KIRII DrywallStudco
KIRII DrywallStudco
!
Sapporo Factory
!
Shiga Factory
!
Ibaragi Factory
!
kyushu Factory
Contents
Page
Introduction 1
Partition Steel Framing System Limiting Heights of 0.5 & 0.6mm Members 3
Lateral Bracing 8
Architectural Specifications 10
Introduction
1
Partition Steel Framing System
Flange
Flange
Table 1 : Availability of stud dimensions and steel thicknesses
Flange Height
Product Stud Width Uncoated Steel Thickness (mm)
inch (mm) inch (mm) inch (mm) inch (mm)
Code
inch (mm) 11/4 32 13/4 45 2 50 3 76 0.5 0.6 0.8 1.0 1.2 1.5 2.3
WS-134 3
1 /4 45
• •
WS-200 2 50
• • • • • • • •
WS-212 21/2 64
• • • • • • • • •
WS-300 3 76
• • • • • • • • •
WS-358 35/8 92
• • • • • • • • •
WS-400 4 102
• • • • • • • • •
WS-500 5 127
• • • • • •
WS-600 6 152
• • • • • •
WS-800 8 200
• •
* WS-400 4 102
• •
* WS-500 5 127
• •
* WS-600 6 152
Non-standard width of stud can be customized to suit individual design and application with an agreed quantity.
• •
* Subject to minimum order and agreed quantity.
2
Partition Steel Framing System
Limiting Heights:
1. Limiting heights calculated are based on the theoretical properties of steel stud and deflection limits of L/120; L/240; and L/360 resulted from
a uniform load of 5psf (240Pa) on partition surface, per ASTM C754 and GA-600 Gypsum Association. Limiting heights shown vary with steel
thickness; steel grade; stud dimensions; stud spacing; allowable deflection limits; and design load level.
2. The design data shown are according to strength and deflection calculations, assuming all stud members being simply supported on a single
span; with unperforated section properties; and full lateral support to both flanges in flexure.
3. Proposed stud framing system may also be designed to conform to prevailing codes e.g. BS 5950 Part 5:1998 "Structural use of steelwork in
Building - Code of practice for design of cold formed thin gauge sections".
3
Partition Steel Framing System
Limiting Heights:
1. Limiting heights calculated are based on the theoretical properties of steel stud and deflection limits of L/120; L/240; and L/360 resulted from
a uniform load of 5psf (240Pa) on partition surface, per ASTM C754 and GA-600 Gypsum Association. Limiting heights shown vary with steel
thickness; steel grade; stud dimensions; stud spacing; allowable deflection limits; and design load level.
2. The design data shown are according to strength and deflection calculations, assuming all stud members being simply supported on a single
span; with unperforated section properties; and full lateral support to both flanges in flexure.
3. Proposed stud framing system may also be designed to conform to prevailing codes e.g. BS 5950 Part 5:1998 "Structural use of steelwork in
Building - Code of practice for design of cold formed thin gauge sections".
4
Partition Steel Framing System
Limiting Heights:
1. Limiting heights calculated are based on the theoretical properties of steel stud and deflection limits of L/120; L/240; and L/360 resulted from
a uniform load of 5psf (240Pa) on partition surface, per ASTM C754 and GA-600 Gypsum Association. Limiting heights shown vary with steel
thickness; steel grade; stud dimensions; stud spacing; allowable deflection limits; and design load level.
2. The design data shown are according to strength and deflection calculations, assuming all stud members being simply supported on a single
span; with unperforated section properties; and full lateral support to both flanges in flexure.
3. Proposed stud framing system may also be designed to conform to prevailing codes e.g. BS 5950 Part 5:1998 "Structural use of steelwork in
Building - Code of practice for design of cold formed thin gauge sections".
5
Partition Steel Framing System
Limiting Heights:
1. Limiting heights calculated are based on the theoretical properties of steel stud and deflection limits of L/120; L/240; and L/360 resulted
from a uniform load of 5psf (240Pa) on partition surface, per ASTM C754 and GA-600 Gypsum Association. Limiting heights shown
vary with steel thickness; steel grade; stud dimensions; stud spacing; allowable deflection limits; and design load level.
2. The design data shown are according to strength and deflection calculations, assuming all stud members being simply supported on
a single span; with unperforated section properties; and full lateral support to both flanges in flexure.
3. Proposed stud framing system may also be designed to conform to prevailing codes e.g. BS 5950 Part 5:1998 "Structural use of
steelwork in Building - Code of practice for design of cold formed thin gauge sections".
6
Partition Steel Framing System
Limiting Heights:
1. Limiting heights calculated are based on the theoretical properties of steel stud and deflection limits of L/120; L/240; and L/360 resulted from
a uniform load of 5psf (240Pa) on partition surface, per ASTM C754 and GA-600 Gypsum Association. Limiting heights shown vary with steel
thickness; steel grade; stud dimensions; stud spacing; allowable deflection limits; and design load level.
2. The design data shown are according to strength and deflection calculations, assuming all stud members being simply supported on a single
span; with unperforated section properties; and full lateral support to both flanges in flexure.
3. Proposed stud framing system may also be designed to conform to prevailing codes e.g. BS 5950 Part 5:1998 "Structural use of steelwork in
Building - Code of practice for design of cold formed thin gauge sections".
7
Partition Steel Framing System
Lateral Bracing
• To brace studs when using single deflection channel stud widths 21/2”, 3”, 35/8”, 4”, 5” and 6”.
system.
bracer channel
screw attachment
8
Partition Steel Framing System
Metal Beads
L-Bead
9
Partition Steel Framing System
Architectural Specifications
PART 1 - MATERIALS 2) Studs to be cut 1/4” (6mm) short of the assembly height to
1) Non-loadbearing wall framing shall be STUDCO Partition Steel twist to secure by friction fit. Space studs at 24” (610mm)
Framing System complying with ASTM C645 standard and maximum centers with open sides facing the same direction.
manufactured by KIRII (HONG KONG) LIMITED. Studs located adjacent to door and window frames, partition
2) C-shaped studs with 45mm height of flanges, hot-dip intersection, and corners shall be anchored to runner flanges
galvanized and shall be in one continuous length. Web of by screws or by crimping at each stud and runner flange.
1) Gypsum wallboard shall be BPB ‘ProRoc’ Regular / Moisture 4) Set fastener heads slightly indented from the surface without
recommendations.
10
General Construction Details
11
General Construction Details
12
!"#$%&
KIRII CONSTRUCTION MATERIAL CO., LTD.
HEAD OFFICE:
IMPERIAL TOWER 18TH FLOOR, UCHISAIWAI-CHO 1-1-1, CHIYODAKU,
TOKYO 100-0011, JAPAN
TEL : (81-3) 3539-6710 FAX : (81-3) 3539-6690
!"#$%