Professional Documents
Culture Documents
BS en 16798-5-1-2017
BS en 16798-5-1-2017
National foreword
This British Standard is the UK implementation of EN 16798-5-1:2017.
It supersedes BS EN 15241:2007 which is withdrawn.
The UK participation in its preparation was entrusted to Technical
Committee RHE/2, Ventilation for buildings, heating and hot
water services.
A list of organizations represented on this committee can be obtained on
request to its secretary.
This publication does not purport to include all the necessary provisions
of a contract. Users are responsible for its correct application.
© The British Standards Institution 2017
Published by BSI Standards Limited 2017
ISBN 978 0 580 86288 5
ICS 91.140.30; 91.120.10
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 31 July 2017.
English Version
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and United Kingdom.
© 2017 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 16798-5-1:2017 E
worldwide for CEN national Members.
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Contents Page
2
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
3
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
European foreword
This document (EN 16798-5-1:2017) has been prepared by Technical Committee CEN/TC 156
“Ventilation for buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by November 2017, and conflicting national standards
shall be withdrawn at the latest by November 2017.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent
rights.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
Regarding the modifications that were made with regard to EN 15241:2007, these are listed in the last
paragraph in the Introduction.
This standard has been produced to meet the requirements of Directive 2010/31/EU 19 May 2010 on
the energy performance of buildings (recast), referred to as “recast EPDB”.
EN 15241:2007 was produced to meet the requirements of Directive 2002/91/EC 16 December 2002
on energy performance of buildings referred to as “EPBD”.
For the convenience of Standards users CEN/TC 156, together with the responsible Working Group
Convenors, have prepared a simple table below relating, where appropriate, the relationship between
the ‘EPBD’ and ‘recast EPBD’ standard numbers prepared by Technical Committee CEN/TC 156
“Ventilation for buildings”.
4
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
5
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
6
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Introduction
This European Standard is part of a series of standards aiming at international harmonization of the
methodology for the assessment of the energy performance of buildings, called “set of EPB standards”.
All EPB standards follow specific rules to ensure overall consistency, unambiguity and transparency.
All EPB standards provide a certain flexibility with regard to the methods, the required input data and
references to other EPB standards, by the introduction of a normative template in Annex A and Annex B
with informative default choices.
For the correct use of this standard a normative template is given in Annex A to specify these choices.
Informative default choices are provided in Annex B.
The main target groups of this standard are all the users of the set of EPB standards (e.g. engineers,
regulators, programmers).
Use by or for regulators: In case the standard is used in the context of national or regional legal
requirements, mandatory choices may be given at national or regional level for such specific
applications. These choices (either the informative default choices from Annex B or choices adapted to
national / regional needs, but in any case following the template of this Annex A) can be made available
as national annex or as separate (e.g. legal) document (national data sheet).
NOTE 1 So in this case:
— the individual user will apply the standard to assess the energy performance of a building, and thereby use
the choices made by the regulators.
Topics addressed in this standard can be subject to public regulation. Public regulation on the same
topics can override the default values in Annex B of this standard. Public regulation on the same topics
can even, for certain applications, override the use of this standard. Legal requirements and choices are
in general not published in standards but in legal documents. In order to avoid double publications and
difficult updating of double documents, a national annex may refer to the legal texts where national
choices have been made by public authorities. Different national annexes or national data sheets are
possible, for different applications.
It is expected, if the default values, choices and references to other EPB standards in Annex B are not
followed due to national regulations, policy or traditions, that:
— national or regional authorities prepare data sheets containing the choices and national or regional
values, according to the model in Annex A. In this case the National Annex (e.g. NA) refers to this
text;
— or, by default, the national standards body will consider the possibility to add or include a National
Annex in agreement with the template of Annex A, in accordance to the legal documents that give
national or regional values and choices.
Default references to EPB standards other than EN ISO 52000-1 are identified by the EPB module code
number and given in Annex A (normative template) and Annex B (informative default choice).
NOTE 2 Example of EPB module code number: M5–5, or M5–5.1 (if module M5–5 is subdivided), or M5–5/1 (if
reference to a specific clause of the standard covering M5–5).
Further target groups are parties wanting to motivate their assumptions by classifying the building
energy performance for a dedicated building stock.
7
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
More information is provided in the Technical Report accompanying this standard (CEN/TR 16798-6
[1] ), including examples aiming to check the quality and usability of the standard.
CEN/TC 156 deals with ventilation and air conditioning systems in buildings. Subjects covered by
CEN/TC 156 are:
a) energy performance calculation for ventilation, air conditioning and cooling systems;
— to cover full air conditioning systems (including heating, cooling humidification, dehumidification;
definition see the module M5-1 standard);
— for an improved fan energy calculation, taking into consideration control strategies according to
CEN/TC 247 and fan product standards/data;
— for an improved calculation of different types of heat recovery devices (air-to-air heat exchangers,
rotary and pumped circuit), delivering the efficiency and auxiliary energy depending on control,
including moisture transfer;
— for an improved humidification calculation for different humidifier types, including auxiliary
energy;
— the formatting according to the new rules set in CEN/TS 16629; and
8
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
1 Scope
This European Standard covers the energy performance calculation of mechanical ventilation and air
conditioning systems, including humidification and dehumidification. It takes into account the
generation (air handling unit) and distribution (duct system) parts. It includes a simplified calculation
of adiabatic cooling systems. It does not cover the emission part (calculation of the required volume
flow rates and/or supply air conditions), which is covered in EN 16798-7. It does not include the
calculation of heating/cooling generation. This method is focussed on large customized ventilation and
air conditioning systems, typically used in commercial buildings, although the application is not
restricted on the basis of building or space use type.
A calculation method for ventilation systems with integrated heating/cooling generation, including
domestic hot water generation, using a monthly or seasonal calculation interval or a bin method, is
provided in a separate standard, EN 16798-5-2. This method does not include humidification and
dehumidification or adiabatic cooling.
Table 1 shows the relative position of this standard within the set of EPB standards in the context of the
modular structure as set out in EN ISO 52000-1.
NOTE 1 In CEN ISO/TR 52000-2 the same table can be found, with, for each module, the numbers of the
relevant EPB standards and accompanying technical reports that are published or in preparation.
NOTE 2 The modules represent EPB standards, although one EPB standard might cover more than one module
and one module might be covered by more than one EPB standard, for instance a simplified and a detailed method
respectively. See also Clause 2 and Tables A.1 and B.1.
9
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Table 1 — Position of this standard (in casu M5–6.1, M5–8.1, M6–5, M6–8, M7–5, M7–8) within
the modular structure of the set of EPB standards
Building
Overarching Technical Building Systems
(as such)
Descriptions
Descriptions
Submodule
Ventilation
PV, wind, ..
Lighting
Heating
Cooling
control
sub1 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11
1 General General General
Common
terms and
Building
definitions;
2 Energy Needs a
symbols,
Needs
units and
subscripts
(Free)
Indoor Maximum
3 Applications Conditions Load and
without Power
Systems
Ways to
Ways to Ways to
Express
Express Express
4 Energy
Energy Energy
Performan
Performance Performance
ce
EN 16798-5-1
EN 16798-5-1
Building Heat
categories Transfer by Emission &
5
and Building Transmissi control
Boundaries on
Building Heat
EN 16798-5-1
Occupancy Transfer by
Distribution &
6 and Infiltration
control
Operating and
Conditions Ventilation
Aggregation
of Energy
Internal Storage &
7 Services and
Heat Gains control
Energy
Carriers
10
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Building
Overarching Technical Building Systems
(as such)
Descriptions
Descriptions
Submodule
Ventilation
PV, wind, ..
Lighting
Heating
Cooling
control
sub1 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11
EN 16798-5-1
EN 16798-5-1
EN 16798-5-1
Building Solar Heat Generation &
8
zoning Gains control
Building Load
Calculated
Dynamics dispatching
9 Energy
(thermal and operating
Performance
mass) conditions
Measured
Measured Measured
Energy
10 Energy Energy
Performan
Performance Performance
ce
11 Inspection Inspection Inspection
Ways to
Express
12 BMS
Indoor
Comfort
External
13 Environment
Conditions
Economic
14
Calculation
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 1507, Ventilation for buildings — Sheet metal air ducts with rectangular section — Requirements for
strength and leakage
EN 1886, Ventilation for buildings — Air handling units — Mechanical performance
EN 12237, Ventilation for buildings — Ductwork — Strength and leakage of circular sheet metal ducts
11
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
EN 13053, Ventilation for buildings — Air handling units — Rating and performance for units,
components and sections
EN 13141-7, Ventilation for buildings — Performance testing of components/products for residential
ventilation — Part 7: Performance testing of a mechanical supply and exhaust ventilation units (including
heat recovery) for mechanical ventilation systems intended for single family dwellings
EN 13141-8, Ventilation for buildings — Performance testing of components/products for residential
ventilation — Part 8: Performance testing of un-ducted mechanical supply and exhaust ventilation units
(including heat recovery) for mechanical ventilation systems intended for a single room
EN 14239 Ventilation for buildings — Ductwork — Measurement of ductwork surface area
EN ISO 7345:1995, Thermal insulation — Physical quantities and definitions (ISO 7345:1987)
3.1
EPB standard
standard that complies with the requirements given in EN ISO 52000-1, CEN/TS 16628 and
CEN/TS 16629
Note1 to entry: CEN/TS 16628 and CEN/TS 16629 contain specific rules to ensure overall consistency,
unambiguity, transparency and flexibility, supported by common templates. EN ISO 52000-1, the overarching EPB
standard, is indispensable for each EPB standard, because of the modular structure, common terms and
definitions, symbols and subscripts and because it provides the general framework for the EPB assessment,
3.2
duct leakage air volume flow rate extracted from, ventilation zone i
leakage air volume flow rate going to the extract air ducts, extracted from a ventilation zone
3.3
duct leakage air volume flow rate going to, ventilation zone i
leakage air volume flow rate from the supply air ducts going to a ventilation zone
12
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
3.4
heat transferred by ground preheating/cooling
heat transferred to the outdoor air by ground preheating and cooling
3.5
heat transferred by recirculation
heat transferred to the outdoor air by recirculation of extract air
3.6
heat transferred by heat recovery
heat transferred to the outdoor air by heat recovery from extract air
3.7
humidification auxiliary energy
auxiliary energy needed for humidification (for pumps, etc.)
