Professional Documents
Culture Documents
Electricity: Estimating The Dielectric Constant of Water in The Decimeter-Wave (UHF) Range
Electricity: Estimating The Dielectric Constant of Water in The Decimeter-Wave (UHF) Range
Electricity Physics
Electromagnetic oscillations and waves Leaflets P3.7.2.4
Decimeter waves
Estimating
the dielectric constant of water
in the decimeter-wave
(UHF) range
Principles
Dielectric materials attenuate the electric field between the l1 1
= (III)
plates of a capacitor, increasing the capacitance. The factor by l0 √ ε
which the capacitance increases is called the dielectric con- l1: wavelength in water, l0: wavelength in air
stant ε.
This experiment demonstrates this contraction phenomenon
Electromagnetic waves can also propagate in dielectric mate- using decimeter waves (UHF, n = 433.92 MHz) with the aid of
rials. However, their phase velocity two dipole antennas of different lengths. Here, the absorption
c=l⋅n (I) of the decimeter waves by the two dipoles is observed in air
l: wavelength, n: frequency and in water. Each of the two dipoles is provided with an
incandescent lamp at its middle extending above the sur-
is less than in vacuum (ε = 1), and is a function of the dielectric rounding water, which lights up when resonant absorption of
constant. We can say the decimeter waves at the appropriate wavelength occurs.
c0 The condition for resonant absorption is:
c(ε) = (II)
√ε l
s= (IV)
c0: speed of light in a vacuum 2
As water molecules have a permanent dipole moment, the The lengths s of the two dipoles have been matched to the
dielectric constant ε of water is high. In contrast, we can experiment such that resonant absorption of the electromag-
assume the dielectric constant of air as 1 as a sufficiently close netic waves will occur in one of the two, depending on the
approximation. As the frequency n remains constant in each respective propagation medium. This allows us to estimate the
case, the wavelength of electromagnetic waves in water is wavelength l of the decimeter waves both in the air and in
shortened considerably as compared to propagation in air. The water.
“contraction factor” can be deduced from (1) and (II), and we
can say that:
Fig. 1: Experiment setup for estimating the dielectric constant of water in the decimeter-wave range
0908-Sel/Wit
1
P3.7.2.4 LD Physics Leaflets
Measuring example
Apparatus The lamp of the long l/2 dipole lights up in the empty tank.
s0 = 31.5 cm.
1 UHF transmitter . . . . . . . . . . . . . . . 587 55
1 Plug-in unit 230 V AC/12 V AC . . . . . . . 562 791 The lamp of the short l/2 dipole lights up when the tank is filled
1 Set of dipoles in water tank . . . . . . . . . 587 54 with water. s1 = 6 cm.
1 Saddle base . . . . . . . . . . . . . . . . . 300 11
Additionally required:
Additional information
Safety notes It is important to understand that the estimation of
wavelengths from the lengths of the dipoles is only approxi-
Experiment setups using the UHF transmitter may not
mate. The resonance condition at l/2 applies for the elemen-
always conform to the limit values of class A (group 2 of
tary (Hertzian) dipole with the diameter D = 0. For diameters D
the standard EN 55011). The device can interfere with
> 0, however, a contraction factor becomes apparent for the
other equipment in the experiment room of the educational
overall length, and the bandwidth is increased due to a flatter
facility. Also, radio interference can occur up to a distance
resonance curve of the antenna. In addition, the resonance
of several hundred meters. It is the responsibility of the
condition is affected by the built-in light bulb.
user to take all precautions to ensure that equipment
installed outside of the experiment room can continue to
function properly.
See the information contained in the Instruction Sheet
of your UHF transmitter.
Do not operate the transmitter longer than is required
to conduct the experiment; when the experiment is
concluded, shut down the device immediately by
switching off the plug-in supply unit.
LD DIDACTIC GmbH ⋅ Leyboldstrasse 1 ⋅ D-50354 Hürth ⋅ Phone (02233) 604-0 ⋅ Telefax (02233) 604-222 ⋅ E-mail: info@ld-didactic.de
© by LD DIDACTIC GmbH Printed in the Federal Republic of Germany
Technical alterations reserved