Professional Documents
Culture Documents
SR-4 Green Book Microprocessor Control System For Trailer Single Temp Units
SR-4 Green Book Microprocessor Control System For Trailer Single Temp Units
SR-4 Green Book Microprocessor Control System For Trailer Single Temp Units
Diagnostic Manual
Revision A
Introduction
This manual is published for informational purposes only. Thermo King makes no
representations warranties express or implied, with respect to the information recommendations
and descriptions contained herein. Information provided should not be regarded as all-inclusive
or covering all contingencies. If further information is required, Thermo King Corporation Service
Department should be consulted.
T h e r m o K i n g ’s w a rr a n t y s h a l l n o t a p p l y t o a n y e q u i p m e n t w h i ch h a s b e e n “ s o i n s t a l l e d ,
m a i n t a i n e d , r e p a i r e d o r a l t e r e d a s , i n t h e m a n u f a c t u r e r ’s j u d g m e n t , t o a ff e c t i t s i n t e g r i t y.”
M a n u f a c t u r e r s h a l l h a v e n o l i a b i l i t y t o a n y p e r s o n o r e n t i t y f o r a ny p e r s o n a l i n j u r y,
p r o p e rt y d a m a g e o r a n y o t h e r d i r e c t , i n d i r e c t , s p e c i a l , o r c o n s e q u e n t i a l d a m a g e s
w h a t s o e v e r, a r i s i n g o u t o f t h e u s e o f t h i s m a n u a l o r a n y i n f o r m a t i o n , r e c o m m e n d a t i o n s o r
descriptions contained herein. The procedures described herein should only be
u n d e rt a k e n b y s u i t a b l y q u a l i f i e d p e r s o n n e l . F a i l u r e t o i m p l e m e n t t h e s e p r o c e d u r e s
c o rr e c t l y m a y c a u s e d a m a g e t o t h e T h e r m o K i n g u n i t o r o t h e r p r o p e rt y o r p e r s o n a l i n j u r y.
Recover Refrigerant
N o t e : In the USA, EPA Section 608 Certification is required to work on refrigeration systems.
At Thermo King, we recognize the need to preserve the environment and limit the potential harm
to the ozone layer that can result from allowing refrigerant to escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the
atmosphere.
When working on transport temperature control systems, a recovery process that prevents or
minimizes refrigerant loss to the atmosphere is required by law. In addition, service personnel
must be aware of the appropriate European Union, National, Federal, State, and/or Local
regulations governing the use of refrigerants and certification of technicians. For additional
information on regulations and technician programs, contact your local THERMO KING dealer.
S e r v i c e To o l s - Use the proper service tools. Gauge manifold sets should include appropriate
shutoff valves or disconnects near the end of each service line.
R e c o v e r y E q u i p m e n t - Recovery equipment must be used. Proper recovering, storing and
recycling of refrigerants is an important part of all service work.
S e r v i c e Pr o c e d u r e s - Recommended procedures must be used to minimize refrigerant loss.
C o m p o n e n t s m a y b e i s o l a t e d by closing service valves and performing system pump-downs.
C o m p o n e n t s u n a b l e t o b e i s o l a t e d for service must be repaired only after refrigerant is
properly recovered.
Revision History
Revision A (6/15) New manual format; Add C-600 information, Pre/Post March 2014 configurations, and update software revision
information throughout manual; Section 1: included additional safety information; Section 2: added optional solar panel
information, other general updates; Section 5: updated alarm code information and added alarm codes; Section 6: updated
service procedures, added A01A, D01A, F01A-F07A, G01A, G03A, G04A, H04A; Section 7: general updates; Section 8:
removed schematic and wiring diagrams and added information on new Precedent Diagrams Manual; Section 9: new section
added for specifications.
Introduction
TK 55533-2-OD-EN 3
(4,1)
Introduction
4 TK 55533-2-OD-EN
(5,1)
Table of Contents
Section 1 - Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Danger, Warning, Caution, and Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Auto Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electrical Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Other Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Units Equipped With Telematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Remote Control Warning Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Refrigerant Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Refrigerant Oil Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
First Aid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Section 2 - Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Precedent Electronic Engine General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Unit Wiring Loom Colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
AC Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
DC Alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fan and Blower Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Optional Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Optional SmartPower™ Electric Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Optional Accessory DC Alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SR-4 Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Control System Overview (S/T Trailer Applications) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
SR-4 Unit Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Microprocessor On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Over-Current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
External Unit Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Base Controller Fuses and Smart FETs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
SR-4 HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
HMI Control Panel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
CargoWatch™ Data Logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Programmable Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Display Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
SR-4 HMI Control Panel Connector Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
SR-4 Base Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Base Controller Hardware Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Base Controller Software Revisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
TK 55533-2-OD-EN 5
(6,1)
Ta b l e o f C o n t e n t s
6 TK 55533-2-OD-EN
(7,1)
Ta b l e o f C o n t e n t s
TK 55533-2-OD-EN 7
(8,1)
Ta b l e o f C o n t e n t s
Pretrip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Flash Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Language. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Gauges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Data Logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Hourmeters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Electric Standby (Model 50 units only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Diesel Mode (Model 50 units only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Adjust Brightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
View Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Clear All ECU Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Maintenance Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Maintenance Menu Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Accessing the Maintenance Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Hourmeters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Gauges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Service Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Output Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Display Self Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Evacuation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Software Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Set Time and Date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Connect Engine Service Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Guarded Access Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Guarded Access Menu Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Security Code Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Entering the Guarded Access Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Leaving the Guarded Access Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Programmable Features Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Temperature Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Pressure Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Restart Unit After Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Setpoint High Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Setpoint Low Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fuel Saver II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
High Speed Pulldown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Fresh Frozen Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Door Open Forces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Door Open Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Sleep Mode After Pretrip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
8 TK 55533-2-OD-EN
(9,1)
Ta b l e o f C o n t e n t s
Rail Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Rail Alternate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Blocked Air Chute Detect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Temperature Differential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Time to Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Door Open Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Discharge Pressure Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Coolant Temperature Setpoint. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Limited Alarm Resets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Remote Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
HMI Control Panel COM 1 Default Baud Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
HMI Control Panel COM 2 Default Baud Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
HMI Control Panel COM 3 Default Baud Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Extended ServiceWatch™ Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
High Temperature Defrost. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Local Authorization of OptiSet™ Plus Flash Load . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Local Authorization of Flash Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
ServiceWatch™ Logging Intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Main Menu Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Add Keypad Lockout to Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Add Sleep to Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Configure Soft Key 2 on Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Configure Soft Key 3 on Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Auto Keypad Lock Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Auto Keypad Lock Pin Num . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Alarm Display Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Hourmeter Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Program Hourmeter Sub-Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Total Run Time Reminder # 1 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Total Run Time Reminder # 2 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Controller Power On Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Pretrip Reminder Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Engine Run Time Reminder # 1 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Engine Run Time Reminder # 2 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Electric Run Time Reminder # 1 Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Electric Run Time Reminder # 2 Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Viewable Hourmeter Setup Sub-Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Total Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Total Run Time Hours (If Model 50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Engine Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Electric Run Hours (If Model 50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Total Run Time Reminder # 1 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Total Run Time Reminder # 2 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Controller Power On Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Pretrip Reminder Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Engine Run Time Reminder # 1 Hours. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
TK 55533-2-OD-EN 9
(10,1)
Ta b l e o f C o n t e n t s
10 TK 55533-2-OD-EN
(11,1)
Ta b l e o f C o n t e n t s
TK 55533-2-OD-EN 11
(12,1)
Ta b l e o f C o n t e n t s
12 TK 55533-2-OD-EN
(13,1)
Ta b l e o f C o n t e n t s
TK 55533-2-OD-EN 13
(14,1)
Ta b l e o f C o n t e n t s
14 TK 55533-2-OD-EN
(15,1)
Ta b l e o f C o n t e n t s
TK 55533-2-OD-EN 15
(16,1)
Ta b l e o f C o n t e n t s
16 TK 55533-2-OD-EN
(17,1)
Ta b l e o f C o n t e n t s
TK 55533-2-OD-EN 17
(18,1)
Ta b l e o f C o n t e n t s
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
Refrigeration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
Electrical Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
Electrical Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
Electrical Standby (SmartPower Units Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Electric Motor and Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Electric Heater Strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Standby Power Cord Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
18 TK 55533-2-OD-EN
(19,1)
Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or
moderate injury and unsafe practices.
General Practices
DA N G E R
Hazard of Explosion!
N e v e r a p p l y h e a t t o a s e a l e d r e f r i g e r a t i o n s y s t e m o r c o n t a i n e r. H e a t i n c r e a s e s i n t e r n a l
p r e s s u r e , w h i ch m i g h t c a u s e a n e x p l o s i o n r e s u l t i n g i n d e a t h o r s e r i o u s i n j u r y.
DA N G E R
Hazardous Gases!
R e f r i g e r a n t i n t h e p r e s e n c e o f a n o p e n f l a m e , s p a r k , o r e l e c t r i c a l s h o rt p r o d u c e s t o x i c
g a s e s t h a t a r e s e v e r e r e s p i r a t o r y i r r i t a n t s w h i ch c a n c a u s e s e r i o u s i n j u r y o r p o s s i b l e
death.
DA N G E R
Risk of Injury!
Keep your hand s, clo thing , and to ols clear of f ans and /o r b elts wh en wor king o n a unit
that is running or when opening or closing compressor service valves. Loose clothing
mi ght e nt an gl e movi ng p ul le y s or b el ts, ca usi ng ser io us i nj ur y or po ssi bl e d ea th .
DA N G E R
R e f r i g e r a n t Va p o r H a z a r d !
Do not inhale refrigerant. Use caution when working with refrigerant or a refrigeration
s y s t e m i n a n y c o n f i n e d a r e a w i t h a l i m i t e d a i r s u p p l y. Re f r i g e r a n t d i s p l a c e s a i r a n d c a n
c a u s e o x y g e n d e p l e t i o n , r e s u l t i n g i n s u ff o c a t i o n a n d p o s s i b l e d e a t h .
DA N G E R
Confined Space Hazards!
Av o i d e n g i n e o p e r a t i o n i n c o n f i n e d s p a c e s a n d a r e a s o r c i r c u m s t a n c e s w h e r e f u m e s f r o m
the engine could become trapped and cause serious injury or death.
TK 55533-2-OD-EN 19
(20,1)
Sec t i o n 1 - Saf e ty I n fo rm at i o n
WA R N I N G
Hazard of Explosion!