3.8
humidification generation input
energy required by the humidifier (for steam humidifiers)
3.9
required AHU cooling coil output
heat required to be extracted from air handling unit for cooling and dehumidification of the supply air
to the setpoints
3.10
required AHU heating coil input
heat required to be supplied to the air handling unit for heating the supply air to the setpoint
3.11
required cooling coil inlet temperature
cooling coil inlet temperature required for cooling and dehumidification of the supply air to the
setpoints
3.12
required heating coil inlet temperature
heating coil inlet temperature required to heat the supply air to the setpoint
3.13
required supply air moisture content
moisture content of the supply air leaving the air distribution
3.14
ventilation auxiliary energy
auxiliary energy for the service of ventilation (for heat recovery drives, electrical preheating and for
control)
13
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
b) bin,
14
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
— the supply air temperature and moisture content, based on the required values;
— heating (including humidification in case of reheat with adiabatic humidification) and cooling input
to the air handling unit (to be transferred to the connected heating and cooling distribution systems
calculation);
— the recoverable heat or cold losses from ventilation/air conditioning system for heating or cooling;
— the ventilation auxiliary energy (electric energy for drives of e.g. rotary or pumped circuit heat
recovery devices, control devices, actuators, etc.);
— the electric energy required for humidification (only for specific humidifier types); and
6 Calculation method
6.1 Output data
The output data of this method are listed in Table 4.
15
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
16
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Intended
Validity
Description Symbol Software name Unit destination Varyingc
interval a
module b
Duct leakage
volume flow
going to
qV;lea;SUP;dis;zv,i q_V_lea_SUP_dis_zv(i) m 3 /s 0— ∞ M5–5 Yes
ventilation zone i
Duct leakage
volume flow
extracted from
qV;lea;ETA;dis;zv,i q_V_lea_ETA_dis_zv(i) m3 /s - ∞ —0 M5–5 Yes
ventilation zone i
Supply outdoor
air fraction
fODA f_ODA — 0—1 M5–5 Yes
Supply air
ϑSUP;dis;out theta_SUP_dis_out °C − 273— ∞ M5–5 Yes
temperature
Supply air kg/kg dry M6–2,
moisture content
xSUP;dis;out x_SUP_dis_out
air
0— ∞
M7–2
Yes
17
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
— bin.
NOTE For the definition and explanation of a bin see CEN ISO/TR 52000-2.
For this method, the output time interval is the same as the input time interval.
6.3 Input data
6.3.1 Source of data, general
Input data about products that are required for the calculation described in this standard shall be the
data supplied by the manufacturer if they are declared according to relevant EN product standards.
If no such data from the manufacturer is available or if the required data are not product data, default
values are given in Annex B.
Default informative data given in Annex B may be replaced by other data, for example nationally
determined data. To ensure consistency with this calculation method, input data shall be presented
according to the template given in Annex A.
NOTE Compliance with the template given in Annex A does not guarantee that the new data set is consistent.
18
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The product data shall be the value declared by the manufacturer according to certified measurements
performed according to the relevant product standards. If values declared by the manufacturer are not
available, then default values are given in Annex A.
Declared values are given at standard reference test conditions. Declared values shall be adjusted
according to actual operating conditions. This adjustment is part of the calculation procedure. This
applies both to standard test values and to field test measurements.
Required technical data for this calculation procedure are listed in Table 9.
19
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Number of stages n st — No
Minimum volume flow rate ratio n q;min — 0—1 No
Recovered ratio of the fan power ffan;rd — No
Nominal heat recovery temperature
η hr;nom — No
efficiency at design air velocity
Maximum (design) supply air flow
rate of the system
qV;SUP;hr;nom m 3 /h No
20
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Validity
Characteristics Symbol Unit Reference Varying b
interval a
efficiency for rotary heat recoveries
Correction factor for the rotation
speed dependence of the humidity
fn;x — 6.4.3.2.6 No
recovery efficiency for rotary heat
recoveries
Correction factor for other heat
fxr;other — 6.4.3.2.6 No
recovery types
Heat recovery efficiency reduced due
to defrost operation at ϑ e = −15°C, εD;-15 — No
according to EN 13053
Heat recovery efficiency reduced due
to defrost operation at ϑ e = −7°C, εD;-7 — No
according to EN 13053
Constant for the cooling coil moisture
CC;1 — No
content
Constant for the cooling coil moisture
CC;2 — No
content
Constant for the cooling coil moisture
CC;3 — No
content
Cooling coil bypass factor fC;bp — No
Cooling coil temperature efficiency η coil;C — No
Heating coil temperature efficiency η coil;H — No
Nominal efficiency of the supply fan,
taken from manufacturer's data, η fan;SUP;nom — No
provided according to EN ISO 5801
Nominal pressure difference over the
supply fan, taken from manufacturer's Δp fan;SUP;nom Pa No
data according to EN ISO 5801
Supply fan design pressure difference Δp fan;SUP;des Pa No
Nominal efficiency of the extract fan,
taken from manufacturer's data, η fan;ETA;nom — No
provided according to EN ISO 5801
Nominal pressure difference over the
supply fan, taken from manufacturer's Δp fan;ETA;nom Pa No
data according to EN ISO 5801
Extract fan design pressure difference Δp fan;ETA;des Pa No
Function for the dependence of the
efficiency of the supply / extract fan
on the volume flow rate, derived from fη (q V) — No
manufacturer's data, provided
according to EN ISO 5801
21
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Validity
Characteristics Symbol Unit Reference Varying b
interval a
Function for the dependence of the
pressure difference over the supply /
extract fan on the volume flow rate, fΔp (q V) — No
derived from manufacturer's data,
provided according to EN ISO 5801
Controlled portion of the total supply
fΔp;SUP;ctrl — No
design pressure difference
Controlled portion of the total return
fΔp;ETA;ctrl — No
design pressure difference
Supply air handling unit surface area A ahu;SUP m2 No
Supply air handling unit heat loss
Uahu;SUP kW/m 2 K No
coefficient
Extract air handling unit surface area A ahu;ETA m2 No
Extract air handling unit heat loss
Uahu;ETA kW/m 2 K No
coefficient
Maximum heat transfer power of the
Φhr;max kW No
heat recovery device
Maximum rotation speed of the rotary
n rot;max min− 1 No
heat recovery device
Rotor drive power at max. rotation
Phr;rot;max kW No
speed
Relative pump power consumption
per transported volume at maximum p el;hr;pu;max kWh/m 3 No
speed
Minimum part load factor of the heat
fpl;hr;min — No
recovery
Supply plus extract design pressure ΔpSUP+ETA;des;hr Pa
difference of the heat recovery device No
at design conditions
Efficiency of the adiabatic cooling η hu;ac
— No
humidifier
Electric power consumption of the
control devices (sensors, actuators, ΣPel;V;ctrl kW No
controllers)
Design air volume flow rate of the
q V;SUP;HU;des m 3 /h No
humidified system
Specific power consumption of the
humidification pump per colume flow p el;HU;des kWh/m 3 No
rate
Design water evaporation mass flow
q m;w;HU,des kg/h 0— ∞ No
rate of the humidifier
22
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Validity
Characteristics Symbol Unit Reference Varying b
interval a
a Practical range, informative
b “Varying”: value may vary over time: different values per time interval, for instance: hourly values or monthly
values (not constant values over the year)
Data shall be defined in accordance with the template given in Annex A. Default data are given in
Annex B.
6.3.2.2.2 Duct leakage factors
where:
qV;lea;du m 3 /h is the air volume flow rate through the duct leakages
A du m2 is the duct area. It shall be calculated according to EN 14239
Δp du Pa is the pressure difference between duct and ambient air. Unless otherwise
specified, this is:
— in supply air ductwork: the average between the pressure difference at the
AHU outlet and the pressure difference right upstream of the air terminal
device;
— in extract air ductwork: the average between the pressure difference right
downstream of the air terminal device and the pressure difference at the
AHU inlet;
clea,du m 3 /(s⋅m 2 ) Air tightness factor of the ductwork. It shall be determined according to
for 1 Pa EN 12237 (circular ducts) and EN 1507 (rectangular ducts).
