Professional Documents
Culture Documents
Lecture 1
Lecture 1
Air Conditioning
Simple Vapor
Compression Cycle
1
Pressure-Enthalpy (P-h) diagram
Critical point
Constant
entropy line
Pressure (P)
Mixture of
Subcooled liquid and Constant
liquid vapor volume line
Superheated
Constant Saturated vapor
Temperature line liquid line Saturated
vapor line
Enthalpy (h)
2
Pressure-Enthalpy (P-h) diagram
3
Pressure-Enthalpy (P-h) diagram
4
5
6
P-h diagram for R-134a
แ"
& จง บอก Pcondenior / คการ +อ P"> Evaporator
%)
.๋ย
.io 5่
มา
- /
,ก
การอบ
23๊_
d 1- 9ย # lb 7
P-h diagram for R-22
8
P-h diagram for R-22
9
P-h diagram for R-22
10
High-pressure ไฟออก T
side ๐
Pกง- DC
condansor
โแP;<๋ euaporator
D Condenser
Liquid Satligtsatvapour
มา ป?อย
กาบ @อน
BC
B
Simple
line
A
= Compressor
B Evaporator
เวลา Fก แw
Isentropic
A e-
suction
Expansion line Low-pressure
device
โชน เ"า → ๐
pแH
\ satvapar
side
A – B : Vaporizing Process แ+ น
B – C : Compression Process Heat
C – D : Condensing Process "น Exchanger .
i. +
.
... .
Condensor
รaL๋ |
^
1_zsgt.it_
คาย ถวาย@อนNอ ลด PณหST ไปU Tsat ดาบ ถกปอบ เVน เWด การ
ปน เVน
กวน
liq
X๋
ylatentheat
superheated-vapsi.rs/cmsatvaPg
YZ
-
ลก ควาย Uบ
+
Lexpansian)
" """" "
( ลด พท .
แปเ"า ]หา ]อก)
erapo_ratorsssr.it/awci+milhitkEtPE).m:ChetkE+PE) +^
evaporabrdheatt_tgl.CI ? อก หาก
evqp
เ_ออกจาก 0
e)
`e * a ihi ร
a ehe → ย . ฅํ Chehi )
r
CRefrigeralingetfecty R
E)
Compmorciseatopicslceoe lรนา
คง
_
นาเองdาไอ H compressor
fiihit^Tfน
f
-
ciwswcomp → ew s a Chi h e)
-
nmoetp
oomp)
CW
mihsmbt0wasai.my
Cheatexd_nanlciotmihismehea csmlhe-hDcictmi.br
Condx
miehy →
cic ร a Ch
4- b)
expansionrahesltntlzsystant)
mik
mihy
hyrty Chconstantl
-
i
i
nnd lhz
o
ICarnotcydetttlne.es Heatengine Pertommax
LKI
inr
¥
fg้-0.4
"et ร
WTWp
µ ๐
→
แ"
tia
TI
Ckwsius Statements
เบา
+nร
>
THl_ficoP.at t.at
น
| , .ro/boierT_7
k๊
II. -
w เ Eฑื #
เ
ฑื๋
n
k¥
l
Ta
1
B carnot aงานoอย กjบ |
สารa การqน |
1
5t_nlcn.no
|
±
+
r๋
mi Chi +
+ gti )
ร + กาย Chet s้ + gze)
tw
clstlansss-Refn.ge
rant ขา เรา ไป พjงงาน วลu พjงงาน
1
Q = W + m (h e h i ) + m (Ve2 Vi2 ) + m g ( Z e Zi )
2
Q = W + m (he hi )
14
Constant pressure heat addition in the evaporator,
A to B
๏_w๋x๋
pressure
.. .
evaporator ...
:& .
.
A
.
enthalpy
15
A B : Vaporizing Process
Vaporization takes place at a constant T and P thus this process is
both isothermal (dU = 0) and isobaric (dQ = dH).
At point B, the refrigerant is completely vaporized and is a
saturated vapor at the evaporating P and T.
Heat is absorbed from the refrigerated space.
The quantity of heat absorbed by the refrigerant in the evaporator
is called Refrigerating Effect (qe) . rimwumn เราไป H Retegerabr
กาก yอน a"อ เzาไป
TA = TB Q = W + m (he hi )
PA = PB
qe = h B h A = h B h D
16
Isentropic compression, B to C
¥
pressure
|%
aไป
การ
compressor
L๊aฒื้
. Heat of
A compression,
evaporator B qw
enthalpy 17
B C : Compression Process
This process occurs in the compressor as the pressure of the vapor is
increased by compression from the evaporating pressure to the
condensing pressure.
The process is assumed to be isentropic (frictionless-reversible adiabatic
or constant-entropy compression).
The energy equivalent of the work done during the compression process
is called Heat of Compression (qw) .
As a result of absorbing qw, the refrigerant vapor discharged from the
compressor is in a superheated state at point C.
SB = SC
q w = hC h B
TD(cond ) Tsat or TB ( evap ) 18
ยาก
รอ 4
~ไ• P €ง •น
Isentripio CR auset Adiabalics)
Compresson
( ไรแไฟ ‚างาบ ไป )
^ ไƒ
g ilhD.me Ch e) +
„ … Chi h e)
-
comps
-
Constant pressure heat rejection in the condenser
, C to D
Total heat
rejected, qc
condenser D* C
D
pressure
compressor
A B
evaporator
enthalpy 19
C D : Condensing Process
Process C-D* occurs in the upper part of the condenser and in the hot-gas
line. It represents the cooling of the vapor from the discharge temperature to
the condensing temperature. During process C-D*, the pressure of the vapor
remains constant.
At point D*, the refrigerant is a saturated vapor at the condensing P and T.
Process D*-D is the condensation of the vapor taking place in the condenser.
The total heat rejected by the refrigerant to the condensing medium (qc) is
equal to the heat absorbed by the refrigerant at all other points in the cycle.
qc = Heat rejected
qc = (hC hD* ) + (hD* hD ) qc = qe + q w
qc = hC hD
20
Throttling in an expansion valve, D to A
heatrejectd
9† 9 etqw
l
senliibkheatknn.no
1
D condenser
D* 1C
•
expansion เป‡ยนแปลง ไm
กาบดกนอน Nอ /
pressure
device gy
Iatn
hD = h A
|
compressor
B
A
evaporator 1
tqe -
/
-9 w
-
I
21
enthalpy
D A : Expansion or Throttling Process
Refrigerant Liquid leaves the condenser and enters the refrigerant control
(expansion valve) as a saturated liquid at the condensing P and T.
As the liquid passes through the refrigerant control, its P and T is reduced from
the condensing P and T to the evaporating P and T.
T of the liquid is reduced by the flashing into vapor phase of a portion of the
liquid; thus, the refrigerant is in the form of a liquid-vapor mixture at point B.
This process is a type of adiabatic expansion in which the enthalpy (h) of the
refrigerant liquid does not change during the process and it is assumed to take
place without the gain and loss of heat through the valves since the drop of
pressure occurs instantaneously and without the performance of work.
hD = hA
22
L๊ tttnam
Capillarytube l ‚อทอง แกง)
P-h Diagram of Simple Saturated Cycle
Pcond , Tcond
Pevap ,
Tevapd
-
เ~ย
23
P-h Diagram VS T-s Diagram
T-s diagram
A 0 E D
D. D
B C ①
b ~าน ษ เ‰ก] ขา ปา
A
E
Compressor
P-h diagram C
C
เŒง B
Šใน ป•มาตร
24
System Capacity
The capacity of any refrigerating system is the rate at which it
<
27
ง นข งค ม พร ซ ร = h2-h1
ค มดน
P2,3 3 2
เ5น ไป กาบ
P1,4 ปพ ร ต ร
1 ใน Aid
4
h2 - h1
h3,4 h1 h2
นทลป
ตร ก รท ค ม ยน = h1- h4
28
P-h diagram for R-12
A E D
B C
29
Saturation Properties of R-12
30
Superheated Vapor Properties of R-12
31
Effect of Suction Temperature on Cycle Efficiency
Increasing the suction or vaporizing
temperature will increase:
Refrigerating Effect (qe)
C.O.P
Increasing the suction or vaporizing
temperature will decrease:
Heat of Compression (qw)
Mass flow rate of refrigerant per
unit kW (m)
Heat rejected at the Condenser (qc)
35
Exercise I (Solution)
1 kW
m=
qe
V = mv
Re frigerating effect (qe ) hB hD
COP = =
Heat of compression (qw ) hC hB
36
ข ง ถม
37
Refrigeration and
Air Conditioning
Actual Vapor
Compression Cycle
38
Content
Deviations from the Simple Vapor
Compression Cycle
Effect of Superheating the Suction Vapor
Effect of Subcooling the Discharge Liquid
Liquid-Suction Heat Exchanger
Effect of Pressure Losses Resulting from
Friction
39
Deviations from the Simple Vapor
Compression Cycle
expansionvaleve
กลาย simple Vapar 9 <
ttropio
41
42
Temp
43
hD hA hD hA
Temp
Total heat rejected at the condenser (qc) is greater than that for the saturated
cycle due to the additional heat absorbed by the vapor in becoming superheated.
Note that the additional heat rejected at the condenser in the superheated cycle is
all sensible heat. 44
Effect of Superheating the Suction Vapor
E
Simple Saturated
Cycle: A-B-C-D-E
= simple Superheated Cycle:
>
ออก
satvapour
A-B-C -D -E
45
mmi
" sat <
Vsuperheat →
Gmpressor ?า8
v Superheate d v Saturated
For each kilogram of refrigerant circulated, the compressor
must compress a greater volume of vapor if the vapor is
superheated than if the vapor is saturated. Therefore, the mass
of refrigerant circulated (m ) b a compressor will alwa s be
less if the suction vapor is superheated than if the vapor is in a
saturated condition. @ ป Superheat @ไA หา
การ
.
mSuperheate d mSaturated
@ คง Cขาย แกน เ5น DอเEย ของ การ@ NS uperheated 46
.io?E.::
↳ .
. . .. . ..
.
.
ไปพบ
แนว degree superhat หา 4 Cop
The effect that superheating of the suction vapor has on the capacity of
the system and on the C.O.P depends entirely upon where and how the
superheating of the vapor occurs and upon whether the heat absorbed by
the vapor in becoming superheated produces any useful cooling.
Regardless of the effect on capacity, superheating the suction vapor is
usually desirable since it will eliminate the possibility of wet suction
vapor reaching the compressor inlet, avoiding the mechanical damage of
compressor.
47
Effect of Superheating the Suction Vapor
E
Simple Saturated
Cycle: A-B-C-D-E
Superheated Cycle:
A-B-C -D -E
f Inlet
following places:
In the end of the evaporator inside the
refrigerated space.
Hatvap C) In the suction piping installed inside
IJ่ eaporator
the refrigerated space, known as
Superheatedwp
Drier Loop .
In the suction piping located outside
the refrigerated space.
In the liquid-suction heat exchanger.
Note that superheating of the vapor in the suction line outside the refrigerated
space should be eliminated by insulating the suction line. 49
When operating at low suction temperature, insulating of the
suction line is necessary to maintain the efficiency of the cycle at a
reasonable level.
Insulating the suction piping is also important to prevent frosting
or sweating the suction piping due to the condensation of the
surrounding air onto the surface of the pipe line.
Superheating the suction vapor in the evaporator is usually not
economical and should always be limited to the amount that is
necessary because the capacity of the evaporator is always reduced
in any portion of the evaporator where only vapor exists.
Often, a drier loop is installed inside the refrigerated space for the
purpose of superheating the suction vapor producing useful
cooling. 50
http://contractingbusiness.com/iaq-amp-ventilation/coolings-dynamic-duo 51
Superheating without Useful Cooling
The refrigerating effect (qe) is the same for both the superheated and
saturated cycles operating at the same vaporizing and condensing
temperatures. q e, Superheate d = q e, Saturated
The mass flow rate (m) of refrigerant required per unit refrigerating
capacity will also be the same for both cycles. mSuperheate d = mSaturated
The volume flow rate of vapor (V) that the compressor must handle
per unit of refrigerating capacity is greater for the superheated cycle
than for the saturated cycle. V Superheate d V Saturated
The C.O.P for the superheated cycle is less than that of the saturated
cycle. C.O.PSuperheate d C.O.PSaturated 52
Superheating that Produces Useful cooling
The refrigerating effect (qe) is greater for the superheated cycle than for the
saturated cycle. The amount of increased qe equals to the amount of heat
absorbed in the superheating. qe, Superheate d qe, Saturated
The mass flow rate (m) of refrigerant required per unit refrigerating capacity
is less for the superheated cycle than for the saturated cycle.
1 kW
mSuperheate d mSaturated m=
qe
The volume flow rate of vapor (V) that the compressor must handle per unit
of refrigerating capacity is less for the superheated cycle than for the
saturated cycle. VSuperheate d VSaturated C.O.PSuperheate d C.O.PSaturated
The C.O.P for the superheated cycle is higher than that of the saturated cycle
because the increase in qe is greater proportionally than that of qw . 53
Effect of Subcooling the Discharge Liquid
The refrigerating effect per unit
mass is increased.
satliq
subodedliq .