N e v e r c l o s e t h e c o m p r e s s o r d i s ch a r g e s e r v i c e v a l v e w h e n t h e u n i t i s o p e r a t i n g . N e v e r
o p e r a t e t h e u n i t w i t h t h e d i s ch a r g e v a l v e c l o s e d ( f r o n t s e a t e d ) . T h i s c o n d i t i o n i n c r e a s e s
i n t e r n a l p r e s s u r e , w h i ch c a n c a u s e a n e x p l o s i o n .
WA R N I N G
Proper Equipment Condition!
Gauge manifold hoses must be in good condition before using them. Never let them
c o m e i n c o n t a c t w i t h m ov i n g b e l t s , f a n s , p u l l e y s o r h o t s u r f a c e s . D e f e c t i v e ga u g e
e q u i p m e n t c a n d a m a g e c o m p o n e n t s o r c a u s e s e r i o u s i n j u r y.
WA R N I N G
Pe r s o n a l P r o t e c t i v e E q u i p m e n t ( P P E ) R e q u i r e d !
A l wa y s w e a r g o g g l e s o r s a f e t y g l a s s e s w h e n w o r k i n g o n a u n i t . Re f r i g e r a n t l i q u i d , o i l ,
a n d b a tt e r y a c i d c a n p e r m a n e n t l y d a m a g e y o u r e y e s . Se e “ F i r s t A i d ”.
WA R N I N G
Equipment Damage and Risk of Injury!
Never drill holes into the unit unless instructed by Thermo King. Holes drilled into high
v o l t a g e c a b l e s c o u l d c a u s e a n e l e c t r i c a l f i r e , s e v e r e p e r s o n a l i n j u r y, o r e v e n d e a t h .
WA R N I N G
Risk of Injury!
W he n us i ng l ad de r s to i ns ta l l or s erv i c e re fri ge ra ti on s y st em s , a l way s o bs er ve the l a dd er
m a n u f a c t u r e r ’s s a f e t y l a b e l s a n d w a r n i n g s . A w o r k p l a t f o r m o r s c a ff o l d i n g i s t h e
recommended method for installations and servicing.
C AU T I O N
Sharp Edges!
E x p o s e d c o i l f i n s c a n c a u s e l a c e r a t i o n s . Se r v i c e w o r k o n t h e e v a p o r a t o r o r c o n d e n s e r
c o i l s i s b e s t l e f t t o a c e r t i f i e d T h e r m o K i n g t e ch n i c i a n .
N OT I C E
Equipment Damage!
A l l m o u n t i n g b o l t s m u s t b e t i g h t a n d a r e t h e c o rr e c t l e n g t h f o r t h e i r a p p l i c a t i o n s .
I m p r o p e r t o r q u e a n d i n c o rr e c t b o l t l e n g t h s c a n d a m a g e e q u i p m e n t .
N o t e : In the USA, EPA Section 608 Certification is required to work on refrigeration systems.
Auto Start/Stop
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
20 TK 55533-2-OD-EN
(21,1)
Se ct i o n 1 - Sa fe t y In fo rm a ti o n
WA R N I N G
Risk of Injury!
Th er mo Kin g uni t s e qui pp ed w it h opt io na l 2 wa y c om m un ic a ti on s c an b e tu rne d on a nd
o ff f r o m r e m o t e l o c a t i o n s a t a ny t i m e v i a s a t e l l i t e o r c e l l u l a r p h o n e . O n c e t u r n e d o n , t h e
u n i t s c a n s t a rt a n d r u n a u t o m a t i c a l l y a t a n y t i m e .
C AU T I O N
Risk of Injury!
T h e u n i t c a n s t a r t a n d r u n a u t o m a t i c a l l y a n y t i m e t h e u n i t i s t u r n e d o n . U n i t s s t a rt
a u t o m a t i c a l l y i n b o t h C y c l e Se n t r y m o d e a n d C o n t i n u o u s m o d e . B e s u r e t o t u r n t h e u n i t
M i c r o p r o c e s s o r O n / O f f s w i t ch O f f b e f o r e o p e n i n g d o o r s , d o i n g i n s p e c t i o n s , o r w o r k i n g
o n a n y p a rt o f t h e u n i t .
C AU T I O N
Risk of Injury!
P r e c e d e n t u n i t s m a y h a v e o p t i o n s t h a t a l l o w f o r r e m o t e s t a rt i n g f r o m a f u l l y o ff s t a t e . B e
s u r e t o t u r n t h e u n i t M i c r o p r o c e s s o r O n / O f f S w i t ch O f f b e f o r e o p e n i n g d o o r s , d o i n g
i n s p e c t i o n s , o r w o r k i n g o n a n y p a rt o f t h e u n i t .
Electrical Hazards
High Voltage
I m p o rt a n t : All Precedent units utilize nominal 230 Vac power supplied from the diesel engine
driven generator to operate the condenser fans and evaporator blower when the unit
is operating in Diesel Mode.
I m p o rt a n t : Do not move the vehicle if the power cable or the electric standby icon is illuminated.
DA N G E R
H a z a r d o u s Vo l t a g e !
L et ha l a m oun ts o f vol ta ge a re p re s en t i n s om e e l ec t ric a l c i rc ui ts . U s e e xt rem e ca re whe n
working on an operating refrigeration unit.
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
TK 55533-2-OD-EN 21
(22,1)
Sec t i o n 1 - Saf e ty I n fo rm at i o n
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
WA R N I N G
H a z a r d o u s Vo l t a g e !