NOTE These standards do not follow the rule “coefficients have dimensions; factors
are dimensionless”; therefore clea,du is called a factor in these standards and has the
symbol f.
ep — is the pressure difference exponent; default value: 0,65
In the absence of detailed information, duct leakage factors can be used depending on the duct air
tightness class according to Table 10. Default tightness classes shall be defined according to the
template given in Table A.2, default values are given in Table B.2.
23
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
where
q V;lea;ahu m 3 /h is the air handling unit leakage airflow determined according to EN 1886
q V;dis;in/out m 3 /h is the supply or extract volume flow rate going into or coming from the
distribution system
Δp SUP / m 3 /h is the pressure difference between the supply or extract air side and the
ETA environment of the air handling unit
Δp test m 3 /h is the test pressure according to EN 1886
In the absence of detailed information, duct leakage factors can be used depending on the AHU air
tightness class according to Table 11. Default tightness classes shall be defined according to the
template given in Table A.3, proposed default values are given in Table B.3.
Table 11 — AHU leakage factors
AHU tightness class flea;ahu
L3 1,1
L2 1,04
L1 1,01
6.3.3 System design data
6.3.3.1 Process design
24
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
25
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
26
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Default data, where appropriate, are given in Annex B. Other data shall be defined in accordance with
the template given in Annex A.
6.3.3.2 Control
27
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
28
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Required operating conditions data for this calculation procedure are listed in Table 26.
29
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
30
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Annex A contains the normative template for choices in references, methods and input data.
Informative default choices in references, methods and input data are given in Annex B, in line with the
template of Annex A.
All these choices and input data are indispensable for the application of this standard.
6.4 Calculation procedure
6.4.1 Applicable time intervals
This procedure has been designed and tested for an hourly calculation interval.
It can be used with bins. In this case, bins for the relevant operational and boundary condition
parameters are formed and the number of hours in each bin calculated. The energy calculation is
performed for each bin with the formulae for the hourly calculation interval, using a calculation interval
tci equal to the number of hours per bin. In the case of a combination with a monthly calculation interval
for the energy needs calculation, the bins shall be defined for each month.
6.4.2 Distribution calculation
6.4.2.1 Operating conditions calculation
6.4.2.1.1 Volume flow rates
6.4.2.1.1.1 Detailed calculation
For this calculation, the supply and extract volume flow rates to and from the specific ventilation zones
are required inputs from the emission calculation (module 5-5). If they are not available, the simplified
calculation according to 6.4.2.1.1.2 is applied.
The required volume flow rates to be provided by the air handling unit to the distribution duct system
are:
qV;SUP;dis;in;req = ∑ (flea;du;SUP ⋅ qV;SUP;dis;zv;req;i ) (4a)
i
where
qV;SUP;dis;zv;req;i m 3 /h is the required volume flow rate for the ventilation zone i;
31
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
qV;ETA;dis;zv;req;i m 3 /h is the required volume flow rate for the ventilation zone i;
NOTE 1 The M5–5 standard treats extract air as negative values.
The supply volume flow rate going to a specific ventilation zone i served by the system is:
qV ; SUP ;dis ; zv ;req ;i
qV ; SUP ;dis ; zv ;i = qV ; SUP ;dis ;in ⋅ (6)
qV ; SUP ;dis ;in ;req
The volume flow rate extracted from a specific ventilation zone i served by the system is:
qV ; ETA ;dis ; zv ;req ;i
qV ; ETA ;dis ; zv ;i = −qV ; ETA ;dis ;out ⋅ (7)
qV ; ETA ;dis ;out ;req
The supply leakage volume flow rate going to the specific zone i is:
qV;lea;SUP;dis;z;i = (flea;du;z −1) · qV;SUP;dis;z;i (8)
The extract leakage volume flow rate extracted from the specific zone i is:
qV;lea;ETA;dis;z;i = (flea;du;z −1) · qV;ETA;dis;z;i (9)
NOTE 2 In Formula (8) and Formula (9), the zone z can be a ventilation zone zv or a thermal zone zt;
see CEN/TR 16798-6 (the accompanying technical report) for explanations.
The leakage volume flow rate going to the non-conditioned space is:
q V;lea;dis;nc = (flea;du;nc −1) · qV;SUP;dis;in (10)
The maximum part load factor of the zone air volume flow rates is:
qV ; SUP ;dis ; zv ;i
fV ;max = max (11a)
i qV ; SUP ; dis ; zv ;max; des ; i
where
qV;SUP;dis;zv;max;des;i m 3 /h is the maximum design volume flow rate for the ventilation zone i
6.4.2.1.1.2 Simplified calculation
For this calculation, instead of the individual supply and extract volume flow rates to and from the
specific thermal zones, only the part load factor and the diversity of the flow rates for the current
calculation interval are required inputs.
The required volume flow rates to be provided by the air handling unit to the distribution duct system
are:
qV;SUP;dis;in;req = fpl · qV;SUP;ahu;nom (4b)
where
qV;SUP/ETA;ahu;nom m 3 /h is the design supply and extract volume flow rates of the system
32
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The maximum part load factor of the zone air volume flow rates is:
fV;max = fpl + ΔfV (11b)
where
fpl - is the total air volume flow partial load factor (total over all zones, input)
ΔfV - is the volume flow rate diversity at the current calculation interval (input)
6.4.2.1.2 Air temperature and humidity change in the ductwork
The required and the real supply air temperature are modified in the duct as follows:
ϑ SUP ; dis ; in ; req = ϑ SUP ; req ; zv + ∑ ∆ϑ SUP ;du;nc , j + ∑ ∆ϑ SUP ;du ,k; zt ,i (12)
j i ,k
ϑ SUP ; dis ; out = ϑ SUP ; dis ; in − ∑ ∆ϑ SUP ;du;nc , j − ∑ ∆ϑ SUP ;du ,k ; zt ,i (13)
j i ,k
where
ϑSUP;req;zv °C required air temperature at the outlet of the duct
ϑSUP;dis;in °C air temperature at the inlet of the duct
The temperature drop due to the heat losses of section j of supply duct to the non-conditioned space is
calculated as:
H du ; SUP ; nc , j
−
( ρ c ) a . qV ; SUP ; dis ; in
∆ ϑ SUP ; du ;nc , j = (ϑ SUP ;du ;in , j − ϑ sur ;nc ) 1 − e (14)
where
ϑsur;nc °C is the air temperature in the non-conditioned surrounding of the duct.
This may be outdoor air or room air of the spaces transferred by the duct
ϑSUP;du;in,j °C is the air temperature of the duct section j considered for this calculation.
For required temperature calculations (Formula (12)) this is generally
the temperature at the entrance of the following duct section; if the duct
sequence is the last in the system, it is equal to ϑSUP;dis;out;req. For the actual
temperature calculation (Formula (13)), it is generally the temperature
at the exit of the preceding duct sequence; if the duct sequence is the first
in the system, it is equal to ϑSUP;dis;in
Hdu;SUP;nc,j kW/K is the heat transfer coefficient of the supply air duct section j to the non-
conditioned surrounding
qv,SUP,dis,in m 3 /h is the air volume flow rate at the supply air duct inlet
ρa kg/m 3 is the density of the air
ca kWh/(kg K) is the specific heat of the air
The temperature drop due to the heat losses of the supply duct section k to a specific conditioned zone i
is calculated as:
33
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
H du ; SUP , k ; zt ; i
−
( ρ c ) a . qV ; SUP ; dis ; in
∆ ϑ SUP ; du , k ; zt ,i = (ϑ SUP ; du ; in , k − ϑ IDA ; zt ; i ) 1 − e (15)
where
Hdu;SUP;zt;i kW/K is the heat transfer coefficient of the supply air duct section k to a specific
conditioned thermal zone
ϑIDA,zt;i °C is the indoor air temperature of the thermal zone i
The supply air humidity content remains unchanged:
xSUP,dis,out = xSUP,dis,in (16)
where
xSUP,dis,in kg/kg dry air is the air moisture content at the inlet of the duct
xSUP,dis,out;req kg/kg dry air
is the required air moisture content at the outlet of the duct; if the
duct sequence considered in this calculation is the last in the system,
it is equal to xSUP;req;zt
The extract air temperature is modified in the duct as follows:
1 f −1
ϑ ETA ;dis ;out = ⋅ ϑ ETA ; zv + lea ; du ⋅ϑ + ∆ϑ du ; ETA (18)
flea ;du flea ;du sur ;nc
where
ϑETA,zv °C is the extract air temperature at the inlet of the duct
The temperature difference due to the extract duct heat losses to the non-conditioned space is
calculated by:
H du ; ETA ; nc
−
( ρ c ) a . qV ; ETA ; dis ; out
∆ ϑ du ; ETA = (ϑ ETA ; zv − ϑ sur ; nc ) 1 − e (19)
where
Hdu;ETA;nc kW/K is the heat transfer coefficient of the extract air duct to the non-conditioned
surrounding
qV;ETA;dis;out m 3 /h is the air volume flow rate at the extract air duct outlet
34
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
where
xETA,zv kg/kg of dry air is the extract air moisture content at the inlet of the duct
xsur;nc °C is the air moisture content in the non-conditioned surrounding of the
duct. This may be outdoor air or room air of the spaces transferred by
the duct
6.4.2.2 Energy calculation
6.4.2.2.1 Distribution heat losses
The recoverable heat losses of the ductwork to a specific thermal zone i are:
QV;ls;dis;rbl;zt;i = [qV;SUP;zt;i ⋅ ρ a ⋅ ca ⋅ ΔϑSUP;du;cnd + qV,SUP,lea,du;zt;i ⋅ ρ a ⋅ ca ⋅ (ϑSUP,dis,in - ϑIDA;zt;i)] ⋅ tci (22)
where
qV,SUP,zt;i m 3 /h is the air volume flow rate crossing the thermal zone i
qV,SUP,lea,du;zt;i m 3 /h is the leakage air volume flow rate going to the thermal zone i
NOTE Recoverable heat losses are recoverable in a thermal zone. Therefore the term is used here. For the
distinction between the ventilation zone and thermal zone see EN ISO 52000-1:2017, Clause 10. See also
CEN/TR 16798–6 (the accompanying Technical Report) for explanation and possible simplifications.
