Professional Documents
Culture Documents
Calculation of Lightning-Induced Voltages On Complex Low-Voltage Distribution Networks
Calculation of Lightning-Induced Voltages On Complex Low-Voltage Distribution Networks
Calculation of Lightning-Induced Voltages On Complex Low-Voltage Distribution Networks
ABSTRACT
In the LV lines, which are illustrated in detail in Figure 2,
This paper presents an investigation of lightning the TN system is assumed. The loads are connected
overvoltages on low-voltage (LV) networks installed in between the phase and neutral conductors, being the latter
urban areas. The combined effect of lightning-induced grounded both at the transformer station (with three
voltages and transferred lightning surges through
grounding rods) and at every service entrance (with a
distribution transformers is taken into account. It is shown
that an accurate estimate of lightning-induced voltages on
single grounding rod). As seen in Figure 2, LV lines 1
LV lines require the consideration of the medium voltage and 2 are identical. They consist each of a 240-m long
line and of its electrical connections with the LV line via the main feeder connected to eight 60-m long laterals and to
distribution transformer. It is also shown that if the stroke twelve three-phase consumers labeled as C1-1 to C1-12
location is relatively close to the evaluated LV line it is (LV line 1) and C2-1 to C2-12 (LV line 2). The main
possible to neglect the influence of other LV lines in the feeder of LV line 3 is slightly longer (300 m) but is
estimation of peak overvoltages on the connected loads. connected to only four 45-m long laterals and nine three-
phase consumers labeled as C3-1 to C3-9. LV line 4
1 INTRODUCTION
consists essentially of a single three-phase consumer load
Lightning overvoltages on LV distribution networks are (labeled as C4-1) connected directly to the transformer
caused by (i) direct strikes, (ii) induced voltages due to secondary via a 15-m long service drop.
nearby strikes, (iii) surge transfer from medium-voltage
(MV) to LV voltage lines through distribution LV line 4 (0,540)
transformers or (iv) direct strikes to nearby structures [1]. MV line configuration P12 LV line configuration
It is accepted that mechanisms ii, iii and iv are the most 1.5 m 0.7 m
MV Line 2
C B A N
likely to occur, but in most cases two or more of such N
P11 R
0.2 m
8.4 m 7.2 m S
mechanisms take place simultaneously [2-9]. The aim of 0.2 m 7.2 m
P10 LV Line 3 T
1268-1
Authorized licensed use limited to: ANNA UNIVERSITY. Downloaded on June 07,2023 at 11:22:09 UTC from IEEE Xplore. Restrictions apply.
the line parameters. The adopted transformer, surge were calculated externally and interfaced with the
arrester, and grounding models are illustrated in Figure 3. Alternative Transients Program (ATP) as described in
The transformer model of Figure 3(a) was shown in [3] to [7]. The method of characteristics [16] was used to solve
accurately reproduce the surge response of typical the transients in the line.
30-kVA (13.8 kV/220-127 V) three-phase ∆-Y
distribution transformers in loaded conditions. The VxI R1 C2 L1
Voltage (kV)
LV lines [6]. Finally, the grounding model of Figure 3(c)
25
20 1
C1 L3 R4 C5 15
is a first order, low-current (linear) approximation to the 10
5
Low-Voltage (right scale) 0.5
consisting of either one 2.4-m long electrode or three C1=493 pF, C2=94.8 pF, C3=21.5 pF, C4=50 pF, C5=759 pF
R1=14 kΩ, R2=0.8 kΩ, R3=1.1 kΩ, R4=1.6 kΩ
Current (kA)
2.4-m long vertical electrodes with a horizontal spacing L1=16 mH, L2=1.84 mH, L3=50 µH (a) (b)
of 3 m [10]. As in [2], the consumer loads were
R PARAMETERS
represented as 30-Ω resistances. They were connected to
1 rod 3 rods
the LV line through 15-m long service drops modeled as C
R(Ω) 0.346/σ 0,119/σ
twisted conductors. (c) Current injection C(nF) 0.0256εr 0.0743εr
1268-2
Authorized licensed use limited to: ANNA UNIVERSITY. Downloaded on June 07,2023 at 11:22:09 UTC from IEEE Xplore. Restrictions apply.
