Professional Documents
Culture Documents
Assignment 1
Assignment 1
Problem#1:
The phase voltage of a balanced three-phase star connected generator is VRN = 120∠− 40°
V. The generator is energizing a balanced three-phase STAR connected load with load
impedance of Z = 20∠30° Ω in each phase.
Task 1:
Draw the three-phase circuit diagram.
IRN
+ IRN +
~
- VRY -
N N
-
-
- -
+
~ ~ +
+ +
B Y B IBN Y
IBN IYN IYN
IY
VBR
VYB
B phase of transmission line
IB
Very Important Note: VRY, VYB and VBR across the generator terminals are the same as VRY,
VYB and VBR across the load terminals BECAUSE transmission line impedance is neglected!
Task 2:
• Compute all load currents. (Note: By load current is meant the current flowing
through each phase of the load.)
The current flowing through a component can be obtained by using Ohm’s law, upon
knowing the impedance of the component and the voltage applied across the component.
Hence, it is very important to be able to visually identify (from the three-phase circuit
diagram) which voltage (is it R-phase voltage? Y-phase voltage? B-phase voltage? R-Y line
voltage? Y-B line voltage? B-R line voltage?) from the generator/input source gets applied
across the load in a given phase of the three-phase load.
Current flowing through load in the R-phase: (Note: Both magnitude and phase angle of
the current, i.e., complex value, need to be calculated.)
Impedance (complex value, i.e., both magnitude and phase angle) in the R-phase of the
load = ZRN = 20∠30° Ω
Complex voltage applied across the R-phase of the load = Complex voltage in the R-phase
of the generator = VRN = 120∠− 40° V
VRN
According to Ohm’s Law, complex current in the R-phase of the load = IRN =
ZRN
120 − 400
IRN = = 6 − 700 A
2030 0
The currents flowing through loads in Y and B phases can also be calculated by means of
the phasor relationships of a balanced three-phase system.
IBN
1200
1200
1200
IRN
IYN
From the phasor diagram of three-phase balanced phase-currents of a star connected load
as shown above, we know that:
IYN = IRN * a2 = IRN * (11200 )
2
(OR)
IYN is the same as IRN magnitude-wise, but lags IRN by 1200, i.e.,
IYN = IRN − 1200
IYN = ( 6 − 700 ) − 1200 = (6 − 1900 ) A
Note : (6 − 1900 ) is the same as (61700 )
i.e., a lag of 1900 is the same as lead of 1700.
IBN is the same as IYN magnitude-wise, but lags IYN by 1200, i.e.,
IBN = IYN − 1200
IYN = (6 − 1900 ) − 1200 = (6 − 3100 ) = (6500 ) A
Magnitudes of the line-to-line voltages (or also simply known as line voltages) and the
line-to-neutral voltages (also known as phase voltages) in star connections are related as:
VLine = 3V300 , i.e., the magnitude of a line voltage is 3 times the corresponding phase
voltage, and the line voltage leads the corresponding phase voltage by 300.
1200
1200
1200
VRY
VYB
The impedance angle of the load (i.e., the power factor angle of the load) is given as 300.
The three-phase power relationships are given as below:
P = 3VLineILine cos = 3VRYIR cos = 3VYBIY cos = 3VBRIB cos
Q = 3VLineILine sin = 3VRYIR sin = 3VYBIY sin = 3VBRIB sin
S = 3VLineILine = 3VRYIR = 3VYBIY = 3VBRIB
Note: In the above power expressions only voltage and current MAGNITUDES are used.
Task 3:
Indicate results of the above Task 2 on the three-phase circuit diagram.
Phase voltages in the star load:
VRN = (120 − 400 ) V
VYN = (120 − 1600 ) V
VBN = (120800 ) V
Line voltages in the star load:
VRY = (207.84 − 100 ) V
VBR = (207.841100 ) V
Phase currents = line currents in the star load:
IRN = 6 − 700 A
IYN = 61700 A
IBN = 6500 A
Task 4:
Draw a complete phasor diagram to scale indicating all the phase voltages, line voltages,
phase currents and line currents for the star connected load.
