Professional Documents
Culture Documents
Ground Fault Overvoltage With Inverter-Interfaced
Ground Fault Overvoltage With Inverter-Interfaced
Ground Fault Overvoltage With Inverter-Interfaced
org/Xplore
Figure 2. Vector diagram of the per-unit load voltages during GFOV driven Figure 3. Ungrounded inverter (left) serving a four-wire circuit and load
by an ungrounded synchronous generator. during a 1LG fault.
3
The key difference between Figures 1 and 3 is that in Figure Equations (7) and (9). Figure 4 shows the sequence networks
3, the voltage VbN between phase b and the inverter’s star point for the (faulted) circuit in Figure 3, with line impedance
is not maintained by a voltage source, and thus the inverter included, and with separate positive, negative and zero-
does not enforce a specific phase-to-star point voltage sequence balanced load impedances. While the zero sequence
relationship. If the inverter continues to produce primarily impedance of an inverter is high due to the lack of a neutral
fundamental-frequency positive-sequence current during the connection, the negative sequence impedance Zinv2 is not
fault (an assumption that must be tested and will be dealt with infinite [8], a subject that will be revisited shortly.
in a moment), then by Ohm’s Law one obtains
Figure 4. Sequence networks during a 1LG fault, after opening of the utility
breaker.
photovoltaic (PV) inverters, this could happen at low to with the existing Yg load, using an impedance of 2Z in both
moderate irradiance levels, under which conditions the inverter loads, and then converting the floating-Y load to delta by
has significant current “headroom”. At high irradiance levels, multiplying its impedances by 3 [11]. In this way, a) the
the inverter output current will be constrained by the inverter’s power dissipation is evenly divided between the Yg and delta
maximum output current limits, causing the output power and portions of the load, and b) the power P and Q flowing across
the resulting Equation (10) overvoltage to drop. However, this the green dashed line in Figure 5 is the same as the P-Q
change will not alter the relative proportions of positive, delivered by the inverter to the load in Figure 3. The 1LG
negative and zero-sequence voltages. fault is again applied to phase b.
What these results indicate is that a) the inverters themselves The sequence network diagram in Figure 4 still applies to
do not cause the traditional star-point-shift GFOV, and b) fast the circuit in Figure 5. The positive and negative sequence
inverter-resident overvoltage trips are the best mitigation load impedances will be determined by both the Yg and the
choice because such overvoltage as does exist with inverters is delta (or floating-Y) load, and with the impedances set as they
not always dominated by the zero sequence component and are in Figure 5, the positive and negative sequence impedances
thus would not be mitigated reliably by a grounding are the same as in Figure 3.. However, the zero-sequence
transformer. impedance Zload0 will be determined only by the Yg-connected
If the generation to load ratio is larger than unity, then an part of the load because the delta-connected load has an
LROV may also result. LROV is beyond the scope of this infinite zero-sequence impedance, and will thus be double
paper, but recent LROV results are available in [9,10]. what it was in the case with all Yg load. Based on this
One final note: the representation shown in Figure 3 reasoning, one would expect the positive and negative
assumes that the inverters are interfaced to the four-wire sequence voltages to remain essentially unchanged from the
distribution feeder via a Yg-Yg GSU transformer. If the GSU Yg load case, but the zero-sequence voltage should increase
transformer has a delta winding facing the four-wire significantly (for the simple circuit in Figure 5, the zero-
distribution circuit, then that inverter + GSU transformer sequence voltage across the load predicted by Equation (7)
combination will look more like Figure 1 than like Figure 3. would approximately double).
Thus, a version of the discussion surrounding Figure 1 applies
in that case, although because of the interactions of GFOV, III. SIMULATIONS
LROV and inverter controls, the overvoltage in that case is
often far less than the theoretically-predicted 173%. The A. Model and procedure
subtleties of that case are beyond the scope of this paper. The theoretical treatment above was tested in simulations
conducted in the MATLAB/SimPowerSystems environment.
