General Notes of Residential Works

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TECHNICAL ADVISORY NOTE Number: TN002-2017

First Issued: Aug 2004


General Notes for Residential Works Revised: June 2017

www.bdav.org.au

General Notes (NCC 2016 BCA Vol 2)


ƒƒ All materials and work practices shall comply with, but not Part 3.9.2.3 for Class 1 and 10 Buildings and NCC 2016
limited to the Building Interim Regulations 2017, National BCA Volume 1 Part D2.16 for other Classes of Buildings.
Construction Code Series 2016 Building Code of Australia
ƒƒ Top of hand rails to be minimum 865mm vertically above
Vol 2 and all relevant current Australian Standards (as
stair nosing and floor surface of ramps.
amended) referred to therein.
ƒƒ Window sizes nominated are nominal only. Actual size
ƒƒ Unless otherwise specified, the term BCA shall refer to
may vary according to manufacturer. Windows to be
National Construction Code Series 2016 Building Code of
flashed all around.
Australia Volume 2.
Where the building (excludes a detached Class 10) is located
ƒƒ All materials and construction practice shall meet
in a termite prone area the building is to be provided with a
the Performance Requirements of the BCA. Where
termite management system.
a performance solution is proposed then, prior to
implementation or installation, it first must be assessed and ƒƒ Concrete stumps:
approved by the Relevant Building Surveyor as meeting –– up to 1400mm long to be 100mm x 100mm
the Performance Requirements of the BCA. (1 No. H.D. Wire)
ƒƒ Glazing, including safety glazing, shall be installed to a –– 1401mm to 1800mm long to be 100mm x 100mm
size, type and thickness so as to comply with: (2 No. H.D. Wires)
–– BCA Part 3.6 for Class 1 and 10 Buildings within a design –– 1801mm to 3000mm long to be 125mm x 125mm
wind speed of not more than N3; and (2 No. H.D. Wires)
–– BCA Vol 1 Part B1.4 for Class 2 and 9 Buildings. –– 100mm x 100mm stumps exceeding 1200mm above
ƒƒ Waterproofing of wet areas, being bathrooms, showers, ground level to be braced where no perimeter base
shower rooms, laundries, sanitary compartments and the brickwork provided.
like shall be provided in accordance with AS 3740-2010: ƒƒ Buildings in marine or other exposure environments shall
Waterproofing of Domestic Wet Areas. have masonry units, mortar and all built in components
ƒƒ These Drawings shall be read in conjunction with any House and the like complying with the durability requirements
Energy Rating (HERS) report and shall be constructed of Table 4.1 of AS 4773.1-2010 ‘Masonry in small buildings’
in accordance with the stamped plans endorsed by Part 1: Design.
the accredited Thermal Performance Assessor without ƒƒ All stormwater to be taken to the legal point of discharge
alteration. to the Relevant Authorities approval.
ƒƒ Step sizes (other than for spiral stairs) to be: ƒƒ These drawings shall be read in conjunction with all
–– Risers (R) 190mm maximum and 115mm minimum relevant structural and all other consultants’ drawings/
–– Going (G) 355mm maximum and 240mm minimum details and with any other written instructions issued in the
course of the contract.
–– 2R + 1G = 700mm maximum and 550mm minimum
ƒƒ Site plan measurements in metres – all other measurements
–– with less than 125mm gap between open treads.
in millimetres unless noted otherwise.
ƒƒ All treads, landings and the like to have a slip-resistance ƒƒ Figured dimensions take precedence over scaled
classification of P3 or R10 for dry surface conditions and dimensions.
P4 or R11 for wet surface conditions, or a nosing strip
ƒƒ The Builder shall take all steps necessary to ensure the
with a slip-resistance classification of P3 for dry surface
stability and general water tightness of all new
conditions and P4 for wet surface conditions.
and/or existing structures during all works.
ƒƒ Provide barriers where change in level exceeds 1000mm
ƒƒ The Builder and Subcontractors shall check and verify
above the surface beneath landings, ramps and/or
all dimensions, setbacks, levels and specifications
treads. Barriers (other than tensioned wire barriers) to be:
and all other relevant documentation prior to the
–– 1000mm min. above finished surface level of balconies, commencement of any works. Report all discrepancies
landings or the like, and to this office for clarification.
–– 865mm min. above finished surface level of stair nosing ƒƒ Installation of all services shall comply with the respective
or ramp, and supply authority requirements.
–– vertical with less than 125mm gap between, and ƒƒ The Builder and Subcontractor shall ensure that all
–– any horizontal element within the barrier between stormwater drains, sewer pipes and the like are located
150mm and 760mm above the floor must not facilitate at a sufficient distance from any buildings footing and/
climbing where changes in level exceeds 4000mm or slab edge beams so as to prevent general moisture
above the surface beneath landings, ramps and/or penetration, dampness, weakening and undermining of
treads. any building and its footing system.
Wire barrier construction to comply with NCC 2016 BCA ƒƒ These plans have been prepared for the exclusive use

