ANNEXURE-I

Dead Loads for Seismic Analysis:


1-A Roof with Shingles:
Roof Slope 3:12
a) Roofing:
psf pcf Thickness Quantity Wt. in psf
Roof Paper 0.50 2 1.00

Asphalt Shingles 2.0 2.00

½" Plywood 0.4 psf per 1/8" (4 X 0.4) 1.60

b) Framing (2"X10" @ 16" OC) 4.818 plf/1.33 3.62


Beams etc. 1.00

c) Misc 1.00
Total= 10.22
Say 11 psf
1-B Roof with Tiles:

a) Roofing
Roof Paper 0.5 2 1.00
Clay Tiles Eagle lite roofing concrete tiles 7.20
½" Plywood 0.4 psf per 1/8" (4 X 0.4) 1.60

b) Framing (2"X10" @ 16" OC) 4.818 plf/1.33 3.62


c) Beams etc. 1.00
d) Misc 1.00
Total= 15.42
Say 16 psf
1-C Roof with Shingles & Vaulted Ceiling:
Roof Slope 3:12
a) Roofing:
psf pcf Thickness Quantity Wt. in psf

Roof Paper 0.50 2 1.00


Asphalt Shingles 2.0 2.00
½" Plywood 0.4 psf per 1/8" (4 X 0.4) 1.60

b) Framing (2"X10" @ 16" OC) 4.818 plf/1.33 3.62


Beams etc. 1.00

c) Misc 1.00

d) Insulation - Typical R -30 --9.5" Thick @ 0.04 psf per inch 0.38

e) Sheet Rock/Gypsum Board -0.55 per 1/8 " Thick (4X0.55) 2.20

f) Duct/Mechanical etc. 1.00


Total= 12.80
Say 13 psf
2 Ceiling with ½" Sheetrock & Insulation:

a) Framing (2"X8" @ 16" OC) 3.776/1.33 2.84

b) Insulation - Typical R -30 --9.5" Thick @ 0.04 psf per inch 0.38

c) Sheet Rock/Gypsum Board -0.55 per 1/8 " Thick (4X0.55) 2.20
d) Duct/Mechanical etc. 1.00

e) Beams etc. 1.00

f) Misc 0.50
Total= 7.92
Say 8.0 psf
psf pcf Thickness Quantity Wt. in psf

3A Floor Loading:

a) Wood Floor (7/8" Hardwood Flooring (4psf) 4 4.00

b) Floor Plywood - 3/4" (0.4 X 3/4)/ 1/8 2.40

c) Framing 2" X 12" @ 16"OC 5.859/1.33 4.41

d) Ceiling Board ½" 0.55 X 4 2.20

e) Duct/Mechanical etc. 1.00

f) Misc 0.50
Total= 14.51
Say 15.0 psf
3B Balcony Floor Loading:
a) Floor Plywood - 3/4" (0.4 X 3/4)/ 1/8 2.40

b) Framing 2" X 12" @ 16"OC 11.875 TJI 2"X12" X1'-0" X 47 5.88


TJI SG = 0.75 12 x 12 1.33

c) Ceiling Board ½" 0.55 X 4 2.20

d) Concrete Toping Ave 2" th. = 2"/12 x1 x1x150 = 25.00


Total= 35.48
Say 36.0 psf
LL = 60.00 psf

3C Deck Floor with Tiles Loading:


a) Floor Plywood - 3/4" (0.4 X 3/4)/ 1/8 2.40

b) Framing 2" X 12" @ 16"OC 11.875 TJI 2"X12" X1'-0" X 47 7.00


TJI SG = 0.75 12 x 12 1.33

c) Ceiling Board ½" 0.55 X 4 2.20

d) Ceramic Tiles 3/4" on 1/2" mortar bed = 16.00


Total= 27.60
Say 28.0 psf
LL = 60.00 psf

4 Exterior Walls:

a) (i) 2" X 4" Wood studs @ 16" OC 1.823/1.33 = 1.37 psf 1.37

(ii) 2" X 6" Wood Studs @ 16" OC 2.865/1.33= 2.15 psf

b) ½" Plywood 0.4psf per 1/8" TH. (0.4X4) 1.60

c) ½" Gypsum Board 0.55 psf per 1/8" TH. (0.4X55) 2.20
d) R-15 insulation (3½" TH) - 0.04 psf per inch TH. (3.5 X 0.04) 0.14

e) Stucco 7/8" 10.00

f) Misc / Plumbing etc. 1.00


Total= 16.31
Say 17.0 psf
5 Interior Walls:

a) Wood Studs with ½" Gypsum on each side : 8.00


Total= 8.00
Say 8.0 psf
6 Garage Concrete Floor:

