LT Panel Specification-Botanical Garden

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 32

LT

Sr.No. Material/Item

LT Panel is totally inclosed outdoor type, dust and vermin proof.


-Main Switchboard suitable for use at 415 V.
- The Panels are free standing floor mounted compartmental type 3B/4B constructi
for load bearing members wherever necessary.
- 3-phase 4 wire 50 Hz system suitable for symmetrical fault level, fabricated from 2
including 3 mm thick gland plate at bottom and including lifting hook and including
-Prefered switchgear Make : CT make - KAPA/ Matrix - Resin Cast , MFM - Shcneide
- The front doors are hinged type , provided with Gasket ,Neoprene, such that the p
- The gland plates are 3mm thick drilled and are provided for cable entry on bottom
-The Panels are Pre- treated by 7 tank process and powder coated for RAL 7035/70
- Hinged doors for feeders and cable alleys will be provided.
- Bolted covers for bus bar chamber will be provided.
- Power cables will be provided of adequate size and with crimping type lugs.
General Notes: - All control wiring will be done using 1.5 sq. mm PVC insulated stranded copper wi
- For CT wiring 2.5 sq. mm PVC insulated stranded copper wire of 600/1100 V grade
Interlocking type ferrule having printed letters/numbers at both ends of the cables
- Name plate/ Tag plate shall be provided on doors of engraved aluminum anodized
-Danger plates will be fixed on bus compartments
Terminal Markers will be provided on terminals for easy identification.
- Terminals will be of Elmex/ Phoenix/ Wago/Connectwell make.
- Terminal will be mounted on din rail
The main/ distribution bus bars are 3ph, 4 wire with neutral 100 % rating of main p
The clearance between Phase to Phase and Phase to Neutral are maintained in co
The panels are sectionalised for ease of transporation.
The system is solidly earthed.
Cables shall be of Havels/Polycab make as per approved specifications
The Bus bars are suitably supported with DMC Supports.
LT Panel is front operated dead front cubicle type MV distribution board is totally in
3-phase 4 wire 50 Hz system suitable for symmetrical fault level 50 KA at 415 V, fab
angle/channel/flat section including 3 mm thick gland plate at bottom and includin
notice plate required.
Switchgear and accessories-
A. 1 in / 1 out ICOG Panel :- 1 Nos.- 4P,2500A,50 KA Microprocessor based ACB EDO
- Under voltage, Over voltage protection,Short ckt protection, over load-over curre
- Spreader link & separator with Aux. & trip contact + shunt coil (240 V AC),
- ACB shall be complete with 3 nos. 2500 A / 5A, 15 VA, 5P10 CT for protection.
- Emergency push button.
- 3 Phase SPD TYPE 1+2, 40 kA.
- 1 nos. Timer for automatic ACB On (at the time of power cut).
Metering and indication :
- 1 set of R,Y,B phase indication lamp with suitable MCB
- indicating lamp to indicates ACB ON,OFF & TRIP
- Separate fault indication for overload, S/C, E/F, provide on panel door.
- MFM 0.5s class - 1 Nos. with 2500/5 A - 3 nos. CT- Class 0.5s, 15VA, Resin Cast, Ins
- Switch and socket 16/6 Amp - 1 nos. with control mcb and neutral link.
- Busbar 4P,415V,2500A, 50KA, BUS BAR Aluminium busbar (1 Sec @ current densit
- Metal double compressor Gland for-
1 Main ACB Panel
Input side: 7 Nos. for - 4C x 400 sq mm ALU armoured XLPE cable
Output side:
7 Nos. for - 4C x 400 sq mm ALU armoured XLPE cable

- Cable entry: Entry-Bottom/TOP


- 7 tank power coated metal enclosure, (IP 55) Double Door outdoor type panel
- All components should be labeled & Dangerous stickers also provide.
- Stand Mounting.
- Thermostat + Space Heater (80/100W) in Cable Chamber - 1 Nos. (in Outgoing).
- INCOMING AND OUTGOING CABLE CHAMBER SHALL BE SEPERATE and BUSBAR ar
- 3 Point door lock.
- Panel illumination LED Light in Outgoing and incoming Chamber with Door limit sw
- A.C supply-based PLC for controlling Load and tripping with Hooter (1nos provide
- 6" Exhaust fan on both side with polycarbonate Louver
- Louver with Filter (1 nos in Incoming side and 2 nos in outgoing side.
- Danger Sticker on Outer Door and Acrylic window in Incoming side.
- Announciator (12 window)
- RTD (PT-100)/3 wire temp. Sensor -Pin type ( Mounted on B/B) - 4nos
- Libratherm make digital temp. / process scanner - 1nos
- Mimic Diagram ON AL PLATE
LT Panel is front operated dead front cubicle type MV distribution board is totally in
3-phase 4 wire 50 Hz system suitable for symmetrical fault level 50 KA at 415 V, fab
angle/channel/flat section including 3 mm thick gland plate at bottom and includin
notice plate required.
Switchgear and accessories-
A. INCOMING :- 1 Nos.- 4P,2500A,50 KA Microprocessor based ACB EDO Type, LSIG
- Negative phase sequence, Reverse power protection relay
- ACB shall be complete with 3 nos. 2500 A / 5A, 15 VA, 5P10 CT for protection.
- Emergency push button.
- 3 Phase SPD TYPE 1+2, 40 kA.
- 1 nos. Timer for automatic ACB On (at the time of power cut).
- A.C supply-based PLC for controlling Load and tripping with Hooter (1nos provide
Metering and indication :
- 1 set of R,Y,B phase indication lamp with suitable MCB
- indicating lamp to indicates ACB ON,OFF & TRIP
- Separate fault indication for overload, S/C, E/F, provide on panel door.
- MFM 0.5s class - 1 Nos. with 2500/5 A - 3 nos. CT- Class 0.5s, 15VA, Resin Cast, Ins