S m a rt Po w e r u n i t s u s e h i g h v o l t a g e A C f o r e l e c t r i c s t a n d b y o p e r a t i o n . L e t h a l v o l t a g e
p o t e n t i a l s c a n e x i s t o n c o n n e c t i o n s i n t h e h i g h v o l t a g e b o x . Ta k e a p p r o p r i a t e p r e c a u t i o n s
and use extreme care when testing the unit.
WA R N I N G
Risk of Injury!
O n S m a rt Po w e r e l e c t r i c s t a n d b y e q u i p p e d u n i t s , t h e p o w e r s u p p l y v o l t a g e a n d v e h i c l e
vol t ag e re qui re m e nts m us t be t he s a m e be fo re c on ne ct in g the el e ct ri c s ta nd by p owe r
c a bl e. Re fe r t o t he e l ec t ri c s ta ndb y vol ta ge la be l l oc a te d ne ar the ve hi c le pow er
c o n n e c t o r.
WA R N I N G
Risk of Injury!
O n S m a rt Po w e r e l e c t r i c s t a n d b y e q u i p p e d u n i t s , a l w a y s t u r n o ff t h e e x t e r n a l s t a n d b y
po we r s ou rc e be fo re h an dl in g, c on ne c ti ng, or di s co nne c ti ng t he po we r c ab le . A l way s
disconnect the standby power cord before servicing the unit.
WA R N I N G
H a z a r d o u s Vo l t a g e !
Tr e a t a l l w i r e s a n d c o n n e c t i o n s a s i f t h e y w e r e h i g h v o l t a g e u n t i l a m e t e r a n d w i r i n g
diagram indicate otherwise. Use tools with well insulated handles. Never hold
u n in s u l at ed m e t a l t o o l s n ea r ex p o s ed , e n e r g i ze d co n d u c t o r s .
WA R N I N G
H a z a r d o u s Vo l t a g e !
N e ve r wor k al on e on hi g h vo lt ag e c i rc ui ts i n th e re fri ge ra ti on u ni t. A n oth er pe r s on
s h o u l d b e n e a r b y t o s h u t o ff t h e u n i t a n d p r o v i d e a i d i n t h e e v e n t o f a n a c c i d e n t .
WA R N I N G
Pe r s o n a l P r o t e c t i v e E q u i p m e n t ( P P E ) R e q u i r e d !
S a f e t y g l a s s e s , r u b b e r- i n s u l a t e d g l o v e s , a n d c a b l e c u tt e r s s h o u l d b e n e a r y o u r w o r k a r e a
in the event of an electrical accident.
WA R N I N G
H a z a r d o u s Vo l t a g e w / C a p a c i t o r s !
B e c a r e f u l w h e n w o r k i n g w i t h e l e c t r i c a l ci r c u i t s t h a t c o n t a i n c a p a c i t o r s . So m e c a p a c i t o r s
h o l d a s i g n i f i c a n t e l e c t r i c a l ch a r g e t h a t m i g h t c a u s e b u r n s o r s h o c k s i f a c c i d e n t a l l y
d i s ch a r g e d . C a p a c i t o r s m u s t b e d i s ch a r g e d b e f o r e w o r k i n g o n e l e c t r i c a l c i r c u i t s .
22 TK 55533-2-OD-EN
(23,1)
Se ct i o n 1 - Sa fe t y In fo rm a ti o n
Low Voltage
I m p o rt a n t : Some SR-4 components are connected directly to un-switched battery power. All
connections and circuits labeled with a “2” prefix are connected directly to battery
power. Always disconnect the battery before servicing the unit.
WA R N I N G
Li ve Electrical Components!
C o n t r o l c i r c u i t s u s e d i n r e f r i g e r a t i o n u n i t s a r e l o w v o l t a g e ( 1 2 t o 2 4 v o l t s d c ) . H o w e v e r,
t h e l a r g e a m o u n t o f a m p e r a g e a v a i l a b l e c a n c a u s e s e v e r e b u r n s i f a c c i d e n t a l l y s h o rt e d t o
g r o u n d w i t h m e t a l o b j e c t s , s u ch a s t o o l s . D o n o t w e a r j e w e l r y, w a t ch e s , o r r i n g s b e c a u s e
t h e y i n c r e a s e t h e r i s k o f s h o rt i n g o u t e l e c t r i c a l c i r c u i t s a n d d a m a g i n g e q u i p m e n t o r
causing severe burns.
N OT I C E
Equipment Damage!
W h e n w o r k i n g w i t h e l e c t r i c a l c i r c u i t s t h a t c o n t a i n m i c r o p r o c e s s o r s , a l wa y s w e a r a n E S D
w r i s t s t r a p ( T K N o . 2 0 4 - 6 2 2 ) a n d c o n n e c t t h e o p p o s i t e e n d t o t h e ch a s s i s g r o u n d o r C H
t e r m i n a l . T h i s p r e c a u t i o n w i l l p r e v e n t e l e c t r o s t a t i c d i s ch a r g e f r o m d a m a g i n g c i r c u i t s .
We l d i n g
Precautions must be taken before welding on the unit. Refer to Service Procedure A26A Welding
on Units Equipped with Microprocessors in Section 6 of this manual for additional information.
C AU T I O N
Risk of Injury!