:X!มาณ
liq
มาก
Pน
มาก
,
เ5นไอ มาก
Mด ค .
→
Mด ค รอน Nอย
Qอน มาก Pน
.
hC hB hC hB
The mass flow rate (m) per unit
capacity is less for the
subcooled cycle than for the
saturated cycle. Then the
@e mttng
Lmn
= 1 ⑥
2.ee
W
'
3
2
Liquid Suction Heat Exchanger
A
C
C
A
hB hB = hC hC
57
The maximum amount of heat exchange taking place between the
liquid and the vapor depends on the initial T of both liquid and
vapor and on the length of time they are in contact.
Since the specific heat of the vapor is less than that of the liquid,
the rise in the vapor T is always greater than the reduction in the
liquid T. TC TC TA TA
C
A
59
A
C
C
A
60
A
C
C
A
55HW 10
55510%
① ③
SEห
+
f l p fg py t h f t l h fg fg r f i p g f p
① หนทาง
อ
•
~•
@
ermn
U์
T
①
heatch คง> ②
า
Pipeline →
frictioninpipe.no )
อ =
Niqe
✓ ✓
✓
M qe
-
=
VA s
4T
B - C represents the drop in pressure (and temperature) in the evaporator.
The qe and m are approximately the same for both cycles.
The specific volume is greater; thus, the volume flow rate of vapor handled
by the compressor is greater for the cycle experiencing the pressure drop.
63
64
65
66
67
68
A A represents the pressure drop resulting from the flow of the
refrigerant through the receiver tank and liquid line.
If the liquid is not subcooled by an external sink as its pressure
drops, a portion of the liquid must flash into a vapor in the
liquid line to provide the required cooling of the liquid.
The drop in pressure in the liquid line has no effect on cycle
efficiency.
Passage of vapor through the refrigerant control will eventually
cause damage to the refrigerant control by eroding the valve
needle and seat.
Flashing of the liquid in the liquid line usually will not take
place when the drop in the line does not exceed 5 psi.
69
Exercise
ร บบ คร งท คว ม ยนท งกลร บบ นง ช้ รท คว ม ยน ปน R-12 มมตว่
ร บบนท ง น บบ Simple Saturated Cycle ณ ภมท Evaporator ท่ กบ -5oC
ล ท Condenser ท่ กบ 40oC ล รท คว ม ยนท กจ ก Evaporator ปน
ร้ นยงยวด (Superheated Vapor) ม ณ ภม พมขน 5oC ก่ นทจ ข้ คร ง ด
(Compressor) จงค นวณ ค่ h ทจดต่ ง (A, B, C, C , D, D ล E)?
70
Exercise (Cont.)
ร บบ คร งท คว ม ยนท งกลร บบ นง ช้ รท คว ม ยน R-12 มมต
ว่ ร บบนท ง น บบ Simple Saturated Cycle ณ ภมท Evaporator
ท่ กบ -5oC ล ท Condenser ท่ กบ 40oC ถ้ รคว ม ยนท กจ ก
คร งควบ น่ น (Condenser) ผ่ น ข้ ป น Liquid Suction Heat
Exchanger ปนผลท ้ รคว ม ยนท กม ม ณ ภมต กว่ ข ง ลว
มตว (Saturated Liquid) 5oC มมตว่ ม่ มก ร ญ ยคว มร้ น จง
ค นวณ
ค่ คว มร้ นท รคว ม ยน (Refrigerant Vapor) ดด ว้ ท
Heat Exchanger (hC hC)?
ค่ ณ ภม TA ล TC ?
71
Exercise (Cont.)
คร งท คว ม ยนขน ด 15 kW ช้ล
R-12 ปน รท คว ม ยน ณ ภมท คร งควบ น่ น
(Condenser) ท่ กบ 35 C ล ณ ภมท Evaporator ท่ กบ 20oC รคว ม ยนท ก
o
น คร งควบ น่ น (Condenser)
-
มมตว่ ก ร ด รคว ม ยน ปน บบ Isentropic ล
คว มดนลดลง ปน ปต มกร บวนก ร Throttling Process (Enthalpy คงท)
จง ขยนวงจรข งร บบ พร้ ม ดงจดต่ ง (A, B, C, D, E ล น ) ลงบน P-h
diagram ข ง R-12
จง ตร① ก ร ล ดยมวลทง มดข ง รท คว ม ยน (m)
(QC) น น่ วล
-
#Author:
#Al
&
Refrigeration and Air Conditioning
Refrigeration
Components
73
Content
Evaporators
Types of Evaporators
Chillers
Condensers
Types of Condensers
Cooling Towers
Expansion devices
Thermostatic Expansion Valve
74
Vapor-Compression Refrigeration Components
F E condenser D C
pressure
expansion
device compressor
A evaporator B
enthalpy
75
Evaporators
An evaporator is any heat transfer surface in which a volatile
liquid is vaporized for the purpose of removing heat from a
refrigerated space of product.
Evaporator may be classified in a number of different ways such
as: Type of construction
Method of liquid feed
Operating condition
Method of air (or liquid) circulation,
Type of refrigerant control
Applications
76
Types of construction
There are normally 3 types of evaporator construction:
- Bare-tube - Plate-surface - Finned
Both bare-tube and plate-surface evaporators are classified as prime-surface
evaporators in that the entire surface of these types is in contact with the
vaporizing refrigerant inside.
Bar-tube evaporators are usually constructed of either steel pipe or copper tubing.
Refrigerant vapor 80
Types of construction
Evaporator Capacity
Evaporator capacity is the rate at which heat will pass through the
evaporator walls from the space or product to the vaporizing liquid
inside by conduction and is influenced by:
Temperature difference between refrigerant and air or water being cooled
Flow rate of air or water through evaporator
Flow rate of refrigerant through evaporator
Q = U x A x LMTD
Q : Quantity of heat transferred (evaporator capacity)
A : Outside surface area of the evaporator
U : Overall conductance factor
LMTD: Logarithmic mean temperature difference 82
Logarithmic Mean Temperature Difference
Assuming that the drop in temperature
occurs at a constant rate as the air
passes through the coil, the
temperature reduction of the air is
represented by a straight line (dashed
line).
Practically, the drop in air temperature
is greatest across the first row of the
coil and reduce as the air passes across
each succeeding row. Thus the actual
drop in air temperature is shown by a
solid curved line.
83
Mean temperature difference of both lines may be calculated by:
(TE TR ) + (TL TR )
MD = TL TE
2 TR
Note that MD is slightly different from LMTD
(TE TR ) (TL TR )
LMTD =
(T TR )
ln E
(TL TR )
Airflow
Liquid
distributor
Suction header
Refrigerant vapor
88
Face-Split Arrangement
When an evaporator contains more than one liquid-refrigerant distributor, it
is split into independently-controlled sections, each being served by its own
expansion valve.
The three common arrangements for splitting finned-tube evaporator coils
include: Face-split
Intertwined
Row-split
The face-split coil configuration, also called horizontal-split or parallel-
flow, is split into parallel sections.
The intertwined coil configuration splits the coil sections by alternating
the tubes fed in each row between two distributors.
the row-split coil configuration, also called vertical-split or series-flow,
places the independently-controlled coil sections in series in the
airstream. 89
Coil Arrangements
Distributors
Row-split or Vertical-split 90
Methods of Refrigerant Feed
Based on the methods of liquid feed, the evaporators can be classified as:
- Dry-expansion - Liquid overfeed - Flooded
With the dry-expansion evaporator, the amount of liquid refrigerant fed into the
evaporator is limited to that which can be completely vaporized by the time it
reaches the end of the evaporator.
Dry-expansion
91
A liquid overfeed evaporator is one wherein the amount of liquid
refrigerant circulated through the evaporator is considerably in
excess of that which can be vaporized.
The excess liquid is separated from the vapor in a low-pressure
accumulator and recirculated to the evaporator while the vapor
is drawn off to the compressor suction.
Liquid overfeed
92
The full-flooded method is operated completely filled with liquid refrigerant,
thus, proving the greatest amount of interior wetted tube surface and the
highest possible heat transfer rate.
An accumulator serves as a reservoir from which the refrigerant is circulated
by gravity through the evaporator circuits.
A low-side or high-side float control maintains the liquid level in the
accumulator.
The vapor generated by the boiling action of the refrigerant in the tubes is
separated from the liquid in the upper part of the accumulator. Therefore, the
flash gas resulting from the reduction of pressure never enters the heat
transfer portion of the evaporator.
93
Liquid-Chilling Evaporators
There are 5 general types of liquid chillers that are commonly used:
Double-pipe cooler
Baudelot cooler
Tank-type cooler
Shell-and-coil cooler
Shell-and-tube chiller (the most widely used type)
Refrigerant vapor
Liquid
refrigerant
Tube bundle
95
Flooded Shell-and-Tube Evaporator
Low-pressure liquid refrigerant enters the distribution system inside the shell and is
distributed uniformly over the tubes , absorbing heat from relatively warm water that
flows through the tubes.
This transfer of heat boils the film of liquid refrigerant on the tube surfaces and the
resulting vapor is drawn back to the compressor.
Refrigerant vapor Chilled
Liquid water
refrigerant supply
Tube bundle
Chilled
water
return Liquid level sensor
96
Packaged Chillers
Centrifugal Water-Cooled Water Chiller
Compressor Motor
Condenser
Starter
Control
panel
Evaporator
Air-Cooled Water Chiller
97
Coolers
Thermoelectric Cooler
99
Condenser Capacity
Condenser capacity is influenced by:
Temperature difference between refrigerant and cooling media
(air, water, or both)
Flow rate of cooling media through condenser
Flow rate of refrigerant through condenser
Q = U x A x LMTD
Qc
T=
(m )(c)
Qc: Heat rejected at the condenser (kW)
m : Mass flow rate of air or water (kg/s)
c : Specific heat of the condensing medium (kJ/kg oK)
101
Temperature Rise of Condensing Medium
In practice, the quantities of air and water are expressed in m3/s or L/s.
The average specific heat values of air and water are:
c (air) = 1.02 kJ/ kg oK
c (water) = 4.19 kJ/ kg oK
The densities of air ( air) and water ( water) are:
= 1.19 kg/m 3
air
water = 1 k g/L
Qc Qc
Tair = Twater =
1.21 V 4.19 m
Outdoor
air
Condenser
coil 103
Subcooler
Condenser
coil
Centrifugal
fan
Centrifugal Fan Air-Cooled Condenser
104
Water-Cooled Condensers
The shell-and-tube is the most common type of water-cooled condenser. With
this design, water is pumped through the tubes while the refrigerant vapor fills
the shell space surrounding the tubes.
As heat is transferred from the refrigerant to the water, the refrigerant vapor
condenses on the tube surfaces.
The condensed liquid refrigerant then falls to the bottom of the shell, where it
flows through an enclosure that contains additional tubes (the subcooler).
More heat is transferred from the liquid refrigerant to the water inside these
tubes, subcooling the refrigerant.
Hot, refrigerant vapor
95ºF
[35ºC]
Cooling water
85ºF
[29ºC]
Subcooler
Subcooled, liquid refrigerant 105
Refrigerant vapor
Baffle
Cooling
Subcooler
tower
water Liquid
refrigerant
Tube bundle
106
Cooling Towers
Propeller Sprays
fan
Filler
Outdoor
air
Sump
85ºF to from 95ºF
[29ºC] condenser condenser [35ºC]
107
A cooling tower is a device commonly used to cool condensing water.
Warm water is sprayed over fill in the cooling tower while a propeller fan
draws outdoor air upward through the fill.
The movement of air through the spray causes some of the water to
evaporate, a process that cools the remaining water. This cooled water
then falls to the tower sump to be returned to the condenser.
The evaporation process uses up water to dissipate heat. As the water
evaporates, the dissolved minerals and water treatment chemicals become
concentrated in the sump.
To prevent this solution from becoming concentrated and possibly
corrosive, water is periodically bled from the sump and an equal amount
of fresh water is added.
108
The effectiveness of the cooling tower depends upon:
The web bulb temperature of the entering air
The amount of exposed water surface and the length of time of
exposure
The velocity of the air passing through the tower
The direction of the air flow with relation to the exposed water surface
- Parallel - Transverse - Counter
The temperature of the water leaving the tower will usually be 7-10 oC
above the web bulb temperature of the entering air.
The difference between the temperature of the water leaving the tower
and the wet bulb temperature of the entering air is called the Approach
of the tower
The temperature difference between the entering and leaving water is
called the Range of the tower.
109
Vary Condenser Water and Air Flow Rates
Cooling tower
Condenser Variable-
speed drive
Variable-speed
drive
Cooling tower
Condenser
110
Evaporative Condensers
Fan
Refrigerant vapor
Condenser coil
Pump
sump
Liquid refrigerant Subcooler
111
A modification of the air-cooled condenser is the evaporative condenser.
Within this device, the refrigerant flows through tubes and air is drawn or
blown over the tubes by a fan. And water is sprayed on the tube surfaces.
As the air passes over the coil, it causes a small portion of the water to
evaporate. This evaporation process absorbs heat from the coil, causing the
refrigerant vapor within the tubes to condense. The remaining water then
falls to the sump to be recirculated and used again.