Outgoing :- 4 Nos.-4P,1000A,50 KA Microprocessor based MCCB with LSIG protec


4 Nos - MFM 0.5s class - with 2500/5 A - 3 nos. CT- Class 0.5s, 15VA, Re
MAIN DISTRIBUTION For capacitor bank: 1 Nos.- 3P,1000 A,36 KA Microprocessor based MCCB with O/C
PANEL -indicating lamp to indicates ON,OFF & TRIP for outgoing Feeder.
2
(IP 55 Double Door, - Switch and socket 16/6 Amp - 1 nos. with control mcb and neutral link.
Outdoor type) - Busbar 4P,415V,2500A, 50KA, BUS BAR Aluminium busbar (1 Sec @ current densit
- Metal double compressor Gland for-
Input side: 7 Nos. for - 4C x 400 sq mm ALU armoured XLPE cable
Output side:
9 Nos. for - 4C x 300 sq mm ALU armoured XLPE cable

- Cable entry: Entry - TOP


- 7 tank power coated metal enclosure, (IP 55) Double Door outdoor type panel
- All components should be labeled & Dangerous stickers also provide.
- Chanel mounting.
- Thermostat + Space Heater (80/100W) in Cable Chamber - 1 Nos. (in Outgoing).
- INCOMING AND OUTGOING CABLE CHAMBER SHALL BE SEPERATE.
- 3 Point door lock.
- Panel illumination LED Light in Outgoing and incoming Chamber with Door limit sw
- 6" Exhaust fan on both side with polycarbonate Louver
- Louvers with Filters at Incoming side and outgoing side.
- Danger Sticker on Outer Door and Acrylic window in Incoming side.
-Announciator (12 window)
- RTD (PT-100)/3 wire temp. Sensor -Pin type ( Mounted on B/B) - 4nos
- Libratherm make digital temp. / process scanner - 1nos
- Mimic Diagram ON AL PLATE
A. INCOMING - Main MCCB :1 Nos.- 4P, 1000A ,50 KA Microprocessor MCCB with O
For fast charger, Outgoing 4 Pole MCCB: 4 NOS- 4P,100A,25KA
For fast charger, Outgoing 4 Pole MCCB: 4 NOS- 4P,160A,25KA
For slow charger, Outgoing 4 Pole MCB: 15 NOS- 4P,63A,16KA