P r e c e d e n t u n i t s m a y h a v e o p t i o n s t h a t a l l o w f o r r e m o t e s t a rt i n g f r o m a f u l l y o ff s t a t e . B e
s u r e t o t u r n t h e u n i t M i c r o p r o c e s s o r O n / O f f S w i t ch O f f b e f o r e o p e n i n g d o o r s , d o i n g
i n s p e c t i o n s , o r w o r k i n g o n a n y p a rt o f t h e u n i t .
Some Thermo King units may be equipped with Telematics options. These options may feature 2
way communications that include the ability to start and stop the unit from a remote location via
satellite or cellular phone.
TK 55533-2-OD-EN 23
(24,1)
Sec t i o n 1 - Saf e ty I n fo rm at i o n
Refrigerant Hazards
DA N G E R
H a z a r d o u s Pr e s s u r e s !
A l wa y s s t o r e r e f r i g e r a n t i n p r o p e r c o n t a i n e r s , o u t o f d i r e c t s u n l i g h t a n d a wa y f r o m
i n t e n s e h e a t . H e a t i n c r e a s e s p r e s s u r e i n s i d e s t o r a g e c o n t a i n e r s , w h i ch c a n c a u s e t h e m t o
b u r s t a n d c o u l d r e s u l t i n s e v e r e p e r s o n a l i n j u r y.
DA N G E R
Combustible Hazard!
Do no t use oxy ge n (O 2 ) or co mpre ssed a i r f or l ea k t esti ng . Oxy ge n mi xe d wi th
refrigerant is combustible.
WA R N I N G
Hazardous Gases!
D o n o t u s e a H a l i d e t o r ch . W h e n a f l a m e c o m e s i n c o n t a c t w i t h r e f r i g e r a n t , t o x i c g a s e s a r e
p r o d u c e d . T h e s e g a s e s c a n c a u s e s u ff o c a t i o n , e v e n d e a t h .
WA R N I N G
Pe r s o n a l P r o t e c t i v e E q u i p m e n t ( P P E ) R e q u i r e d !
Ref rigerant in a liqu id state evapor at es rap idly wh en exp osed t o the at mosph ere, f reezing
a ny t h i n g i t c o n t a c t s . We a r b u t y l l i n e d g l o v e s a n d o t h e r c l o t h i n g a n d e y e w e a r w h e n
handling refrigerant to help prevent frostbite.
WA R N I N G
Pe r s o n a l P r o t e c t i v e E q u i p m e n t ( P P E ) R e q u i r e d !
Prot ect y ou r e y es fro m con ta ct w i th re fri ge ra nt o il . T he oi l ca n ca use se ri ou s e ye i nj ur ie s.
P r o t e c t s k i n a n d c l o t h i n g f r o m p r o l o n g e d o r r e p e a t e d c o n t a c t w i t h r e f r i g e r a n t o i l . To
p r e v e n t i rr i t a t i o n , wa s h y o u r h a n d s a n d c l o t h i n g t h o r o u g h l y a ft e r h a n d l i n g t h e o i l .
Rubb er gl ov es are re co mmen de d.
N OT I C E
Equipment Damage!
W h e n b e i n g t r a n s f e rr e d , r e f r i g e r a n t m u s t b e i n l i q u i d s t a t e t o a v o i d p o s s i b l e e q u i p m e n t
damage.
24 TK 55533-2-OD-EN
(25,1)
Se ct i o n 1 - Sa fe t y In fo rm a ti o n
N OT I C E
Equipment Damage!
U s e t h e c o rr e c t o i l i n T h e r m o K i n g s y s t e m s t o a v o i d d a m a g i n g e q u i p m e n t a n d n u l l i f y i n g
i t s w a rr a n t y.
N OT I C E
Equipment Damage!
Do not mix refrigerant oils because that can cause refrigeration system damage.
N OT I C E
Equipment Damage!
Use dedicated refrigeration equipment to prevent contaminating refrigeration systems
with the wrong type of oil.
N OT I C E
System Cont aminat ion!
D o n o t e x p o s e t h e r e f r i g e r a n t o i l t o t h e a i r a n y l o n g e r t h a n n e c e s s a r y. S t o r e r e f r i g e r a n t o i l
i n an a pp rove d s ea l ed c on ta in er to a voi d m oi s ture co nt am i na ti on . Th e oi l w il l a bs or b
m o i s t u r e , w h i c h r e s u l t s i n m u ch l o n g e r e v a c u a t i o n t i m e s a n d p o s s i b l e s y s t e m
contamination.
N OT I C E
Material Damage!
W i p e u p s p i l l s i m m e d i a t e l y. R e f r i g e r a n t o i l c a n d a m a g e p a i n t s a n d r u b b e r m a t e r i a l s .
TK 55533-2-OD-EN 25
(26,1)
Sec t i o n 1 - Saf e ty I n fo rm at i o n
First Aid
R E F R I G E R A NT
• E y e s : For contact with liquid, immediately flush eyes with large amounts of water and get
prompt medical attention.
• S k i n : Flush area with large amounts of warm water. Do not apply heat. Remove
contaminated clothing and shoes. Wrap burns with dry, sterile, bulky dressing to protect from
infection. Get prompt medical attention. Wash contaminated clothing before reuse.
• I n h a l a t i o n : Move victim to fresh air and use CPR (cardio pulmonary resuscitation) or mouth-
to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency
personnel arrive.