Figure 1 shows the air treatment stages and the associated air type subscripts (in accordance with M5-
1, prEN 16798-3) used in 6.4.3.
35
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Key
Treatment stage Air type Subscript
A frost protection / ground 1 outdoor air ODA
preheating/-cooling
B exhaust air fan 2 preheated outdoor air ODA;preh
C heat recovery 3 supply air after heat recovery SUP;hr
D recirculation 4 supply air after recirculation a SUP;RCA
E cooling / dehumidification 5 supply air after cooling/dehumidification SUP;C
F humidification 6 supply air after humidification SUP;hu
G heating 7 supply air after heating SUP;rh
H supply fan 8 supply air entering the distribution system SUP;dis;in
9 extract air leaving the distribution system ETA;dis;out
10 extract air entering the heat recovery / ETA;hr;in
recirculation
11 extract air after heat recovery ETA;hr;out
12 exhaust air EHA
a A preheating coil after the heat recovery / recirculation mixing would be necessary in the case of adiabatic
humidification. This is not represented here. The associated heating energy is taken into account in the
(re)heating coil.
The volume air flow rate supplied to the distribution system is calculated as follows:
— If AIR_FLOW_CTRL = NO_CTRL (no flow rate control, continuous operation)
36
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
where
qV;SUP;ahu;nom m 3 /h is the nominal supply volume flow rate of the air handling unit
fop;V - is the ventilation system operation signal
qV;SUP;ahu;st1..stn m 3 /h is the supply volume flow rate of the air handling unit at stage 1.. n st
qV;SUP;ahu;stn is usually qV;SUP;ahu;nom
n st - is the number of stages
fq;min - is the minimum volume flow rate ratio
The volume air flow rate extracted from the distribution system is calculated as follows:
— If AIR_FLOW_CTRL = NO_CTRL
— If AIR_FLOW_CTRL = ON/OFF_CTRL
where
qV;ETA;ahu;nom m 3 /h is the nominal extract volume flow rate of the air handling unit
qV;ETA;ahu;st1..stn m 3 /h is the extract volume flow rate of the air handling unit at stage 1..n
qV;ETA;ahu;stn is usually qV;ETA;ahu;nom
37
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The air volume flow rates transported by the supply and exhaust fans in the air handling unit are
calculated as:
q v;SUP;ahu = flea;ahu;SUP ⋅ [(1 – fODA;min) + fODA;min ⋅ flea;hr;SUP] ⋅ q v;SUP;dis;in (25)
where
flea;hr;SUP - is the correction factor of the heat recovery system leakage for the supply volume
flow rate;
- is the correction factor of the heat recovery system leakage for the extract volume
flea;hr;ETA
flow rate.
The correction factors depend on the arrangement of the components (especially the fans) in the AHU.
Default values are given in Annex B, Table B.4.
The leakage air volume flow rates from and to the air handling unit are calculated as:
q v;lea;ahu;SUP = (flea;ahu;SUP −1) ⋅ q v;SUP;dis;in (27)
where
ϑSUP;hr °C is the supply air temperature after the heat recovery
ϑSUP;set °C is the supply air temperature setpoint (input)
ϑSUP;set;max °C is the maximum supply air temperature setpoint for ODA_COMP control option
(input)
ϑSUP;set;min °C is the minimum supply air temperature setpoint for ODA_COMP control option
(input)
fe - is the slope factor for ODA_COMP control option (input)
Δϑoff °C is the temperature offset for ODA_COMP control option (input)
6.4.3.2.3 Temperature rise in the fan
38
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Δϑfan;SUP/ETA = 0 (30a)
— else
where
Δpfan;SUP / ETA Pa is the supply/extract fan pressure difference, calculated according to
Formulae (74) and (75)
η fan;SUP / ETA - is the supply/extract fan efficiency
ffan;rd is the recovered ratio of the fan power. Values shall be defined in dependence
-
of the FAN_MOT_LOC identifier according to the template given in Table A.12;
Default values are given in Table B.12.
The air temperature entering the recirculation and heat recovery is:
— If ETA_FAN_LOC = UP_HR
— else
else
— else
else
39
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
where
Δϑgnd K is the temperature difference from ground preheating, if present, according to
Annex C
ΔϑODA;du Kis the temperature difference due to heat losses in the ODA air duct, if this is passing
conditioned and/or unconditioned zones. It is calculated in analogy to the
supply/extract air heat losses in 6.4.2.1.2
The air moisture content after the ground preheating is:
xODA;preh = xe + Δxgnd + ΔxODA;du (33)
where
Δxgnd K is the difference of moisture content from ground preheating, in present, according
to Annex C
ΔxODA;du K is the difference of moisture content due to leakage in the ODA air duct, if this is
passing conditioned and/or unconditioned zones. It is calculated in analogy to the
extract air losses in 6.4.2.1.2
6.4.3.2.5 Recirculation
Recirculation is only considered if located inside the heat recovery (downstream in the supply air) or
without heat recovery. If located outside (upstream in the supply air), it is considered to serve for frost
protection and is treated in 6.4.3.2.8.
The required supply temperature after the heat recovery is:
— If RCA_CTRL = FIX
— else
40
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
qV ;ODA ; zv ; req ; i
fODA ;min = min fODA ; hr ; max
(35a)
i qV ; SUP ; dis ; zv ; i
fODA ;min = min fODA ; hr ;
∑ qV ;ODA; zv;req ;des;i (35b)
qV ; SUP ;ahu ;nom
— else
where
qV;ODA;zv;req;i m 3 /h is the required outdoor air volume flow rate of zone i at the current
calculation interval (input from M5–5)
qV;ODA;zv;req;des;i m 3 /h is the required outdoor air volume flow rate of zone i at design conditions
fODA;hr -
is the outdoor air fraction after the heat recovery device, caused by
leakage. Values depend on the arrangement of the components in the AHU,
especially the fans. Default values are given in Annex B, Table B.5.
The supply temperature after the recirculation is:
— If HEAT_REC_CTRL = NO_CTRL or SUP_AIR_TEMP_CTRL = NO_CTRL:
— else
where the outdoor air factor of the current calculation interval is:
— if ϑSUP;hr = ϑETA;hr:in
— else
ϑ − ⋅ϑ ETA ; hr ; in
fODA = max fODA ;min ; min fODA ; hr ; SUP ; RCA (38b)
ϑ SUP ; hr − ϑ ETA ; hr ; in
The calculation procedure covers the most frequent types of heat recovery devices. The choice and the
associated control options are given in Tables 5 and 17, default values are given in Table B.15.
The supply air temperature after the heat recovery is:
— If HEAT_REC_CTRL = NO_CTRL (no heat recovery control)
41
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
— else
ϑODA;fp is calculated according to Formula (47). The control may be used for the limitation of the supply
temperature in case of mechanical ventilative cooling.
The temperature ratio (defined according to EN 13053) is calculated as:
η hr = η hr;nom ⋅ fq fv fn
⋅ ⋅ (40)
where
η hr,nom - is the nominal temperature efficiency;
fn - is the correction factor for the rotation number for rotary heat exchangers.
The correction factor for the mass flow ratio other than 1 is:
0.4
q −q
fq = V ;ETA ;ahu V ; SUP ;ahu + 1 (41)
qV ; SUP ;ahu ⋅ fODA ;min
where
C1 s/m is a coefficient, depending on the heat recovery type;
C2 - is a constant, depending on heat recovery type;
vhr;nom m/s is the air velocity at nominal conditions (for η hr,nom ).
Values shall be given according to the template in Table A.6; default values are given in Table B.6.
