SIVACON S8plus Arc fault protection

in low-voltage switchboards

Unrestricted | © Siemens 2024 | SI EA


Testing under arc fault protection

Not required in IEC 61439-1/2

These is a voluntary tests either at the discretion of the manufacturer or the


subject of an agreement between the manufacturer and the user

Seite 2 Unrestricted | © Siemens 2024 | SI EA


Arc fault in low-voltage
switchboards

Origin and impact


Seite 3 Unrestricted | © Siemens 2024 | SI EA
Definition of arc fault

free burning short-circuit through air arising from a fault between live parts of different potential
and/or between live parts and other conductive parts within an assembly.

Serial arc faults Parallel arc faults


Origin LX -LX LX - Land LX -ON

Temperature Up to approx. 6 000° C Up to approx. 13 000°C (base points approx. 20 000°C)


Current In the range of the nominal Up to the level of short-circuit current
current

Seite 4 Unrestricted | © Siemens 2024 | SI EA


Origin and effects of arc faults

Seite 5 Unrestricted | © Siemens 2024 | SI EA


Effects of an arc fault as part of an arc fault test

Seite 6 Unrestricted | © Siemens 2024 | SI EA


Causes of arc faults in low-voltage switchgear

Seite 7 Unrestricted | © Siemens 2024 | SI EA


Impact of an arc flash
for assembly
and operator

Unrestricted | © Siemens 2024 | SI EA


Downtime costs

8.000 – Costs on average for an


unplanned shutdown in Oil &
Gas or Automotive Industry.
€20,000/
min
Quelle: senseye.io The True Cost of Downtime 2022

Seite 9 Unrestricted | © Siemens 2024 | SI EA


What does the IEC have to say?

Unrestricted | © Siemens 2024 | SI EA


Standards - Technical Report

IEC/TR 61641
Enclosed low-voltage switchgear
and controlgear assemblies

Guide for testing under conditions of


arcing due to internal fault

Seite 11 Unrestricted | © Siemens 2024 | SI EA


Arc fault zones according to standard

Arc tested zone


Part of a circuit or compartment where the ignition of
an arc is made and all selected criteria
for the assessment of the test(s) are fulfilled

Arc ignition protected zone Part of a circuit within an assembly where specific
measures are provided to ensure the initiation of an
arcing fault is a remote possibility

Seite 12 Unrestricted | © Siemens 2024 | SI EA


Arc fault protection according to standard

Personnel protection

Assembly protection

Seite 13 Unrestricted | © Siemens 2024 | SI EA


Limiting effects of an internal arcing to a defined area

Seite 14 Unrestricted | © Siemens 2024 | SI EA


Test setup of an arc fault test

Seite 15 Unrestricted | © Siemens 2024 | SI EA


Criteria according to IEC/TR 61641

Criteria

1 Doors and covers do not open Arcing class A Arcing class B Arcing class C Arcing
Personnel Personnel Personnel class I
2 No parts of the switchgear combination are
protection protection and protection and
thrown away assembly assembly
protection protection
3 No holes due to burnout of the arc fault on the
outer parts of the housing designated as freely
accessible
4 The indicators do not ignite
5 The protective conductor circuit for touchable
parts of the enclosure is still effective

6 The arc fault is limited to the defined area of


the switchgear and switchgear combination

7
After the fault has been rectified or after the
affected functional units have been
disconnected or removed in the defined area,
emergency operation of the remaining
switchgear combination is possible

Seite 16 Unrestricted | © Siemens 2024 | SI EA


Preventive and passive
Protective measures

Unrestricted | © Siemens 2024 | SI EA


Preventive measures to avoid arc faults
Proper planning in SIMARIS project/curves

Seite 18 Unrestricted | © Siemens 2024 | SI EA


Terms and definitions

• Rated operating voltage Ue

• Design short-term resistance Icw

• Switching capacity of the incoming breakers, or outgoing breakers Icu

• Permissible short-circuit current under arcing conditions Ip arc

• Permissible arc duration tarc or test duration td

• Permissible conditional short-circuit current under arcing conditions Ipc arc

• Permissible short-circuit current under self-extinguishing arcing conditions Ips arc

Seite 19 Unrestricted | © Siemens 2024 | SI EA


Measure to avoid electric arc faults
Uniform operating concept

Seite 20 Unrestricted | © Siemens 2024 | SI EA


Measures to prevent and limit arc faults

Preventive protective measures


• Prevention of operator errors due to interlocks
• Insulation of live parts
• Main busbar, customer connection
• Use of shutters
• Withdrawable units, ACB 3WA
• Coding of withdrawable units

