Professional Documents
Culture Documents
Geothermal Powel Plant Design
Geothermal Powel Plant Design
Geothermal Powel Plant Design
Presented to
Submitted by:
Mike E. Suan
March 2024
CHAPTER 1: INTRODUCTION
1.1 PROBLEM STATEMENT AND INTRODUCTION
Since its inception, electricity has become one of humanity’s fundamental needs. The demand
for electricity continues to increase globally and is projected to continually increase further. As such,
power generation also becomes increasingly important. In the Philippines, power generation is heavily
reliant on fossil fuels. The installed capacity for the country in 2019 was 15,124 MW, more than 70% of
which was generated using fossil. Currently, the Philippines is still heavily reliant on fossil fuels,
considered the primary contributor to climate change. Renewables make up only 29.5% of the country’s
energy mix, according to a report from the Department of Energy.
However, this dependence on fossil fuels have resulted to several negative consequences. The
Philippines imports fossil fuels which have led to inflexibility, high and unstable power costs, and trade
deficits. In addition to this, fossil fuels have been linked as primary contributors to environmental crisis
This necessitates the need for alternative means of power generation. The Philippines is in the
Pacific Ring of Fire, a series of tectonically active structures surrounding the Pacific Ocean which has
significant prospects for geothermal energy. As such, power generation by geothermal means is an
attractive prospect for the Philippine energy mix. In fact, the Philippines is one of the world’s leading
producers of geothermal energy.
One location in the Philippines that has been identified of having a geothermal already is in
Sorsogon City. In this paper, a design of a single flash geothermal power plant is proposed. The power
plant is intended to cater for the 8MW power demand in Osiao, Sorsogon City.
In flash steam power plants, the geofluid is a liquid-vapor mixture. By lowering the pressure, the
geofluid mixture is separated into their vapor and liquid components. The vapor component is used to
drive the turbine. This power plant can only be used for geofluids whose temperature is above 182°C
(CEC, 2015). Since the geothermal reservoir in Sorsogon City has an estimated temperatures range
240°C to 320°C based on previous geoscientific research and downhole data, flash steam is the most
suitable type of power plant for the project. A simplified schematic diagram for flash steam geothermal
power plants is shown in Figure 3.
Figure 2. Simplified schematic diagram for flash steam geothermal power plants (CEC, 2015)
Although all types of geothermal power plants use geothermal fluids as energy source, they vary
in the way in which energy is extracted from the geofluid. In this paper, the proposed power plant takes
the form of a single flash steam geothermal power plant. Hence, only the energy source cycle for the
said power plant is discussed.
Figure 5 shows the temperature-entropy diagram for single flash steam power plant operation.
The process begins at point 1 where a high-pressure geofluid is pumped to the Earth’s surface. The
flashing process (process 1-2) is considered as an isenthalpic process as it occurs steadily without heat or
work involved and changes in potential and kinetic energies are considered negligible. After flashing, the
liquid and vapor components are separated isobarically. Process 2-3 accounts for the liquid component
sent back to the well while process 2-4 accounts for the steam being sent to the turbine. Steam expands
in the turbine in process 4-5. Process 4-5s represents the ideal turbine expansion process. After
expansion, the steam is condensed into a saturated liquid in the condenser as shown by isobaric process
5-6 and pumped back into the reservoir.
Figure 3.
Temperature-entropy diagram for single flash steam power plant (DiPippo, 2012).
The geothermal fluid will be obtained from 1 production wells. In a production well, a wellhead
valve will be used to reduce the pressure of the fluid to the flash tank pressure. A well will also have a
flash tank where the steam will be generated. The fluid retained after the flashing process will be
reinjected into the reservoir using the reinjection well.
The steam produced from the well-separator units will be collected in the steam receiver tank.
The steam will then be sent to drive the turbine-generator unit to produce electricity.
After undergoing expansion, the steam will be turned back into a fluid in the surface condenser.
Cooling water will be used to remove heat from the steam. A cooling tower will be used to cool the
cooling water as it reenters the condenser. Some part of the condensed fluid will be used as make-up
water for the cooling tower. The remaining fluid will be reinjected into the reservoir.
The T-s diagram for the proposed geothermal diagram is shown in Figure 7.