• F r o s t B i t e : In the event of frost bite , the objectives of First Aid are to protect the frozen area
from further injury, warm the affected area rapidly, and to maintain respiration.
R E F R I G E R A NT O I L
• E y e s : Immediately flush with large amounts of water for at least 15 minutes. Get prompt
medical attention.
• S k i n : Remove contaminated clothing. Wash thoroughly with soap and water. Get medical
attention if irritation persists.
• I n h a l a t i o n : Move victim to fresh air and use CPR (cardio pulmonary resuscitation) or mouth-
to-mouth resuscitation to restore breathing, if necessary. Stay with victim until emergency
personnel arrive.
• I n g e s t i o n : Do not induce vomiting. Immediately contact local poison control center or
physician.
E N G I N E C O O L A NT
• E y e s : Immediately flush with large amounts of water for at least 15 minutes. Get prompt
medical attention.
• S k i n : Remove contaminated clothing. Wash thoroughly with soap and water. Get medical
attention if irritation persists.
• I n g e s t i o n : Do not induce vomiting. Immediately contact local poison control center or
physician.
ELECTRICAL SHOCK
Take IMMEDIATE action after a person has received an electrical shock. Get quick medical
assistance, if possible.
The source of the shock must be quickly stopped, by either shutting off the power or removing
the victim. If the power cannot be shut off, the wire should be cut with an non-conductive tool,
such as a wood-handle axe or thickly insulated cable cutters. Rescuers should wear insulated
gloves and safety glasses, and avoid looking at wires being cut. The ensuing flash can cause
burns and blindness.
If the victim must be removed from a live circuit, pull the victim away with a non-conductive
material. Use wood, rope, a belt or coat to pull or push the victim away from the current. DO NOT
TOUCH the victim. You will receive a shock from current flowing through the victim’s body. After
separating the victim from power source, immediately check for signs of a pulse and respiration.
If no pulse is present, start CPR (cardio pulmonary resuscitation). If a pulse is present, respiration
might be restored by using mouth-to-mouth resuscitation. Call for emergency medical
assistance.
26 TK 55533-2-OD-EN
(27,1)
Engine
There are two engine types used in Precedent Single Temperature Trailer Units; Mechanical and
Electronic.
• Mechanical Engine < 25 HP (C-600)
Mechanical Engines use the traditional Base Controller Engine Controls.
• Electronic Engine > 25 HP (S-600/S-700)
Electronic Engines are controlled by an electronic Engine Control Unit (ECU) rather than
by the SR-4 Base Controller. The SR-4 Base Controller supplies a Keyswitch Signal to
enable the ECU and a Run Signal when the diesel engine is required to run. All other
engine control functions are handled by the ECU and an Engine Control Relay/Fuse Board
located below the SR-4 Base Controller. The SR-4 Base Controller engine control features
such as Preheat and Start Relays, RPM Sensor, Coolant Temperature Sensor and Coolant
and Oil Level Sensors are not used.
The Electronic Engine is a Thermo King TK488CR/CRH. This engine features Common Rail Fuel
Injection and an Engine Control Unit (ECU) to control and monitor engine functions. The engine
also features an Exhaust Gas Recirculation System (EGR) and a Diesel Oxidation Catalyst (DOC)
exhaust treatment system. The engine is EPA Tier 4 Compliant and CARB Evergreen. The
compressor is directly coupled to the engine on Model 30 units and clutch driven on Model 50
units. Belts drive the AC Generator, water pump, and alternator (if present).
I m p o rt a n t : Older SR-4 controllers P/N 45–2448 and P/N 45–2521 can only be used on early S-600
units equipped with the Engine Relay/Fuse Board.
I m p o rt a n t : SR-4 controllers with P/N 45–2548 or P/N 845–2548 require software revision BA20 or
later for single temperature units.
N o t e : For more information, see Service Bulletin TT722.
AC Generator
An AC Generator is used to supply AC power to the Condenser Fan Motors and Evaporator
Blower Motors. The engine speed (high speed or low speed) determines the voltage and
frequency of the AC power. The AC Generator is belt driven by the diesel engine.
DC Alternator
In standard units, an alternator provides 12 Vdc to charge the battery and power the 12 Vdc
control system.
TK 55533-2-OD-EN 27
(28,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
The Evaporator Blowers and Condenser Fans are powered by three phase AC electric motors.
Fan and blower motor speed is dependent upon the AC voltage and frequency supplied by the
AC Generator when the diesel engine is running in high speed or low speed. Motor speed of the
Evaporator Blower Motor is also controlled by high speed and low speed windings on the motor.
N o t e : Fan Motors - Electric Standby Operation 230/3/60 or 460/3/60 (Unit transformer reduces
460/3/60 input voltage to 230/3/60 applied to fan motors).
Optional SmartPower™
™ Electric Standby
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
SmartPower™ Model 50 Electric Standby is available as an option. This option allows unit
operation on external three phase standby electric power as well as the diesel engine. 460-480
VAC units utilize a step-down transformer to reduce the voltage to 230 VAC. The evaporator and
condenser fans run on 230 VAC from supply, or from the step-down if 460–480 supply.
28 TK 55533-2-OD-EN
(29,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
TK 55533-2-OD-EN 29
(30,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Rev H Controller
30 TK 55533-2-OD-EN
(31,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Figure 4. SR-4 Control System Overview Single Temp - Electronic/Mechanical Engine (Rev K
Controller)
Rev K Controller
CargoW atch SR-4 HMI Control Panel
PRINTER CONNECT OR HMI Software Not all devices shown
Supervisor Software here are used on all
Keypad applications.