Subcooling of the refrigerant can be accomplished by piping the condensed
liquid back through another few rows of coil tubing, located either in the
condenser air stream or in the water sump, where additional heat transfer
reduces the temperature of the liquid refrigerant.
112
Expansion Devices
An expansion device is used to maintain a pressure difference between
the high-pressure (condenser) and low-pressure (evaporator) sides of the
system established by the compressor.
This pressure difference allows the evaporator temperature to be low
enough to absorb heat from the air or water to be cooled, while also
allowing the refrigerant to be at a high enough temperature in the
condenser to reject heat to air or water at normally available
temperatures.
There are several types of expansion devices, including expansion valves
(thermostatic or electronic), capillary tubes, and orifices.
Thermostatic expansion valves (TXVs) are commonly used and perform
essentially the same function as other expansion devices. 113
Thermostatic Expansion Valve (TXV)
thermostatic
expansion valve
(TXV)
liquid
evaporator refrigerant
liquid/vapor
mixture
A
refrigerant
vapor
Spring
Remote
bulb
Suction
line external equalizer Distributor
The outlet of the valve is connected to the distributor. A remote bulb is
attached to the suction line, where it senses the refrigerant vapor temperature
leaving the evaporator. This bulb is charged with refrigerant and as heat is
transferred from the suction line to the bulb, the refrigerant inside the bulb
vaporizes. The resulting refrigerant vapor pressure is transmitted through a
tube to the space above a diaphragm in the TXV.
The pressure of the refrigerant vapor leaving the evaporator is transmitted to
the space beneath the diaphragm through an external equalizing line that is
tapped into the suction line downstream of the bulb.
Finally, the valve contains an adjustable spring that applies a force to the
lower side of the diaphragm. 115
valve diaphragm
Assuming the 9.4°C 0.67 MPa
Performance of
Reciprocating
Compressors
117
Content
o Types of Compressors
o Refrigerating Capacity
o Compressor Power
118
Types of Compressors
Four types of compressors used in the air-conditioning industry:
- Reciprocating - Scroll
- Helical-rotary (or Screw) - Centrifugal
The reciprocating compressor has been the one most frequently
used in the refrigeration industry.
The traditional reciprocating compressor contains cylinders,
pistons, rods, a crankshaft, and valves.
– Refrigerant is drawn into the cylinders on the downstroke of
the piston and compressed on the upstroke.
Reciprocating, scroll, and helical-rotary work on the principle of
trapping the refrigerant vapor and compressing it by gradually
shrinking the volume of the refrigerant.
Centrifugal compressors uses centrifugal force, generated by a
rotating impeller, to compress the refrigerant vapor.
Scroll Compressor
The scroll compressor uses two scroll Stationary
scroll
configurations, mated face-to-face, to
perform the compression process.
The upper scroll, called the stationary Discharge
scroll, contains a discharge port. The port
lower scroll, called the driven scroll, is
Driven
connected to a motor by a shaft and scroll
bearing assembly.
Discharge
The refrigerant vapor enters through
the outer edge of the scroll assembly
and discharges through the port at the Intake Intake
center of the stationary scroll. Motor
shaft 120
This orbiting motion causes the mated scrolls Intake
to form pockets of refrigerant vapor. Discharge
As the orbiting motion continues, the relative port
movement between the orbiting scroll and the
stationary scroll causes the pockets to move
toward the discharge port at the center of the
Intake
assembly, gradually decreasing the
refrigerant volume and increasing the
pressure. Dome
Refrigerant vapor enters through the suction Discharge
opening. The refrigerant then passes through Scrolls opening
a gap in the motor.
The refrigerant vapor is drawn into the
scroll assembly where it is compressed, Motor
discharged into the dome, and finally Suction
discharged out of the compressor through the opening
discharge opening. 121
Helical-Rotary (Screw)
Compressor
The helical-rotary compressor traps the refrigerant
vapor and compresses it by gradually shrinking the
volume of the refrigerant.
This helical-rotary compressor design uses two
mating screw-like rotors to perform the
compression process.
The rotors are meshed and fit, with very close
tolerances, within the compressor housing. Female rotor
Only the male rotor is driven by the Male rotor
compressor motor. The lobes of the male
Housing
rotor engage and drive the female rotor,
causing the two parts to counter-rotate.
122
Intake
port
Discharge
port
Pocket of
refrigerant vapor
Refrigerant vapor enters the compressor housing through the intake port and fills the
pockets formed by the lobes of the rotors.
After the pockets of refrigerant travel past the intake port area, the vapor, still at suction
pressure, is confined within the pockets by the compressor housing.
Continuing rotation of the meshed rotor lobes drives the trapped refrigerant vapor (to the
right), toward the discharge end of the compressor. This action progressively reduces the
volume of the pockets, compressing the refrigerant.
Finally, when the pockets of refrigerant reach the discharge port, the compressed vapor is
released and the rotors force the remaining refrigerant from the pockets. 123
Suction
opening
Slide valve
Motor
Rotors
Discharge
opening
Inlet
vanes
Piston
Rod
Motor Crankshaft
The refrigerant vapor from the suction line enters the compressor through the suction
opening. It is then compressed by a piston that is located inside a cylinder.
The piston is connected to the crankshaft by a rod. As the crankshaft rotates, it causes
the piston to travel back and forth inside the cylinder. This motion is used to draw
refrigerant vapor into the cylinder, compress it, and discharge it from the cylinder.
A pair of valves, the suction valve and the discharge valve, are used to trap the
refrigerant vapor within the cylinder during the compression process.
The compressed refrigerant travels through the headspace, and leaves the compressor
through the discharge opening.
Most reciprocating compressors have multiple piston cylinder pairs attached to a
single crankshaft. 127
Types of Reciprocating Compressors
Open compressor
Open compressor is driven by an
external power source, such as an
electric motor. The motor is
coupled to the compressor Housing
crankshaft by a flexible coupling. Compressor
crankshaft
Piston
Compressor
Motor crankshaft
Housing
129
Compression Cycle of
Reciprocating Compressor
Suction stroke
Compression stroke
Theoretical time - pressure (T-p) diagram
131
At point A, the piston is at the top of its stroke (top dead center (a)).
At this position, a small volume of clearance between the top of the piston and the
valve plate is called the clearance volume.
Both the suction and discharge valves are closed at this position.
The high pressure of the vapor trapped in the clearance space, known as the
clearance vapor, acts upward on the suction valves and holds them closed against the
pressure of the suction vapor in the suction line.
Because the pressure of the vapor in the head of the compressor is approximately the
same as that of the vapor in the clearance volume, the discharge valves are held
closed either by their own weight or by light spring-loading.
Discharge
valve
Suction
valve
132
The piston moves downward on the suction stroke (b).
The high-pressure vapor trapped in the clearance space is allowed to expand.
The expansion takes place along line A-B so that the pressure in the cylinder decreases
as the volume of the clearance vapor increases.
When the pressure of the reexpanded clearance vapor in the cylinder becomes slightly
less than the pressure of vapor in the suction line, the suction valves are forced open by
the higher pressure in the suction line.
The refrigerant vapor from the suction line flows into the cylinder.
Discharge
valve
Suction
valve
Refrigerant Piston
vapor
Rod
Cylinder 133
The flow of suction vapor into the cylinder begins when the
suction valves open at point B and continues until the piston
reaches the bottom of its stroke (bottom dead center (c)) at
point C.
During the time that the piston is moving from B to C, the
cylinder is filled with suction vapor and the pressure in the
cylinder remains constant at the suction pressure.
At point C, the suction valves close, usually by spring action.
134
The pressure of the vapor in the cylinder increases along line C-D as the piston moves
upward on the compression stroke.
By the time the piston reaches point D, the pressure of the vapor in the cylinder has
been increased until it is higher than the pressure of the vapor in the head of the
compressor and the discharge valves are forced open.
The high-pressure vapor passes from the cylinder into the hot-gas line through the
discharge valves.
The flow of the vapor through the discharge valves continues as the piston moves from
D to A while the pressure in the cylinder remains constant at the discharge pressure.
When the piston returns to point A, the compression cycle is completed and the
crankshaft of the compressor has rotated one complete revolution.
Headspace
Discharge
valve
Suction
valve
Discharge
opening
135
Piston Displacement (Vp)
The Piston Displacement (Vp) of a reciprocating compressor is the total
cylinder volume swept through by the piston in any certain time interval,
usually expressed in L/s.
For any single-acting of a reciprocating compressor, the piston
displacement is computed by:
Vp = /4 x D2 xL 0.7854 * D2* L * N * n
Vp =
1,000
137
The mass of refrigerant circulated by the compressor per unit time is
calculated by:
m = Vp * OR m = Vp /
138
Actual Refrigerating Capacity
The actual refrigerating capacity of a compressor is always less than
that of the theoretical refrigerating capacity due to:
The compressibility of the refrigerant vapor and the mechanical
clearance between the piston and the valve plate of the compressor
(clearance volume) that cause the volume of suction vapor filling the
cylinder during the suction stroke to be less than the piston displacement
of the compressor (VP).
The density (ρ) of the vapor filling the cylinder is lower than the density
of the vapor in the suction line.
Actual Refrigerating Capacity = Theoretical Refrigerating Capacity * (Ev / 100)
where Ev : Total volumetric efficiency of the compressor (%)
139
Total Volumetric Efficiency of the Compressor
141
Factors Influencing Total Volumetric Efficiency
Theoretical Pressure -
Volume (p-V) Diagram
Since the vapor left in the clearance space has been compressed to the discharge
pressure and it must be reexpanded to the suction pressure before the vapor in
the suction line can flow into the cylinder, the suction vapor will fill only that part
of the cylinder volume that is not already filled with the reexpanded clearance
vapor, which is the difference between Vc and Vb.
143
Effect of Clearance on Volumetric Efficiency (Cont.)
If the clearance volume of the compressor is increased, the percentage of
the high-pressure vapor remaining in the cylinder at the end of each stroke
will be increased; therefore, the volume of suction vapor taken in per
stroke will be less than that of smaller clearance volume.
To obtain maximum volumetric efficiency, the clearance volume of a vapor
compressor should be kept as small as possible.
If the discharge pressure is increased, the vapor in the clearance will be
compressed to a higher pressure and a greater amount of reexpansion will
be required, thus reducing the volumetric efficiency of the compressor.
If the suction pressure is lowered, the clearance vapor must experience a
greater reexpansion in expanding to the lower pressure before the suction
valves will open, thus decreasing the volumetric efficiency of the
144
Effects of Wiredrawing
Wi ed a i g i defi ed a a restriction of area for a flowing fluid that
causes a loss in pressure by (internal and external) friction without the loss of
heat or performance of work; throttling .
Wiredrawing is generally a function of the velocity of the refrigerant vapor
flowing through the valves and passages of the compressor. As the velocity
of the vapor through the valves is increased, the effect of wiredrawing
increases.
Since the suction vapor experiences a mild drop in pressure as it flows
through the suction valves, the pressure of the suction vapor filling the
cylinder is always less than the pressure of the vapor in the suction line.
The volume of suction vapor taken in from the suction line each stroke is
less than if the vapor filling the cylinder was at the suction line pressure,
reducing the volumetric efficiency of the compressor.
145
Since a pressure differential is required across the discharge valves to
cause the discharge valve to open, the vapor in the cylinder must be
compressed to a pressure higher than the actual condensing pressure. As
a result, the clearance vapor must suffer a greater reexpansion than if it
had been compressed only to the condensing pressure, decreasing the
volumetric efficiency of the compressor.
From the p-V diagram, the areas above line p2 and below line p1
represent the increased work of the cycle due to wiredrawing.
146
Effects of Cylinder Heating
The suction vapor entering the compressor cylinder is heated by heat
conducted from the hot cylinder walls and by friction resulting partly from
the turbulence of the vapor in the cylinder.
The heating of the suction vapor in the compressor cylinder tends to
reduce the volumetric efficiency of the compressor.
The heating causes the vapor to expand after entering the cylinder so that
a smaller mass of vapor will fill the cylinder and thereby still further
reduce the volume of vapor taken in from the suction line.
Cylinder heating increases as the compression ratio increases.
At high compression ratios, the work of compression is greater and the
discharge temperature is higher, causing the rise in the temperature of the
cylinder walls and other compressor parts. 147
Effects of Piston and Valve Leakage
Any back leakage of gas through either the suction or discharge valves
or around the piston will decrease the volume of vapor pumped by the
compressor, reducing the volumetric efficiency of the compressor.
As the pressure in the cylinder is lowered at the beginning of the
suction stroke, a small amount of high-pressure vapor in the head of
the compressor will leak back into the cylinder before the discharge
valves can close tightly.
At the start of the compression stroke, some of the vapor in the
cylinder will flow back through the suction valves into the suction line
before the suction valves can close.
The amount of back leakage through the valves is a function of the
compression ratio and the speed of the compressor (i.e., the higher the
compression ratio, the greater the amount of the valve leakage). 148
Determination of the Total Volumetric Efficiency
Relationship between
the compression ratio
and the volumetric
efficiency of halocarbon
compressor 5-25 hp
1kW
m = Vp /· m=
qe
150
Actual Compressor Power Requirements
The total power that must be supplied to the shaft of the compressor is called
the shaft power (PS).
