Space Input Data

LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012


CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

OFFICE 007

1. General Details:
Floor Area ............................................................. 31.0 m²
Avg. Ceiling Height .................................................. 4.5 m
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 3 People
Wattage ............................................................... 40.00 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................... 20.00 W/m² Sensible .................................................................. 100 W
Schedule .................................... Lighting Schedule Schedule ................................................ people range
Latent ....................................................................... 40 W
Schedule ................................................ people range
2.3. Electrical Equipment:
Wattage ............................................................... 50.00 W/m²
Schedule ................................................ people range

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 27.0 2 0 0
SW 23.0 0 0 0

3.1. Construction Types for Exposure NW


Wall Type .................................................................... WALL
1st Window Type .......................................... default window
1st Window Shade Type ...................... Default Shade Type

3.2. Construction Types for Exposure SW


Wall Type .................................................................... WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.0 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 1.27 L/(s-m²)
Design Heating ...................................................... 1.27 L/(s-m²)
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 31.0 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 35.0 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. .......................... 12.0 °C
Ambient at Space Min Temp. ................................. -5.0 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 23.0 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 35.0 °C
Ambient at Space Max Temp ................................ 55.0 °C
Uncondit. Space Min Temp ................................... 12.0 °C
Ambient at Space Min Temp .................................. -5.0 °C

Hourly Analysis Program v.4.1 Page 1 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name .......................................................................... OFFICE 007
Equipment Class ...................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ............................................................................ Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
OFFICE 007 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.9 °C
Cooling T-stat: Unocc. ................................................................................ 29.4 °C
Heating T-stat: Occ. ................................................................................... 21.1 °C
Heating T-stat: Unocc. ............................................................................... 15.6 °C
T-stat Throttling Range .............................................................................. 1.67 °K

Thermostat Schedule .................................................... THERMO SCHEDULE


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Heating Coil:
Design Supply Temperature ...................................................................... 43.3 °C
Heating Source ................................................................ Electric Resistance
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On


Outdoor Ventilation Air ............................................................................... 7.08 l/s/person

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 l/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating .......................................................................................................... 10 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 937.9 - - 21.2

Hourly Analysis Program v.4.1 Page 2 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Compressor


Maximum Design Cooling & OD Fan Cutoff
Load OAT Capacity Power OAT
Zone (kW) (°C) (kW) (kW) (°C)
1 11.9 35.0 0.3 1.0 12.8

Hourly Analysis Program v.4.1 Page 3 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

STORE 008

1. General Details:
Floor Area ............................................................. 15.5 m²
Avg. Ceiling Height .................................................. 4.5 m
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 1 Person
Wattage ............................................................... 32.29 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ................................................................. 0.00 W/m² Sensible ...................................................................... 0 W
Schedule ............................................................. None Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

Hourly Analysis Program v.4.1 Page 4 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

2.3. Electrical Equipment:


Wattage ................................................................. 0.00 W/m²
Schedule ............................................................. None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 11.4 0 0 0

3.1. Construction Types for Exposure NW


Wall Type .................................................................... WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.5 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 5.00 ACH
Design Heating ...................................................... 5.00 ACH
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 15.5 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 35.0 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. .......................... 12.0 °C
Ambient at Space Min Temp. ................................. -5.0 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v.4.1 Page 5 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name ........................................................................... STORE 008
Equipment Class .............................................................................. Undefined
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1

2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Design Airflow ............................................................................................ 7.08 l/s/person
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %

Central Cooling Data:


Supply Air Temperature ............................................................................. 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source ............................................................................................ Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Central Heating Data:


