DOCUMENT: RELAY SETTING CALCULATION Doc. No.

: EE-221424

STATION: QATIF 115/13.8KV SUBSTATION NO.2 Rev. No.: A

1.1 115KV BUSBAR DIFFERENTIAL PROTECTION (WITH BUILT IN BF) RELAY SETTING (REB 500)
Circuit Bus 1A,1B,2A,2B Relay Relay
87B+50BF REB500 Make ABB Doc. Ref
Ref : and check zone Designation Type
Aux.
125 V DC CT Ratio 2000/1 PT Ratio _
Voltage

Nominal 1A Rated Voltage Freq 60HZ


Current

CT Data

CT Ratio : Primary 3000 A Adopted tap

: Secondary 1 A 2000 A

Class TPS
CT Knee Point Voltage (Vkp) 1666.6 V

Magnetising current IM at Vkp 30 mA

CT Secondary resistance RCT 3.13 Ohms

Ik min Op char. L1,L2.L3 10001000 A

k Op char. L1,L2.L3 0.8

Diff. current Alarm c Op char. L1,L2.L3 10 % I kmin

Delay Op char. L1,L2.L3 5S

Ik min Op char. L0 1000300 A

k Op char. L0 0.8
Diff. current Alarm c Op char. L0 10 % I kmin

Delay Op char. L0 10 s

Breaker Failure Protection

BFP Active Active

Setting (per CT) 1.2 In

Timer 1 Active Active

Ttimer 2 Active Active

Timer 1 100 ms

Ttimer 2 150 ms

Inter trip pulse Duration 200 ms

Logic type 1

QATIF 115/13.8KV RELAY SETTING


SUBSTATION NO. 2 5 REV.A