Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

QSF-QC-07

Conductor Test Report Ver:01, Rev:00

PO No 12553 Sample No: 1


Check Date 03.04.22 Tested By: Adex Engineering Ltd.
Supplier: Meghna Star

Sample Details:
Length 1000 mm Conductor Size 30 X 12 mm
Insulation Thickness (mm) N/A Temperature 28 °C
Conductor Type Rectangular Copper Bar

Test Data: The following test were conducted as per IEC-60851-5:2008 standard.
Parameter At Ambient Temperature At 20 °C At 75 °C
Resistance
50 48.428 59.2355
(μΩ)
Resistivity
0.000018 1.74341E-05 2.13248E-05
(Ω-mm )
Conductivity
98.887
%

Insulation Breakdown Voltage (KV) Leakage Current (mA)


N/A N/A

Summary:
Parameter Decleared Measured
Conductor Size (mm) 30.00 X 12.00 30.0 X 12.0
Covered Conductor Size (mm) N/A X N/A N/A X N/A
Insulation Thickness (mm) N/A N/A
Resistivity at 20°C (Ω-mm) N/A 1.74341E-05
Conductivity (%) 99 98.89
Insulation Breakdown Voltage (KV) N/A N/A

Observations: Conductivity of this sample copper bar is good.

_____________________________
Testted By:
MD. Islam Hossain
Engineer (QA &QC)