PT
Eo = * 100
Ps
mq w * 1.1
Ps =
Ev
152
Exercise
-ameter #
คร ง ด บบลก บ (Reciprocating Compressor) จ นวน 3 บ มนทคว ม รวร บ
1,500 ร บ/น ท ถ้ ้ นผ่ น นย์ กล งข งลก บ ท่ กบ 5 cm ล ร ย ชก ท่ กบ 5 cm
ถ้ คร ง ดน ช้ กบ รท คว ม ยน R-12 ณ ภมท Evaporator ล Condenser
ท่ กบ 10oC ล 40oC ต มล ดบ จงค นวณ
ตร ก ร ล ดยมวลข ง รท คว ม ยนทผ่ น คร ง ด (kg/s)
คว ม ม รถข งก รท คว ม ยนท งทฤ ฎข ง คร ง ด& (Theoretical refrigerating
capacity of the compressor,
- kW) = >
/
DO5CM
no 0.000
milleg. @ Gin 01.45 3k
Ho3,
IDYLEN = #
up:
'
# 100
(55101024)
comp Upo =(5 +
c
Up ธ
7.363x10 m↓/ ↳ 7.363
#pring
0.09817
7.363 / /5
#" - P
Lig #
↳
leg
1ธ (0,078 103)
<
>
-
Cors-supatter#res
#
#womChanelcoloans
->> Evo #Vs 5 :3554
/-Pre -
1.032
mil-
+ 10
The lo
vp 7,363
tvo War (
<
U #US)+355 7.363
พๆ: 2.532110 - N
Can · EV/
100) - (#0321 =( 2.4543)
is
of(hige) = ( Er
1100) 8 miaw? 37B 3 4
3.3736< 10 "
1to
of tr #
2.53 x 10 5 0.75 & Pos
ewp
7.363
Events.
%
ค่
R12 xxL=#
①Up. #
2 - (5
#- mio ( kin * (5 +1024)
Up . #
+ 10 -
Pe
4,54124011Jllg
9ม
<
# & -
2
· >
! ⑨ 9n
!
# !
31
!
373
⑧
925 373- 345
ล
- 28//er
#ร
·
uper.
# / 925 344 -192.
& 900 w
Er w Va 1 100%
=
Er ธ
0@
&
·
P
update
try 1500 =3
60 2 1000)
cm
5
EvoU
<
Up retro1 .(
Upoo"
ทาง toms
##
ส 9. 2 x 10-
5
s
tag Is
overpris
Er ส
!
UsomiVs
②
Promise ) * ( Ev/
100) · Charl /Usส (
Uso ( 0.08)
> 9.2220-
-
7.36 +10- 6
Er ร 4.07 6
< 10-
lesen)
Per (9220- 3) ( 192
hn) ( +During Case
10 -
Pr 1,8546 x
kWe
อ (2000W
-
awresleylleg -
%
of
·
IID. 0.8
& %
&
:
ต่
=
Refrigeration and Air Conditioning
Multiple Evaporator
and Compressor
Systems
154
Content
Multiple Evaporator Systems
Multiple Compressor Systems
Compound Compression
155
Multipressure Systems
A multipressure system is a refrigeration system that has two or more low side pressures.
A multipressure system may be found in:
A dairy where one evaporator operates at -35oC to harden ice cream while another
evaporator operates at 2oC to cool milk.
A process industry where a two- or three-stage compression arrangement serves an
evaporator operating at a low temperature of -20oC or lower.
There are two methods employed to increase the refrigerating capacity and to reduce the
power consumption for multipressure system:
Flash gas removal
Intercooling
156
สามารถ พมค่า C.O.P ของระบบการทาความ ยน ดย
1. พมประสทธผลการทาความ ยน (Refrigerating effect), RE, ซงจะสามารถ
ทา ด้ ดยการ ห้สารทาความ ยนมสถานะ ปนของ หลว ห้ ด้มากทสด
-
157
Flash Gas Removal
Refrigerant vapor to
compressor
Vap.li
g.
? liq เออ%
liq
.
+
vap
From expansion Liquid refrigerant
device to evaporator
Here the liquid refrigerant settles to the bottom of the chamber and the fraction of vapor
(flash gas) is drawn off the top and routed directly to the suction side of the compressor.
The remaining liquid refrigerant is then routed to the evaporator.
By removing the vapor portion of the mixture before it gets to the evaporator the separator
enhances the effectiveness of the evaporation process.
158
Flash Gas Removal |
Sat
vap
.
Condenser
ns.ISatliq .
1
Pressure (P)
ฅูlashyas 4
% & max
3 6 m 3 = m4 + m6
Satliq Satvap
|
.
&4
L
m4 = mf
5 7
• •
าrrt1
1- RE
1- RE Tnt
m6 = mg
Enthalpy (h) 159
Flash Gas Removal (Cont.)
The expansion process (1-3) takes place through a float valve,
which serves the further purpose of maintaining a constant level in
the flash tank.
The liquid and vapor phases (4 and 6) are separated.
The expansion could then continue by expanding the liquid at 4 to
the final pressure at 5.
Another compressor could be used to recompress the vapor at 6.
160
Intercooling
Satvap .
เสมอ
superheated
vap .
m 5 = m6 + m7
4
5
Pressure (P)
m3 = m6 + m2
6 3
2 barlane at Interc
7 1 m3 = mg
mass
*า i =
ie
&เ + & = &3
2
Enthalpy (h)
Energybalance & เhเ + & 2h
2
= *า 3h
}
161
Intercooling
Water or some part of liquid refrigerant from In Out
condenser
6 5 3
m4 ต้องมสถานะอย่ระหว่าง ตา หน่งท 2 ( อร้อนยอด
4
Pressure (P)
163
There is an optimum pressure at which the intercooling should take place.
In the compression of air, where the intercooling is achieved by rejecting heat to the
ambient or to cooling water, the intermediate pressure is computed by:
=
In refrigeration systems, complete intercooling is not possible as it is done by water or air.
Thus, the recommended expression in refrigeration
p = p systems
i p
d s
is estimated by:
*
p i = p d ps (Td / Ts )
where pi = Intercooler pressure
pd and Td = Discharge pressure and temperature (oK) of high-stage compressor
ps and Ts = Suction pressure and temperature (oK) of low-stage compressor
164
Pressure (P)-Enthalpy (h) Chart : Flash Gas Removal
h 6 = h5
h8 = h 7
kpa
↳ ง
000
Qe ,&
เhเ
/
*า 3h mihfhf เออ kk
C.O.P =
.
= +
}
Qw
& s
=
& เ
mi &8 &
4
= =
5 2 Qe
Pressure (P)
&} &
*า 4 &เ
m1 =
max.it
= +
h1 h8
7 6 3
Qc = m1 (h 2 h 5 ) + m3 (h 4 h 5 )
8 1 Q w = m1 (h 2 h1 ) + m 3 (h 4 h 3 )
CR E) -11- w , -1
tnnqe
-
m 7 = m1 165
Enthalpy (h)
Heat and Mass Balances : Flash Gas Removal
3
Heat balance: h 6 m 6 = h 7 m 7 + h 3m 3
Mass balance: m6 = m7 + m3
h 6 (m1 + m 3 ) = h 7m1 + h 3m 3
h6 h7 x6 h6 h7
m 3 = m1 ( ) m 3 = m1 x gas = x6 =
h3 h6 1 x6 h3 h7
166
IA.tt
& s
= &เ + &7
, ระ, = &
เ 2
, เhเ + mih = / 3h 3
.
&3 =
&4 = &s
0
Pressure (P)-Enthalpy (h) Chart : Intercooling
h5 = h6 = h7
Qe
C.O.P =
Qw
5 4 m1 =
Qe
Pressure (P)
h1 h 7
3 2
6
Q w = m1 (h 2 h 1 ) + m 3 (h 4 h3 )
Q w = m1 (h 2 h1 ) + m 3 (h 4 h 3 )
7 1 Q c = m 3 (h 4 h5 )
Heat balance: h 6 m 6 + h 2 m1 = h 3 m 3
Mass balance: m 3 = m 6 + m1
h 6 (m 3 m1 ) + h 2 m1 = h 3 m 3
h2 h6 h2 h3
m 3 = m1 ( ) m 6 = m1 ( )
h3 h6 h3 h6
168
Exercise I
เ3ยน
2.
diagram
Exercise II
จ กรปข งร บบท คว ม ยนท ดง ว้ข้ งล่ ง ช้ R-12 ปน รท คว ม ยน
จง ขยน p-h diagram ข งร บบท คว ม ยนนลงบน p-h diagram ข ง R-12 พร้ มร บต น่ งข งจด 1
ถง 8 ลงบนวงจรท คว ม ยนนด้ วย
จง ค่ ตร ก ร ล ดยมวลข ง รคว ม ยนทจด 1 ล จด 3
ม ย ต: รคว ม ยนท กจ ก condenser ม ถ น ปนข ง ลว มตว (saturated liquid) ล รคว ม
ยนทท งด้ นดด (suction) ข ง compressor ปน มตว (saturated vapor)
5 Condenser 4
45oC
25oC
Flash High-stage
intercooler
Compressor
and flash
tank
6 2
7 8 Evaporator 1
60 kW
-10oC
Low-stage 170
Compressor
Exercise I & II
3
2
m 3 = m 3 + m 3 + m1
h 6m 3 h 2 m1 h 7 m1
x6
h2 h3 m 3 = m1 ( )
m 3 = m1 ( ) 1 x6
h3 h6 171
Multiple Evaporator Systems
>Eใ
Expansion Valve Outdoor
fa
3 Condenser
40oC
M, M3
MA MB
= = +
+
Mc
m
: 4
÷÷
:/ "
Evaporator I
35 kW; -10oC
2
MB
@ A๊ MB
=
=
Evaporator II
70 kW; -10oC
mc =
% %=
ma
1
Evaporator III Compressor
105 kW; -10oC
173
1: Multiple evaporators - Single temperature, Compressor, and
Expansion Valve (Cont.)
3 40oC 2
Pressure (P)
-10oC
4 1
m1 = m I + m II + m III
Q w = m1 (h 2 h1 )
35 kW 70 kW 105 kW Q c = m1 (h 2 h3 )
m1 = + +
h1 h 4 h1 h 4 h1 h 4
Qe
C.O.P =
Qw
(35 kW + 70 kW + 105 kw ) Qe
m1 = =
h1 h 4 h1 h 4
175
2: Multiple Evaporators and Temperatures Single Compressor
with Individual Expansion Valves mg m, =
Mเ + + mแ
mh mh maha mnh แ
3
= + +
, เ
Condenser
40oC M
า
* i
fte-ttfftf.TL
Pc
|itnteu
D๋
¥ %
F๋
Pressorereducingvalve
4
m→
h คง G*
๓ 11
Satvap
→ enen
วาจา
สบ
.
f5
J่
4 Evaporator I 6 2
c 35 kW; 10oC
Satvap . Pmin
7 Evaporator II L8 9 t
B 70 kW; 5oC
1
Pmin
10 Evaporator III f 11 Compressor
A 105 kW; -10oC
\ satvap .
176
2: Multiple Evaporators and Temperatures Single Compressor
with Individual Expansion Valves (Cont.)
3 40oC 2
Pressure (P)
4 10oC 5
7 5oC 8
10 -10oC 11
1 6
9
mI
5
Mass balance:
8 1 m1 = m I + m II + m III
m II m1
11 Heat balance:
m III
h1m1 = h 5m I + h8m II + h11m III
178
3: Multiple Evaporators and Temperatures Single Compressor
with Multiple Expansion Valves
3
Condenser
40oC
$อน
f!
Pc
.tn/n,
w re
_"๋ |
4 Evaporator I 5 6
0
hmixture
35 kW; 10oC 2
7 ←
satdiq .
8 mixture
Evaporator II 9 10
70 kW; 5oC
11 ←
satliq .
1
12 Evaporator III 13 Compressor
105 kW; -10oC
179
3: Multiple Evaporators and Temperatures Single Compressor
with Multiple Expansion Valves (Cont.)
3 40oC 2
Pressure (P)
7 4 10oC 5
11 8 5oC 9
-10oC 13
12 1 106
m 13 = m III m 9 = m II + m II m5 = mI + mI
x x4
m II = m III ( 8 ) m I = (m 9 + m 13 ) ( )
1 x8 1 x4
h8 h11 h4 h7
x8 = x4 =
h9 h11 h5 h7
181
3: Multiple Evaporators and Temperatures Single Compressor
with Multiple Expansion Valves (Cont.)