3.3469 MPa
240°C
Figure 7. T-s
diagram for the power plant
State 1 represents the condition of the geothermal fluid at the reservoir. The temperature of the
geothermal fluid is 240°C. The fluid is assumed to be a saturated liquid, and the corresponding pressure
is 3.3469 MPa. The enthalpy of the geofluid is:
kJ
h1=hf @ 240℃ sat .temp .=1037.6
kg
State 2 represents the liquid-vapor mixture obtained after the flashing process. The flashing process is
assumed to be isenthalpic; hence, the enthalpy and quality at State 2 are:
kJ
h2 =h1=1037.6
kg
kJ kJ
1037.6 −670.56
h2−h f @ P =600kPa kg kg
x 2= = =0.1759
h fg@ P=600 kPa kJ
2086.3
kg
The liquid-vapor mixture is separated isobarically into its liquid and vapor component. The
separator pressure is set to 600 kPa, adjusted from the average 620 kPa separator pressure for single
flash power plants reported from literature. State 3 represents the liquid component while State 4
represents the vapor component. Their properties are:
kJ
h3 =hf @ 600 kPa=670.56
kg
kJ
h 4=h g @600 kPa=2756.8
kg
kJ
s4 =s g @ 600 kPa=6.76
kg−K
State 5s represents the working fluid after undergoing the ideal isentropic turbine expansion process.
The condenser pressure is set to 10 kPa, adjusted from the average 12 kPa condenser pressure for single
flash power plants. The properties are:
kJ
s5 s =s 4 =6.76
kg−K
kJ kJ
6.76 −0.6493
s −s kg−K kg−K
x 5 s= 5 s f @ P=10kPa = =0.81466
s fg @ P=10 kPa kJ
7.5009
kg−K
h4−h5
nt =
h4 −h5 s
At the exhaust of the condenser or State 6, it is assumed that the wet mixture has been converted into a
saturated liquid. The enthalpy of the liquid is:
kJ
h6 =hf @ 10 kPa sat . press .=191.83
kg
The state working fluid during the entire cycle is summarized in Table 1.
The typical efficiency of single flash power plants at a given reservoir enthalpy is shown in Figure
8. The enthalpy of the geothermal fluid in the geothermal prospect in Osiao, Sorsogon City was
determined to be 1037.6 kJ/kg (See Table 1). At this enthalpy, the typical single flash geothermal power
plant efficiency is approximately 8%.
Figure 8. Efficiency of single flash power plant vs. reservoir enthalpy
This efficiency can be used to estimate the total amount of groundwater needed to achieve the rated
capacity of the plant.
Power Output
η=
mgw (h1 )
(
ms =x2 ( mgw )=0.1759 96.38
kg
s )
=16.95
kg
s
kg kg kg
mi=m gw−ms=96.38 −16.95 =79.43
s s s
Number of Units 1
Operating Pressure 600 kPa
Mass of Groundwater kg
96.38
s
Mass of Steam Produced kg
16.95
s
Mass of the liquid for reinjection kg
79.43
s
Manufacturers will be asked to customize flash tanks that will meet the specifications stated in Table 2.
The steam turbine must have a rated capacity of 8 MW to sustain the load demand. The inlet and outlet
pressure of the steam turbine are 600 kPa and 10 kPa, respectively. The steam entering the turbine has
a temperature of 158.85°C, and the turbine must be able to handle 16.95 kg/s of steam. The
specifications required for the turbine are summarized in Table 3.
Rated Capacity 8 MW
Steam pressure 600 kPa
Steam temperature 158.85 °C
Exhaust pressure 10 kPa
Mass of steam 16.95 kg/s
Figure 9. The Geothermal Steam Turbine Range
The selected turbine that meets the requirement for this power plant is the SST-400 GEO unit. The unit
is shown in Figure 12.
m s =16.95
s (
kg 2.20462 lb
1 kg
=37.37)lb
s
T sat =114.4768 ℉
3
ft
v=0.0161679071
lb
The temperature of the cooling water at entering the condenser is set to 80ºF. The terminal difference
between the steam and the cooling water at the outlet is set to 10ºF.
T cw ,out =114.4768−10=104.4768 ℉
T cw ,∈¿
θm =T cw ,out − ¿
ln ¿ ¿
104.4768 ℉−80℉
θm =
114.4768℉−80 ℉
ln ( )
114.4768℉−104.4768 ℉
The tubes are designed to be 18 BWG, admiralty metal with 7/8” diameter. The velocity of the cooling
water is set to 7 fps. The cleanliness factor is set to 0.85 and the prime mover is set to 1.0. Other factors
are obtained as c=263, Ft=1 ,∧Fp=1 .