CargoW atch Display
CargoW atch Data Logger
SENSOR OPTION Setpoint Buzzer
TK 55533-2-OD-EN 31
(32,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Figure 5. Precedent Electronic Engine Control Unit (ECU) Single Temp - Electronic Engine
Unit Power
Fuel Injector #1
and Signals
Fuel Injector #2
12 VDC Power (15 A Fuse)
Fuel Injector #3
Fuel Injector #4
Chassis Ground
Engine Ambient
Air Temp Sensor
Engine
Components
Keyswitch Signal from SR-4
High Pressure
Fuel Pump
Run Signal from SR-4 Fuel Pressure
Sensor
Fuel Temp
Sensor
CAN Bus
From previous Figure
Exhaust Temp
Diagnostic Sensor
EGR Temp
Tool CAN Bus
Sensor
55533-2-2-1a
32 TK 55533-2-OD-EN
(33,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Figure 6. Precedent Fan and Blower Control Single Temp - All Units
55533-2-2-1b
TK 55533-2-OD-EN 33
(34,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Phase Phase
Contactor Contactor
1 2
460 VAC applications use
a fuse protected stepdown
transformer to provide
230 VAC
Ground Fault 3 Phase AC
Detector Generator
Compressor Evaporator
Note 1
Drive Motor Heater Current
Current Sensor
Contactor Contactor Sensor
used only on units
without optional (See Note 1)
Overload Overload Battery Charger .
Relay Relay
Generator
Contactor
Compressor Evaporator
Drive Motor Heaters
10 A
Fuse
55533-2-2-1c
34 TK 55533-2-OD-EN
(35,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
N o t e : The Microprocessor On/Off Switch is covered by the side panel when it is closed.
TK 55533-2-OD-EN 35
(36,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
WA R N I N G
Risk of Injury!
T h e u n i t c a n s t a rt a t a ny t i m e w i t h o u t w a r n i n g . P r e s s t h e O F F k e y o n t h e H M I c o n t r o l
p a n e l a n d p l a c e t h e m i c r o p r o c e s s o r O n / O f f s w i t ch i n t h e O f f p o s i t i o n b e f o r e i n s p e c t i n g o r
s e r v i c i n g a n y p a rt o f t h e u n i t .
I m p o rt a n t : Always turn the Microprocessor On/Off switch off before inspecting or working on
any part of the unit.
The Microprocessor On/Off switch is located on the control box door above the HMI Control
Panel. It is concealed when the unit side panel is closed.
Figure 9. Microprocessor On/Off Switch
55533-2-2-5
Over-Current Protection
External Unit Fuses
Over-current protection is provided by fuses. The following tables show which external fuses
may be used.
N o t e : Refer to the applicable Schematic Diagram for locations and the most accurate
information.
N o t e : Refer to Section 7 for additional Base Controller information.
Table 1. Early Units (Pre March 2014)
15A ECU Input Power (Electronic Engine) Engine Control Unit (ECU)
36 TK 55533-2-OD-EN
(37,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
F 5A LED
FB1 (3 fuses) 15A ea Primary Alt & Battery Charger (Option) 230 VAC
TK 55533-2-OD-EN 37
(38,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
WA R N I N G
Risk of Injury!
T h e u n i t c a n s t a rt a t a ny t i m e w i t h o u t w a r n i n g . P r e s s t h e O F F k e y o n t h e H M I c o n t r o l
p a n e l a n d p l a c e t h e m i c r o p r o c e s s o r O n / O f f s w i t ch i n t h e O f f p o s i t i o n b e f o r e i n s p e c t i n g o r
s e r v i c i n g a n y p a rt o f t h e u n i t .
I m p o rt a n t : The SR-4 HMI Control Panel is not compatible with SR-2 and SR-3 Control Systems.
It is critical that the correct software be used.
• Units with SR-4 HMI Control Panels must use HMI Control Panel Software Revision 7A25 or
later.
Refer to Section 7 of this manual for additional hardware and software details and requirements.
Figure 10. SR-4 HMI Control Panel
55533-2-2-6
The Human Machine Interface (HMI) Control Panel consists of an LCD graphics display screen
and eight touch sensitive keys.
• The four keys on the sides of the display screen are used to turn the unit on and off, initiate a
manual defrost cycle, and select the desired operating mode. These keys are designated
“Hard” keys as their function is always the same.
• The function of the four keys located below the display screen change as required by the
current menu. The current function of the key is controlled by software and is displayed
directly above the key. These keys are known as software controlled keys or “Soft” keys.
• The same HMI Control Panel is used for single temperature and multi-temperature
applications.
38 TK 55533-2-OD-EN
(39,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
The display screen is used by the Base Controller to provide visual prompts and information to
the operator, such as operating mode, setpoint temperatures, gauges, hourmeter readings and
operating conditions of the diesel engine or electric motor. The HMI also contains the
CargoWatch Data Logger.
Information can be displayed in four possible languages (English, Spanish, French, and
Portuguese).
If the HMI Control Panel is disconnected from the unit while the unit is running, the unit will shut
down. When the HMI Control Panel is reconnected the unit will not restart until the On key is
pressed.