5 Mass balance:
m5
m 1 = m 5 + m 9 + m 13
9 1
m9 m1 m1 = (mI + mI ) + (mII + mII ) + mIII
13
m 13
Heat balance:
h 1m 1 = h 5 m 5 + h 9 m 9 + h 13 m 13
h 1m 1 = h 5 (m I + m I ) + h 9 (m II + m II ) + h 13 m III
Q w = m1 (h 2 h1 ) Q c = m1 (h 2 h3 )
35 kW + 70 kW + 105 kW
C.O.P =
Qw
182
Multiple Compressor Systems
183
1: Multiple evaporators, Temperatures, and Compressors with
Individual Expansion Valves
M, mา+m
Ms
=
+
7 Condenser
3
40oC
6 Pcond
8 Evaporator I Le
ms
35 kW; 10oC
5 Compressor I 4
9 Evaporator II M 3
hn Pcond
70 kW; 5oC
3 Compressor II 2
Pccnd
10 Evaporator III M
ng
7 40oC 6 42
Pressure (P)
10oC 5
8 5oC
9 3
-10oC 1
10
Q c = m I (h 6 h 7 ) + m II (h 4 h 7 ) + m III (h 2 h7 )
35 kW + 70 kW + 105 kW
C.O.P =
Q w ,I + Q w ,II + Q w ,III
186
2: Multiple evaporators, Temperatures, and Compressors
with Multiple Expansion Valves
7 Condenser
40oC
C
6
8 Evaporator I
35 kW; 10oC C
9 5
B Compressor I 4
10 Evaporator II
70 kW; 5oC B
11 3
A
Compressor II 2
12 Evaporator III
105 kW; -10oC A
1 Compressor III 187
2: Multiple evaporators, Temperatures, and Compressors
with Multiple Expansion Valves (Cont.)
7 40oC 6 42
Pressure (P)
9 8 10oC 5
11 10 5oC 3
-10oC 1
12
Q w ,III = m 1 (h 2 h1 ) x
m II = m III ( 10 ) m I = (m 3 + m 1 ) (
x8
)
1 x10 1 x8
h 10 h 11 h8 h9
x 10 = x8 =
h 3 h 11 h5 h9
Q w ,II = m 3 (h 4 h3 ) Q w , I = m 5 (h 6 h5 )
189
2: Multiple evaporators, Temperatures, and Compressors with
Multiple Expansion Valves (Cont.)
Q c = m 5 (h 6 h 7 ) + m 3 (h 4 h 7 ) + m 1 (h 2 h7 )
35 kW + 70 kW + 105 kW
C.O.P =
Q w ,I + Q w ,II + Q w ,III
190
Compound Compression
1. Two or more evaporators operate with different
temperatures using two or more compressors and
individual expansion valves along with flash
intercooling.
_
6
8 Evaporator I
Mcgsat
my
35 kW; 10oC
mixtcre v.
c f
Sat v.
my
5Compressor I
i_fey4M45uperhe.at
, Miz
→
4
ed
9 mixture
Evaporator II MB Sat v.
70 kW; 5oC , B
mixture
mx , Sat V.
3Compressor II Mx Sat
,
9
v.
mi i Intercooler mzsuperheated
10 Evaporator III 2 m"µ÷ fiadetfmy
105 kW; -10oC A superheat
7 40oC 6
เ$น mixtvre รวม )บ 4
Pressure (P)
กาโร
+ Intercoder 2
8 10oC .
5 4 .
5oC
. . . . .
3 2
. . . . . . .
. . . . .
9
-10oC
g.
. . . .
1
. . . . . . . . .
10
เ$นของ mixture + ไป รวม
)บ 2 + Intercooler 1
m1 = m III Q w ,II = m 3 (h 4 h3 )
Q w ,III = m 1 (h 2 h1 )
Mass balance:
m 3 = m II + m II + m 1
Heat balance:
(m1 + mII )
h 2 m 1 + m II h 9 = h 3 (m 1 + m II )
3
m II 9 Intercooler 2 (h 2 h3 )
m1 m II = m 1
(h 3 h9 )
194
1: Multiple evaporators, Temperatures, and Compressors with
Individual Expansion Valves and Flash Intercooling (Cont.)
(m 4 + m I ) Mass balance:
5 m5 = mI + mI + m4
8 Intercooler 4
mI m4 m3 = m4
35 kW + 70 kW + 105 kW
Q c = m 5 (h 6 h7 ) C.O.P =
Q w ,I + Q w ,II + Q w ,III
195
2: Multiple evaporators, Temperatures, and Compressors with
Multiple Expansion Valves and Flash Intercooling
7 Condenser
40oC
6
iii.
8
Evaporator I
35 kW; 10oC
5Compressor I
9 Intercooler
Evaporator II 4
10 B
70 kW; 5oC
3Compressor II
11 Intercooler
12 Evaporator III 2
105 kW; -10oC 1 Compressor III
A
196
2: Multiple evaporators, Temperatures, and Compressors with
Multiple Expansion Valves and Flash Intercooling (Cont.)
7 40oC 6
Pressure (P)
9 8 e- -2 TT zrn
10oCe- e- czn TTI mr n Ty f- -
5 4
e- Tn
10 3 2
c- e- g-
11 5oC -
1
- - os e- e- vnnn e. - -
- nn nn nn _
-10oC
12
Enthalpy (h)
197
2: Multiple evaporators, Temperatures, and Compressors with
Multiple Expansion Valves and Flash Intercooling (Cont.)
Evaporator III Evaporator II
105 kW 70 kW
m III = m II =
h 1 h 12 h 3 h 10
m1 = m III Q w ,II = m 3 (h 4 h3 )
Q w ,III = m 1 (h 2 h1 )
Mass balance:
m 3 = m II + m II + m II + m 1
h 10 h 11
x 10 =
Mass balance: h 3 h 11
m5 = mI + mI + mI + m4
Evaporator I
m3 = m4
Heat balance: 35 kW
mI =
h5 h8
h 8 m I + h 4 m 3 = h 5 (m I + m 3 )
Q w , I = m 5 (h 6 h5 )
(h 4 h5 )
mI = m3
(h 5 h8 )
199
2: Multiple evaporators, Temperatures, and Compressors with
Multiple Expansion Valves and Flash Intercooling (Cont.)
Evaporator I (Cont.)
x8
mI = m3
1 x8
h8 h9
x8 =
h5 h9
35 kW + 70 kW + 105 kW
Q c = m 5 (h 6 h7 ) C.O.P =
Q w ,I + Q w ,II + Q w ,III
200
Exercise
จ กรปข้ งล่ งน จง ขยนวงจรนลงบน P-h diagram ข ง R-12
ล จงค นวณ ค่ m ล h ทจด 3 ?
5
Condenser
40oC
4
11 12
Flash Tank
6 30oC
7
Evaporator I 13
8 70 kW; 10oC
3
Compressor I
9 Intercooler
2
10 Evaporator II
105 kW; -10oC
1
Compressor II
201
Satvi
iimtintt
!๋ _
15
I.tnn.fm
satliq 3
sat v.
mxh ×
= mnoh เอ
Pinter =
Pevap ± +
mแhแ
hx
Sat ย
=
_
.
g.
Superpeated v.
M = Mx + M เ3
µ
Psychrometric
Properties of Air
Content
Weight: m = m a + m
- w Enthalpy: H = H a + H w
mw 0.2871 pw p
= = 0.622 w
ma 0.461 pa pa
m w 0.622 p w
w= =
ma pa
w = Humidity ratio; lb water vapor / lb of dry air
pa = Partial pressure of dry air in the mixture; psi
p = pa + pw : p = Barometric pressure; psi (14.696 psi)
pw = Partial pressure of water vapor in the mixture; psi
ma = Weight of dry air; lb
mw = Weight of water vapor; lb
Specific volume (v) is defined as the volume of air per unit
weight of dry air at a specific temperature and pressure.
As one pound of air is heated it occupies more space
the specific volume increases.
Specific enthalpy (h) is the heat content of air per unit
weight of dry air (Btu/lb dry air).
The specific enthalpy of air is the enthalpy of the dry air
and the water vapor taken above an arbitrary reference
temperature at which the enthalpy is given a value of
zero, for example, 0oF for the dry air and 32oF for the
water vapor portion of air.
Enthalpy (Heat Content) of Air
The enthalpy of air is the sum of the individual enthalpies of
the dry air and water vapor.
This includes the sensible heat of the dry air and the
sensible and latent heat of the water vapor.
The total heat of the air at any condition is the sum of the
sensible heat and latent heat.
The sensible heat of the air is a function of the DB
temperature.
The latent heat of air is a function of the DP temperature.
The total heat of the air is a function of the WB
temperature.
h = 0.24 DB + w (1061 + 0.45 DP )
(P)
pewpoin
·
P A ( Wron
Cooling
2. Latent Heat Change Process (Humidification and
Dehumidification):
If moisture is added to air without changing the DB
temperature, the air condition moves upward along a DB
temperature line (Humidification).
If moisture is removed from the air without changing its DB
temperature, the air condition moves downward along a DB
temperature line (Dehumidification).
Humidification results in an increase in humidity ratio and
enthalpy. The enthalpy of the air increases due to the
enthalpy of the water vapor added.
Dehumidification results in a decrease in humidity ratio and
enthalpy.
Latent Heat Change Process
Dehumidifying
3. Combination Sensible and Latent Heat Change Process:
In actual practice, both the DB temperature and moisture
content of the air generally change simultaneously. When
this happens, the resulting air conditions move from A at
some angle.
The exact angle and direction depend upon the
proportions of sensible and latent heat added or
removed. Sensible heat causes a change in the air s DB
temperature with no change in moisture content. Latent
heat causes a change in the air s moisture content with
no change in DB temperature.
For example, to provide summer comfort, air is cooled
and dehumidified, moving the air condition downward
and to the left, resulting in a lower DB temperature and a
lower moisture content (Cooling and Dehumidifying).
Combination Sensible and Latent Heat Change Process
Humidifying
Cooling A Heating
Dehumidifying
Calculations
Sensible Heating and Cooling
Q s = 0.24 * m a * TC + 0.45 * m w * TC
Q s = 1.1 * CFM * TC
where
Qs = Sensible heat added to or removed from air, Btu/hr
TC = (t2 t1) = DB Temperature change; oF
ma = Weight of air; lb/hr
mw = Weight of water vapor; lb/hr
0.24 = Average specific heat of air; Btu/lb oF
0.45 = Average specific heat of water vapor; Btu/lb oF
h2 h1= Specific enthalpy change; Btu/ lb of dry air
Example II
A cooling coil with a rated sensible cooling capacity of 50,000
Btu/hr while handling 2,000 CFM of air entering at 80oF must
be checked to see that it is performing properly.
Thermometers at the air entrance and exit of the unit read
80oF and 62oF , and the air flow rate of the measured and
found to be 2,000 CFM. Is the unit performing satisfactorily?
Solving for the temperature change:
Q s = 1.1 * CFM * TC
TC = t2 t1 = 23 oF
80 oF t1 = 23 oF
t1 = 57 oF
Latent Heat Change (Humidifying and Dehumidifying)
Amount of water vapor added to or removed from air in a
humidifying or dehumidifying process is:
m w = m a * (w 2 w1 )
If the flow rate is expressed in CFM:
m w = 4.5 * CFM * ( w 2 w1 )
If the humidity ratio is given in gr w./lb dry air:
mw = 58 lb w./hr
Solving for the latent heat required:
Q l = 0.68 * CFM * ( w '2 w 1' ) Q l = 4.5 * CFM * (h 2 h1 )
Ql = 61,200 Btu/hr Ql = 62,100 Btu/hr
Combined sensible and latent heat change:
Air conditioning for human comfort usually requires
a process where both sensible and latent heat are
removed from air-that is, the air is cooled and
dehumidified.
Total heat removed or added to the process is:
Q t = Qs + Ql
Example IV
An air conditioning unit has a cooling coil that cools and
dehumidifies 20,000 CFM of air from 82oF DB and 50% RH to
64oF WB. Find the sensible, latent, and total capacity of the
cooling coil and the amount of moisture condensed?
Solving for Qs, Ql, Qt and mw :
Cooling coil
2 1
20,000 CFM
82 F DB 64 oF DB
50% RH 61oF WB
Solving for Qs: Q s = 1.1 * CFM * TC Q s = 4.5 * CFM * (h X hA )
supply outdoor
mixture
fan C air (OA)
B
Cooling coil
Recirculated air (RA) A
80 F
Example V
Return Air, RA
2,000 CFM
2 75o F DB, 50% RH
1,000 CFM
90oF DB, 72oF WB 1 3
Outside air (OA) and return air (RA) are mixed. Find the mixed air DB
and WB and write a process line on the psychrometric chart ?
80°F DB
50% RH
Guide point
Drawing an SHF Line
80°F DB
Guide point 50% RH
SHF Dictates Room Supply Air Condition
Supply air with any combination of DB and WB temperatures that falls
on an SHF line will be able to absorb the room's sensible and latent
heat in the correct proportions needed to maintain the desired room
conditions (A).
Each of these combinations, however, requires a different quantity of
air to do the task. If the supply air is warm, a higher quantity of air is
required than if the supply air is cold.
A
Drawing an SHF Line for Room Supply Air
Assume that room design conditions are 80°F DB and 60%
RH, and that the SHF is calculated as 0.60.
First, line up the guide point with the 0.60 marking on the
SHF scale and draw a line.
Next, draw a second line, parallel to the first, through the
point (B) that represents the design room conditions. This
is the 0.60 SHF line for a room at 80°F DB and 60% RH.
Supply air at C (60°F DB and 58°F WB) will maintain the
desired room conditions, as will supply air at D (70°F DB
and 64°F WB).
To do so, each of these combinations will require a
different quantity of air (CFM).