Slab Thickness = 3''


Concrete Density = 150 pcf

a) Concrete Self Weight = =D/12 * 150 = 38


Wood Framing = =

b) Framing 2" X 12" @ 16"OC 5.859/1.33 = 4.41

c) Ceiling Board ½" 0.55 X 4 = 2.20

d) Duct/Mechanical etc. = 1.00

e) Misc = 0.50
Total= 46 psf
LL= 40 psf
Gravina ..\..\Bria
DESIGN FOR GRAVITY LOADS 2" X 4" DL LL
Loads: 2" X 6" DECK 15/20 60

Roof DL = 11 psf LL = 20 psf BALCONY 36 60


FARAFE 46 40
Ceiling DL = 8 psf LL = 10 psf PERFOLA 11 20
Floor DL = 15 psf LL = 40 psf
Exterior Walls DL = 17 psf of Wall Area
Interior Walls DL = 8 psf of Wall Area

Deflection Criteria:

Live Load = Span/360


Total Load = Span/240
Lateral Wall Deflection = Span(L)/360

Design of Beam FB1 Span = 7'.00'' = 7.00'


Between FB3 P2

DL= 1 10.42 X 15 ÷ 2 = 78
78

LL= 1 10.42 X 40 ÷ 2 = 208


208

Design as per software Sheet attatched

Provide Beam FB1 1X 4" X 8" DF-#2

REACTIONS DL LL RLL
FB1 RA 293 728 0
FB1 RB 293 728 0

Design of Beam FB2 Span = 7'.08'' = 7.67'


Between P2 P4

DL= 1 10.42 X 15 ÷ 2 = 78
78

LL= 1 10.42 X 40 ÷ 2 = 208


208

Design as per software Sheet attatched

Provide Beam FB2 1X 4" X 8" DF-#2

REACTIONS DL LL RLL
FB2 RA 321 798 0
FB2 RB 321 798 0

Design of Beam FB3 Span = 10'.05'' = 10.42'


Between FB6 P1

DL= 2 1.33 X 15 ÷ 2 = 20
20

LL= 2 1.33 X 40 ÷ 2 = 53
53

Point Load from DL LL SL


FB1 RA 293 728 0
293 728 0 @ 5'.10'' from left
Design as per software Sheet attatched

Provide Beam FB3 1X 4" X 12" DF-#2

REACTIONS DL LL RLL
FB3 RA 280 597 0
FB3 RB 315 683 0

Design of Beam FB4 Span = 5'.10'' = 5.83'


Between P3 P2

DL= 2 1.33 X 15 ÷ 2 = 20
20

LL= 2 1.33 X 40 ÷ 2 = 53
53

Design as per software Sheet attatched

Beam FB4 1X 4" X 6" DF-#2


Provide Beam FB2 1 X 3.5" X 11.875"- 2.2E Parallam PSL
REACTIONS DL LL RLL
FB4 RA 71 154 0
FB4 RB 71 154 0

Design of Beam FB5 Span = 5'.10'' = 5.83'


Between P5 P4

DL= 1 1.33 X 15 ÷ 2 = 10 L

1 8.25 X 15 ÷ 2 = 62 R
72

LL= 1 1.33 X 40 ÷ 2 = 27 L

1 8.25 X 40 ÷ 2 = 165 R
192

Design as per software Sheet attatched

Provide Beam FB5 1X 4" X 6" DF-#2

REACTIONS DL LL RLL
FB5 RA 223 560 0
FB5 RB 223 560 0

Design of Beam FB6 Span = 22'.05'' = 22.42'


Between P6 P3

DL= 1 10.42 X 15 ÷ 2 = 78 T

Railing 1 5.00 X 3.5 ÷ 1 = 18


96

LL= 1 10.42 X 40 ÷ 2 = 208 T

1 1.00 X 50 ÷ 1 = 50
258

Point Load from DL LL SL


FB3 RA 280 597 0
280 597 0 @ 15'.07'' from left

Design as per software Sheet attatched

Provide Beam FB6 1 X 7" X 14"- 2.2E Parallam PSL

REACTIONS DL LL RLL
FB6 RA 1505 3074 0
FB6 RB 1614 3307 0

Design of Header H1 Span = 5'.05'' = 5.42'