The air velocity at the calculation interval is calculated as:
v hr ;des ⋅ qV ; SUP ;ahu ⋅ fODA ;min
v hr ;eff = (43)
qV;SUP;hr;nom
where
vhr;des m/s is the maximum design air velocity
qV;SUP;hr;nom
m 3 /h is the air volume flow rate at design conditions
The moisture content of the supply air after the heat recovery is:
xSUP;hr = xODA;preh + η xr (xETA;hr;in - xODA;preh) (44)
42
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The calculation of the humidity recovery efficiency for heat exchangers is:
— If HEAT_REC_TYPE = ROT_SORP or ROT_NH or ROT_HYG
— else
η xr = 0 (45c)
where
η xr;nom - is the nominal moisture recovery efficiency at 2 m/s
fΔx;x - is the correction factor for the condensation potential, defined by a function given in
a national annex according to the template given in Table A.7; a default function is
given in Table B.7
fq;x - is the correction factor for the mass flow relation other than 1; defined by a function
given in a national annex according to the template given in Table A.7; a default
function is given in Table B.7
fv;x - is the correction factor for the air velocity, defined by a function given in a national
annex according to the template given in Table A.7; a default function is given in
Table B.7
fn;x - is the correction factor for the rotation number, defined by a function given in a
national annex according to the template given in Table A.7; a default function is
given in Table B.7
fxr;other - is the correction factor for other type of heat recovery, defined by a function given in
a national annex according to the template given in Table A.7
6.4.3.2.7 Frost protection
else: η hr = η hr (46)
ϑODA;fp = ϑODA;preh (47a)
ϑSUP;hr;lim = ϑSUP;hr;req (48a)
The resulting effect is considered by corrected efficiency values. These shall be provided according to
EN 13053.
— If DEFR_CTRL = INDIRECT:
if DEFR_TYPE = PREH:
43
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
else:
ϑODA;fp = ϑODA;preh (47c)
where
ϑe;lim1 °C is the outdoor air temperature limit 1
ϑe;lim2 °C is the outdoor air temperature limit 2
εD;-15 - is the heat recovery efficiency reduced due to defrost operation at ϑe = −15°C,
according to EN 13053
εD;-7 - is the heat recovery efficiency reduced due to defrost operation at ϑe = −7°C,
according to EN 13053
ϑEHA;hr;lim°C is the l for the exhaust air temperature after the heat recovery
Values shall be defined according to the template in Table A.14; default values are given in Table B.14.
6.4.3.2.8 Adiabatic cooling
At the presence of an adiabatic cooling (adiabatic humidifier in the extract air and heat recovery on
operation), the recirculation is off (fODA;min = fODA;hr) and the recirculation supply temperature is:
ϑSUP;RCA = min(ϑSUP;ahu;req; ϑSUP;hr) (50)
The properties of the supply air after the heat recovery ϑSUP;hr and xSUP;hr are calculated according to
Formulae (39a) and (44), at full operation of the heat recovery, with the air properties on the ETA side
as follows:
The extract air temperature entering the heat recovery is:
— in case of adiabatic cooling:
ϑ −ϑ
ϑ ETA ; hr ;in = max SUP ; dis ; in ; req ODA ; preh + ϑ ODA ; preh ; ϑ ETA ; dis ; out − η hu ;ac (ϑ ETA ;dis ;out − ϑ wb ; ETA ;dis ;out )
η hr
(51a)
44
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
where
η hu;ac - is the efficiency of the adiabatic cooling humidifier
ϑwb;ETA;dis;out °C is the extract air distribution leaving wetbulb temperature; this is calculated
through psychrometric calculation methods, e.g. according to [5] , which
involves iteration
The extract air moisture content entering the heat recovery is:
— in case of adiabatic cooling
where
xwb;ETA;dis;out kg/kg dry is the saturation moisture content at extract air distribution leaving
air wetbulb temperature, calculated according to Formulae (51)a) and (52a)
with ϑwb;ETA;dis;out.
6.4.3.2.9 Final supply air conditions
6.4.3.2.9.1 General
The supply air temperature and moisture content delivered to the distribution system are calculated
through the air treatment steps, with the intermediate temperatures and moisture contents, as follows
in the next subclauses of 6.4.3.2.9.
6.4.3.2.9.2 Cooling and dehumidification
The required supply air temperature after the cooling coil in the current calculation interval is:
— If SUP_AIR_TEMP_CTRL = NO_CTRL
— else
ϑSUP;DHU;req is calculated according to Formula (70). The required supply air moisture content after the
cooling coil is:
xSUP;C;req = min(xSUP;dis;in;max;req; xSUP;RCA - ΔxC ) (54)
where
xSUP;dis;in;max;req kg/kg dry air is the maximum required moisture content of the supply air
45
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The difference in moisture content due to uncontrolled dehumidification in the cooling coil is:
ΔxC = max[0; (xSUP;RCA - xC;coil;req) ⋅ (1 - fC;bp)] (55)
where
CC;1 to CC;3
are constants for the calculation of the cooling coil moisture content; values shall be
defined according to the template given in Table A.8; default values are given in
Table B.8
The required coil surface temperature for cooling is:
ϑ SUP ;C ; req − fC ; bp ⋅ ϑ SUP ; RCA
ϑ C ; coil ; req = (57)
1 − fC ; bp
where
fC;bp - is the cooling coil bypass factor; values shall be given according to the template in
Table A.8; a default value is given in Table B.8
The required coil surface moisture content for dehumidification is:
x SUP ; dis ; in ;max; req − fC ; bp ⋅ x SUP ; RCA
x DHU ; coil = (58)
1 − fC ; bp
— else
The required inlet temperature to the cooling coil in the current calculation interval is:
ϑ SUP ;C ;req − ϑ SUP ; RCA ( 1 − η coil ;C )
ϑ C ;ahu ; in ; req = (61)
η coil ;C
where
η coil;C - is the cooling coil temperature efficiency
The required energy to be extracted by the cooling coil in the current calculation interval, QC;ahu;out;req, is
calculated with Formula (80).
46
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The actual supply air temperature after the cooling coil in the current calculation interval is:
Q C ;ahu ;out r
ϑ SUP ;C = ϑ SUP ; RCA − − w
qV ; SUP ;ahu ⋅ ρ a ⋅ c a c a ( x SUP ;C − x SUP ;RCA ) (62)
where
QC;ahu;out kWh is the heat extracted from cooling coil (input from M4–1)
The actual supply air moisture content after the cooling coil in the current calculation interval is:
CC1 − CC 2
x SUP ;C = min fC ; bp ⋅ x SUP ; RCA + 1 − fC ; bp ⋅ e ϑ C ; coil +CC3
( )
; x SUP ; RCA (63)
The actual cooling coil temperature at the current calculation interval is:
η coil ; c (ϑ C ; ahu ; in − ϑ SUP ; RCA )
ϑ C ; coil = + ϑ SUP ; RCA (64)
1 − fC ; bp
where
ϑC;ahu;in °C is the actual cooling coil inlet temperature (water or refrigerant, input from M4–1)
6.4.3.2.9.3 Humidification
where
xSUP;dis;in;min;req
kg/kg dry air is the minimum required moisture content of the supply air
The change in supply air temperature in the humidifier is:
— If HUM_TYPE = STEAM:
ΔϑSUP;HU = 0 (66a)
— else:
r
∆ϑ SUP ; HU = max 0; w ( x SUP ; HU − x SUP ;C ) (66b)
ca
6.4.3.2.9.4 Heating
The required supply air temperature after the heating coil in the current calculation interval is:
— If SUP_AIR_TEMP_CTRL = NO_CTRL
— else
47
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The required inlet temperature to the heating coil in the current calculation interval is:
ϑ SUP ; H ; req − ϑ SUP ;C ( 1 − η coil ; H )
ϑ H ; ahu ; in ; req = (68)
η coil ; H
where
η coil;H - is the heating coil temperature efficiency
The actual supply air temperature after the heating coil in the current calculation interval is:
Q H ;ahu ;in
ϑ SUP ; H = ϑ SUP ;C + − ∆ϑ SUP ; HU (69)
qV ; SUP ;ahu ⋅ ρ a ⋅ c a
where
QH;ahu;in kWh is the heat input to the heating coil in the current calculation interval (input from
M3–1)
6.4.3.2.9.5 Fan
The supply air temperature after the supply fan is the final supply temperature delivered to the
distribution system:
ϑSUP;dis;in = ϑSUP;H + Δϑfan;SUP (70)
The fan energy consumption for the current calculation interval is the energy consumption for
ventilation and is calculated as:
qV ; SUP ; ahu q t ci
EV ; gen ;in ;el = ( Pel ; fan ; SUP + Pel ; fan ; ETA ) ⋅ t ci = ⋅ ∆p fan ; SUP + V ; ETA ; ahu ⋅ ∆p fan ; ETA ⋅
3.6 ⋅ 10 6
η fan ; SUP η fan ; ETA
(72)
The efficiency of the supply/extract fan at the current calculation interval is:
η fan;SUP/ETA = η fan;SUP/ETA;nom ⋅ fη (q V) (73)
where
η fan;SUP/ETA;nom - is the nominal efficiency of the supply/extract fan, taken from
manufacturer's data, provided according to EN ISO 5801
fη (q V) -
is a function for the dependence of the efficiency of the supply/extract fan
on the volume flow rate, derived from manufacturer's data, provided
according to EN ISO 5801
In the absence of available data, default characteristic functions shall be defined on a national basis.