TN002-2015 General Notes for Residential Works – Revised November 2016 Page 1 of 2 Pages
by the Client of [Insert Drafting Service] (‘The Designer’) Distance of site from predominate vegetation-[Insert
for the purpose expressly notified to the Designer. Any distance of the site from the classified vegetation]
other person who uses or relies on these plans without the Effective slope of land-[Insert effective slope of land]
Designer’s written consent does so at their own risk and
Determination of Bushfire Attack Level (BAL)-[Insert BAL]
no responsibility is accepted by the Designer for such use
and/or reliance. Site Classification
ƒƒ A building Permit is required prior to the commencement Site classification as Class: [Insert soil classification]
of these works. The release of these documents is Refer to soil report No: [Insert soil report number]
conditional to the Owner obtaining the required Building
Permit. By: [Insert Soil Engineer]
ƒƒ The Client and/or the Client’s Builder shall not modify or Design Gust Wind Speed / Wind Classification
amend the plans without the knowledge and consent of Building tie-downs to be provided in accordance with
[building designer’s name] except where a Registered AS1684-2010 for an assumed design gust wind speed
Building Surveyor makes minor necessary changes / wind classification of [Insert wind speed or wind
to facilitate the Building Permit application and that classification] (subject to confirmation on site by Relevant
such changes are promptly reported back to [building Building Surveyor at first inspection) refer to AS1684 for
designer’s name]. construction requirements.
ƒƒ The approval by this office of a substitute material, work
Climate Zone
practice, variation or the like is not an authorisation for its
use or a contract variation. All variations must be accepted Climate zone for thermal design / thermal performance
by all parties to the agreement and where applicable assessment : Zone [Insert Climate Zone].
the Relevant Building Surveyor prior to implementing any Corrosion protection of built-in structural members
variation.
Provide corrosion protection of built-in structural steel
ƒƒ (soil classification relocated) members such as steel lintels, shelf angles, connectors,
accessories (other than wall ties) in accordance with
STORMWATER Table 4.1 of AS4773.1-2010 Masonry in Small Buildings,
[Insert stormwater size] mm DIA. Class 6 UPVC stormwater Part 1: Design suitable for an Environment Classification of
line laid to a minimum grade of 1:100 and connected [Insert environment classification]
to the legal point of stormwater discharge. Provide
inspection openings at 9000mm C/C and at each Corrosion protection for sheet roofing
change of direction. Provide corrosion protection for sheet roofing in
accordance with BCA Table 3.5.1.1a suitable for
The cover to underground stormwater drains shall be not
an Environment Classification of [Insert environment
less than
classification].
– 100mm under soil
Design events for safety - earthquake actions
– 50mm under paved or concrete areas
For determination of domestic structures of a height less than
– 100mm under unreinforced concrete or
paved driveways
or equal to 8.50m
– 75mm under reinforced concrete Building type importance level – [insert importance level
driveways from BCA Table 3.11.3a]
Annual probability of exceedance – [insert probability from
SITE ENVIRONMENT DESIGN INFORMATION BCA Table 3.11.3b]
Site Bushfire Attack Assessment (simplified method) Probability factor (kp) – [insert probability factor from
Reference document ‘AS 3959-2009 construction of buildings in AS1170.4 Table 3.1]
bush fire prone areas’
Relevant Fire Danger Index (FDI)-[insert FDI] Hazard factor (Z) for project location – (insert hazard factorfor
project location from AS1170.4 Table 3.2)
Predominate vegetation:-
Hazard at the (kpZ) – [insert kpZ value from AS1170.4 Table
Classification-[Insert vegetation classification) A1]
Type-[Insert Vegetation type] Design required – [insert design required from AS1170.4 Table
A1]
AUTHORITIES / CONSULTANTS
Municipality Name___________________________________________________________________________________Ph_______________________________

Sewerage Authority Name___________________________________________________________________________________Ph_______________________________

Relevant Building Surveyor Name___________________________________________________________________________________Ph_______________________________

Consulting Structural Engineer Name___________________________________________________________________________________Ph_______________________________

Geotechnical Engineer Name___________________________________________________________________________________Ph_______________________________

Thermal Performance Assessor Name___________________________________________________________________________________Ph_______________________________

Disclaimer
The information contained in this Building Designers Association of Victoria (BDAV) representation or warranty as to the accuracy, reliability, completeness or timeliness
Advisory Note provides general information only. You should obtain professional advice of the information, nor does it accept any responsibility arising in any way (including
tailored to your specific circumstances and needs. The BDAV does not give any negligence) for errors in, or omissions from, the information contained in this Advisory Note.

TN002-2017 General Notes for Residential Works – Revised June 2017 Page 2 of 2 Pages

You might also like