Between P7 P8

DL= 1 28.75 X 11 ÷ 2 = 158


1 28.75 X 8 ÷ 2 = 115
1 10.42 X 15 ÷ 2 = 78
1 3.00 X 17 ÷ 1 = 51
402

LL= 1 28.75 X 20 ÷ 2 = 288


1 28.75 X 10 ÷ 2 = 144
1 10.42 X 40 ÷ 2 = 208
640

Design as per software Sheet attatched

Provide Header H1 1X 4" X 12" DF-#2

REACTIONS DL LL RLL
H1 RA 1114 1734 0
H1 RB 1114 1734 0

Design of Header H2 Span = 9'.01'' = 9.08'


Between P9 P10

DL= 1 21.92 X 11 ÷ 2 = 121


1 21.92 X 8 ÷ 2 = 88
1 17.42 X 15 ÷ 2 = 131
1 2.00 X 17 ÷ 1 = 34
373

LL= 1 21.92 X 20 ÷ 2 = 219


1 21.92 X 10 ÷ 2 = 110
1 17.42 X 40 ÷ 2 = 348
677

Design as per software Sheet attatched

Provide Header H2 1 X 3.5" X 11.25"- 2.2E Parallam PSL

REACTIONS DL LL RLL
H2 RA 1749 3074 0
H2 RB 1749 3074 0

Design of Columns & Total Load on Footings:


1.5=2800(3% Width of existing footing = 1ft-4in Load carrying capacity = 6250 lbs
2=5000(2%) DL LL
2.5=8000(0%) Perimeter Col = 200 533 733
3=11000(4%) Non-Perimeter Cols = 720 1920 2640
3.5=14000(1
Tablecol *Perimeter Cols *Beam Width=6" ***Cols Above Beams 2640/733 Footing Design Loads
4=15000(5%)
Post No Perimeter LOAD END DL LL SL TOTA SIZE Total SIZE Col Col Col Gross
Total DL

Total LL

Total SL

FROM L (As per (DL+LL) (Provide) (DL+LL) DL+ LL+ Footin


GROUP

g
DL+LL Design) Fl Fl Load
+SL Loa Load
d
P12 Yes H3, H4 RB, RA 1749, 3498 3074, 6148 0, 0 0 9646 C2 4" X 6" 9646 9646 3698 6681 10379
1749 3074
3_15.618074

P3 No FB6, FB4 RB, RA 1614, 1685 3307, 3461 0, 0 0 5146 C1 4" X 4" 5146 4" X 8" 5146 2405 5381 7786
71 154
2.5_7.02971

P9 Yes H2 RA 1749 1749 3074 3074 0 0 4823 C3 4" X 4" 4823 4823 1949 3607 5556
2.5_49.9880

P10 Yes H2 RB 1749 1749 3074 3074 0 0 4823 C3 4" X 4" 4823 4823 1949 3607 5556

2.5_49.9880
P11 Yes H3 RA 1749 1749 3074 3074 0 0 4823 C3 4" X 4" 4823 4823 1949 3607 5556
2.5_49.9880

P13 Yes H4 RB 1749 1749 3074 3074 0 0 4823 C3 4" X 10" 4823 4823 1949 3607 5556
2.5_49.9880

P6 Yes FB6 RA 1505 1505 3074 3074 0 0 4579 C1 4" X 4" 4579 4" X 8" 4579 1705 3607 5312
2_0.4016064

P2 No FB1, RB, RA, 293, 685 728, 798, 1680 0, 0, 0 0 2365 C3 4" X 4" 2365 2365 1405 3600 5005
2_6.5601065
FB2, FB4 rb 321, 71 154
P4 No FB2, FB5 RB, RB 321, 544 798, 560 1358 0, 0 0 1902 C3 4" X 4" 1902 1902 1264 3278 4542
2_17.422574
223
P1 No FB3 RB 315 315 683 683 0 0 998 C3 4" X 4" 998 998 1035 2603 3638
2_46.600696

P7 Yes H1 RA 1114 1114 1734 1734 0 0 2848 C3 4" X 4" 2848 2848 1314 2267 3581
2_48.934189

