First, pls press down “PRG” key on the panel , and use the arrow key to choose
the parameter you need.
STEP 1.Set FP-01=1,it’ll restore all the setting to factory default setting.
STEP 3.Confirm the direction of the motor and whether the limit signal is correct.
(Pls ensure F0-01=1)D1-D4 light is on the operation panel
a. Manually rotate the motor to clockwise, if D2 light is brightening ,the signal is correct.
b. Manually rotate the motor to another direction, if D2 light be off, the signal is correct.
c. Manually rotate the motor, pls check D3 light whether flashing when you rotate the motor
per round, if no maybe the signal is incorrect. If the direction of a,b step is opposite, pls
change UVW of the motor any two phase, then return to STEP 2.
d.If the closing door limit signal is effective,D1 light will brighten; If the opening door limit
signal is effective,D4 light will brighten.
STEP 4.Self-learning the distance of the door. (Before this step pls install whole the electrical
door)
1.Set Opening door parameter:
F300=8HZ
F301=0.5S
F303=30HZ
F304=0.5
F305=3HZ
F306=0.5S
2. Set Closing door parameter:
F400=8HZ
F401=0.5S
F403=30HZ
F404=0.5
F405=3HZ
F406=0.5S