B. Emergency Push Button at front door


C. Switch and socket 16/6 Amp - 1 nos. with control mcb and neutral link.
D. 1 nos MFM for Main 1000/5 A- 3 Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast ch
Link.
F. R-Y-B indication and ON-OFF-Trip Indication Lamp
G. Earthing provided - 2 Nos. on bottom both left – right side of panel
H. Busbar 4P,415V,1000A, 50KA, BUS BAR Aluminium busbar for Main busbar (1 Se
Busbar 4P,415V,630A, 50KA, BUS BAR Aluminium busbar for Fast charger (1 Sec @
I. Metal double compressor Gland for-
Input side: 2 Nos. for - 4C x 400 sq mm ALU Armoured XLPE cable
Output side metal gland for: 4 nos. 35 sq. mm Alu Armoured XLPE cable
: 4 nos. 70 sq. mm Alu Armoured XLPE cable
Fast Charger + Slow
: 15 nos. 16 sq. mm Alu Armoured XLPE cable
3 Charge Panel -1
(IP 55 Double Door)
K. 7 tank power coated metal enclosure, OUTDOOR type (IP 55) Double Door
L. All components should be labeled & Dangerous stickers also provide.
M. Stand mounting (Stand height-500mm & 50x50x5 mm Angle Stand) and Panel C
N. Thermostat + Space Heater (80/100W) in Outgoing Cable Chamber - 1 Nos.
O. INCOMING AND OUTGOING CABLE CHAMBER SHALL BE SEPERATE.
Q. 3 Point door lock.
R. Stud type terminal / Spring loaded terminal.
R. Panel illumination LED Light in Outgoing and incoming Chamber with Door limit s
T. 6" Exhaust fan on both side with polycarbonate Louver.
U. Louver with Filter (1 nos in Incoming side and 2 nos in outgoing side.
V. Danger Sticker on Outer Door and Acrylic window in Incoming side.
W. Panel door opening for cable termination should be back side.
ON-OFF-Trip Indication Lamp for all outgoing MCCB-100A and 160A MCCB feeder
Y. Feeder name should be per as layout of GA are hub charger details
Z. RTD (PT-100)/3 wire temp. Sensor -Pin type ( Mounted on B/B) - 4nos
AA .Libratherm make digital temp. / process scanner - 1nos
AB. Mimic Diagram
A. INCOMING - Main ACB :1 Nos.- 4P, 1250A ,50 KA Microprocessor ACB,EDO type
For fast charger, Outgoing 4 Pole MCCB: 2 NOS- 4P,100A,25KA
For fast charger, Outgoing 4 Pole MCCB: 5 NOS- 4P,160A,25KA
For slow charger, Outgoing 4 Pole MCB: 17 NOS- 4P,63A,16KA
B. Emergency Push Button at front door
C. Switch and socket 16/6 Amp - 1 nos. with control mcb and neutral link.
D. 1 nos MFM for Main 1000/5 A- 3 Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast c
Link.
F. R-Y-B indication and ON-OFF-Trip Indication Lamp
G. Earthing provided - 2 Nos. on bottom both left – right side of panel
H. Busbar 4P,415V,1000A, 50KA, BUS BAR Aluminium busbar for Main busbar (1 Se
Busbar 4P,415V,630A, 50KA, BUS BAR Aluminium busbar for Fast charger (1 Sec @
I. Metal double compressor Gland for-
Input side: 2 Nos. for - 4C x 400 sq mm ALU Armoured XLPE cable
Output side metal gland for: 2 nos. 35 sq. mm Alu Armoured XLPE cable
: 5 nos. 70 sq. mm Alu Armoured XLPE cable
Fast Charger + Slow : 17 nos. 16 sq. mm Alu Armoured XLPE cable
4 Charge Panel-2 J. Cable entry: Entry-Bottom
(IP 55 Double Door) K. 7 tank power coated metal enclosure, OUTDOOR type (IP 55) Double Door
L. All components should be labeled & Dangerous stickers also provide.
M. Stand mounting (Stand height-500mm & 50x50x5 mm Angle Stand) and Panel C
N. Thermostat + Space Heater (80/100W) in Outgoing Cable Chamber - 1 Nos.
O. INCOMING AND OUTGOING CABLE CHAMBER SHALL BE SEPERATE.
Q. 3 Point door lock.
R. Stud type terminal / Spring loaded terminal.
R. Panel illumination LED Light in Outgoing and incoming Chamber with Door limit s
T. 6" Exhaust fan on both side with polycarbonate Louver.
U. Louver with Filter (1 nos in Incoming side and 2 nos in outgoing side.
V. Danger Sticker on Outer Door and Acrylic window in Incoming side.
W. Panel door opening for cable termination should be back side.
ON-OFF-Trip Indication Lamp for all outgoing MCCB-100A and 160A MCCB feeder
Y. Feeder name should be per as layout of GA are hub charger details
Z. RTD (PT-100)/3 wire temp. Sensor -Pin type ( Mounted on B/B) - 4nos
AA .Libratherm make digital temp. / process scanner - 1nos
AB. Mimic Diagram
A. INCOMING - Main ACB :1 Nos.- 4P, 1250A ,50 KA Microprocessor ACB with O/C
For fast charger, Outgoing 4 Pole MCCB: 3 NOS- 4P,100A,25KA
For fast charger, Outgoing 4 Pole MCCB: 4 NOS- 4P,160A,25KA
For slow charger, Outgoing 4 Pole MCB: x20 NOS- 4P,63A,16KA, 2 Pole MCB: 7 N
B. Emergency Push Button at front door
C. Switch and socket 16/6 Amp - 1 nos. with control mcb and neutral link.
D. 1 nos MFM for Main 1250/5 A- 3 Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast c
Link.
F. R-Y-B indication and ON-OFF-Trip Indication Lamp
G. Earthing provided - 2 Nos. on bottom both left – right side of panel
H. Busbar 4P,415V,1250A, 50KA, BUS BAR Aluminium busbar for Main busbar (1 Se
Busbar 4P,415V,800A, 50KA, BUS BAR Aluminium busbar for Fast charger (1 Sec @
I. Metal double compressor Gland for-
Input side: 3 Nos. for - 4C x 400 sq mm ALU Armoured XLPE cable
Output side metal gland for: 3 nos. 35 sq. mm Alu Armoured XLPE cable
: 4 nos. 70 sq. mm Alu Armoured XLPE cable
Fast Charger + Slow : 20 nos. 16 sq. mm Alu Armoured XLPE cable
4 Charge Panel-3 J. Cable entry: Entry-Bottom
(IP 55 Double Door) K. 7 tank power coated metal enclosure, OUTDOOR type (IP 55) Double Door
L. All components should be labeled & Dangerous stickers also provide.
M. Stand mounting (Stand height-500mm & 50x50x5 mm Angle Stand) and Panel C
N. Thermostat + Space Heater (80/100W) in Outgoing Cable Chamber - 1 Nos.
O. INCOMING AND OUTGOING CABLE CHAMBER SHALL BE SEPERATE.
Q. 3 Point door lock.
R. Stud type terminal / Spring loaded terminal.
R. Panel illumination LED Light in Outgoing and incoming Chamber with Door limit s
T. 6" Exhaust fan on both side with polycarbonate Louver.
U. Louver with Filter (1 nos in Incoming side and 2 nos in outgoing side.
V. Danger Sticker on Outer Door and Acrylic window in Incoming side.
W. Panel door opening for cable termination should be back side.
ON-OFF-Trip Indication Lamp for all outgoing MCCB-100A and 160A MCCB feeder
Y. Feeder name should be per as layout of GA are hub charger details
Z. RTD (PT-100)/3 wire temp. Sensor -Pin type ( Mounted on B/B) - 4nos
AA .Libratherm make digital temp. / process scanner - 1nos
AB. Mimic Diagram
A. INCOMING - Main MCCB :1 Nos.- 4P, 1000A ,50 KA Microprocessor MCCB with O
For fast charger, Outgoing 4 Pole MCCB: 6 NOS- 4P,100A,25KA
For fast charger, Outgoing 4 Pole MCCB: 3 NOS- 4P,160A,25KA
For slow charger, Outgoing 4 Pole MCB: 18 NOS- 4P,63A,16KA