P8 Yes H1 RA 1114 1114 1734 1734 0 0 2848 C3 4" X 4" 2848 2848 1314 2267 3581
2_48.934189

P5 No FB5 RA 223 223 560 560 0 0 783 C3 4" X 4" 783 783 943 2480 3423
2_55.808744

Design of Footing for Cols:


4" X 4" - 1.8E Parallam PSL

4" X 6" - 1.8 Capacity of Footing Falling over Perimeter :


4" X 8"- 1.8E Parallam PSL

4" X 10"- 1.8 Load Carrying Capacity of Existing Footing:


4" X 12"- 1.8E Parallam PSL
Size of Columns = 4 '' X 4 ''
Taking 1'.03'' wide footing --18" deep
Taking 1'.00'' wide footing --18" deep
4" X 4" DF-L#Effective length of the footing below the column =

4" X 6" DF-L#1'.06'' + '.04'' + 1'.06'' = 3.33' = 3'.04''


4" X 8" DF-L#2 4 ''
4" X 10" DF- Load carrying Capacity (1'-4" Wide footing) = 3'.04'' X 1'.03'' X 1500 = 6250 lbs
4" X 12" DF-L#2

6" X 6" DF-L# Load carrying Capacity (1'-0" Wide footing) = 3'.04'' X 1'.00'' X 1500 = 5000 lbs
6" X 8" DF-L#2

6" X 10" DF- Therefore, No footing is required below the Columns with Total load less than 6250 lbs for (1'-4" Wide footing)
6" X 12" DF-L#2 or 5000 lbs for (1'-0" Wide footing)
2'=3Nos For Interior Footings , adding Floor L 6.0 ' X 8.0 ' X 15 lbs/Sqft = 720 lbs DL
2.5'=4Nos 6.0 ' X 8.0 ' X 15 lbs/Sqft = 720 lbs LL
3'=6Nos 15 lbs/Sqft 1440
3.5'=7Nos For Perimeter Footings adding Floor 3.3 ' X 4.0 ' X 15 lbs/Sqft = 200 lbs DL
4'=8Nos 3.3 ' X 4.0 ' X 15 lbs/Sqft = 200 lbs LL
Design as per Software Sheet Attached 400

*Perimeter Cols Width of existing footing = 1ft-4in <5000 lbs, No Footing Required<6667 lbs, No Footing Required
GROUP Max Peri. COLS Col Load+ Total Load Size of Footing Dept Reinf. COL SIZES
Loaded col Floor Load h
Group

Col (IN)
DL LL

F1 P12 No P3, P12 3698 6681 10379 3'-0" X 3'-0" 12'' 9Nos - #4 Bothways F1 P3 - 4" X 8"
P12 - 4" X 6"

F2 P6 No P2, P4, P6 1705 3607 5312 2'-6" X 2'-6" 12'' 5Nos - #4 Bothways F2 P2, P4, P9, P10" -
4" X 4"
P6 - 4" X 68

F3 P1 No P1, P5 1035 2603 3638 2'-0" X 2'-0" 12'' 4Nos - #4 Bothways F3 4" X 4"

P11 yes P7, P8, P9, P10, P11, 1949 3607 5556 <6667 lbs, No Footing Requied
P13

Gravina
COLS/FOOTINGS SCHEDULE
COLS COL SIZES Size of Footing Depth Reinf.

FOOTING
Length X Width

P12 P3, P12 P3 - 4" X 8" 3'-0" X 3'-0" F1 12" 9Nos - #4 Bothways
P12 - 4" X 6"
4" X 4" DF-#2
P6 P2, P4, P6 P2, P4, P9, P10" - 4" X 4" 2'-6" X 2'-6" F2 12" 5Nos - #4 Bothways
P6 - 4" X 68
4" X 8" DF-#2
P1 P1, P5 4" X 4" 2'-0" X 2'-0" F3 12" 4Nos - #4 Bothways

NOTE: Columns P7, P8, P9, P10, P11, P13 are Perimeter columns. Existing footing is sufficient,
hence No footing is required. Column P6 is above beam.
INPU DESIGN FOR LATERAL LOADS
1.39 Gravina
Calculation of Seismic Coefficient 'Cs'
A) SEISMIC PARAMETERS AS PER SEISMIC DATA SHEET:
1 Ss= 1.737
2 S1= 0.6
3 Fv= 1.7 Fv=NA
5 Fa= 1.2
SOIL CLASS= "D" DEFAULT
B) TIME PERIOD OF THE BUILDING:
1 Ct= 0.02
2 X= 0.75
3 Ht= 16 Ft
4 T=Ct(Ht)^X 0.160