C. Case of Yg and delta-connected load with inverter source The test circuit used, shown in Figure 6, is based on the one
Many loads, such as three-phase induction motor loads or described by Acharya et.al [12]. This is a four-wire, 25 kV
any load connected via a transformer with a delta winding on distribution circuit in which the neutral is explicitly
the distribution circuit side, would appear to the distribution represented and the line segment impedances are given by
circuit as delta loads, and it is not uncommon for a four-wire
distribution circuit to serve a mixture of Yg and delta load.
Consider Figure 5, which shows the same system as in Figure
3 except that the load has been separated into a Yg component
and a delta component. The load impedances are selected by
first adding to Figure 3 a floating-Y load connected in parallel
A. Experimental procedure
The experimental test setup is shown in Figure 13. To create
a 1LG fault without also faulting the AC voltage source to
which the inverters were connected, a balanced resonant RLC
load with quality factor of approximately 1.0 was connected in
parallel with the inverter under test and tuned to absorb the
inverter’s real and reactive power. This allowed the AC
source to be disconnected using switch S1 without
immediately tripping the inverter before the creation of the
fault. The 1LG fault was created by closing switch S2.
Baseline tests in which S1 was opened and S2 remained open
confirmed that each inverter remained connected and in stable
operation for at least 1 s following the opening of S1. For
Inverter 1, anti-islanding controls were disabled during all tests
Figure 11. Simulated TOV result: phase voltages, 1:1 generation:load ratio, described here to better observe the 1LG fault response. Thus
balanced load, floating Y capacitor, half of the load connected Yg and the
other half delta. each inverter’s response to the fault was observed in isolation
from other effects [13].
7
Figure 15. Inverter 1 sequence voltages during test shown in Figure 14.
Figure 16. Inverter 1 sequence currents during test shown in Figure 14.
Figure 17. Inverter 2 voltage and current during a 1LG fault event.
8
Figure 18: Inverter 2 sequence voltages during the test shown in Figure 17.
Figure 21. Sequence voltages during the test shown in Figure 20.
Figure 19: Inverter 2 sequence currents during the test shown in Figure 17. Phase voltages and inverter currents during a typical 1LG
C. Experimental results with transformers fault test with ȴ-Yg transformer are shown in Figures 22 and
23 for the fault (ȴ) side of the transformer and the inverter (Y)
Inverter 1 was also tested with Yg-Yg and ȴ-Yg 1:1
side of the transformer, respectively. Note that the current
transformers connected between the inverter and the fault
increases on all phases following the fault as the inverter
location. Tests with Yg-Yg transformers showed consistently
controls increase the power on the unfaulted phases, leading to
similar phase voltage magnitudes to those from tests without a
a peak TOV of 127%. This confirms the analysis and
transformer: the inverter remained connected for about 2
simulated results predicting a TOV caused by power rejection
cycles following the fault and no RMS TOV was observed.
to the unfaulted phases.
Figure 20 shows phase voltages and inverter currents on both
Figure 24 shows the symmetrical components of voltage on
sides of the transformer for a typical test. Note that in Figure
both sides of the ȴ-Yg transformer for the test shown in
20, the phase voltages after the fault are 180° out of phase
rather than 120° as in the tests without a transformer. This Figures 22 and 23. On the grid side of the transformer, both
eliminates the zero-sequence voltage, as shown in Figure 21. negative and zero sequence components arise following the
fault and hold relatively steady around 0.38 pu until the
inverter disconnects, while the positive sequence falls to
roughly 0.75 pu. It is important to note that the results shown
in Figures 22-24 had anti-islanding controls disabled, as in all
tests of Inverter 1 presented here. Enabling anti-islanding
controls tended to greatly reduce the duration of TOV
following 1LG fault tests with the ȴ-Yg transformer because it
caused the inverter to disconnect more quickly [11]. Figure 25
shows the symmetrical components of inverter current from
the test shown in Figures 22-23. After the fault, the positive
sequence current is about 1.05 pu and the negative sequence
current is about 0.1 pu. No zero-sequence current is produced.
