SanDrgNo3 16c
SanDrgNo3 16c
SanDrgNo3 16c
ROOF
CONNECTION OF VENTILATING
STACK TO DISCHARGE STACK
AT A POINT NOT LESS THAN 150mm
ABOVE THE SPILL OVER LEVEL OF THE
TOP MOST SOIL SANITARY APPLIANCE
OR FLOOR TRAPWHICHEVER IS HIGHER
wb wb
wc(p) wc(p)
lb lb UPPER
ft ft STOREY
MIN /
075mm VENTILATING STACK
/
050mm VENTILATING PIPE TO
CONNECT TO VENTILATING CROSS VENTING TO BE PROVIDED:
STACK AT AN ANGLE OF 45
a) AT MID HEIGHT (for building up to 20 storey).
ABOVE SPILL OVER LEVEL OF
b) EVERY 10 storey (for building higher than 20 storey).
SOIL SANITARY APPLIANCE OR
FLOOR TRAP WHICHEVER See Drawing No. 3-21
a for details.
IS HIGHER wb
wc(p)
lb THIRD
ft STOREY
/ /
075mm x 0100mm ADAPTOR
MIN /
0100mm SECONDARY DISCHARGE STACK
wb u
wc(p) SECOND
fw ft ut STOREY
MIN /
0100mm DISCHARGE STACK
CROSS VENTING
MIN /
0100mm DISCHARGE PIPE
NO DISCHARGE PIPE CONNECTION
MIN 225
AT SHADED AREA ALL THE WAY
TO IC
wc(p)
FIRST
ft STOREY/GROUND FLOOR
300
SCALES
ISSUED: DEC 2021 FULLY VENTILATED SYSTEM
NOT
(WITH SECONDARY DISCHARGE STACK)
TO WATER RECLAMATION (NETWORK) DEPARTMENT
LAST REVIEWED: N OV 2021
SCALE FOR ALL BUILDINGS DRAWING NO. 3-16c