CABLE SCHEDULE
BUILDING MANAGEMENT SYSTEM
CABLE DETAILS FROM TO: BMS PANEL

CABLE NO / CABLE
NO NUMBER OF BMS POINT DEVICE ID / SIGNAL RANGE APPLICATION / REMARKS
TAG ESTIMATED ACTUAL CABLE
CABLE TYPE PAIR / CORE / SIZE (mm²) EQUIPMENT NO DESCRIPTION LOCATION WIRE IDENTITY TB NO. EQUIPMENT NO SLAVE ID / DESCRIPTION LOCATION WIRE IDENTITY TB NO.
LENGTH (m) LENGTH (m) USAGE
TRIAD / QUAD IP ADDRESS

BLUE (PAIR) NO (12) BLUE (PAIR) DI - 10


1 BREAKER ON/OFF STATUS DRY CONTACT
BROWN (PAIR) COM (24VDC) DIGITAL INPUT BROWN (PAIR) COM
MC-10-1 CAT5 4 PAIRS 0.75 100 75 DI MC-10 ELECTICAL PANEL EE RM 1 16DI 1 UPS ROOM
GREEN (PAIR) NO (92) MODULE GREEN (PAIR) DI - 11
2 BREAKER TRIP ALARM DRY CONTACT
ORANGE (PAIR) COM (24VDC) ORANGE (PAIR) COM
BLUE (PAIR) NO BLUE (PAIR) DI - 12
3 INCOMING SUPPLY HEALTHY DRY CONTACT
BROWN (PAIR) COM (24VDC) DIGITAL INPUT BROWN (PAIR) COM
MC-10-2 CAT5 4 PAIRS 0.75 100 75 DI MC-10 ELECTICAL PANEL EE RM 1 16DI 1 UPS ROOM
GREEN (PAIR) SPARE MODULE GREEN (PAIR) SPARE
4 (SPARE) -
ORANGE (PAIR) SPARE ORANGE (PAIR) SPARE
RED NO FACILITY RED DO - 1
TWISTED TF
5 WLD-PANTRY-SV-10 2C 1.5 100 100 DO SOLENOID OPEN/CLOSE CONTROL SV-01 SOLENOID VALVE PANTRY FM GUARD 192.168.1.10 MONITORING UPS ROOM DRY CONTACT
WIRE BLK COM (24VDC) BLK COM
SYSTEM PANEL
BLUE (PAIR) 1 BLUE (PAIR) AI - 1
TEMPERATURE BROWN (PAIR) 2 FACILITY BROWN (PAIR) 24VDC
TEMPERATURE AND HUMIDITY ROOM
6 THS-IDF-10 CAT5 4 PAIRS 0.75 35 30 AI THS-10-1 AND HUMIDITY HUB ROOM 8AI MONITORING UPS ROOM 0-10VDC
MONITORING GREEN (PAIR) 3 GREEN (PAIR) 0VDC
SENSOR SYSTEM PANEL
ORANGE (PAIR) 4 ORANGE (PAIR) AI - 2
WHITE RS485 + FACILITY WHITE RS485 + MODBUS
UNINTERUPTED
7 UPS-10 STP 2C + S 1.5 50 45 RS485 UPS POINTS UPS 10 UPS ROOM BACK RS485 - FMS-10 MONITORING UPS ROOM BACK RS485 - PROTOCOL
POWER SUPPLY
SHIELD SHIELD SYSTEM PANEL SHIELD SHIELD RS485
CABLE SCHEDULE
FMS PANEL
CABLE DETAILS FROM TO
CABLE NO / CABLE
NO APPLICATION
TAG NUMBER OF PAIR / ESTIMATED ACTUAL
CABLE PROJECT SPEC SIZE (mm²) CABLE USAGE EQUIPMENT NO DESCRIPTION LOCATION WIRE IDENTITY TB NO. EQUIPMENT NO DESCRIPTION LOCATION WIRE IDENTITY TB NO.
CORE / TRIAD / QUAD LENGTH (m) LENGTH (m)

BLUE (PAIR) NO (12) BLUE (PAIR) DI - 10


1 BROWN (PAIR) COM (24VDC) FACILITY BROWN (PAIR) COM BREAKER ON/OFF STATUS
MC-10-1 CAT5 4 PAIRS 0.75 100 75 - MC-10 ELECTICAL PANEL EE RM 1 FMS-10 MONITORING UPS ROOM
GREEN (PAIR) NO (92) SYSTEM PANEL GREEN (PAIR) DI - 11
2 ORANGE (PAIR) COM (24VDC) ORANGE (PAIR) COM BREAKER TRIP ALARM
RED NO FACILITY RED DO - 1
3 WLD-PANTRY-SV-10 TWISTED TF WIRE 2C 1.5 100 DI SV-01 SOLENOID VALVE PANTRY FMS-10 MONITORING UPS ROOM
BLK COM (24VDC) SYSTEM PANEL BLK COM SOLENOID CONTROL
BLUE (PAIR) 1 BLUE (PAIR) AI - 1
TEMPERATURE BROWN (PAIR) 2 FACILITY BROWN (PAIR) 24VDC HUB ROOM TEMPERATURE AND HUMIDITY
THS-IDF-10 CAT5 4 PAIRS 0.75 20 30 AI THS-10-1 AND HUMIDITY HUB ROOM FMS-10 MONITORING UPS ROOM
GREEN (PAIR) 3 GREEN (PAIR) 0VDC MONITORING
SENSOR SYSTEM PANEL
4 ORANGE (PAIR) 4 ORANGE (PAIR) AI - 2