Supply Temperature ................................................................................... 43.3 °C
Heating Source ........................................................................................... Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Supply Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ........................................................................................ 124 Pa
Overall Efficiency .......................................................................................... 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain ................................................................................................ 0 %
Duct Leakage .................................................................................................. 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
STORE 008 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 35.0 °C
Cooling T-stat: Unocc. ................................................................................ 40.0 °C
Heating T-stat: Occ. ................................................................................... 15.0 °C
Heating T-stat: Unocc. ............................................................................... 10.0 °C
T-stat Throttling Range .............................................................................. 1.67 °K
Diversity Factor ........................................................................................... 100 %
Direct Exhaust Airflow .................................................................................. 0.0 L/s
Direct Exhaust Fan kW ................................................................................ 0.0 kW

Thermostat Schedule ................................................................................. FAN


Unoccupied Cooling is ....................................................................... Available

Supply Terminals Data:


Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 l/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None

Zone Unit Heat Source ................................................................................ Any


Zone Heating Unit Schedule ................................................ JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Supply Fan Airflow ..................................................................................... 60.7 L/s

Hourly Analysis Program v.4.1 Page 6 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

Ventilation Fan Airflow ................................................................................. 7.1 L/s


Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ............................................................................................. 0 %
Cooling Latent ................................................................................................. 0 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ..................................... Peak zone sensible load
Space Airflow Sizing Method .................................... Coincident space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)

1 60.7 - -

5. Equipment Data
No Equipment Data required for this system.

Hourly Analysis Program v.4.1 Page 7 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

BATERY ROOM 009

1. General Details:
Floor Area ............................................................. 20.5 m²
Avg. Ceiling Height .................................................. 4.5 m
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 1 Person
Wattage ............................................................... 32.29 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ................................................................. 0.00 W/m² Sensible .................................................................. 100 W
Schedule ............................................................. None Schedule .................................... Lighting Schedule
Latent ....................................................................... 60 W
Schedule .................................... Lighting Schedule

Hourly Analysis Program v.4.1 Page 8 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

2.3. Electrical Equipment:


Wattage ............................................................... 50.00 W/m²
Schedule .................................... Lighting Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 14.8 0 0 0

3.1. Construction Types for Exposure NW


Wall Type .................................................................... WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 20.5 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 7.00 ACH
Design Heating ...................................................... 7.00 ACH
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 20.5 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 35.0 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. .......................... 12.0 °C
Ambient at Space Min Temp. ................................. -5.0 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v.4.1 Page 9 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name .......................................................... BATTERY ROOM 009
Equipment Class ...................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ............................................................................ Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
BATERY ROOM 009 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.9 °C
Cooling T-stat: Unocc. ................................................................................ 29.4 °C
Heating T-stat: Occ. ................................................................................... 21.1 °C
Heating T-stat: Unocc. ............................................................................... 15.6 °C
T-stat Throttling Range .............................................................................. 1.67 °K

Thermostat Schedule .................................................... THERMO SCHEDULE


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Heating Coil:
Design Supply Temperature ...................................................................... 43.3 °C
Heating Source ................................................................ Electric Resistance
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On


Outdoor Ventilation Air ............................................................................... 7.08 l/s/person

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 l/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 356.2 - - 7.1

5. Equipment Data

Hourly Analysis Program v.4.1 Page 10 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Compressor


Maximum Design Cooling & OD Fan Cutoff
Load OAT Capacity Power OAT
Zone (kW) (°C) (kW) (kW) (°C)
1 4.3 35.0 0.3 1.0 12.8

Hourly Analysis Program v.4.1 Page 11 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

MECH. EQUI. STORE 010

1. General Details:
Floor Area ............................................................. 35.4 m²
Avg. Ceiling Height .................................................. 4.5 m
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 1 Person
Wattage ............................................................... 32.29 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ................................................................. 0.00 W/m² Sensible ...................................................................... 0 W
Schedule ............................................................. None Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

Hourly Analysis Program v.4.1 Page 12 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

2.3. Electrical Equipment:


Wattage ................................................................. 0.00 W/m²
Schedule ............................................................. None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 17.5 0 0 0