The supply and extract fan pressure differences are:
— If SYS_TYPE = SINGLE_ZONE
If FAN_CTRL = NO_CTRL
48
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
2
q V ; SUP ; ahu
∆p fan ; SUP = ∆p SUP ,des (74b)
q V ; SUP ; ahu ;nom
2
q V ; ETA ; ahu
∆p fan ; ETA = ∆p ETA ; des (75b)
qV , ETA ; ahu ; nom
— If SYS_TYPE = MULTI_ZONE
If FAN_CTRL = NO_CTRL
q
2
∆p fan ; SUP = ∆p SUP ,des 1 −( )
f∆p ; SUP ;ctrl V ; SUP ;ahu + f∆p ; SUP ;ctrl (74d)
qV ; SUP ;ahu ;nom
q
2
∆p fan ; ETA = ∆p ETA ,des 1 −( )
f∆p ; ETA ;ctrl V ; ETA ;ahu + f∆p ; ETA ;ctrl (75d)
qV ; ETA ;ahu ;nom
q
2
∆p fan ; SUP = ∆p SUP ,des 1 −( )
f∆p ; SUP ;ctrl V ; SUP ;ahu + f∆p ; SUP ;ctrl ⋅ fV ;max 2
(74e)
qV ; SUP ;ahu ;nom
q
2
∆p fan ; ETA = ∆p ETA ,des 1 −( )
f∆p ; ETA ;ctrl V ; ETA ;ahu + f∆p ; ETA ;ctrl ⋅ fV ;max 2 (75e)
q V ; ETA ;ahu ;nom
where
Δp SUP/ETA;des Pa is the supply/extract fan design pressure difference
Δp fan;SUP/ETA;n Pa is the nominal pressure difference over the fan, taken from manufacturer's
om data according to EN ISO 5801
fΔp(qV) - is a function for the dependence of the Pressure difference over the supply/
extract fan on the volume flow rate, derived from manufacturer's data,
provided according to EN ISO 5801
49
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
fΔp;SUP/ETA;ctrl -
is the controlled portion of the total supply/return design pressure
difference
In the absence available of data, default characteristic values and functions shall be defined on a
national basis.
The maximum part load factor of the zone air volume flow rates fV;max is calculated according to
Formula (11).
6.4.3.3.2 Ground preheating and -cooling
The energy transferred by the ground preheating, if present, in the current calculation interval is:
Qgnd = ρ a ⋅ ca ⋅ qv;SUP;ahu ⋅ fODA ⋅ (ϑODA,preh – ϑe) ⋅ tci (76)
6.4.3.3.3 Heat recovery
The energy transferred by the heat recovery in the current calculation interval is:
rw
Q hr = ρ a ⋅ c a ⋅ qV ; SUP ;ahu ⋅ fODA ⋅ (ϑ SUP ; hr − ϑ ODA ; preh ) + ( x SUP ; hr − x ODA ; preh ) ⋅ t ci (77)
c p ;a
The required energy supplied by the heating coil without heat recovery in the current calculation
interval is:
QH;ahu;in;tot;req = max[0 ; ρ a ⋅ c a ⋅ qv;SUP;ahu ⋅ (ϑSUP;H;req + ΔϑSUP;HU – ϑe) ⋅ tci ] (78)
6.4.3.3.4 Recirculation
The energy transferred by the recirculation, if present, in the current calculation interval is:
QRCA = ρa ⋅ ca ⋅ qv;ETA;ahu ⋅ (1 - fODA) ⋅ (ϑETA;hr;in – ϑe) ⋅ tci (79)
6.4.3.3.5 Cooling and dehumidification
The required energy to be extracted by the cooling coil in the current calculation interval is:
Q C ;ahu ;out ;req = qV ; SUP ;ahu ⋅ ρ a c a (ϑ SUP ; RCA − ϑ SUP ;C ;req ) + ρ a rw ( x SUP ; RCA − x SUP ;C ;req ) ⋅ t ci (80)
The required energy to be extracted for dehumidification in the current calculation interval is:
ρ c min ϑ
a a
Q DHU ;ahu ;out ;req = qV ; SUP ;ahu ⋅
( )
SUP ; RCA ; ϑ SUP ; ahu ; req − ϑ SUP ;C ; req
⋅ t ci (81)
(
+ ρ a rw x SUP ; RCA − ∆x C − x SUP ;C ; req
)
6.4.3.3.6 Humidification
The energy supplied for humidification in the current calculation interval is:
— If HUM_TYPE = STEAM
— else:
EHU;gen;in;cr = 0 (82b)
50
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The energy carrier GEN_CRHU;gen for EHU;gen;in;cr (see Table 8) shall be indicated and reported together
with the value.
The water use for humidification in the current calculation interval is:
m w ; HU = qV ; SUP ;ahu ⋅ ρ a ⋅ ( x SUP ; HU − x SUP ;C ) ⋅ t ci (83)
NOTE This is not needed for energy performance calculation, but is calculated for the purpose of quality
assurance.
6.4.3.3.7 Heating
The required energy supplied by the heating coil in the current calculation interval is:
QH;ahu;in;req = ρac a · qv;SUP;ahu · (ϑSUP;H;req + ΔϑSUP;HU – ϑ SUP,C ) · tci (84)
6.4.3.3.8 Generation heat losses
— else:
where
A ahu;SUP m2 is the supply air handling unit surface area
Uahu;SUP kW/m 2 K is the supply air handling unit heat loss coefficient
A ahu;ETA m2 is the extract air handling unit surface area
Uahu;ETA kW/m 2 K is the extract air handling unit heat loss coefficient
Values for the heat loss coefficients depending on classes according to EN 1886 shall be defined
according to the template given in Table A.8; default values are given in Table B.8.
6.4.3.3.9 Recoverable generation heat losses
— else:
QV;ls;gen;rbl = 0 (86b)
51
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The auxiliary energy required ventilation system at the current calculation interval is:
WV;aux = WV;aux;hr + WV;preh + WV;aux;ctrl (87)
The auxiliary energy required by the heat recovery system at the current calculation interval is:
— If HEAT_REC_TYPE = ROT_NH or ROT_HYG or ROT_SORP
n rot
WV ;aux ; hr = Phr ;rot ;max ⋅ t ci (88a)
n rot ;max
— else if HEAT_REC_TYPE = PUMP_CIRC
2.5
WV ;aux ; hr = qV ; SUP ;ahu ⋅ fODA ⋅ p el ; hr ; pu ;max ⋅ t ci ⋅ max fpl ; hr ;min ; Q hr
(88b)
t ci ⋅ Φ hr ;max
— else
WV;aux;hr = 0 (88c)
where
n rot,max min − 1 is the maximum rotation speed
Phr;rot;max kW is the maximum rotor drive power at max. rotation speed
pel;hr;pu;max kWh/m 3 is the relative pump energy consumption per transported volume at
maximum speed
Φhr;max kW is the maximum heat transfer power of the heat recovery
fpl;hr;min- is the minimum part load factor of the heat recovery
Values shall be defined according to the template given in Table A.6; default values are given in
Table B.6.
The portion of the fan energy consumption for the pressure drop of the heat recovery in current
calculation interval is:
EV ; gen ;in ;el ⋅ ∆p SUP + ETA ;des ; hr
EV ; gen ;in ;el ; hr = (89)
∆p SUP ; des + ∆p ETA ; des
where
ΔpSUP+ETA;des;hr Pa
is the supply plus extract design pressure difference of the heat recovery
device at design conditions
The energy supplied for frost protection in the current calculation interval is:
— if DEFR_TYPE = PREH
52
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
— else
WV;preh = 0 (90b)
The auxiliary energy consumption of the control components at the current calculation interval is:
WV;aux;ctrl = Σ Pel;V;ctrl fop;ctrl tci
⋅ ⋅ (91)
where
Σ Pel,V;ctrl kW is the electric power consumption of the control devices (sensors, actuators,
controllers)
fop;ctrl - is the operation factor of the control devices
6.4.3.3.10.2 Humidification
The power consumption of the humidification pump at the current calculation interval is:
— If HUM_TYPE = STEAM:
WHU;aux = 0 (92a)
— else
where
qV;SUP;HU;des m 3 /h is the design air volume flow rate of the humidified system
pel,HU,des Wh/m 3 is the specific energy consumption of the humidification pump per volume
flow rate
The part load factor is calculated in dependence of the control of the pump. The dependence between
the control and the humidifier type shall be defined according to the template given in Table A.10, with
a default given in Table B.10.
Uncontrolled operation or valve control:
— If HUM_CTRL = NO_CTRL:
fpl;HU =1 (93a)
2,5
q ⋅ρ ⋅ x (
fpl ; HU = V ; SUP ;ahu a SUP ; HU SUP ;C
−x ) (93c)
q m ;w ; HU ;des
where
qm;w;HU,des kg/h is the design water evaporation mass flow rate of the humidifier
53
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
7 Quality control
The report with the results of the application of the standard shall include which input and method
selection data sheet, in line with the template of Annex A, has been used.
The calculation report shall, besides the output values of Table 4 transferred to other modules, include
the values of the following data:
Specific fan power, defined in prEN 16798–3 SFP
Heat transferred by ground preheating/cooling Qgnd
Heat transferred by recirculation QRCA
Duct heat losses QV;ls;dis
Heat losses of the AHU QV;ls;gen
Water use for humidification m w;HU
All options chosen for the calculation.
8 Compliance check
Check whether all options chosen for the calculation correspond to the real system or adequately
represent the technical solutions.
54
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Annex A
(normative)
A.1 General
The template in Annex A to this standard shall be used to specify the choices between methods, the
required input data and references to other standards.
