6.

Characteristics and Dimensions


Miniature Circuit Breakers

BH Type BH BH-P
Number of poles 1 2 3 1 2 3
BH-P Rated current (A)
70 70, 100 70, 100 70 70, 100 70, 100
at ambient temperature 40°C
AC 230/400 230/400
Rated voltage (V)
DC 125 125

Breaking IEC60898 AC230/400V 3 — 3 —


capacity AC400V — 3 — 3
(kA) sym. — DC125V 1 1

Type BH Type BH-P

■Operating Characteristics ■Ambient Compensating Curve


4h
Operating Characteristics
2h Type:BH, BH-P 140
Rated Current:70, 100A
1h 135
Amb. temp.:40°C
30min 130
20min 125

Rated ambient
Current rating (%)
14min
10min 120

6min 115
4min 70, 100A
110
2min 105

1min 100

95
30s
Operating time

20s 90
Max. 85
10s
0 10 20 30 40 50 60

5s Ambient temperature (°C)


Min.
2s

1s

0.5s

0.2s

0.1s

0.05s

0.02s

0.01s
1 1.13 1.45 2 3 4 5 6 7 10 15 20 30 40

×100% of rated current

■Outside Dimension Diagram


Plug-in terminal
•BH Mtg bracket
M5 × 0.8 screw 32 •BH-P (line side)
7.5

(line side & load side)


57.5

71.5

74

M5 x 0.8
100
113
73
95

57

95

screw

Breaker
center

25 25 25 60.5
Mtg slot
25 50 57.5
25 50 75 65.5
25 50 75 Mtg hole ø4.5
63.5
77.5
22 47 47 20.5 45.5 70.5 79

Bus t max. =4
.5
ø5
6
5.5

12
4.5

1-pole 2-pole 3-pole Bus drilling


13.5

14
1-pole 2-pole 3-pole
Note: Two mounting brackets are used for single-pole breakers.