B. Emergency Push Button at front door


C. Switch and socket 16/6 Amp - 1 nos. with control mcb and neutral link.
D. 1 nos MFM for Main 1000/5 A- 3 Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast ch
Link.
F. R-Y-B indication and ON-OFF-Trip Indication Lamp
G. Earthing provided - 2 Nos. on bottom both left – right side of panel
H. Busbar 4P,415V,1000A, 50KA, BUS BAR Aluminium busbar for Main busbar (1 Se
Busbar 4P,415V,630A, 50KA, BUS BAR Aluminium busbar for Fast charger (1 Sec @
I. Metal double compressor Gland for-
Input side: 2 Nos. for - 4C x 400 sq mm ALU Armoured XLPE cable
Output side metal gland for: 6 nos. 35 sq. mm Alu Armoured XLPE cable
: 3 nos. 70 sq. mm Alu Armoured XLPE cable
Fast Charger + Slow
: 18 nos. 16 sq. mm Alu Armoured XLPE cable
3 Charge Panel -4
(IP 55 Double Door)
K. 7 tank power coated metal enclosure, OUTDOOR type (IP 55) Double Door
L. All components should be labeled & Dangerous stickers also provide.
M. Stand mounting (Stand height-500mm & 50x50x5 mm Angle Stand) and Panel C
N. Thermostat + Space Heater (80/100W) in Outgoing Cable Chamber - 1 Nos.
O. INCOMING AND OUTGOING CABLE CHAMBER SHALL BE SEPERATE.
Q. 3 Point door lock.
R. Stud type terminal / Spring loaded terminal.
R. Panel illumination LED Light in Outgoing and incoming Chamber with Door limit s
T. 6" Exhaust fan on both side with polycarbonate Louver.
U. Louver with Filter (1 nos in Incoming side and 2 nos in outgoing side.
V. Danger Sticker on Outer Door and Acrylic window in Incoming side.
W. Panel door opening for cable termination should be back side.
ON-OFF-Trip Indication Lamp for all outgoing MCCB-100A and 160A MCCB feeder
Y. Feeder name should be per as layout of GA are hub charger details
Z. RTD (PT-100)/3 wire temp. Sensor -Pin type ( Mounted on B/B) - 4nos
AA .Libratherm make digital temp. / process scanner - 1nos
AB. Mimic Diagram

1 Nos.- 4P, 100A ,25 KA MCCB with O/C ,S/C protection, with spreader, Rotary hand
R/Y/B Indication Light
Stand mounting, and Panel Confirming IP 55, Outdoor type
metal gland for: 1 nos. 35 sq. mm Alu Armoured XLPE cable
1 nos. 25 sq. mm CU Armoured XLPE cable
6 MCCB BOX-100A
Cable entry & Exite shall be bottom side
I. 7 tank power coated metal enclosure, OUTDOOR type (IP 55).
J. All components should be labeled & Dangerous stickers also provide.
K. Stand mounting and Panel Confirming IP 55.
N. Danger Sticker on Outer Door and Acrylic sheet window in Incoming side.
1 Nos.- 4P, 160A ,25 KA MCCB with O/C ,S/C with spreader, Rotary handle, earthing
R/Y/B Indication Light
Stand mounting, and Panel Confirming IP 55, Outdoor type
metal gland for: 1 nos. 70 sq. mm Alu Armoured XLPE cable
1 nos. 35 sq. mm CU Armoured XLPE cable
7 MCCB BOX-160A
Cable entry & Exite shall be bottom side
- 7 tank power coated metal enclosure, OUTDOOR type (IP 55).
- All components should be labeled & Dangerous stickers also provide.
- Stand mounting and Panel Confirming IP 55.
- Danger Sticker on Outer Door and Acrylic sheet window in Incoming side.
LT Panel Specification - Botanical Garden, Noida project
Description

type, dust and vermin proof.