NOTE 1 Following this template is not enough to guarantee consistency of data.
NOTE 2 Informative default choices are provided in Annex B. Alternative values and choices can be imposed by
national / regional regulations. If the default values and choices of Annex B are not adopted because of the
national / regional regulations, policies or national traditions, it is expected that:
— national or regional authorities prepare data sheets containing the national or regional values and choices, in
line with the template in Annex A; or
— by default, the national standards body will add or include a national annex (Annex NA) to this standard, in
line with the template in Annex A, giving national or regional values and choices in accordance with their
legal documents.
NOTE 3 The template in Annex A is applicable to different applications (e.g. the design of a new building,
certification of a new building, renovation of an existing building and certification of an existing building) and for
different types of buildings (e.g. small or simple buildings and large or complex buildings). A distinction in values
and choices for different applications or building types could be made:
— by adding columns or rows (one for each application) , if the template allows;
— by including more than one version of a Table (one for each application) , numbered consecutively as a, b, c, …
For example: Table NA.3a, Table NA.3b.
— by developing different national / regional data sheets for the same standard. In case of a national annex to
the standard these will be consecutively numbered (Annex NA, Annex NB, Annex NC, …) .
NOTE 4 In the section “Introduction” of a national / regional data sheet information can be added, for example
about the applicable national / regional regulations.
NOTE 5 For certain input values to be acquired by the user, a data sheet following the template of Annex A,
could contain a reference to national procedures for assessing the needed input data. For instance, reference to a
national assessment protocol comprising decision trees, tables and pre-calculations.
The shaded fields in the tables are part of the template and consequently not open for input.
55
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
A.2 References
The references, identified by the module code number, are given in Table A.1.
Table A.1 —References
Reference Reference document
M1-9
M1-13
M2-2
M3-1
M4-1
M5-4
M5-5
M6-2
M7-2
56
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
fODA;hr
flea;hr;SUP
fODA;hr
flea;hr;SUP
fODA;hr
flea;hr;SUP
fODA;hr
A.4.4 Nominal heat recovery temperature efficiency and constants for the velocity
dependence
The nominal temperature efficiencies and values for the constants C1 and C2 are given in Table A.6.
57
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Table A.6 — Nominal temperature efficiencies and values for the constants
HEAT_REC_TYPE
Parameter Unit PLATE ROT_NH ROT_HYG ROT_SORP PUMP_CIRC OTHER
cross flow counter flow
η hr;nom —
vhr;nom m/s
C1
C2
58
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
59
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Table A.10 — Specific humidification pump energy power consumption for different humidifier
types and control strategies
HUM_TYPE HUM_CTRL Specific energy qm;w;HU,des
pel,HU,des kg/h
kWh/m3
CONTACT NO_CTRL
NO_CTRL
ROT_SPRAY ON_OFF
SPEED
HI_PRES SPEED
HYBRID ON_OFF
STEAM — — —
OTHER — — —
IN_AIR
OUTS_AIR
60
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
61
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Annex B
(informative)
B.1 General
The template in Annex A to this standard shall be used to specify the choices between methods, the
required input data and references to other standards.
NOTE 1 Following this template is not enough to guarantee consistency of data.
NOTE 2 Informative default choices are provided in Annex B. Alternative values and choices can be imposed by
national / regional regulations. If the default values and choices of Annex B are not adopted because of the
national / regional regulations, policies or national traditions, it is expected that:
— national or regional authorities prepare data sheets containing the national or regional values and choices, in
line with the template in Annex A; or
— by default, the national standards body will add or include a national annex (Annex NA) to this standard, in
line with the template in Annex A, giving national or regional values and choices in accordance with their
legal documents.
NOTE 3 The template in Annex A is applicable to different applications (e.g. the design of a new building,
certification of a new building, renovation of an existing building and certification of an existing building) and for
different types of buildings (e.g. small or simple buildings and large or complex buildings). A distinction in values
and choices for different applications or building types could be made:
— by adding columns or rows (one for each application), if the template allows;
— by including more than one version of a Table (one for each application) , numbered consecutively as a, b, c,…
For example: Table NA.3a, Table NA.3b;
— by developing different national / regional data sheets for the same standard. In case of a national annex to
the standard these will be consecutively numbered (Annex NA, Annex NB, Annex NC, …).
NOTE 4 In the section “Introduction” of a national / regional data sheet information can be added, for example
about the applicable national / regional regulations.
NOTE 5 For certain input values to be acquired by the user, a data sheet following the template of Annex A,
could contain a reference to national procedures for assessing the needed input data. For instance, reference to a
national assessment protocol comprising decision trees, tables and pre-calculations.
The shaded fields in the tables are part of the template and consequently not open for input.
B.2 References
The references, identified by the module code number, are given in Table B.1.
62
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
M1-9
EN ISO 52000-1, Energy performance of buildings — Overarching EPB
assessment — Part 1: General framework and procedures (ISO 52000-1)
EN ISO 52010-1, Energy performance of buildings - External climatic conditions -
M1-13
Part 1: Conversion of climatic data for energy calculations (ISO 52010-1)
EN ISO 52016-1, Energy performance of buildings — Calculation of the energy
M2-2 needs for heating and cooling, internal temperatures and heating and cooling load
in a building or building zone — Part 1: Calculation procedures (ISO 52016-1)
EN 15316-1, Heating systems in buildings — Method for calculation of system
M3-1
energy requirements and system efficiencies — Part 1: General
EN 16798-9, Energy performance of buildings — Part 9: Ventilation for
M4-1 buildings — Module M4-1 — Calculation methods for energy requirements
Calculation methods for energy requirements of cooling systems — General
prEN 16798-3, Energy performance of buildings — Part 3: Ventilation for non-
M5-4 residential buildings — Performance requirements for ventilation and room-
conditioning systems
EN 16798-7, Energy performance of buildings — Part 7: Ventilation for buildings
M5-5 — Module M5-5 — Calculation methods for the determination of air flow rates in
buildings including infiltration
EN ISO 52016-1, Energy performance of buildings — Calculation of the energy
M6-2 needs for heating and cooling, internal temperatures and heating and cooling load
in a building or building zone — Part 1: Calculation procedures (ISO 52016-1)
EN ISO 52016-1, Energy performance of buildings — Calculation of the energy
M7-2 needs for heating and cooling, internal temperatures and heating and cooling load
in a building or building zone — Part 1: Calculation procedures (ISO 52016-1)
63
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
B.4.4 Nominal heat recovery temperature efficiency and constants for the velocity
dependence
The nominal temperature efficiencies and values for the constants C1 and C2 are given in Table B.6.