Reactive protective measures


• Arc-proof hinge and locking systems
• Protective measures on front ventilation openings
• Pressure relief dampers in the roof
• Arc Fault Barriers

Seite 21 Unrestricted | © Siemens 2024 | SI EA


Test under arcing condition

Seite 22 Unrestricted | © Siemens 2024 | SI EA


Thermal effects over time

Seite 23 Unrestricted | © Siemens 2024 | SI EA


Active arc fault protection

Unrestricted | © Siemens 2024 | SI EA


Arc Detection
Integration and testing according to IEC/TS 63107

Components
02 02 02 02 02 02
01 Basic unit AQ110 for
12 Sensor (IACD)

02 02 Optical Sensors (light)


05
03 Current transformer (in incomer)
04
04
Circuit breaker (incomer)
with voltage release 5 % ED
01
05 Arc quenching device (AQD)
02 03
Combined sensor
06 (Light and Pressure)

02 02 02 02 02 06

Seite 25 Unrestricted | © Siemens 2024 | SI EA


Effects of pressure over time

Seite 26 Unrestricted | © Siemens 2024 | SI EA


Design of AQD

Seite 27 Unrestricted | © Siemens 2024 | SI EA


Limitation of active measures to pressure and temperature

IACD+AQD

IACD+AQD

IACD+ACB

Seite 28 Unrestricted | © Siemens 2024 | SI EA


Test with activated arc quenching device

Seite 29 Unrestricted | © Siemens 2024 | SI EA


Advantages of AQD

Reusable
Two full-load operations under
fault conditions
with simple reset mechanism

Testable

up to 100 test cycles

Seite 30 Unrestricted | © Siemens 2024 | SI EA


Summary – Conclusion

Unrestricted | © Siemens 2024 | SI EA


Summary – Conclusion

Arc fault as a worst-case Conversion of large amounts of energy in Effects: Flash of light, large current surge,
in an assembly the shortest possible time – considerable explosive pressure surge
potential of damage

Considerable downtime costs possible –


Definition by IEC 61439-2, IEC/TR 61641, Differentiation according to arc flash avoidance/limitation of the arc fault
IEC/TS 63107 categories (A, B, C, I) necessary

Active arc fault mitigation


Preventive, passive and with IACD+AQD Measures to reduce/minimize damage
active measures Active arc fault detection with IAMS and downtime costs

Seite 32 Unrestricted | © Siemens 2024 | SI EA


Whitepaper
Arc fault prevention and protection

Download Whitepaper

Seite 33 Unrestricted | © Siemens 2024 | SI EA


Visit us at the Hannover fair

© Deutsche Messe AG
22/04/24 – 26/04/24 Hall 9

Seite 34 Unrestricted | © Siemens 2024 | SI EA


Contact
Siemens AG Siemens AG
Andreas Stoecker Martin Sichting
Product Manager SIVACON S8plus Promoter SIVACON S8plus
Suedstr. 74 Schützenstr. 4-10
04178 Leipzig 04103 Leipzig
GERMANY GERMANY

+49 (152) 28864828 +49 (152) 02385384


stoecker.andreas@siemens.com martin.sichting@siemens.com

Seite 35 Unrestricted | © Siemens 2024 | SI EA


Thank you for attending the webinar

If you are interested in our upcoming


Watch
or past webinars register for free here:
our past
https://www.siemens.com/electrification-automation-webinars
webinars

Stay up to date with subscriptions?


www.siemens.com/ea-subscriptions
Subscribe

Looking for trainings?


Visit our http://www.siemens.com/poweracademy
trainings

Seite 36 Unrestricted | © Siemens 2024 | SI EA


Contact / Disclaimer
Published by Siemens 2024

Smart Infrastructure
Electrification & Automation
Mozartstraße 31 C
91052 Erlangen
Germany
For the U.S. published by
Siemens Industry Inc.
100 Technology Drive
Alpharetta, GA 30005
United States

© Siemens 2024
Subject to changes and errors. The information given in this
document/video only contains general descriptions and/or performance
features which may not always specifically reflect those described, or
which may undergo modification in the course of further development of
the products. The requested performance features are binding only
when they are expressly agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens,
its affiliated companies or other companies whose use by third parties
for their own purposes could violate the rights of the respective owner.

Unrestricted | © Siemens 2024 | SI EA

You might also like