3.1. Construction Types for Exposure NW


Wall Type .................................................................... WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.4 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 5.00 ACH
Design Heating ...................................................... 5.00 ACH
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 35.4 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 35.0 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. .......................... 12.0 °C
Ambient at Space Min Temp. ................................. -5.0 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v.4.1 Page 13 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name .................................................... MECH. EQUI. STORE 010
Equipment Class .............................................................................. Undefined
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1

2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Design Airflow ............................................................................................ 7.08 l/s/person
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %

Central Cooling Data:


Supply Air Temperature ............................................................................. 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source ............................................................................................ Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Central Heating Data:


Supply Temperature ................................................................................... 43.3 °C
Heating Source ........................................................................................... Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Supply Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ........................................................................................ 124 Pa
Overall Efficiency .......................................................................................... 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain ................................................................................................ 0 %
Duct Leakage .................................................................................................. 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
MECH. EQUI. STORE 010 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 35.0 °C
Cooling T-stat: Unocc. ................................................................................ 40.0 °C
Heating T-stat: Occ. ................................................................................... 15.0 °C
Heating T-stat: Unocc. ............................................................................... 10.0 °C
T-stat Throttling Range .............................................................................. 1.67 °K
Diversity Factor ........................................................................................... 100 %
Direct Exhaust Airflow .................................................................................. 0.0 L/s
Direct Exhaust Fan kW ................................................................................ 0.0 kW

Thermostat Schedule ................................................................................. FAN


Unoccupied Cooling is ....................................................................... Available

Supply Terminals Data:


Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 l/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None

Zone Unit Heat Source ................................................................................ Any


Zone Heating Unit Schedule ................................................ JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Supply Fan Airflow ................................................................................... 111.8 L/s
Ventilation Fan Airflow ................................................................................. 7.1 L/s

Hourly Analysis Program v.4.1 Page 14 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ............................................................................................. 0 %
Cooling Latent ................................................................................................. 0 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ..................................... Peak zone sensible load
Space Airflow Sizing Method .................................... Coincident space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)

1 111.8 - -

5. Equipment Data
No Equipment Data required for this system.

Hourly Analysis Program v.4.1 Page 15 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

INSTRUMENT GAS&FIRE 011

1. General Details:
Floor Area ............................................................. 35.4 m²
Avg. Ceiling Height .................................................. 4.5 m
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 1 Person
Wattage ............................................................... 32.29 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ................................................................. 0.00 W/m² Sensible ...................................................................... 0 W
Schedule ............................................................. None Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None
2.3. Electrical Equipment:
Wattage ................................................................. 0.00 W/m²
Schedule ............................................................. None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 17.5 0 0 0
NE 25.5 0 0 0

3.1. Construction Types for Exposure NW


Wall Type .................................................................... WALL

3.2. Construction Types for Exposure NE


Wall Type .................................................................... WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.4 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 5.00 ACH
Design Heating ...................................................... 5.00 ACH
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................. 35.4 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 35.0 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. .......................... 12.0 °C
Ambient at Space Min Temp. ................................. -5.0 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 24.7 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 35.0 °C
Ambient at Space Max Temp ................................ 55.0 °C
Uncondit. Space Min Temp ................................... 12.0 °C
Ambient at Space Min Temp .................................. -5.0 °C

Hourly Analysis Program v.4.1 Page 16 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name ........................................... INSTRUMENT GAS &FIRE 011
Equipment Class .............................................................................. Undefined
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1

2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Design Airflow ............................................................................................ 7.08 l/s/person
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %

Central Cooling Data:


Supply Air Temperature ............................................................................. 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source ............................................................................................ Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Central Heating Data:


Supply Temperature ................................................................................... 43.3 °C
Heating Source ........................................................................................... Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Supply Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain ................................................................................................ 0 %
Duct Leakage .................................................................................................. 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
INSTRUMENT GAS&FIRE 011 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.9 °C
Cooling T-stat: Unocc. ................................................................................ 29.4 °C
Heating T-stat: Occ. ................................................................................... 21.1 °C
Heating T-stat: Unocc. ............................................................................... 15.6 °C
T-stat Throttling Range .............................................................................. 1.67 °K
Diversity Factor ........................................................................................... 100 %
Direct Exhaust Airflow .................................................................................. 0.0 L/s
Direct Exhaust Fan kW ................................................................................ 0.0 kW

Thermostat Schedule ................................................................................. FAN


Unoccupied Cooling is ....................................................................... Available

Supply Terminals Data:


Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 l/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None

Zone Unit Heat Source ................................................................................ Any


Zone Heating Unit Schedule ................................................ JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Supply Fan Airflow ................................................................................... 552.2 L/s

Hourly Analysis Program v.4.1 Page 17 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

Ventilation Fan Airflow ................................................................................. 7.1 L/s


Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ............................................................................................. 5 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 5 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)

1 552.2 - -

5. Equipment Data
No Equipment Data required for this system.

Hourly Analysis Program v.4.1 Page 18 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

SWITCHGEARS 012

1. General Details:
Floor Area ........................................................... 663.0 m²
Avg. Ceiling Height .................................................. 4.5 m
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 1 Person
Wattage ............................................................... 32.29 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................... 20.00 W/m² Sensible .................................................................. 100 W
Schedule .................................... Lighting Schedule Schedule ................................................ people range
Latent ....................................................................... 40 W
Schedule ................................................ people range
2.3. Electrical Equipment:
Wattage ............................................................. 140.00 W/m²
Schedule ................................................ people range

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 120.0 0 0 0
SE 113.0 0 0 0
SW 120.0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type .................................................................... WALL

3.2. Construction Types for Exposure SE


Wall Type .................................................................... WALL

3.3. Construction Types for Exposure SW


Wall Type .................................................................... WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 663.0 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 0.00 ACH
Design Heating ...................................................... 0.00 ACH
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ........................................................... 663.0 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 35.0 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. .......................... 12.0 °C
Ambient at Space Min Temp. ................................. -5.0 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ........................................ Wall Partition (No partition data).
Area ....................................................................... 65.4 m²
U-Value ............................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .................................. 35.0 °C
Ambient at Space Max Temp ................................ 55.0 °C
Uncondit. Space Min Temp ................................... 12.0 °C
Ambient at Space Min Temp .................................. -5.0 °C

Hourly Analysis Program v.4.1 Page 19 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name .............................................................. SWITCH GEAR 012
Equipment Class ...................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ............................................................................ Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SWITCHGEARS 012 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.9 °C
Cooling T-stat: Unocc. ................................................................................ 29.4 °C
Heating T-stat: Occ. ................................................................................... 21.1 °C
Heating T-stat: Unocc. ............................................................................... 15.6 °C
T-stat Throttling Range .............................................................................. 1.67 °K

Thermostat Schedule .................................................... THERMO SCHEDULE


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Heating Coil:
Design Supply Temperature ...................................................................... 43.3 °C
Heating Source ................................................................ Electric Resistance
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On


Outdoor Ventilation Air ............................................................................... 7.08 l/s/person

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 l/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating .......................................................................................................... 10 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 16529.7 - - 7.1

Hourly Analysis Program v.4.1 Page 20 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Compressor


Maximum Design Cooling & OD Fan Cutoff
Load OAT Capacity Power OAT
Zone (kW) (°C) (kW) (kW) (°C)
1 185.6 35.0 0.3 1.0 12.8

Hourly Analysis Program v.4.1 Page 21 of 25


Space Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

WC 013

1. General Details:
Floor Area ............................................................... 6.7 m²
Avg. Ceiling Height .................................................. 4.5 m²
Building Weight ................................................... 341.8 kg/m²

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ............................. Recessed (Unvented) Occupancy ................................................................. 1 Person
Wattage ............................................................... 40.00 W/m² Activity Level ............................................ Office Work
Ballast Multiplier .................................................... 1.08 Sensible ................................................................. 71.8 W/person
Schedule .................................... Lighting Schedule Latent .................................................................... 60.1 W/person
Schedule ................................................ people range

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ................................................................. 0.00 W/m² Sensible ...................................................................... 0 W
Schedule ............................................................. None Schedule ............................................................. None
Latent ......................................................................... 0 W
Schedule ............................................................. None

Hourly Analysis Program v.4.1 Page 22 of 25


OFFICE 007 Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

2.3. Electrical Equipment:


Wattage ................................................................. 0.00 W/m²
Schedule ............................................................. None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 5.4 1 0 0

3.1. Construction Types for Exposure W


Wall Type .................................................................... WALL
1st Window Type ............................................. WC WINDOW

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.7 0 0

4.1. Construction Types for Exposure H


Roof Type .......................................... insulated floor ceiling

5. Infiltration:
Design Cooling ...................................................... 0.00 ACH
Design Heating ...................................................... 0.00 ACH
Energy Analysis .................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .................. Floor Above Unconditioned Space
Floor Area ............................................................... 6.7 m²
Total Floor U-Value ............................................. 0.568 W/(m²-°K)
Unconditioned Space Max Temp. ......................... 23.9 °C
Ambient at Space Max Temp. ............................... 55.0 °C
Unconditioned Space Min Temp. ........................... -5.0 °C
Ambient at Space Min Temp. ................................ 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v.4.1 Page 23 of 25


OFFICE 007 Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

1. General Details:
Air System Name ................................................................................. WC 013
Equipment Class .............................................................................. Undefined
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1

2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Design Airflow ............................................................................................ 7.08 l/s/person
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %

Central Cooling Data:


Supply Air Temperature ............................................................................. 14.4 °C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source ............................................................................................ Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Central Heating Data:


Supply Temperature ................................................................................... 43.3 °C
Heating Source ........................................................................................... Any
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ............................. Cycled or Staged Compressor - Fan On

Supply Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ........................................................................................ 124 Pa
Overall Efficiency .......................................................................................... 54 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain ................................................................................................ 0 %
Duct Leakage .................................................................................................. 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
WC 013 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 35.0 °C
Cooling T-stat: Unocc. ................................................................................ 40.0 °C
Heating T-stat: Occ. ................................................................................... 15.0 °C
Heating T-stat: Unocc. ............................................................................... 10.0 °C
T-stat Throttling Range .............................................................................. 1.67 °K
Diversity Factor ........................................................................................... 100 %
Direct Exhaust Airflow .................................................................................. 0.0 L/s
Direct Exhaust Fan kW ................................................................................ 0.0 kW

Thermostat Schedule ................................................................................. FAN


Unoccupied Cooling is ....................................................................... Available

Supply Terminals Data:


Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 l/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None

Zone Unit Heat Source ................................................................................ Any


Zone Heating Unit Schedule ................................................ JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.4 °C
Supply Fan Airflow ..................................................................................... 33.1 L/s

Hourly Analysis Program v.4.1 Page 24 of 25


OFFICE 007 Input Data
LUC-CIV-MECH-MELE- EXISTING V3 07/24/2012
CALCULTED Eng.: KOSRAT FARAYDOON 01:10AM

Ventilation Fan Airflow ................................................................................. 7.1 L/s


Heating Supply Temperature ..................................................................... 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 °K
Hot Water Delta-T ...................................................................................... 11.1 °K

Safety Factors:
Cooling Sensible ............................................................................................. 0 %
Cooling Latent ................................................................................................. 0 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ..................................... Peak zone sensible load
Space Airflow Sizing Method .................................... Coincident space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)

1 33.1 - -

5. Equipment Data
No Equipment Data required for this system.

Hourly Analysis Program v.4.1 Page 25 of 25