at 415 V.
mounted compartmental type 3B/4B construction or other wise non compartmental design ,conforming IEC 60439 manuf
er necessary.
ble for symmetrical fault level, fabricated from 2 mm thick CRCA MS Steel with hinged, GASKETTED and lockable door havin
bottom and including lifting hook and including G.I earth strip required size with 2 earthing terminals including powder coa
ke - KAPA/ Matrix - Resin Cast , MFM - Shcneider 6400NG/Secure Elite 440 , MCCB - L&T Make-(DN Series),Shcneider
provided with Gasket ,Neoprene, such that the panels are dust and vermin proof in conformity with Degree Of Protection.
illed and are provided for cable entry on bottom of the panel.
nk process and powder coated for RAL 7035/7032
e alleys will be provided.
r will be provided.
dequate size and with crimping type lugs.
ng 1.5 sq. mm PVC insulated stranded copper wire of 600/1100 V grade.
lated stranded copper wire of 600/1100 V grade will be used.
nted letters/numbers at both ends of the cables for easy identification & maintenance proposes shall be provided.
ovided on doors of engraved aluminum anodized with black background
compartments
on terminals for easy identification.
ix/ Wago/Connectwell make.
ail
3ph, 4 wire with neutral 100 % rating of main phase bus bar.
hase and Phase to Neutral are maintained in conformity with IEC 60439.
e of transporation.

ake as per approved specifications


d with DMC Supports.
nt cubicle type MV distribution board is totally inclosed outdoor, dust and vermin proof.
e for symmetrical fault level 50 KA at 415 V, fabricated from 2 mm thick CRCA MS Steel with hinged, GASKETTED and lockab
g 3 mm thick gland plate at bottom and including lifting hook and including G.I earth strip required size with 2 earthing term

4P,2500A,50 KA Microprocessor based ACB EDO TYPE.


ction,Short ckt protection, over load-over current and restricted Earth fault protection.
x. & trip contact + shunt coil (240 V AC),
2500 A / 5A, 15 VA, 5P10 CT for protection.

n (at the time of power cut).

p with suitable MCB


N,OFF & TRIP
oad, S/C, E/F, provide on panel door.
/5 A - 3 nos. CT- Class 0.5s, 15VA, Resin Cast, Insulation Class - E, Type- BPL ,Freq.-50 Hz (Meter - Schneider 6400ng+) with S
os. with control mcb and neutral link.
BAR Aluminium busbar (1 Sec @ current density 0.8)
or-
sq mm ALU armoured XLPE cable

0 sq mm ALU armoured XLPE cable

sure, (IP 55) Double Door outdoor type panel


d & Dangerous stickers also provide.

00W) in Cable Chamber - 1 Nos. (in Outgoing).


E CHAMBER SHALL BE SEPERATE and BUSBAR arrangement for incoming and outgoing side cable termination.

tgoing and incoming Chamber with Door limit switch


ng Load and tripping with Hooter (1nos provide in outer door) and push button (2 nos. Accept & Reset provide in outer door
olycarbonate Louver
ng side and 2 nos in outgoing side.
Acrylic window in Incoming side.

-Pin type ( Mounted on B/B) - 4nos


rocess scanner - 1nos
nt cubicle type MV distribution board is totally inclosed outdoor, dust and vermin proof.
e for symmetrical fault level 50 KA at 415 V, fabricated from 2 mm thick CRCA MS Steel with hinged, GASKETTED and lockab
g 3 mm thick gland plate at bottom and including lifting hook and including G.I earth strip required size with 2 earthing term

0 KA Microprocessor based ACB EDO Type, LSIG protection, with Aux. & trip contact + shunt coil (240 V AC),
e power protection relay
2500 A / 5A, 15 VA, 5P10 CT for protection.

n (at the time of power cut).


ng Load and tripping with Hooter (1nos provide in outer door) and push button (2 nos. Accept & Reset provide in outer door

p with suitable MCB


N,OFF & TRIP
oad, S/C, E/F, provide on panel door.
/5 A - 3 nos. CT- Class 0.5s, 15VA, Resin Cast, Insulation Class - E,Freq.-50 Hz (Meter - Schneider 6400ng+) with Short Link

A Microprocessor based MCCB with LSIG protection with Aux. & trip contact + shunt coil (240 V AC),with ON, OFF & Trip ind
- with 2500/5 A - 3 nos. CT- Class 0.5s, 15VA, Resin Cast, Insulation Class - E,Freq.-50 Hz (Meter - Schneider 6400ng+) with S
A,36 KA Microprocessor based MCCB with O/C, S/C & E/F protection with spreader & separator with Aux. & trip contact + s
F & TRIP for outgoing Feeder.
os. with control mcb and neutral link.
BAR Aluminium busbar (1 Sec @ current density 0.8)
or-
sq mm ALU armoured XLPE cable

0 sq mm ALU armoured XLPE cable

sure, (IP 55) Double Door outdoor type panel


d & Dangerous stickers also provide.

