InTech December 2021 - 15

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

OPERATIONS AND MAINTENANCE

FAST FORWARD
l An Excel worksheet makes it practical to
include the graphing of installed flow and
gain in the valve selection process.
l Extremely low gains are undesirable, because
a low gain means that when the valve
moves, the flow does not change by much.
l Pump selection affects installed gain and
installed flow.

be adjusted within 8 percent steps, which may cess model and the worksheet require the fol-
not be desirable. The reason for limiting the lowing information about the process:
gain change within the required flow range to • The minimum design flow, Qmin
2:1 is so it will be easier to tune the controller • The maximum design flow, Qmax
for stable and fast response throughout the re- • The valve inlet pressure at the minimum
quired flow range. design flow, P1 minQ
To calculate and graph the installed flow and • The valve inlet pressure at the maximum
gain using the reference 4 worksheet, the pro- design flow, P1 maxQ

Installed flow characteristic Installed gain


1.0 4.0
80

550
6” 550
6” 80

0.8 6”
3.0
3” 80
Relative flow, Q

3”
0.6
6” 3”
Gain

2.0
0.4
3” 550

1.0
0.2

0.0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2
Relative travel Q/Qmax

Figure 1. Control valve installed flow and installed gain characteristics comparing a properly sized 3-inch valve and an oversized 6-inch
valve in the same system. Emphasis is added to show the portion of the graphs that fall within the user’s specified flow range between
minimum and maximum required flow of 80 to 550 gpm.

WWW.ISA.ORG INTECH DECEMBER 2021 29


OPERATIONS AND MAINTENANCE

Control valve sizing: Liquid ating at about 20 percent to 78 percent


open from the minimum design flow to
the maximum design flow. An installed
flow and gain calculation yielded sur-
prising results (figure 3).
The installed flow graph shows the
minimum specified flow intersecting
the installed flow graph at 20 percent
relative travel, and the maximum de-
sign flow intersecting the installed flow
graph just a bit below 80 percent rela-
tive travel, which agrees with the user’s
calculation. What the user’s calculation
Metal seated V-port segment valve did not show is 95 percent of the valve’s
fully open flow is at the maximum de-
sign flow, leaving no safety factor at the
high end.
About 20% to 78% open At about 60 percent travel (relative
Figure 2. User’s calculation of required valve CV at maximum and minimum design flows travel of 0.6), the installed flow graph
and valve manufacturer’s CV table for a 6-inch segment ball valve. starts rounding off to a much shallower
slope. This fact is identified on the in-
stalled gain graph where the installed
Installed relative
Installed Relative flow
Flow vs.vs. relative
Relative travel
Travel Installed gain vs. Q/Qmax gain drops to below 0.5, emphasizing
1.0 4.0
95%
95%
the fact that changes in valve position
3.5
0.8
would have only a small effect on flow
Installed gain
Flowflow

3.0

0.6 2.5
in the system. The gain change from
Relative

2.0
Relative

0.4 1.5
> 4:1
the maximum design flow (Q/Qmax)
1.0
0.2
0.5 < 0.5
and the maximum gain on the graph is
0.0 0.0 greater than 4:1, making it difficult to
0.0 0.2 0.4 0.6 0.8 1.0 0 0.2 0.4 0.6 0.8 1 1.2
Relative travel
Relative Travel Q/Qmax tune the controller for fast and stable
control. It turned out the problem lies
Installed pressure
Installed Pressure Level level
with the user’s pump choice.
100

90
Reference 4 does not include the
80 ability to graph what is happening to P1
P1
Pressure

70
and P2, and thus the pressure differen-
Pressure

60

50
P2 tial available to the valve. However, the
40 reference 4 worksheet has a tabulation
30
0.0 0.2 0.4 0.6 0.8 1.0
of P1 and P2, so constructing a graph
Relative travel
Relative Travel of P1 and P2 versus relative valve travel
was simple. In the installed pressure
Figure 3. Installed characteristics of the valve proposed in figure 2. level graph, as valve relative travel
approaches 0.8 (80 percent valve trav-
• The valve outlet pressure at the mini- pressure changes in the system up- el), the pressure drop available to the
mum design flow, P2 minQ (calculated stream and downstream of the control valve decreases rapidly.
from the user’s input of the valve valve (references 5–6).
pressure drop at the minimum design Reference 4 prompted several inqui- Different pump, different valves
flow, DELTA P minQ) ries as to what applications would be The user found a pump with a slightly
• The valve outlet pressure at the maxi- candidates for installed flow and gain higher and flatter head curve. A new
mum design flow, P2 maxQ (calculated graph analysis. Below are some of the analysis of the upstream system gave
from the user’s input of the valve most common. the revised values of P1 and DELTA P
pressure drop at the maximum design shown in red in figure 4. Putting these
flow, DELTA P maxQ). Surprising results new values of P1 and DELTA P into the
The values of P1 and P2 at the mini- Figure 2 shows a user’s Excel control user’s valve-sizing program and into
mum and maximum design flow need valve-sizing worksheet. The calculated the reference 4 worksheet gives the
to be obtained by an analysis of the CV range appears to show a 6-inch seg- graphs of figure 4. The valve is now op-
frictional pressure losses and static ment ball control valve would be oper- erating between 25 percent and 75 per-

30 INTECH DECEMBER 2021 WWW.ISA.ORG

You might also like