g)
WGS-20-TB P11731 Ø 20 mm 0,1 80
WGC-25-TB P11751 Ø 25 mm 0,1 86
WGC-35-TB P11752 Ø 35 mm 0,1 126
WGC-55-TB P11753 Ø 55 mm 0,3 180
WGC-80-TB P11755 Ø 80 mm 0,5 321
Speed drives WGC-110-TB P11756 Ø 110 mm 0,5 440
WGC-140-TB P11757 Ø 140 mm 0,5 790
WGC-180-TB P11758 Ø 180 mm 0,5 1530

www. circutor. com


CIRCUTOR, SA - Vial Sant Jordi, s/n
08232 Viladecavalls (Barcelona) Spain
Tel. (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14
Photovoltaic installations central@circutor.es

Technology for energy efficiency

Designed by: communication dept.. - CIRCUTOR, SA. Code: C2P1C3-01


Electronic earth leakage monitoring Preventive maintenance Full range of earth
relay for type B applications Alarm or prealarm relay for indicating events leakage transformers

RCM. Universal earth leakage (IEC 62020) monitor (AC, DC


AC/DC) with LCD screen that displays instantaneous leakage
current with a WGC-TB earth leakage transformer. Enables the
possibility of remote signaling with outputs by potential free
contacts. Correct Prealarm Alarm

Prevents possible earth leakage protection triggers in any


installation that may have important current leakages with a DC √ Sinusoidal currents
component IEC 60755). Apt for single-phase or three-phase Typ e B u n ive rs a l √ Rectified currents
installations with or without a neutral. Apt for AC , DC an d AC /DC installations √ Frequencies up to 1 kHz

Programmable External Test/Reset


Programmable relay for: Connection/Disconnection
Sensitivity: 30 mA ... 3 A capacity by external input
Delay: 0.1 s ... 10 s

Only 3 modules
Saves space in the electric panel with
its reduced size. Assembly on DIN Rail.

*Depending on the transformer

RCM* Audible and visual Speed


Monitoring alarm signaling drives
Earth leakage

Correct Instantaneous display 50-100% I∆N I∆N Motors


LCD display that enables quick Prealarm Alarm
viewing of the mean leakage current. *Residual Current
Incorporates illuminated status Monitoring./ Residual
current or small
Alarm change for instantaneous detection current monitor. Standard
of the status of the installation. IEC 62020, IEC 60755