3 RESULTS AND ANALYSIS The obtained results are in line with the findings of
Borghetti et al. [9, 19], who have also considered the
3.1 Lightning-Induced Voltages along the MV lines effect of lightning-induced voltages on distribution lines
with complex topologies and observed the reducing effect
of distributed grounding points and surge arresters on the
Figure 4 shows lightning-induced voltages calculated at resulting overvoltages.
the primary of the distribution transformers at poles P4,
P6, P10 and P12 for stroke locations X and Y. For 3.2 Load overvoltages along LV line 2 considering
illustrative purposes, voltages at poles P5 and P2 were or not the presence of the MV lines
also included in Figures 4 (a) and (b), respectively. This
was made to illustrate the peak voltages calculated along
A common simplification adopted in the evaluation of
the MV lines for the different stroke locations (note that
lightning-induced overvoltages on LV networks is to
strictly speaking the peak voltage referring to stroke
disregard the presence of the MV line and assume that for
location Y occurs between poles P1 and P2, but it is does
relatively close stroke locations only the effect of the
not differ significantly from the one calculated at pole
incident lightning electromagnetic field is important. This
P2). As seen in Figure 4, voltage waveforms calculated at
is equivalent to neglecting the surge transfer through the
the primary of the distribution transformers present
distribution transformer in the characterization of load
relatively low magnitudes (below 60 kV) and an overall
overvoltages. In this section this hypothesis is tested with
oscillatory shape. Both features are a consequence of the
the calculation of overvoltages across loads C2-2, C2-5,
periodical grounding points and of the surge arresters
C2-7, C2-9, and C2-12 for stroke locations X (which is
installed at the transformer terminals. Interestingly, the
very close to LV line 2) and Y (which is about 600 m far
peak overvoltages calculated along the MV lines (about
from LV line 2). Figure 5(a) illustrates the resulting load
125 kV for stroke location X and nearly 80 kV for stroke
overvoltages for stroke location X considering the
location Y) are different even though the distance from
complete system of Figure 1, whereas Figure 5(b)
the stroke location to the closest point along the line is
illustrates load overvoltages calculated for the same event
the same (50 m) in both cases. This happens mostly
but without considering the connection of LV line 2 to
because voltages induced along MV line 2 contribute
MV line 1. Figures 6(a) and 6(b) do the same but for
differently to the resulting voltages along the MV line 1
stroke location Y.
depending on the considered stroke location.
1.1
140 (a) total (transferred+induced) voltages
(a) Stroke location X (x=0, y=-50) 0.9
120
P5 0.7 C2-5
100
P4 and P6 0.5 C2-2
Voltage (kV)
80
Voltage (kV)
60
0.3
C2-9
40 0.1
P10
20 -0.1
0 -0.3 C2-12
C2-7
-20 -0.5
P12
-40 -0.7
0 2 4 6 8 0 2 4 6 8
Time (us) Time (µs)
100 1.1
(b) Stroke location Y (x=-540, y=-50) (b) partial (induced-only) voltages
80 0.9
P2
0.7 C2-7 C2-5
60
0.5
Voltage (kV)
Voltage (kV)
40
0.3
P10
20 P4 0.1 C2-2
0 -0.1
C2-9
-0.3
-20
P6 P12 C2-12
-0.5
-40
-0.7
0 2 4 6 8
0 2 4 6 8
Time (us)
Time (µs)
Figure 4 – Phase-to-ground overvoltages along the MV line for Figure 5 – Phase-to-neutral overvoltages across loads connected
two different stroke locations. to LV line 2 for stroke location X (a) considering or (b) not
considering the transformer connection to MV line 1.
1268-3
Authorized licensed use limited to: ANNA UNIVERSITY. Downloaded on June 07,2023 at 11:22:09 UTC from IEEE Xplore. Restrictions apply.
0.2 affect the relative importance of the induced and
(a) total (transferred+induced) voltages
transferred surge components on resulting load
0.15 overvoltages. However, this does not change the
conclusion that a more accurate analysis of lightning-
Voltage (kV)
0.1
C2-7 induced voltages on LV networks should consider the
0.05 C2-2 surge transfer from the MV line to the LV line through
C2-9 C2-5
the distribution transformer.
0
C2-12 3.3 Load overvoltages along LV line 2 considering
-0.05 or not the presence of other LV lines
0 2 4 6 8
Time (µs)
0.2
(b) partial (induced-only) voltages Another useful evaluation regarding the system of Figure
0.15
1 is whether the presence of LV lines 1, 3 and 4 can be
neglected in the calculation of load overvoltages along
Voltage (kV)
1268-4
Authorized licensed use limited to: ANNA UNIVERSITY. Downloaded on June 07,2023 at 11:22:09 UTC from IEEE Xplore. Restrictions apply.
fact that peak overvoltages along LV line 1 are not LV line under consideration, the inclusion of nearby LV
affected by the presence of the remaining LV lines if lines may be of some importance for the characterization
stroke location Y is considered (results not shown here). of load overvoltages especially if those lines are
This happens because LV line 1 is in this case the first to illuminated by the incident electromagnetic field before
be illuminated by the incident electromagnetic field, the the line under analysis.
effect of the remaining LV lines on load overvoltages
being experienced on the tail of the calculated waveforms 0.2
(a) Complete system
as in Figure 7.