00W) in Cable Chamber - 1 Nos. (in Outgoing).


E CHAMBER SHALL BE SEPERATE.

tgoing and incoming Chamber with Door limit switch


olycarbonate Louver
de and outgoing side.
Acrylic window in Incoming side.

-Pin type ( Mounted on B/B) - 4nos


rocess scanner - 1nos
4P, 1000A ,50 KA Microprocessor MCCB with O/C ,S/C,E/F protection with Aux. &trip contact -Auxillary contact (2c/o) - shu
MCCB: 4 NOS- 4P,100A,25KA
MCCB: 4 NOS- 4P,160A,25KA
e MCB: 15 NOS- 4P,63A,16KA

door
nos. with control mcb and neutral link.
Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast chargers 630/5 A- 3 Nos. CT- Class 0.5s 15VA,1 nos MFM for Slow chargers 40

p Indication Lamp
ttom both left – right side of panel
US BAR Aluminium busbar for Main busbar (1 Sec @ current density 0.8),
AR Aluminium busbar for Fast charger (1 Sec @ current density 0.8), Busbar 4P,415V,400A, 50KA, BUS BAR Aluminium busb
for-
sq mm ALU Armoured XLPE cable
os. 35 sq. mm Alu Armoured XLPE cable
nos. 70 sq. mm Alu Armoured XLPE cable
nos. 16 sq. mm Alu Armoured XLPE cable

sure, OUTDOOR type (IP 55) Double Door


d & Dangerous stickers also provide.
00mm & 50x50x5 mm Angle Stand) and Panel Confirming IP 55.
100W) in Outgoing Cable Chamber - 1 Nos.
LE CHAMBER SHALL BE SEPERATE.

d terminal.
utgoing and incoming Chamber with Door limit switch.
polycarbonate Louver.
ming side and 2 nos in outgoing side.
d Acrylic window in Incoming side.
mination should be back side.
outgoing MCCB-100A and 160A MCCB feeder X.Mimic diagram requried
yout of GA are hub charger details
r -Pin type ( Mounted on B/B) - 4nos
/ process scanner - 1nos
4P, 1250A ,50 KA Microprocessor ACB,EDO type with O/C ,S/C,E/F protection with Aux. &trip contact -Auxillary contact (2c/o
MCCB: 2 NOS- 4P,100A,25KA
MCCB: 5 NOS- 4P,160A,25KA
e MCB: 17 NOS- 4P,63A,16KA
door
nos. with control mcb and neutral link.
3 Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast chargers 630/5 A- 3 Nos. CT- Class 0.5s 15VA,1 nos MFM for Slow chargers 4

p Indication Lamp
ttom both left – right side of panel
US BAR Aluminium busbar for Main busbar (1 Sec @ current density 0.8),
AR Aluminium busbar for Fast charger (1 Sec @ current density 0.8), Busbar 4P,415V,400A, 50KA, BUS BAR Aluminium busb
for-
sq mm ALU Armoured XLPE cable
os. 35 sq. mm Alu Armoured XLPE cable
nos. 70 sq. mm Alu Armoured XLPE cable
nos. 16 sq. mm Alu Armoured XLPE cable

sure, OUTDOOR type (IP 55) Double Door


d & Dangerous stickers also provide.
00mm & 50x50x5 mm Angle Stand) and Panel Confirming IP 55.
100W) in Outgoing Cable Chamber - 1 Nos.
LE CHAMBER SHALL BE SEPERATE.

d terminal.
utgoing and incoming Chamber with Door limit switch.
polycarbonate Louver.
ming side and 2 nos in outgoing side.
d Acrylic window in Incoming side.
mination should be back side.
outgoing MCCB-100A and 160A MCCB feeder
yout of GA are hub charger details
r -Pin type ( Mounted on B/B) - 4nos
/ process scanner - 1nos
4P, 1250A ,50 KA Microprocessor ACB with O/C ,S/C,E/F protection with Aux. &trip contact -Auxillary contact (2c/o) - shunt c
MCCB: 3 NOS- 4P,100A,25KA
MCCB: 4 NOS- 4P,160A,25KA
e MCB: x20 NOS- 4P,63A,16KA, 2 Pole MCB: 7 NOS- 4P,40A,16KA
door
nos. with control mcb and neutral link.
3 Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast chargers 800/5 A- 3 Nos. CT- Class 0.5s 15VA,1 nos MFM for Slow chargers 6

p Indication Lamp
ttom both left – right side of panel
US BAR Aluminium busbar for Main busbar (1 Sec @ current density 0.8),
AR Aluminium busbar for Fast charger (1 Sec @ current density 0.8), Busbar 4P,415V,630A, 50KA, BUS BAR Aluminium busb
for-
sq mm ALU Armoured XLPE cable
os. 35 sq. mm Alu Armoured XLPE cable
nos. 70 sq. mm Alu Armoured XLPE cable
nos. 16 sq. mm Alu Armoured XLPE cable

sure, OUTDOOR type (IP 55) Double Door


d & Dangerous stickers also provide.
00mm & 50x50x5 mm Angle Stand) and Panel Confirming IP 55.
100W) in Outgoing Cable Chamber - 1 Nos.
LE CHAMBER SHALL BE SEPERATE.