C) SDs & SD1


Ss= 1.737 S1= 0.6
Fa= 1.2 Fv= 1.7
SMs= Fa*Ss 2.08 SM1(Fv*S1)= 1.02
SDs(2/3*SMs)= 1.39 SD1(2/3*SM1) 0.68

D) SEISMIC DESIGN CATEGORY:

S1 = 0.600 Less than 0.75


RISK CATEGORY= II

SEISMIC DESIGN CATEGORY IS = D


AS per Section 1613A.3.5 of CBC 2022
E) BASE SHEAR COEFF Cs :

Ts(SD1/SDs) = 0.489
T= 0.160
As per Exception 3 of 11.4.8 of ASCE 7-16:
Since T<Ts and we are using equivalent force procedure

Cs=SDs/R . Ie R= 6.5
Ie= 1

Cs= 0.214

F) MODIFIED BASE SHEAR COEFFICIENT:


Modified CS = ⍴XCs
SINCE ⍴ = 1.3
MODIFIED Cs= 0.28
Gravina-Calculation of Additional Weight due to Loft
A loft area
S.NO. L B Area sq.ft
1 15.83 10.51 166.37
2 14.25 5.92 84.36
Total = 250.73 sq.ft

Weight of loft= 250.73 x15= 3760.95 lbs


Weight of Railing= 18x17.75 139.5 lbs
Weight of additional Bath room wall8x17.75x9= 1260.00 lbs
Total additional weight 5160 lbs (Wad)

B Roof area Remark


S.NO. L B Area sq.ft
1 25.41 4.91 124.76
2 26.05 14.22 370.43
3 26.27 4.25 111.65
4 15.50 18.20 282.10
5 58.44 29.03 1696.51
6 33.02 2.41 79.58
7 14.91 10.25 152.83
8 22.50 1.50 33.75
9 21.09 1.50 31.64
Total= 2883.25 sq.ft
Weight of Roof= 2883.25 x11= 31716 lbs (W1)
Second Floor wall weights
External wall length Internal wall length
22.41 22.82
5.41 27.96
13.09 18.67
48.13 14.29
20.93 16.25
7.75 31.34
11.91 2.29
10.25 14.76
4.16 11.74
6.75 10.91
15.75 5.58
29.03 5.00
15.83 1.73
4.25 9.13
2.17 3.59
14.22 9.92
2 10.80
3.41 15.37
Total 237.45 14.84
Weight= 237.5x17x9 5.02
Weight= 36338 lbs 7.11
wse 4.75
Total = 259.12
Weight= 259.12x8x9
Weight= 18656.64
wsi
w2=wse+wsi= 54994 lbs W2

C Second floor area Remark


S.NO. L B Area sq.ft
1 22.41 3.41 76.42
2 24.55 14.22 349.10
3 26.27 4.25 111.65
4 13.90 16.70 232.13
5 55.44 29.03 1609.42
6 33.02 2.41 79.58
7 11.91 10.25 122.08
8 9.00 20.00 180.00
9 13.09 5.41 70.82
10 22.50 10.25 230.63
11 21.09 7.75 163.45
Total= 3225.28 sq.ft
Weight of S.F = 3225.28 x15= 48379 lbs (W3)

First Floor wall weights 50%


External wall length Internal wall length
9.00 16.75
3.33 46.16 2*23.08
37.50 curved 18.25
57.08 15.75
21.09 2.00
2.17 12.17
11.91 4.41
10.61 9.00
6.78 12.42
15.75 10.58
29.17 v 12.66 3*4.22
9.00 9.17
18.56 4.04
Total= 231.95 16.17
Weight= 231.95x17x8/2 2.17
4.08
Weight= 15773 lbs Total= 195.78
wse Weight= 195.378x8x8/2

Weight= 6264.96 lbs


wsi
W4=wse+wsi= 22038 lbs W4

Total weight roof+SF walls+SF+ff walls 50%


Wt=(W1+W2+W3+W4) 157127 lbs

%Additional weight=(Wad/Wt) x100 3.28 %


NOTE: The additional seismic weight added for the addition/alteration is less than 10% of the
existing seismic weight and,therefore, lateral seismic analysis of the modified structure is not
required."