Drawing an SHF Line for Room Supply Air
B
D
C
Guide point 80°F
Coil Process Line: The straight line drawn between the air conditions entering
and leaving the coil.
This line depends on the coil configuration, air velocity, and refrigerant
temperature.
It is actually a curved line but it is possible to locate a straight line on the
chart to select a coil or to check the performance of a coil.
The capacity of a coil is defined as the sensible, latent and total heat that
it removes from the air it is conditioning ( Cooling Coli Capacity ).
Example VI
A cooling coil handles 24,000 CFM of air entering at 86oF DB and 73oF WB.
The air leaves the coil at 59oF DB and 56oF WB. Determine the coil capacity
using the psychrometric chart?
Solving for Qs, Ql, and Qt
Qs = 4.5 * CFM * (h X h2 )
Qt = Qs + Ql
Qt = 1,404,000 Btu/hr
Psychrometric Analysis of the A/C System (Cont.)
The temperature of the outside surface of a cooling coil is not the same at all
places along the coil tubing. It will vary due to a number of factors; e.g., tube
size spacing, and number of row, etc.
Effective Surface Temperature (EST) or Apparatus Dew Point (ADP): An
average coil surface temperature.
If all the air passing over the coil contacted the surface (CF = 1), the air would
leave at a temperature equal to the EST.
Psychrometric Analysis of the A/C System (Cont.)
When air passes across the outside
surface of a cooling coil, only part of the
air actually contacts the surface and is
cooled.
Contact Factor (CF) : the proportion of
air passing through the coil that touches
the cooling surface and is thus cooled.
Bypass Factor (BF): the proportion of air
that does not touch the surface, and is
thus not cooled.
CF + BF = 1
CF = b/a
BF = (a-b)/a
Example VII
The following design data has been established for the high life insurance company
office building:
RSCL = 740,000 Btu/hr; RLCL = 150,000 Btu/hr
Outside design conditions: 94oF DB, 75oF WB
Inside design conditions: 78oF DB, 50% RH
Outside air required is 6,730 CFM; Supply air temperature difference is 20oF
Determine 1) supply air CFM 2) Supply air condition 3) conditions entering
cooling coil 4) Cooling coil sensible, latent, and total load 5) ADP
Example VII (Cont.)
Solving for supply air CFM:
Qs = RSCL = 1.1 * CFM 3 * ( t 4 t3 )
Q l = 4.5 * CFM * (h 2 hX )
Qt = Qs + Ql
Example VII (Cont.)
1 2 3 SA
OA
RA Conditioned
7 6 FCU 5 Room
EA 4
รปท 3.1
Exercise (Cont.)
จ กรปท 3.1 ดงร บบปรบ ก ภ ย น ้ ง จง ค่ ต่ ปน ดย ช้ ข้ มลท ดง ว้
ด้ นล่ ง
ลดคว มร้ น มผ ข ง ้ ง (Room sensible cooling load, RSCL) = 812,000
Btu/hr
ลดคว มร้ น ฝงข ง ้ ง (Room latent cooling load, RLCL) = 235,000
Btu/hr
ปรม ณข ง ก ภ ยน กทน ข้ ม น ้ ง (Outside air, OA) = 6,000 CFM
ณ ภมข ง ก ท กจ กค ยล์ ยน (Supply air) = 59oF DB
ภ ว ข ง ก ภ ย น ้ ง (Inside design conditions) = 77oF DB, 50 % RH
ภ ว ข ง ก ภ ยน ก (Outside design conditions) = 91oF DB, 75oF WB
1. ปรม ณข ง ก ทจ่ ย กจ ก Fan Coil Unit (FCU) น น่ วย CFM ล ณ ภม
กร ป ปยก (WB) ข ง ก
2. ณ ภมกร ป ้ ง (DB), ณ ภมกร ป ปยก (WB), คว มชน มพทธ์ (RH) ล
คว มชนจ พ (w) ข ง ก ผ ม (จด 2)
Exercise (Cont.)
3. ลดคว มร้ น มผ (Sensible load), ลดคว มร้ น ฝง (Latent load), ล ลด
คว มร้ นทง มด (Total load) ข ง ก ภ ยน ก (Outside air)
4. ลดคว มร้ น มผ (Coil sensible load), ลดคว มร้ น ฝง (Coil latent load), ล
ลดคว มร้ นทง มด (Coil total load) ข ง Coil
5. ณ ภมจดน ค้ งข ง ปกรณ์ (Apparatus dew point temperature), ตวปร ก บ ม่
มผ (Bypass factor) ล ปรม ณข ง ก ท มผ Coil น น่ วย CFM
6. ดงจดต่ ง นกร บวนก รนลงบน Psychrometric chart
Refrigeration and Air Conditioning
257
Human Comfort
Air conditioning systems use the principles of heat
transfer to maintain comfortable indoor conditions for
people.
Heat energy is transferred from one substance to
another by one of three basic processes: conduction,
convection, or radiation.
convection
warm air
radiation
260
Human Comfort
The average adult, seated and working, generates excess
heat at the rate of approximately 450 Btu/hr [132 W]. About
60% of this heat is transferred to the surrounding environment
by convection and radiation, and 40% is released by
perspiration and respiration.
As the level of physical activity increases, the body generates
more heat in proportion to the energy expended. When
engaged in heavy labor, as in a factory for example, the body
generates 1,450 Btu/hr [425 W]. At this level of activity, the
proportions reverse and about 40% of this heat is transferred
by convection and radiation and 60% is released by
perspiration and respiration.
In order for the body to feel comfortable, the surrounding
environment must be of suitable temperature and humidity to
transfer this excess heat.
261
Human Comfort
If the temperature of the air surrounding the body is
too high, the body feels uncomfortably warm. The
body responds by increasing the rate of perspiration
in order to increase the heat loss through
evaporation of body moisture.
Additionally, if the surrounding air is too humid, the
air is nearly saturated and it is more difficult to
evaporate body moisture.
If the temperature of the air surrounding the body is
too low, however, the body loses more heat than it
can produce. The body responds by constricting the
blood vessels of the skin to reduce heat loss.
In summary, the factors that affect human comfort
are the DB temperature, humidity, air movement,
fresh air, clean air, noise level, adequate lighting,
and proper furniture and work surfaces.
262
Comfort Zone
Research studies have been conducted to show that, with a
specific amount of air movement, thermal comfort can be
produced with certain combinations of DB temperature and
relative humidity (RH).
When plotted on a psychrometric chart, these combinations
form a range of conditions for delivering acceptable thermal
comfort to 80% of the people in a space. This “comfort zone”
and the associated assumptions are defined by ASHRAE
Standard 55, Thermal Environmental Conditions for Human
Occupancy.
Determining the desired condition of the space is the first step
in estimating the cooling and heating loads for the space.
At 78ºF [25.6ºC] DB and 50% relative humidity (A) is usually
the desired indoor condition during the cooling season.
263
Comfort Zone
humidity ratio
A
comfort zone
70°F 80°F
[21.2°C] [26.7°C]
dry-bulb temperature 264
265
Cooling Load Components
The space cooling load is the rate at which heat must
be removed from a space in order to maintain the
desired conditions in the space, generally a DB
temperature and relative humidity
roof (RH).
lights partition
people wall
infiltration
glass solar
equipment
glass
conduction
exterior
wall
floor 266
The cooling load for a space can be made up of many components,
including:
Conduction heat gain from outdoors through the roof, exterior walls,
skylights, and windows. (This includes the effects of the sun shining
on these exterior surfaces.)
Solar radiation heat gain through skylights and windows.
Conduction heat gain from adjoining spaces through the ceiling,
interior partition walls, and floor.
Internal heat gains due to people, lights, appliances, and equipment
in the space.
Heat gain due to hot, humid air infiltrating into the space from
outdoors through doors, windows, and small cracks in the building
envelope. 267
In addition, the cooling coil in the building Heating and
Ventilating Air-Conditioning (HVAC) system has to
handle other components of the total building cooling
load, including:
Heat gain due to outdoor air deliberately brought into
the building for ventilation purposes.
Heat generated by the fans in the system and possibly
other heat gains in the system.
Throughout this period, we will assume that all of the
heat gain due to the roof and lighting affects the space
directly. 268
These load components contribute sensible and/or latent heat to the space.
Conduction through the roof, exterior walls, windows, skylights, ceiling,
interior walls, and floor, as well as the solar radiation through the windows
and skylights, all contribute only sensible heat to the space.
The people inside the space contribute both sensible and latent heat.
Lighting contributes only sensible heat to the space, while equipment in the
space may contribute only sensible heat (as is the case for a computer) or
both sensible and latent heat (as is the case for a coffee maker).
Infiltration generally contributes both sensible and latent heat to the space.
The cooling coil has to handle the additional components of ventilation and
system heat gains. Ventilation contributes both sensible and latent heat to
the coil load.
Other heat gains that occur in the HVAC system (e.g., from the fan)
generally contribute only sensible heat. 269
Cooling load components Sensible Latent Space Coil
load load load load
Conduction through roof, walls, windows,
and skylights
Solar radiation through windows, skylights
Conduction through ceiling, interior
partition walls, and floor
People
Lights
Equipment/Appliances
Infiltration
Ventilation
System heat gains
270
Heat Storage and Time Lag Effects
Radiation Heat stored in Convection
furnishings, structure
(delayed in time)
Convection
The amount of heat that must be removed is not always equal to the amount of heat
received at a given time.
This difference is a result of the heat storage and time lag effects.
Of the total amount of heat entering the building at any instant, only a portion of it heats
the room air immediately; the other part heats the building mass (e.g., roof, walls, floors,
and furnishings) Heat storage effect .
At a later time, the stored heat portion contribute to heating the room air Time lag
effect . 271
Heat storage and time lag effects cause the cooling load to often be different in value
from the entering heat (called instantaneous heat gain).
In the afternoon, the instantaneous heat gain is the highest but the cooling load is
less than that of the instantaneous heat gain.
Later in the day, the stored heat plus some of the new entering heat is released to the
room air, so the cooling load becomes greater than the instantaneous heat gain.
272
Time of Peak Cooling Load
One of the more difficult aspects of estimating the maximum cooling
load for a space is determining the time at which this maximum load
will occur. This is because the individual components that make up the
space cooling load often peak at different times of the day, or even
different months of the year.
For example, the heat gain through the roof will be highest in the late
afternoon, when it is warm outside and the sun has been shining on it
all day.
Conversely, the heat gain due to the sun shining through an east-facing
window will be highest in the early morning when the sun is rising in
the east and shining directly into the window. 273
Time of Peak Cooling Load
East-facing
window Roof
Heat gain
12 6 12 6 12
mid a.m. noon p.m. mid
274
Design Conditions
The cooling load calculations are usually based on inside and outside design conditions
of temperature and humidity. Suggested inside design conditions listed above.
275
Design Conditions (Cont.)
Obviously, A/C systems would be greatly oversized if cooling load calculations
were based on the most extreme outdoor temperature ever recorded for the
location. Instead, outdoor design temperatures are based on their frequency of
occurrence.
The outdoor summer design conditions are based on reasonable maximums,
using weather records.
The 2.5% values will provide a reasonable compromise between comfort and
cost for most applications.
2.5% means that the temperature equal or exceed 2.5% of the hours in the
summertime hours.
Table A.9 (page 497) lists these conditions for some cities.
Use the DB and coincident WB temperature as the corresponding outdoor
design values.
For Bangkok, Thailand, DB, WB temperature and Daily DB temperature
range are approximately 35oC, 28oC and 10oC, respectively.
276
Conduction through Exterior Structure
Conduction is the process of transferring heat through a solid, such as a wall,
roof, floor, ceiling, glass window, or skylight.
Heat naturally flows by conduction from a higher temperature to a lower
temperature.
The most common conduction heat gains to a space are: through the roof,
external walls, and glasses.
Q=U A T Q = U A CLTDc
Q = Heat gain by conduction; Btu/hr
U = Overall heat-transfer coefficient of roof, wall, or glass; Btu/hr ft2 oF
A = Area of roof, wall, or glass; ft2
T = DB temperature difference across the surface; ºF
CLTDc = Corrected cooling load temperature difference; ºF 277
Conduction through Exterior Structure (Cont.)
The cooling load temperature difference (CLTD) is not the actual temperature
difference between the outdoor and indoor air.
It is a modified value that accounts for the heat storage and time lag effects.
Table 6.1 and 6.2 (page 122-124) list CLTD values for some roof and wall
constructions. The listed hour is Solar time which is approximately equal to
Standard time. Add one hour for Daylight Savings time.
These values are based on the following conditions:
Indoor temperature is 78oF DB.
Outdoor average temperature on the design day is 85oF DB.
Date is July 21st.
Location is 40o N latitude.
If the actual condition differs from any of the above, the CLTD must be
corrected as following:
278
Conduction through Exterior Structure (Cont.)
CLTDc = CLTD + LM + (78 tR) + (ta - 85)
ta = to (DR/2)
283
Conduction through an Interior Structure
The heat flowing from interior unconditioned spaces to the conditioned space
through partitions, floors, and ceilings can be found from:
Q = U x A x TD
where Q = Heat gain by conduction through partition, floor, or ceiling; Btu/hr
U = Overall heat-transfer coefficient for partition, floor, or ceiling;
Btu/hr ft2 oF
A = Area of partition, floor, or ceiling; ft2
TD = Temperature difference between unconditioned and conditioned
space; ºF
If the temperature of the unconditioned space is not known, an approximation
often used is to assume that it is at 5oF less than outdoor temperature, except for
a room with heat sources, such as a boiler room or a mechanical room.