d terminal.
utgoing and incoming Chamber with Door limit switch.
polycarbonate Louver.
ming side and 2 nos in outgoing side.
d Acrylic window in Incoming side.
mination should be back side.
outgoing MCCB-100A and 160A MCCB feeder
yout of GA are hub charger details
r -Pin type ( Mounted on B/B) - 4nos
/ process scanner - 1nos
4P, 1000A ,50 KA Microprocessor MCCB with O/C ,S/C,E/F protection with Aux. &trip contact -Auxillary contact (2c/o) - shu
MCCB: 6 NOS- 4P,100A,25KA
MCCB: 3 NOS- 4P,160A,25KA
e MCB: 18 NOS- 4P,63A,16KA

door
nos. with control mcb and neutral link.
Nos. CT- Class 0.5s 15VA, 1 nos MFM for Fast chargers 630/5 A- 3 Nos. CT- Class 0.5s 15VA,1 nos MFM for Slow chargers 40

p Indication Lamp
ttom both left – right side of panel
US BAR Aluminium busbar for Main busbar (1 Sec @ current density 0.8),
AR Aluminium busbar for Fast charger (1 Sec @ current density 0.8), Busbar 4P,415V,400A, 50KA, BUS BAR Aluminium busb
for-
sq mm ALU Armoured XLPE cable
os. 35 sq. mm Alu Armoured XLPE cable
nos. 70 sq. mm Alu Armoured XLPE cable
nos. 16 sq. mm Alu Armoured XLPE cable

sure, OUTDOOR type (IP 55) Double Door


d & Dangerous stickers also provide.
00mm & 50x50x5 mm Angle Stand) and Panel Confirming IP 55.
100W) in Outgoing Cable Chamber - 1 Nos.
LE CHAMBER SHALL BE SEPERATE.

d terminal.
utgoing and incoming Chamber with Door limit switch.
polycarbonate Louver.
ming side and 2 nos in outgoing side.
d Acrylic window in Incoming side.
mination should be back side.
outgoing MCCB-100A and 160A MCCB feeder X.Mimic diagram requried
yout of GA are hub charger details
r -Pin type ( Mounted on B/B) - 4nos
/ process scanner - 1nos

O/C ,S/C protection, with spreader, Rotary handle, earthing link provied

ing IP 55, Outdoor type


lu Armoured XLPE cable
Armoured XLPE cable
side
ure, OUTDOOR type (IP 55).
d & Dangerous stickers also provide.
rming IP 55.
d Acrylic sheet window in Incoming side.
O/C ,S/C with spreader, Rotary handle, earthing link provied

ing IP 55, Outdoor type


lu Armoured XLPE cable
Armoured XLPE cable
side
ure, OUTDOOR type (IP 55).
d & Dangerous stickers also provide.
ming IP 55.
Acrylic sheet window in Incoming side.

`
Qty.(Nos) Remarks
0
1
1
1
1
1

14
12
SR DESCRIPTION

1 ACB

2 Moulded Case Circuit breakers > 200A

3 Moulded Case Circuit breakers <200A

4 Switch Fuse Units with HRC fuses

5 Timers in Distribution Boards


6 Cast resin current transformer (CT)-
7 Control / Potential Transformer (PT)

8 Protective Relays (Feeder Protection IDMT)

9 Selector switches
10 Push Buttons/ Indicating Lamps with LED’s
11 Indicating True RMS Meters – Digital type.

12 Energy Meters

13 MCB Distribution Boards

14 Miniature Circuit Breakers

15 RCCB
16 11 KV HT XLPE cables
17 1100 V LT XLPE Cables
18 1100 V Copper Control Cables

19
Double Compression glands and Lugs for 1100 volt grade
Cables
20 Cu / Al (Crimping type)Cable Lugs for 11000 V grade Cables
21 Cable Joint(Heat shrinkable ) HT cable termination
22 FLMAE PROOF LED LIGHTS
23 FRLS PVC conduits & Accessories (Heavy duty)
24 GI Conduits & Accessories
25 Copper Conductor FRLS PVC Insulated Wires

26 Modular Switches & Socket Outlets

27 Weather proof Switches & Sockets


28 Industrial Socket Outlets – Metal Clad type
29 Industrial Socket Outlets – Thermoplastic moulded type

30 Raceways/ PVC Trunking

31 Perforated / Ladder Type cable tray


32 11 KV HT VCB
33 11 KV HT RMU

34 11 KV HT Panel (OEM VCB Panel)

35 Distribution Transformer

36 LT panels AS PER IEC 60439

37 UPS System

 IMPORTANT: -

 Brand/Make of item will be selected by Customer and as approved before ordering.


