Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Maximum Excessive Pressure ΔP (kPa) at Different Leaking

Parameters (LP>0) at Different Design Densities of Aerosol for


Stat-X Generators

LP = .001m-1
Design Generators Generators Generators Generators
Density 100 E 1000 E 500 E 2500 E
g/m3 250 E 1500 E

ΔP (kPa) ΔP (kPa) ΔP (kPa) ΔP (kPa)

50 0.66 0.53 0.21 0.12


75 0.93 0.89 0.32 0.20
100 1.62 1.43 0.66 0.31
125 2.40 2.12 0.85 0.52

LP = .002m-1
Design Generators Generators Generators Generators
Density 100 E 1000 E 500 E 2500 E
g/m3 250 E 1500 E

ΔP (kPa) ΔP (kPa) ΔP (kPa) ΔP (kPa)

50 0.25 0.22 0.07 0.03


75 0.40 0.32 0.14 0.05
100 0.63 0.53 0.21 0.06
125 0.82 0.76 0.32 0.11

LP = .005m-1
Design Generators Generators Generators Generators
Density 100 E 1000 E 500 E 2500 E
g/m3 250 E 1500 E

ΔP (kPa) ΔP (kPa) ΔP (kPa) ΔP (kPa)

50 0.04 0.05 0.01 0.00


75 0.10 0.08 0.03 0.00
100 0.14 0.15 0.04 0.01
125 0.20 0.20 0.07 0.02
Δ