284
Solar Radiation through Glass
A large part of the solar heat energy that
shines on a window or skylight is radiated sun rays
through the glass and transmitted directly into
the space.
The amount of solar heat radiated through the transmitted
reflected energy
glass depends primarily on the reflective energy glass
characteristics of the glass and the angle at window
which the sun s rays strike the surface of the
glass.
Its value varies with time, orientation, shading, and storage effect.
To limit the amount of solar radiation entering the space, heat-absorbing glass,
reflective glass, or internal or external shading devices can be used.
285
Sunlit Surfaces
286
Solar Radiation through Glass (Cont.)
The equation used to estimate the solar heat gain (cooling load) through
glass is:
Q = SHGF A SC CLF
288
Shading Devices
Installing internal shading devices, such as venetian blinds, curtains, or drapes, can
reduce the amount of solar heat energy passing through a window.
The effectiveness of these shading devices depends on their ability to reflect the
incoming solar radiation back through the window, before it is converted into heat
inside the space.
Light-colored blinds or drapes lined with light-colored materials, therefore, are more
effective than dark-colored shading devices.
The type of internal shading device used affects the shading coefficient of the window-
and-shading-device combination.
External shading devices, such as overhangs, vertical fins, or awnings, can also reduce
the amount of solar heat energy passing through a window. They can be used to
reduce the area of the glass surface that is actually impacted by the sun s rays.
289
External Shading Effect
The values for the SHGF shown in Table 6.6 are for direct solar radiation
when the sun shines on the glass.
External shading from building projections (or other objects) may shade
all or part of the glass. Only an indirect radiation reaches the glass from
the sky and ground.
The SHGF values for any shaded glass is the same as the North side of the
building, which also receives only indirect radiation.
Table 6.11 (page 134) can be used to find the shading from overhead
horizontal projections. The values in this table are the vertical feet of
shade for each foot of horizontal projection.
290
Examples
1. A building wall facing southwest has a window area of 240 ft2. The glass is ¼ in. single
clear glass with light-colored interior venetian blinds. The building is of medium
construction, and is located at 40oN latitude. Find the solar cooling load in August at
3PM Solar time?
SHGF =196 Btu/hr-ft2; SC= 0.67 ;CLF= 0.83; A = 240 ft2;Qsolar=26,160
Btu/hr
2. A building at 32oN latitude has a wall facing west with a 4 ft
overhang, and a 5 ft wide by 6 ft high window whose top is 1 ft
4 ft
below the overhang. How much of the glass receives direct solar
1 ft
radiation at 3 PM?
2.9 ft
Vertical proportion of shade = 0.97; Total vertical
3.1 ft
distance the shade extends down = 0.97*4 = 3.9 ft; The
height of shade on the window = 3.9 - 1 = 2.9 ft; The
unshaded height = 6 - 2.9 = 3.1 ft; The unshaded area of
window = 5*3.1 = 15.5 ft2 291
Examples (Cont.)
3. A room with no carpeting and a wall facing east at 40N latitude has a
total window glass area of 80 ft2. The building is of heavy weight (H)
construction. The glass is ¼ in. single heat-absorbing glass with no
interior shading device. At 10 AM ST in June, and adjacent building
shades 30 ft2 of the window. What is the solar cooling load?
SHGF = 216 Btu/hr-ft2; SC = 0.69 ; CLF = 0.50; A = 50 ft2 (direct
radiation); Qdirect solar= 3,730 Btu/hr
SHGF (North orientation) = 48 Btu/hr-ft2; SC = 0.69 ; CLF= 0.50;
A = 30 ft2 (diffuse radiation); Qindirect solar= 500 Btu/hr
Total solar cooling load (Qtotal solar ) = 3,730 + 500 = 4,230 Btu/hr
292
Internal Heat Gains
The next component of the space cooling load is the heat that originates
within the space.
Typical sources of internal heat gain are people, lights, cooking
processes, and other heat-generating equipment, such as motors,
appliances, and office equipment.
While all of these sources contribute sensible heat to the space, people,
cooking processes, and some appliances (such as a coffee maker) also
contribute latent heat to the space.
293
Heat Gain from Lighting
Heat generated by lights in the space is a significant contribution to the
cooling load. For example, a 120-watt light fixture generates 410 Btu/hr of
heat approximately the same amount of heat gain from an average office
worker.
Additionally, when estimating the heat gain generated by fluorescent
lights, approximately 20% is added to the lighting heat gain to account
for the additional heat generated by the ballast.
Similar to the sensible heat gain from people, a cooling load factor (CLF)
can be used to account for the capacity of the space to absorb and store
the heat generated by the lights.
294
Heat Gain from Lighting (Cont.)
The storage effect depends on how long the lights and cooling system are
operating, and the building construction, type of lighting fixture, and
ventilation rate.
No storage effect can be allowed for any of the following conditions:
Cooling system operates only during occupied hours
Cooling system operates more than 16 hr.
Temperature of the space is allowed to rise during nonoccupied hours
(temperature swing)
The CLF tables for lighting are not presented, use CLF = 1.0.
If the lights are left on 24 hours a day, or if the air-conditioning system is
shut off or set back at night, the CLF is assumed to be equal to 1.0.
295
Heat Gain from Lighting (Cont.)
The equation used to estimate the heat gain from lighting is:
Q = 3.41 x W x BF x CLF
296
Heat Generated by People
The heat gain from people is composed of two parts, sensible heat and the latent
heat resulting from perspiration.
Some of the sensible heat may be absorbed by the heat storage effect, but not the
latent heat.
The equations for cooling loads from sensible and latent heat gains from people
are:
Qs = qs x n x CLF
Ql = ql x n
298
Heat Generated by Equipment
The heat gain from equipment may sometimes be found directly from the
manufacturer or the nameplate data, with allowance for intermittent use.
Some equipment produces both sensible and latent heat.
Some values of heat output for typical appliances are shown in Table 6.15.
The heat output from motors and the equipment driven by them results
from the conversion of the electrical energy to heat.
The proportion of heat generated that is gained by the A/C space depends
on whether the motor and driven load are both in the space or only one of
them is. Table 6.16 lists heat outputs for each condition.
299
Examples
1. A room has eight 40 W fluorescent lighting fixtures in use. The cooling
system operates only during occupied hours. What is the solar cooling load
from the lighting?
BF = 1.25; CLF = 1.0; W = 40 watts; Qlighting = 1,360 Btu/hr
2. What is the heat gain from 240 people at night in a movie theater at 75 oF
DB?
n = 240; qs = 245 Btu/hr; ql = 105 Btu/hr; CLF = 1.0; Qtotal = 84,000
Btu/hr
300
Examples (Cont.)
3. Diane s Deli Diner has the following equipment operating in the A/C area,
without hoods: 1 coffee burner (2 burners); 1 coffee heater (1 burner); 1
toaster (large). What are the sensible, latent, and total heat gains from
equipment?
Qs, burner= 3,750 Btu/hr; Ql, burner= 1,910 Btu/hr; Qs, heater= 230 Btu/hr;
Ql, heater= 110 Btu/hr; Qs, toaster= 9,590 Btu/hr; Ql, toaster= 8,500 Btu/hr
;Qtotal = 24,090 Btu/hr
4. A hotel with 150 rooms has a fan-coil air conditioning unit in each room, with
a 0.16 HP motor. What is the heat gain to the building from the units?
Both motor and fan are in the conditioned spaces.
Qequipment = 1,160 Btu/hr x 150 = 174,000 Btu/hr
301
Infiltration
In a typical building, air leaks into or out of a
space through doors, windows, and small
cracks in the building envelope.
Air leaking into a space is called infiltration.
During the cooling season, when air leaks into
a conditioned space from outdoors, it can
contribute to both the sensible and latent heat
gain in the space because the outdoor air is
typically warmer and more humid than the
indoor air.
302
Infiltration (Cont.)
The amount of heat required to offset the sensible and latent heat loss from
infiltration air can be determined by:
Qs = 1.1 x CFM x TC
Ql = 0.68 x CFM x (Wi Wo )
Where Q = Sensible heat loss from infiltration or ventilation air; Btu/hr
Q = Latent heat required for infiltration or ventilation air; Btu/hr
CFM = Air infiltration or ventilation flow rate; ft/min
TC = Temperature change between indoor and outdoor air; F
Wi , Wo = Higher (indoor) and lower (outdoor) humidity ratio in
grains water / lb dry air (from psychrometric chart)
303
Methods of Estimating Infiltration
There are two methods used to estimate infiltration airflow (CFM): crack method and
air change method.
The crack method is based upon the average quantity of air known to enter through
cracks around windows and doors when the wind velocity is constant.
Table 3.4 (page 55) lists typical allowable infiltration rates, based on a 25 MPH wind.
The crack lengths and areas are determined from architectural plans or field
measurements.
Poorly fitted windows may have up to five times the sash leakage shown in Table 3.4
Table 3.4 Typical allowable design air infiltration rates through exterior windows and doors
Component Infiltration Rate
Windows 0.37 CFM per ft or sash crack
Residential doors 0.50 CFM per ft2 of door area
Nonresidential doors 1.00 CFM per ft2 of door area
304
Methods of Estimating Infiltration (Cont.)
For a corner room with door or window openings on both sides, we assume
that infiltration air comes through cracks on one side only.
For building that have frequent door usage such as department stores, the
infiltration resulting from door opening should be included. Table 3.5 (page
56) shows some average infiltration rates for frequent door usage.
305
Methods of Estimating Infiltration (Cont.)
The air change method is the easiest, but may be the least accurate of these
methods.
It involves estimating the number of air changes per hour that can be expected in
spaces of a certain construction quality.
Using this method, the quantity of infiltration air is estimated using the equation:
CFM = (ACH x V) 60
where, CFM = Quantity of air infiltrating into the room, cfm
V = Room volume, ft3
ACH (Air Change per Hour) = Number of air changes per hour
One ACH (Air Change per Hour) is defined as being equal to the room air volume.
Determination of the expected number of air changes is based on experience and
testing.
Suggested values range from 0.5 ACH to 1.5 ACH for buildings ranging from
tight to loose construction.
306
Methods of Estimating Infiltration (Cont.)
The air change method is used primarily in residential construction heating
load estimates, but there is no reason why the crack method cannot be used if
reliable data are available.
The crack method is generally used in nonresidential construction. Reliable
data from window manufacturers and quality control of installation and
maintenance may provide good estimates using this method.
For a building that is not mechanically ventilated and that has reasonably
free interior passages for air movement, the following rule is suggested:
The building air infiltration CFM is equal to one-half the sum of the
infiltration CFM of every opening on all sides of the building.
307
Methods of Estimating Infiltration (Cont.)
Most summer A/C systems have mechanical ventilation using some
outside air, which reduces or eliminates infiltration by creating a
positive air pressure the building.
Ventilation air is not a load on the room, but is a load on the central
cooling equipment.
Many modern buildings have fixed (sealed) windows and therefore
have no infiltration loss, except for entrances.
308
Room Cooling Load
The room cooling load is the sum of each of the cooling load components
(roof, walls, glass, solar, people, equipment, and infiltration) in the room.
A commercial cooling load calculation form is shown in Appendix (page
504). This form can be used for individual rooms or for a small building.
The following abbreviations will be used for convenience:
TCL, SCL, LCL = Component total, sensible, latent cooling loads
RTCL, RSCL, RLCL = Room total, sensible, latent cooling loads
BTCL, BSCL, BLCL = Building total, sensible, latent cooling loads
CTCL, CSCL, CLCL = Coil total, sensible, latent cooling loads
309
Room Peak Cooling Load
The A/C system must be sized to handle peak (maximum) load, the peak cooling
load must be determined.
The external heat gain components vary in intensity with time of day and time of
year because of changing solar radiation as the orientation of the sun changes and
because of outdoor temperature changes.
Some general guidelines can be offered to simplify this task.
From the CLTD, SHGF, and CLF tables, we can note the following:
Facing Glass Maximum solar load Times
West Mid-summer Afternoon
East Early or mid-summer Morning
South Fall or winter Early afternoon
Southwest Fall Afternoon
Roofs Summer Afternoon or evening
Walls Summer Afternoon or evening 310
Room Peak Cooling Load (Cont.)
These generalizations can be used to localize approximate times of room
peak loads.
For example, we might expect a south-facing room with a very large
window area to have a peak load in early afternoon in the fall not in the
summer.
However, if the room had a small glass area, the wall and glass heat
conduction might dominate and the peak load time would be a summer
afternoon.
311
Example
A room facing east, in the Shelton Motel in St. Louis, Missouri, has a 60 ft2
window with an aluminum frame with a thermal break. The window is ¼ in.
single heat-absorbing glass. Light colored interior venetian blinds are used.
The wall is a metal curtain wall with a U-value of 0.14. Building construction
is lightweight. Find the time and value of room peak cooling load. The room is
at 78 oF DB.