 Detail submittals in the form of catalogues specification sheets, and samples were called for, shall be submitted one week
before procurement are made.
 Out of the approved makes of materials mentioned above, the make of materials to be used on the work shall be as decide
 In respect of materials for which approved makes are not specified above, these will be of makes to be decided by the Cus
 Equipment’s approved and supplied shall have local servicing facilities available in the region.
MAKES

ABB/Schneider /L & T

ABB/Schneider /L & T

ABB/Schneider /L & T

ABB/Schneider /L & T

ABB/Schneider /L & T
Kalpa / Newtek / Rishab /Kappa /Precise
Kalpa / Magnetic & controls / ECS

ABB/Schneider /GE/C&S

Salzer / Kaycee/ L & T


Technic / Siemens/ Schneider
TRINITY/SCHNEIDER/RISHAB

SECURE/SCHENIEDER

System house with CPRI approval

Legrand / Schneider/ Hager /ABB /L&T

Legrand / Schneider/ Hager


KEI / POLYCAB /AVOCAB
KEI / POLYCAB /AVOCAB
Avocab/ RR Cables/FINOLEX

Dowells / Comet / Jainson

Dowells / Comet / Jainson


Raychem/3M
SHREYA TECH / SUDHIR / TRI-FLP
VIP/ NELCO/PRECISION
Bharat Industries / Supreme/ AKG.
Finolex / RR Kabel /POLYCAB
Legrand- MOASIC /Anchor -ROMA/
Schneider-LIVIA
Legrand /Anchor / Schneider
Legrand / Schneider / Hager
Mennekes /Scame / NEPTUNE-Bals

Schneider/ Honey well/ Legrand.

NEIDAX / Profab / OBO BETTERMEN/


ABB/ SCHINDER / SIEMENS /L&T
ABB /SCHINDER / SIEMENS /L&T
LOTUS SWGR / LOAD CONTROLS/ ACE
ELECTROTREND /SWATI SWITCHGEAR
/or any CPRI APPROVED SYSTEM
HOUSE

VIJAY TRAFO / KIRLOSKAR


ELECTRIC/Sudhir Power / TMC India/ Essenar
/ATLAS or any BIS Approved MFg.
LOTUS SWGR / LOAD CONTROLS/ ACE
ELECTROTREND / IMPERIAL ELECTRO CONTROLS
/SWATI / HI TECH
NA

rdering.
were called for, shall be submitted one week from the date of order and approvals shall be obtained on the type of accepted make

erials to be used on the work shall be as decided by the / Customer.


hese will be of makes to be decided by the Customer and as per sample approved before procurement.
ble in the region.
Model/Accuracy/Remark
EMAX PR111/P , MASTERPACT LOGIC 6.0X,
OMEGA UW MTX 1.5Gi
(WITH SPARE NO + NC CONTACT )

SACE T-MAX -Ekip E-LSIG


PowePacT LSIG
Dsine MTX 2.0 DN 2/3
(WITH SPARE NO + NC CONTACT )

T-MAX with TMA –T4 Trip Unit, COMPACT CVS TM Release,


Dsine DN 1 TM Release,
(WITH SPARE NO + NC CONTACT )
L&T FN C LINE ABB OS SWITCH
SCHNEIDER Tysy GS
DIGITAL ONLY WITH FEEDBACK
0.5S For Metering and 5P10/20 for Protection
0.5S for Metering and 5P10/20 for Protection
CSENex 1450
ABB REJ 601 MiCOM P12X
GE P40 Agile P14N
--
--
--
Elite 440 - 0.5s
Elite 30 B - 0.5s EM 6400 - 0.5s
--
Legrand DX3 Schneider ACTi9 ABB SU204MR L&T AU10
HAGER NBN420N
--
CPRI APPROVED & TYPE TESTED FOR SPEC
CPRI APPROVED & TYPE TESTED FOR SPEC
CPRI APPROVED & TYPE TESTED FOR SPEC

ISI Marked

ISI Marked
CPRI APPROVED & TYPE TESTED FOR SPEC
As per Lumens and Fixture Type
ISI Marked
ISI Marked
Type Tested Design and Fire resistant

ISI MARKED

ISI MARKED
ISI MARKED
ISI MARKED
Type Tested Design and Fire resistant more than
2 Hrs.
>125 Micron Coating or as per specification
As Per Configuration
As per Configuration

A System House shall be CPRI Approved design for Indoor/Outdoor


application

OEM shall have CPRI Approved design for Indoor/Outdoor application


for offered Rating or Rating above required Specification.

A System House shall be CPRI Approved design for Indoor/Outdoor


application

--

he date of order and approvals shall be obtained on the type of accepted make

he / Customer.
and as per sample approved before procurement.
Ref img - MCCB BOX
MCCB BOX