VBN -VYN
VBR VRY
IBN
θ0
300
300
-VRN θ0 VRN
IYN θ0
300
IRN
VYN -VBN
VYB
Note: The above phasor diagram is drawn with VRN as the reference, i.e., (12000 ) V
(coinciding with x-axis.)
VBN -VYN
VBR VRY
IBN
θ0
300
300
-VRN θ0 VRN
IYN θ0
300
IRN
VYN -VBN
VYB
Problem#2:
Problem Description:
The phase voltage of a balanced three-phase star connected generator is VRN = 120∠− 40°
V. The generator is energizing a balanced three-phase DELTA connected load with load
impedance of Z = 10∠− 30° Ω in each phase.
Task 1:
IRN
+
~
+
IRY
- VRY
+
IBR
- -
~ ~
+ +
IYB
B Y B Y
IBN IYN
+
Y phase of transmission line
IY
VBR
VYB
B phase of transmission line
IB
Task 2:
• Compute all load currents. (Note: By load current is meant the current flowing
through each phase of the load.)
The current flowing through a component can be obtained by using Ohm’s law, upon
knowing the impedance of the component and the voltage applied across the component.
Hence, it is very important to be able to visually identify (from the three-phase circuit
diagram) which voltage (is it R-phase voltage? Y-phase voltage? B-phase voltage? R-Y line
voltage? Y-B line voltage? B-R line voltage?) from the generator/input source gets applied
across the load in a given phase of the three-phase load.
Current flowing through load (delta connected) in the R-phase: (Note: Both magnitude
and phase angle of the current, i.e., complex value, need to be calculated.)
Impedance (complex value, i.e., both magnitude and phase angle) in the R-phase of the
load = ZRY = 20∠30° Ω
Complex voltage applied across the R-phase of the load = Complex voltage between R and
Y phases of the generator, i.e., VRY of the generator.
VRY
According to Ohm’s Law, complex current in the R-phase of the delta load = IRY =
ZRY
207.84 − 100
IRY = = 20.784200 A
10 − 300
Currents flowing through loads in Y and B phases can be calculated similarly:
V
IYB = YB ;
Z YB
VBR
IBR = .
ZBR
The currents flowing through loads in Y and B phases can also be calculated by means of
the phasor relationships of a balanced three-phase system.
IBR
1200
1200
1200
IRY
IYB
IYB is the same as IRY magnitude-wise, but lags IRY by 1200, i.e.,
IYB = IRY − 1200
IYB = (20.784200 ) − 1200 = (20.784 − 1000 ) A
IBR is the same as IYB magnitude-wise, but lags IYB by 1200, i.e.,
IBR = IYB − 1200
IBR = (20.784 − 1000 ) − 1200 = ( 20.784 − 2200 ) = ( 20.7841400 ) A
IR = IRY − IBR
= 3IRY − 300
Similarly:
The currents flowing through Y and B phases of the transmission line can also be
calculated by means of the phasor relationships of a balanced three-phase system.
IB
1200
1200
1200
IR
IY
The impedance angle of the load (i.e., the power factor angle of the load) is given as -300.
The three-phase power relationships are given as below:
P = 3VLineILine cos = 3VRYIR cos = 3VYBIY cos = 3VBRIB cos
Q = 3VLineILine sin = 3VRYIR sin = 3VYBIY sin = 3VBRIB sin
S = 3VLineILine = 3VRYIR = 3VYBIY = 3VBRIB
Note: In the above power expressions only voltage and current MAGNITUDES are used.
Find the single-phase power in one phase, say phase-R (i.e., RY phase of the delta load).
Since the load is balanced, three-phase power is three times the single-phase power.
Task 3:
Line currents of the delta load (i.e., currents flowing through the transmission lines into
the delta load):
IR = (36 − 100 ) A
IY = (36 − 1300 ) A
IB = (361100 ) A
IRY = ( 20.784200 ) A
IYB = ( 20.784 − 1000 ) A
IBR = ( 20.7841400 ) A
Task 4:
Draw a complete phasor diagram to scale indicating all the phase voltages, line voltages,
phase currents and line currents for the delta connected load.
IB
IBR -IYB
300
IY IR
IYB -IBR
VRY lags IRY by impedance angle, which is 300; in this particular case, it co-incides with IR.
(Voltages are not explicitly shown in the above phasor diagram.)
Problem#3: