Different Types of Relay (7SR11/7SR12)

Connection Summary

Arrangement of Terminals
Connection Diagram
Different Types of Relay (REF 615)
X120

X130

Connection Summary

Arrangement of Terminals
Connection Diagram
Different Types of Relay (Micom)

Connection Summary

Arrangement of Terminals Connection Diagram


Basic Parameters of Protection Settings
IEC Standard Inverse Curve Formula

Here,

IFault = Fault Current (A)

IPickup = Pickup Current (A)


Basic Parameters of Protection Settings
Protection Parameters Representation by Different Manufacturers
Type Siemens ABB Micom
Pickup 51-1 Setting Start value (PHLPTOC1) I>
Overcurrent

Curve Type 51-1 Char Operating curve type Idmt([50/51] Phase OC)
Protection

(PHLPTOC1)
TMS 51-1 Time Mult Time multiplier Tms ([50/51] Phase OC)
(PHLPTOC1)
Instantaneous 50-1 Setting Start value (PHIPTOC1) I>>>
Pickup 51N-1 Setting Start value (EFLPTOC1) Ie>
Earth Fault

Curve Type 51N-1 Char Operating curve type Idmt ([50N/51N] E/Gnd)
Protection

(EFLPTOC1)
TMS 51N-1 Time Mult Time multiplier Tms ([50N/51N] E/Gnd)
(EFLPTOC1)
Instantaneous 50N-1 Setting Start value (EFIPTOC1) Ie>>>
Present Co-ordination Plan

Relay/ ACR Protection Pick up Inst. Setting


Curve TMS
Position Type (A) (A)
OC 180 IEC-SI 0.07 1000
33kV XR
Incomer
EF 30 IEC-SI 0.05 500
Outdoor
10MVA OC Max 200 IEC-SI 0.05 2000
11kV
Outgoing
EF 50 or 30 IEC-SI 0.15 1500

OC Pick up< 1MW (60A)


OC Pick up> 1MW (60A)