64
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Table B.6 — Nominal temperature efficiencies and values for the constants
HEAT_REC_TYPE
Parameter Unit PLATE ROT_NH ROT_HYG ROT_SORP PUMP_CIRC OTHER
cross flow counter flow
η hr;nom — 0,60 0,85 0,69 0,67 0,69 0,71
vhr;nom m/s 3,5
C1 − 0,0201 − 0,0201 − 0,0643 − 0,0684 − 0,0665 − 0,0491
C2 1,0
Φhr;max kW n/a n/a from design calculation or inspection n/a
n rot;max min− 1 n/a n/a 20 20 20 n/a
Phr;rot;max kW n/a n/a 0,12 0,12 0,12 n/a
p el;hr;pu;max kWh/m 3 n/a n/a n/a n/a n/a 0,03
fpl;hr;min — n/a n/a n/a n/a n/a 0,5
Δp SUP+ETA;des;hr Pa 300 500 400 500
65
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Depending on size
A ahu;ETA m2
(q V;ETA;ahu;nom )
W/m 2
Uahu;ETA K
1,0
ΣPel;V;ctrl kW 0,1
66
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Table B.10 — Specific humidification pump energy power consumption for different humidifier
types and control strategies
HUM_TYPE HUM_CTRL Specific energy pel,HU,des qm;w;HU,des
kWh/m3 kg/h
CONTACT NO_CTRL 0,01
NO_CTRL 0,20
ROT_SPRAY ON_OFF 0,20
from design or inspection
SPEED 0,20
HI_PRES SPEED 0,04
HYBRID ON_OFF 0,02
STEAM — — —
OTHER — — —
IN_AIR 1,0
OUTS_AIR 0,6
67
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
68
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
69
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Annex C
(normative)
C.1 Calculation
C.1.1 Temperature difference
The temperature difference by preheating or –cooling in the ground is:
U du ⋅ A s
−
e qV ; SUP ρ a c a
(
∆ϑ gnd = ϑ gnd − ϑ e 1 −
)
(C.1)
where
t
ϑ gnd = ϑ e ; mn ; an + ( ϑ e ;max; m − ϑ e ; mn ; an ) ⋅ e −ξ ⋅ cos 2π ⋅ an − ξ − ft (C.2)
8760
where
π ⋅ ρ gnd ⋅ c gnd
ξ = z⋅ (C.3)
λ gnd ⋅ 8760 ⋅ 3600
where
ρ gnd kg/m 3 is the density of the ground material; default values see Table C.2
cgnd J/(kg K) is the specific heat of the ground material; default values see
Table C.2
λgnd W/(m K) is the conductivity of the ground material; default values see
Table C.2
z m is the depth in the ground
70
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The time shift factor to correct the time position of the minimal ground temperature factor is:
2 ⋅ t an ;min
ft =π +1 (C.4)
8760
where
tan;min h is the time of the year when the monthly mean outdoor air temperature is minimal
(depends on regional climate conditions); default values see Table C.1
The heat transfer coefficient of the ground heat exchanger is:
−1
do
1 1 1
U du = ⋅ ⋅ ln 2 + (C.5)
2π λ du di hi
2
where
ϑm ϑ m v 0,75
2
h i = 4, 13 + 0, 23 ⋅ − 0, 0077 ⋅ ⋅ (C.6)
100 100 d i 0 ,25
where
ϑm °C is the average air temperature in the duct; to avoid iteration, this can be simplified by
setting ϑm = ϑe
v m/s is the velocity of the air in the duct
C.1.2 Moisture difference
The moisture difference by preheating or –cooling in the ground is:
∆x gnd = x ODA ; gnd − x e (C.7)
The moisture content of the outdoor air leaving the ground heat exchanger is:
p p ;ODA ; gnd
x ODA ; gnd = min x e ; 0, 622 ⋅ (C.8)
p atm − p p ;ODA ; gnd
where the partial pressure of the outdoor air leaving the ground heat exchanger is:
p ODA ; gnd ; sat ⋅ ϕ ODA ; gnd ;max
p p ;ODA ; gnd = (C.9)
100
where
φODA;gnd;max % is the maximum relative humidity of the air leaving the ground heat exchanger
(input); it can be assumed to be 100 %
71
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
The saturation pressure of the air leaving the ground heat exchanger is:
17 ,62(ϑ e +∆ϑ gnd )
243 ,12 + (ϑ e +∆ϑ gnd )
p ODA ; gnd ; sat = 611, 2 ⋅ e (C.10)
C.2 Data
Table C.1 — Time of minimum outdoor air temperature and time shift factor
Time of the year
with the monthly
mean minimum Time shift factor
Month of mean minimum outdoor air outdoor air ft
temperature temperature
tan;min
h —
January 350 1,08 * π
February 1 100 1,25 * π
March 1 800 1,41 * π
November 7 650 2,75 * π
December 8 400 2,92 * π
72
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Annex D
(informative)
D.1 Calculation
D.1.1 Heat recovery
The correction factor for the rotation number for rotary heat exchangers is:
e1
n rot
fn = C3 − C 4 + C5 (D.1)
n rot ;max
where
n rot min− 1 is the rotation number of the rotor
n rot;max min− 1 is the maximum rotation number of the rotor
C3 to C5 are constants
e1 - as an exponent
The temperature efficiency necessary to reach the supply air set point temperature is:
— if ϑODA;preh = ϑETA;hr:in
η hr;req = 0 (D.2a)
— else
For rotary heat exchangers, HEAT_REC_CTRL = SPEED and the rotation number in case of controlled
heat recovery is calculated as:
1
fn ; req − C3 e1
n rot = n rot ;max ⋅ min 1 ; − − C5 (D.3)
C4
where
η hr ; req
fn ; req = (D.4)
η hr ; nom ⋅ fq ⋅ fv
73
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
— If HEAT_REC_TYPE = ROT_HYG
where
C6 to C8 are constants, depending on heat recovery type
The saturation moisture content of the outdoor air xe;sat is calculated as:
p e ; sat
x e ; sat = 0, 622 ⋅ (D.6)
p atm − p e ; sat
where the saturation pressure p e;sat is:
17,62ϑ e
243,12 +ϑ e
p e ; sat = 611, 2 ⋅ e (D.7)
D.1.2.2 Correction factor for the mass flow relation other than 1
The correction factor for the mass flow relation other than 1 is:
qV ; ETA ; ahu − q V ; SUP ; ahu
fq ; x = 1 − C 9 +1 (D.8)
qV ; SUP ;ahu ⋅ fODA ;min
where
C9 -
ia a constant, depending on the heat recovery type
D.1.2.3 Correction factor for the air velocity
where
C10, C11
are constants, depending on the heat recovery type
D.1.2.4 Correction factor for the rotation number
where
C12 to C14 are constants
e2 - is an exponent
74
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
D.2 Data
The values for the constants, depending on the heat recovery type, are given in Table D.1.
Table D.1 — Constants for the calculation
HEAT_REC_TYPE
Parameter ROT_NH ROT_HYG ROT_SORP
C3 1,018 2
C4 0,035 2
C5 0,276
e1 − 2,7
C6 248 129 16,4
C7 − 0,240 0,357 0,918
C8 — 23,8 —
Δxe;nom 0,005 kg/kg dry air
C9 0,1 0,1 0,1
C10 − 0,200 − 0,152 − 0,098
C11 1,0
C12 1,053 3
C13 80 000
C14 15
e2 –4
75
BS EN 16798-5-1:2017
EN 16798-5-1:2017 (E)
Bibliography
[1] CEN/TR 16798-6, Energy performance of buildings — Part 6: Ventilation for buildings — Modules
M5-6, M5-8, M 6-5, M6-8, M7-5, M7-8 — Calculation methods for energy requirements of ventilation
and air conditioning systems — Technical report — Interpretation of the requirements in
EN 16798-5-1 and EN 16798-5-2
[2] EN 16798-5-2, Energy performance of buildings — Modules M5-6, M5-8 — Ventilation for
buildings — Calculation methods for energy requirements of ventilation systems — Part 5-2:
Distribution and generation (revision of EN 15241) — method 2
[3] EN 16798-7, Energy performance of buildings — Part 7: Ventilation for buildings — Module M5-
5 — Calculation methods for the determination of air flow rates in buildings including infiltration
[4] CEN/TS 16628, Energy Performance of Buildings — Basic Principles for the set of EPB standards
[5] CEN/TS 16629, Energy Performance of Buildings — Detailed Technical Rules for the set of EPB-
standards
[6] EN 15316-1, Heating systems in buildings — Method for calculation of system energy requirements
and system efficiencies — Part 1: General
[7] EN 16798-9, Energy performance of buildings — Part 9: Ventilation for buildings — Module M4-
1 — Calculation methods for energy requirements Calculation methods for energy requirements of
cooling systems — General
[8] CEN ISO/TR 52000-2, Energy performance of buildings — Overarching EPB assessment — Part 2:
Explanation and justification of ISO 52000-1 (ISO 52000-2)
[9] EN ISO 52010-1, Energy performance of buildings — External climatic conditions — Part 1:
Conversion of climatic data for energy calculations (ISO 52010-1)
[10] EN ISO 52016-1, Energy performance of buildings — Calculation of the energy needs for heating
and cooling, internal temperatures and heating and cooling load in a building or building zone —
Part 1: Calculation procedures (ISO 52016-1)
[11] ASHRAE Handbook of Fundamentals. SI Edition, F01. Psychrometrics, 2013
76
This page deliberately left blank
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW
Buying standards PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
You can buy and download PDF versions of BSI publications, including British revised or replaced.
and adopted European and international standards, through our website at
To f nd out more about becoming a BSI Subscribing Member and the bene f ts
bsigroup.com/shop, where hard copies can also be purchased.
of membership, please visit bsigroup.com/shop.
If you need international and foreign standards from other Standards Development
With a Multi-User Network Licence (MUNL) you are able to host standards
Organizations, hard copies can be ordered from our Customer Services team.
publications on your intranet. Licences can cover as few or as many users as you
Copyright in BSI publications wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email subscriptions@bsigroup.com.
All the content in BSI publications, including British Standards, is the property
of and copyrighted by BSI or some person or entity that owns copyright in the
information used (such as the international standardization bodies) and has
Revisions
Our British Standards and other publications are updated by amendment or revision.
formally licensed such information to BSI for commercial publication and use.
We continually improve the quality of our products and services to benef t your
Save for the provisions below, you may not transfer, share or disseminate any
business. If you f nd an inaccuracy or ambiguity within a British Standard or other
portion of the standard to any other person. You may not adapt, distribute,
BSI publication please inform the Knowledge Centre.
commercially exploit, or publicly display the standard or any portion thereof in any
manner whatsoever without BSI’s prior written consent.
Useful Contacts
Storing and using standards Customer Services
Standards purchased in soft copy format: Tel: +44 345 086 9001
• A British Standard purchased in soft copy format is licensed to a sole named
Email (orders): orders@bsigroup. com
user for personal or internal company use only. Email (enquiries): cservices@bsigroup. com
• The standard may be stored on more than 1 device provided that it is accessible Subscriptions
by the sole named user only and that only 1 copy is accessed at any one time. Tel: +44 345 086 9001
• A single paper copy may be printed for personal or internal company use only. Email: subscriptions@bsigroup. com
Standards purchased in hard copy format: Knowledge Centre
• A British Standard purchased in hard copy format is for personal or internal Tel: +44 20 8996 7004
company use only. Email: knowledgecentre@bsigroup.com
• It may not be further reproduced – in any format – to create an additional copy.
This includes scanning of the document.
Copyright & Licensing
Tel: +44 20 8996 7070
If you need more than 1 copy of the document, or if you wish to share the Email: copyright@bsigroup. com
document on an internal network, you can save money by choosing a subscription
product (see ‘Subscriptions’). BSI Group Headquarters
389 Chiswick H igh Road London W4 4AL UK