8 AM in August (page 143)
312
Building Peak Cooling Load
The building cooling load is the rate at which heat is removed from all air-
conditioned rooms in the building at the time the building cooling load is at its
peak value.
Since the peak cooling loads for each room in the building do not occur at the
same time, the time of year and time of day at which the building cooling load is
at a peak should be determined.
The following guidelines can be used to find the building peak cooling load:
For a square-shaped buildings with similar construction on all four walls,
the peak load is usually in late afternoon in summer.
For a long south or southwest exposure building having large glass areas,
the peak load may occur in the fall, around mid-day.
For one-story buildings with very large roof areas, the peak load usually
occurs in the afternoon in summer. 313
Building Peak Cooling Load (Cont.)
These suggestions must be verified in each case because there are so many variations
in building orientation and construction.
Once the peak load time is determined, the total building heat gains can be
calculated.
Note that the search for the time and value of peak room and building cooling loads is
greatly simplified by using computer software programs.
In some buildings, the actual building peak load may be less than the calculated value
due to load diversity or usage practice. In these cases, a diversity factor or usage
factor is sometimes estimated and applied to reduce the calculated building peak
load. For example, if it is estimated that only 90% of the lighting is actually on at
peak load time, the calculated lighting load would be multiplied by a factor of 0.90.
Choosing a proper diversity factor requires both experience and judgment about
building use practices.
314
Cooling Coil Load
The cooling coil load is the rate at which heat must be removed by the air
conditioning equipment cooling coil.
The cooling coil load will be greater than the building load because there
are heat gains to the A/C system itself. These gains may include:
Ventilation (outside air)
Heat gains to ducts
Heat produced by the A/C system fans and pumps
Air leakage from ducts
315
Ventilation
outdoor-air
supply duct
intake
diffuser
air handler
with fan and
cooling coil
Outdoor air is often used to dilute or remove contaminants from the indoor
(room) air for health and comfort.
The sensible and latent heat of this air is usually greater than that of the
room air, so it becomes part of the cooling load.
Since it usually removed in the cooling equipment, it is part of the cooling coil
load, not the building load.
316
Ventilation (Cont.)
It is common to introduce outdoor air through the A/C system, not only to
meet the ventilation needs, but also to maintain a positive pressure (relative
to the outdoors) within the building. This positive pressure reduces, or may
even eliminate, the infiltration of unconditioned air from outdoors.
To pressurize the building, the amount of outdoor air brought in for
ventilation must be greater than the amount of air exhausted through central
and local exhaust fans.
The equations for determining the sensible and latent cooling loads from
ventilation air are described previously as:
Qs = 1.1 x CFM x TC
Ql = 0.68 x CFM x (Wo Wi )
Qt = Qs + Ql
317
Ventilation (Cont.)
Recommended outdoor air ventilation rates for some applications are listed
in Table 6.17 (page 145).
Note that the values shown in this table do not make special allowance for
the amount of indoor air pollutants being generated.
If the peak load does not occur at the time of the day that the outdoor
temperature is at a maximum, a correction must be made to the outdoor
temperature used for calculating ventilation and infiltration loads.
Table 6.18 (page 146) lists this correction to reduce the peak design outdoor
dry-bulb temperature.
318
Heat Gain to Ducts
Another source of heat gain in the system
may be heat that is transferred to the
conditioned air through the walls of the
supply and return air ducts.
For example, if the supply ductwork is
routed through an unconditioned space,
such as a ceiling plenum or an attic, heat can
be transferred from the air surrounding the
duct to the supply air.
Supply ductwork is generally insulated to
prevent this heat gain and the associated
increase in temperature of the supply air
319
Heat Gain to Ducts (Cont.)
Return ductwork, on the other hand, is generally not insulated unless it passes
through a very warm space.
The heat gain can be calculated from the heat transfer equation as:
Q = U x A x TD
321
System Heat Gains
air handler
fan motor
Some of the energy from the system fans and pumps is converted into heat
through friction and other effects, and becomes part of the sensible heat gain
that should be added to the load.
It is important to know where the fan heat gain occurs with respect to the
cooling coil.
For a draw-through fan arrangement (fan downstream from the cooling coil),
the heat is added to the BSCL.
For a blow-through arrangement (fan upstream from the coil), the heat gets
added to the CSCL load. 322
System Heat Gains (Cont.)
blow-through
configuration
draw-through
configuration
324
Duct Air Leakage
Duct systems will leak air at joints.
A careful duct installation should limit duct leakage to 5% or less of the
total CFM.
If ducts are outside the conditioned space, the effect of leakage must be
added to the BSCL and BLCL.
If the air leaks into the conditioned space, then it does useful cooling,
but care should be taken that it is not distributed to the wrong location.
325
Summary of Commercial Cooling Load Calculation
Procedures
1. Select indoor and outdoor design conditions from Table 1.1 and A.9.
2. Use architectural plans to measure dimensions of all surfaces through
which there will be external heat gains, for each room.
3. Calculate areas of all these surfaces.
4. Select heat transfer coefficient U-values for each element from appropriate
tables, or calculate from individual R-values
5. Determine time of day and month of peak load for each room by
calculating external heat gains at times that they are expected to be a
maximum. Search Tables 6.1, 6.2, 6.6 and 6.8 to find maximum values.
Often calculations at a few different times will be required, but the
suggestions described previously should be helpful.
326
Summary of Commercial Cooling Load Calculation
Procedures (Cont.)
6. Calculate each room peak load (RSCL, RLCL, and RTCL).
7. Find the time of building peak load using a similar search process as in
item 5.
8. Calculate the building load at peak time, adding all external and internal
heat gains and infiltration, if any. Add supply duct heat gain, duct heat
leakage and draw-through supply fan heat gain, if significant.
9. Find the cooling coil and refrigeration load by adding the ventilation load
to the building heat gains; adding blow-through fan, return air fan, and
pump heat gains, if significant.
10. Calculate required supply air conditions using the psychrometric chart.
327
328
Example
The Superb Supermarket, shown below, is located in Indianapolis, Indiana. It is
a one-story building with a basement used for storage. Construction and
conditions are as follows:
329
Example (Cont.)
Roof is 4 in. h.w.concrete slab, 2 in. insulation, gypsum board ceiling, U=0.09
Btu/hr-ft2-oF
Floor is 4 in. concrete slab, U = 0.35 Btu/hr-ft2-oF
Walls are 4 in. face brick, 4 in. common brick, 2 in. insulation, ½ in. gypsum
wallboard, U = 0.11 Btu/hr-ft2-oF
Front window is ¼ in. single heat absorbing glass, 10 ft high, aluminum frame,
not shaded.
Doors are ¼ in. single clear glass, aluminum frame.
Receiving door is 1½ in. steel with urethane core.
Occupancy is 60 people.
Construction is medium (M) weight.
Lighting is 3 watts per square foot of floor area, fluorescent fixtures.
Outdoor ventilation rate as per Table 6.17.
Store is open from 10 AM to 8 PM (9 AM to 7 PM Standard time)
Determine the required cooling load? 330
331
Refrigeration and Air Conditioning
ng
หั
ท่
ท่
น้
ำ
ำ
น้
ป็
ำ
ลั
Hydronic Piping Systems and Terminal Units
พบ
ร าตวา มเ มเ อ ผลิต
Hydronic piping system is the piping used to circulate chilled water for
A/C system.
The heat exchangers that transfer the heat between the water and the
-
#
Series loop
มก มขนา ดารา กา นทเ
One-pipe main
Two-pipe direct return
Two-pipe reverse return
ต่
ร่
นื้
ท่
ที่
สื
generator Series Loop ส
ful
~ า Temp- ุ่งเก
~
wa
chili water2 vi
Hot /
if <
The entire water supply flows through each terminal unit and then returns to the
generator and pump. -
-
There are several disadvantages:
-
Designan).
The maintenance or repair of any unit requires shutdown of the entire system.
Separate capacity control of each unit is not possible.
The number of units is limited since the water temperature in later units may be
too high for adequate cooling.
ราคาในการ ร ด ง ต าง กท ุด
่อ- / ญหาใ
ที่
ช่
ปั
ติ
สุ
ถู
ต่
ผ่
=
Series Loop (Cont.)
-
By arranging the piping in two or more split series loops, as shown above,
some disadvantages of the series loop can be partially remedied.
The series loop arrangement is simple and inexpensive.
-
Each terminal unit is connected by a supply and a return branch pipe to the
main.
By locating valves in the branch lines, each unit can be separately controlled
and service.
If there are too many units, the water going to the later units may be too hot to
cool the rooms adequately.
A special diverting tees are used at each supply branch takeoff to direct some of
the water to the branch.
Two-Pipe Direct Return
There are two main lines, one for supply water and one for return.
Each terminal unit is fed by an individual supply branch.
A return branch carries the water back to the return main.
In this manner, all units receive water directly from the source.
The supply water temperature to each unit is the same.
The total system flow rate is split up among the terminal units, according to
the design.
Each terminal unit can be separately controlled and serviced.
Two-Pipe Direct Return (Cont.)
The return main is routed to bring the water back to the source by the
shortest path.
This creates a problem since the path the water takes from the pump to the
first units and back is shorter than the units further away.
Thus, there will be too much water going to the units nearest the pump and
too little to the units furthest from the pump.
Balancing valves can be installed in every branch, but the balancing process
is difficult and requires considerable expense.
All larger systems use two-pipe arrangements.
Two-Pipe Reverse Return
Q = 500 x GPM x TC
The energy of the fluid at any point in a pipe or duct consists of pressure,
velocity (kinetic energy), and elevation (potential energy).
The added energy may be that of a pump or fan whereas the energy lost is due
to friction.
Other energy changes such as temperature change are usually small and may
be neglected.
Energy balance is expressed as:
Flow Energy Equation (Cont.)
(V22 V12 )
H p = (H s 2 H s1 ) + + (H e2 H e1 ) + H f
2g
Solution H s 2 = H s1 + H p Hf +(
V12 V22
) + ( H e1 H e 2 )
2g
V1 2 V
H s 2 = 1.10 0.43 + ( ) ( 2 )2
4000 4000
However, there is always some friction loss; thus, the actual static pressure
regain is never as high as that shown above.
The proportion of static regain that can be recovered, called the recovery
factor R, depends upon the shape of the transition that changes velocity.
Conversion of Velocity Pressure to Static Pressure
(Static Regain) (Cont.)
The actual static pressure regain (SPR) is therefore:
2 2
V1 V2
SPR = R( H v1 Hv2 ) = R
4000 4000
Recovery factors (R) of 0.7 to 0.9 can be achieved with reasonably gradual
transitions, thereby keeping friction losses low.
The opposite event to a static pressure regain will occur in a converging
transition, resulting in a decrease in static pressure (such as in a nozzle).
A1 = 8 ft2 A2 = 16 ft2
30o
Find the pressure loss through the fitting: from Table 8.5b, with A2/A1 = 2.0, read C = 0.25
V1 = Q/A = 12000/8 = 1500 ft/min
V2 = 12000/16 = 750 ft/min
Hf = 0.25*(1500/4000)2 = 0.035 in. w.
Find Hv1 and Hs1: Hv1 = (1500/4000)2 = 0.14 in. w. ; Hs1 = Ht1 Hv1 = 2.21 in. w.
Find Ht2, Hv2 and Hs2 : Ht2 = Ht1 Hf= 2.315 in. w. ; Hv2 = (750/4000)2 = 0.035 in. w.
Hs2 = Ht2 Hv2 = 2.28 in. w.g.
Find the static pressure regain (SPR) = Hs2 Hs1 = 0.07 in. w.
Pressure Loss at Fan Inlet and Outlet
There will also be a pressure loss at the fan inlet and outlet, the value of which
depends on the shape of the fan-duct connection, called the system effect.
Table 8.9 (page 230) shows some values of the resulting loss coefficient C.
No straight inlet duct (poor connection) Long straight inlet duct (good connection)
Duct System Pressure Loss
The system total pressure loss is defined as the total pressure loss through
the duct path that has the largest pressure losses.
This path is often the longest one, but it may be a shorter path that contains
an unusual number of fittings or devices with large pressure loses.
To find the system total pressure loss, the losses are summed up for each
section of straight duct and each fitting in the path chosen.
Pressure losses through any equipment (coils, filters, diffusers) must be
included. The manufacture will finish this data.
Example
For the duct system shown below, determine the system total pressure loss
and fan requirements. The fan inlet and outlet connections are not shown,
but it has been found that the system effect inlet loss is 0.20 in. w. and the
outlet loss is 0.08 in. w. The total pressure required at each air outlet for
proper distribution is 0.1 in. w.g.?
Example (Cont.)
Solution
Path XABCDEF is the longest. It is also the path with the greatest pressure loss,
because none of the shorter paths have unusual pressure losses.
Note that the diverging transitions have a negligible pressure loss due to the
gradual transformation and relatively low velocities.
Duct Design Methods
Two methods of sizing ducts will be explained: the equal friction method and
the static regain method.
Example
Where
80 G 60 H 60 J
A B C D E
50 40 30 35
Fan
4 diffusers
2000 CFM each
Pressure Loss in Closed and Open Systems
Where
Pressure Loss in Closed and Open Systems