C2-7
0.15
Voltage (kV)
0.9
(a) Complete system 0.1
0.7 C2-5
0.3
C2-9 0
0.1
C2-12 C2-2
-0.1 -0.05
-0.3 C2-12 0 2 4 6 8
C2-7 Time (µs)
-0.5
0.2
-0.7 (b) Incomplete system C2-7
0 2 4 6 8
0.15
Time (µs) Voltage (kV)
0.9
(b) Incomplete system 0.1
0.7 C2-5
0.5 0.05 C2-5
C2-2
C2-9
Voltage (kV)
0.3
C2-9 0
0.1
C2-12
-0.1 C2-2
-0.05
-0.3 C2-12 0 2 4 6 8
1268-5
Authorized licensed use limited to: ANNA UNIVERSITY. Downloaded on June 07,2023 at 11:22:09 UTC from IEEE Xplore. Restrictions apply.
[6] A. De Conti and S. Visacro, “Evaluation of lightning surges [13] V. Cooray, “Horizontal fields generated by return strokes”,
transferred from medium voltage to low-voltage Radio Sci., vol. 27, pp. 529-537, 1992.
networks”, IEE Proc. Gen. Transm. Distrib., vol. 152, no. [14] M. Rubinstein, “An approximate formula for the
3, pp. 351-356, doi:10.1049/ip-gtd:20041306, 2005. calculation of the horizontal electric field from lightning at
[7] A. De Conti, S. Visacro, “Calculation of Lightning-Induced close, intermediate, and long range”, IEEE Trans. EMC,
Voltages on Low-Voltage Distribution Networks”, Proc. vol. 38, no. 3, pp. 531-535, 1996.
VIII SIPDA – Int. Symp. on Lightning Protection, São [15] A. K. Agrawal, H. J. Price, and S. H. Gurbazani,
Paulo, Brazil, pp. 483-488, 2005. “Transient response of a multiconductor transmission line
[8] A. Piantini, J. M. Janiszewski, A. Borghetti, C. A. Nucci, excited by a nonuniform electromagnetic field”, IEEE
and M. Paolone, “A scale model for the study of the LEMP Trans. EMC, vol. EMC-22, no. 2, pp. 119-129, 1980.
response of complex power distribution networks”, IEEE [16] C. R. Paul, “Analysis of multiconductor transmission
Trans. Power Del., Vol. 22, No. 1, pp. 710-720, 2007. lines”, John Wiley and Sons, 1994.
[9] A. Borghetti, A. Morched, F. Napolitano, C. A. Nucci, and [17] D. Pavanello, F. Rachidi, M. Rubinstein, J. L. Bermudez,
M. Paolone, “Lightning-induced overvoltages transferred W. Janischewskyj, V. Shostak, C. A. Nucci, A. M.
through distribution power transformers”, IEEE Trans. Hussein, and J. S. Chang, “On return stroke currents and
Power Del., vol. 24, no. 1, pp. 360-372, 2009. remote electromagnetic fields associated with lightning
[10] A. De Conti and S. Visacro, “A Simplified Model to strikes to tall structures: 1. Computational models”, J.
Represent Typical Grounding Configurations Applied in Geophys. Res., vol. 112, D13101,
Medium-Voltage and Low-Voltage Distribution Lines”, doi:10.1029/2006JD007958, 2007.
Proc. IX SIPDA – Int. Symp. on Lightning Protection, Foz [18] F. H. Silveira and S. Visacro, “Lightning effects in the
do Iguaçu, Brazil, 2007. vicinity of elevated structures”, J. Electrostatics, vol.65,
[11] C. A. Nucci, C. Mazzetti, F. Rachidi, and M. Ianoz, “On 2007.
lightning return stroke models for LEMP calculations”, [19] A. Borghetti, C. A. Nucci, and M. Paolone, “Indirect-
Proc. 19th ICLP – Int. Conf. Lightning Protection, Graz, lightning performance of overhead distribution networks
Austria, 1988. with complex topology”, IEEE Trans. Power Del., vol. 24,
[12] A. De Conti and S. Visacro, “Analytical representation of no. 4, pp. 2206-2213, 2009.
single- and double-peaked lightning current waveforms”,
IEEE Trans. EMC, vol. 49, no. 2, doi:
10.1109/TEMC.2007.897153, 2007.
1268-6
Authorized licensed use limited to: ANNA UNIVERSITY. Downloaded on June 07,2023 at 11:22:09 UTC from IEEE Xplore. Restrictions apply.