Figure 22. Voltage and current on the grid (delta) side of the transformer for
a typical test with a ȴ-Yg transformer. (AI disabled).
Figure 20. Phase voltages and currents on both sides of a Yg-Yg transformer
during a 1LG fault.
9
VI. REFERENCES
[1] H. Lee, S. Chase, R. Dugan, “Overvoltage Considerations for
Figure 23. Voltage and current on the inverter (Yg) side of the transformer Interconnecting Dispersed Generators with Wye-Grounded Distribution
for a typical test with a ȴ-Yg transformer. (AI disabled). Feeders”, IEEE Transactions on Power Apparatus and Systems PAS-
103(12), December 1984, p. 3587-3594.
[2] IEEE Standard 142-2007: “IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems” (“Green
Book”), June 2007.
[3] P. Barker, “Overvoltage considerations in applying distributed resources
on power systems,” 2002 IEEE Power Engineering Society Summer
Meeting, 2002, vol. 1, pp. 109–114.
[4] “IEEE Standard C62.92 - IEEE Guide for the Application of Neutral
Grounding in Electrical Utility Systems.” IEEE, 2000.
[5] M. E. Ropp, M. Johnson, D. Schutz, S. Cozine, “Effective Grounding of
Distributed Generation Inverters May Not Mitigate Transient and
Temporary Overvoltage”, Proceedings of the Western Protective Relay
Conference (WPRC), October 2012, 8 pgs.
[6] A. Fitzgerald, C. Kingsley, Jr., S. Umans, Electric Machinery, 5th ed.,
pub. McGraw-Hill 1990, ISBN 0070211345.
[7] S. Chapman, Electric Machinery Fundamentals, 3rd ed., pub. McGraw-
Hill 1999, ISBN 0070119503.
[8] W. Cao, Y. Ma, X. Zhang, F. Wang, “Sequence Impedance
Measurement of Three-Phase Inverters Using a Parallel Structure”, IEEE
Applied Power Electronics Conference and Exposition, March 2015, p.
3031-3038.
Figure 24. Sequence voltages on both sides of the ȴ-Yg transformer for the [9] A. Nelson, A. Hoke, S. Chakraborty, J. Chebahtah, T. Wang, B.
test shown in Figures 22 and 23. Zimmerly, “Inverter Load Rejection Over-voltage Testing,” NREL/TP-
5D00-63510, February 2015.
[10] A. Nelson, A. Hoke, S. Chakraborty, M. Ropp, J. Chebahtah, T. Wang,
B. Zimmerly, “Experimental Evlauation of Load-Rejection Over-
Voltage from Grid-Tied Solar Inverters”, 42nd IEEE Photovoltaics
Specialists Conference, June 2015, 6 pgs.
[11] J. Glover, M. Sarma, T. Overbye, Power System Analysis and Design,
5th ed., pub. Cengage Learning 2012, ISBN 9781111425777.
[12] J. Acharya, Y. Wang, W. Xu, “Temporary Overvoltage and GPR
Characteristics of Distribution Feeders with Multigrounded Neutral”,
IEEE Transactions on Power Delivery 25(2), April 2010, p. 1036-1044.
[13] A. Hoke, A. Nelson, S. Chakraborty, J. Chebahtah, T. Wang, M.
Figure 25. Sequence currents for the test shown in Figures 22 and 23. McCarty, “Inverter Ground Fault Overvoltage Testing,” NREL/TP-
5D00- 64173, 2015.
[14] “Three-phase Inverters and Short-Duration Overvoltages: Preliminary
V. CONCLUSIONS Testing and Analysis.” EPRI, Palo Alto, CA, 2014.