Figure 15. Heat
transfer coefficient factors
U =c √ vel
U =263 √ 7 fps
BTU
U =695.8326 2
ft −hr −℉
BTU
U =695.8326 2
(1)(1)(0.85)(1)
ft −hr −℉
BTU
U =591.4577 2
ft −hr −℉
It was suggested by the Heat Exchanger Institute that for surface condensers for non-reheat turbines,
the change in specific enthalpy is hfg=950 BTU /lb . The surface area required is
BTU
(m s )(950 )
lb
A=
(U )(θ m)
lb 3600 s BTU
(37.37 )( )(950 )
s 1 hr lb
A=
BTU
(591.4577 2 )(19.7760 ℉ )
ft −hr −℉
2
A=10920.80289 ft
Q R=mc w (cp c w )¿
QR
mc w=
(cpc w )¿ ¿
lb 3600 s BTU
(37.37 )( )(950 )
s 1hr lb
mc w =
BTU
1 (104.4768 ℉−80 ℉ )
lb−℉
lb
m c w =5 , 221 , 491.371
hr
Converting to volume,
mw
volw =
ρw
volw =
5 ,221 , 491.371 (
lb 1 hr
hr 60 min )
gal
(7.48 3 )
lb ft
62.4 3
ft
tube
No . of tubes=1006.93
pass
2
Area 10920.80289 ft
Length of tubes= =
(no . of tubes)(factor ) ft
2
(1006.93)(0.2297 )
ft
Length of tubes=47.22 ft
Based on recommended tube lengths shown in Figure 17, for a condenser surface area of over 10,000 to
20,000 sq. ft., the length of the tubes must be 18-24 ft. In order to satisfy this condition, the
configuration of the condenser is set to be a two-pass condenser, and the number and length of tubes
are adjusted.
Lemgth of tubes
Actual Length= + [ 2(tube sheet thickness) ]
no . of pass
Actual Length=
47.22 ft
2 pass [
+ 2(0.49∈×
1 ft
12inches
)
]
Actual Length=23.69 ft
Due to the specificity of the condenser, the developers will find manufacturers for the condenser to be
custom-made based on the parameters listed in Table 5.
With a two-pass configuration and a cooling water velocity of 7 fps, the friction loss on the condenser
can be computed using the factors shown in Figure 18.
Figure 18. Friction loss factors on the tube
h f =18.20 ft
The cooling water leaving from the condenser will be discharged into the cooling tower. The point of
discharge within the cooling tower is 10 m (32.81 ft) above the inlet of the cooling water to the pump.
Therefore, the total dynamic head is
1 1 lb
ρ= = =61.85
v ft
3
ft
3
0.0161679071
lb
With pump efficiency set to 75%, the required brake horsepower of the pump is
g0
(H t )(volw )( ρ)( )
gc
BP= 3
ft −lbf
33,000 (η)
hp−min
ft
3 32.2
ft lb s
(51.01 ft )(1394.53 )(61.85 3 )( )
min ft 32.2 lbm−ft
lbf −s 2
BP=
ft 3−lbf
33,000 (0.75)
hp−min
BP=177.77 HP
The summary for the cooling water pump specifications is shown in Table 6.
For the calculations for the cooling tower, the information regarding the cooling water has been
computed in the calculations for the condenser. For the air entering the cooling tower, the temperature
is set to 29°C while and the relative humidity is 76% which are average values according to online
sources [ CITATION Tim21 \l 13321 ]. The air leaving the cooling tower is assumed to be 27°C and
saturated. A system diagram for the cooling tower is shown in Figure 22.
Figure 22. System diagram for the cooling tower
@ water inlet
kJ
h w ,i=168.6542
kg
@ water outlet
kJ
h w ,o=111.3706
kg
kJ
h a ,i=78 , SH a , i=0.019
kg
kJ
h a ,o=86 , SH a , o=0.023
kg
kg kJ kJ kJ kJ
2410 (168.6542 )−m w ,o (111.3706 )=ma (86 −78 )
s kg kg kg kg
ma=50,807.08−13.92 mw ,o
kg
2410 −mw , o=50,807.08−13.92 mw, o (0.023−0.019)
s
kg
m w , o=2,336.9
s
The mass of air is
kg
ma=50,807.08−13.92(2,336.9 )
s
kg
m a=18,277
s
kg kg
m make−up=m w ,i−mw , o=2410 −2,336.9
s s
kg
mmake−up=73.1
s
lb BTU 1.055 kW
Q=ms hfg =37.37 (950 )( )
s lb BTU
1
s
Q=37,454.08 kW
Checking if the air conditions are sufficient to reject this amount of heat,
Q=18,277
kg
s ( kJ
86 −78
kg
kJ
kg )
=146,216 kW
Typical generator efficiencies used in geothermal plants ranges from 95.7 to 99%. Taking 99% as the
generator efficiency, the electrical power that is produced by the turbine is
EP 8403.64 kW
η= = =0.084=8.4 %
mgw (h1) kg kJ
96.38 (1037.6 )
s kg
This efficiency is close to the typical 6% - 9% efficiency of single flash steam geothermal power plant
associated with the enthalpy of the geothermal reservoir as shown in Figure 11.