N o t e : If necessary, the HMI Control Panel can be bypassed using fuse F10. Refer to Section 2
Fuse F10.
CargoWatch™
™ Data Logger
The HMI Control Panel contains the CargoWatch Data Logger. The CargoWatch Data Logger is a
fully independent temperature logger. Up to six temperature sensors and three digital inputs can
be connected to the CargoWatch Data Logger. The optional CargoWatch temperature sensors are
separate sensors installed as desired by each user. The CargoWatch Data Logger records
CargoWatch temperature sensors, unit setpoint, unit operating condition, and alarm codes.
The Countdown and Conservative features allow the CargoWatch Data Logger to continue to log
after the unit is turned off. Refer to CargoWatch Sensor Configuration in Section 3 for details of
operation.
Programmable Features
The settings of all programmable features are held in non-volatile memory in the Base Controller.
The settings are supplied to the HMI Control Panel each time the unit is turned on. If the HMI
Control Panel is changed, the current programmable feature settings will be supplied to the HMI
Control Panel when the unit is turned on.
Display Heater
The HMI Control Panel is equipped with a display heater. This heater is necessary to make the
display quickly visible in cold ambient temperatures.
The HMI has its own internal temperature sensor for the display heater. The display heater is
energized when the unit is turned on and the temperature sensed by the internal sensor is below
29°F (-2°C). The display heater turns off when the temperature sensed by the internal sensor rises
above 37°F (3°C). The display heater draws from 1.4 to 1.7 amps when energized.
The colder the ambient temperature the longer it will take for the heater to make the display
visible on a cold startup. It may take 10-15 seconds for the display to appear with very cold
ambient temperatures.
TK 55533-2-OD-EN 39
(40,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
1 S6P-01 CargoWatch Sensor 6 positive 22 BLK4–CANH HMI Control Panel CAN Bus
2 S5P-01 CargoWatch Sensor 5 positive 10 RED4–CANL HMI Control Panel CAN Bus
13 S5N-01 CargoWatch Sensor 5 negative 35 BLK1–CH HMI Control Panel Chassis Ground
22 BLK4–CANH HMI Control Panel CAN Bus 16 S1N-01 CargoWatch Sensor 1 negative
33 RED1–OFF HMI Control Panel Off Line 13 S5N-01 CargoWatch Sensor 5 negative
35 BLK1–CH HMI Control Panel Chassis Ground 24 S6N-01 CargoWatch Sensor 6 negative
Figure 11. HMI Control Panel Connector (shown from pin side)
55533-2-2-7
40 TK 55533-2-OD-EN
(41,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
WA R N I N G
Risk of Injury!
T h e u n i t c a n s t a rt a t a ny t i m e w i t h o u t w a r n i n g . P r e s s t h e O F F k e y o n t h e H M I c o n t r o l
p a n e l a n d p l a c e t h e m i c r o p r o c e s s o r O n / O f f s w i t ch i n t h e O f f p o s i t i o n b e f o r e i n s p e c t i n g o r
s e r v i c i n g a n y p a rt o f t h e u n i t .
Programmable Features
The settings of all programmable features are held in non-volatile memory in the Base Controller.
The settings are supplied to the HMI Control Panel each time the unit is turned on. If the Base
Controller is changed, all programmable features must be reprogrammed. Refer to Section 3 of
this manual for programmable feature details.
TK 55533-2-OD-EN 41
(42,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Smart FETs are self-protecting. An LED next to each relay or Smart FET is illuminated when the
relay or FET is energized by the Base Controller. With relays the LED lights only when the relay
coil is energized and the relay contacts have transferred to the energized position.
Figure 12. SR-4 Base Controller
55533-2-2-8
42 TK 55533-2-OD-EN
(43,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Relay Functions
I m p o rt a n t : Do not attempt to remove the relays from the Base Controller. They are soldered in
place.
Relay Function
K6 On/Off Relay
K8 Run Relay
Notes:
1. Used only on applications with mechanical
engines.
Notes:
1. Fuse F4 fuse must be in place for Prestolite alternators to charge. Fuse F4
must be removed for Bosch and Thermo King alternators. Service Parts
Base Controllers are shipped without the F4 fuse.
2. The F5 preheat fuse is a “slow blow” type fuse. It is designed for use with the
Yanmar trailer engine air pre-heater. Always replace the fuse with the TK
specified fuse. Service Parts Base Controllers are shipped without the F5
fuse.
3. Used only on applications with mechanical engines.
TK 55533-2-OD-EN 43
(44,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Fuse F10
There are three in-line fuse clips that allow for two configurations of the F10 fuse. The downward
position is the normal position. This position has a white bar below it on the circuit board. When
fuse F10 is installed in the downward position, control power is routed to the K6 On/Off Relay
contacts. The On/Off keys on the HMI Control Panel energize and de-energize the K6 On/Off Relay.
When the K6 On/Off Relay is energized, power is supplied through the normally open K6 contacts
to turn the unit on.
When fuse F10 is installed in the upward position, power bypasses the K6 On/Off relay contacts
and the unit will start and run without the HMI Control Panel connected. T h i s f u s e p o s i t i o n i s f o r
e m e r g e n c y b y p a s s o p e r a t i o n o n l y. T h e u n i t w i l l c o n t r o l t e m p e r a t u r e t o t h e l a s t e n t e r e d
s e t p o i n t . The white bar on the relay board represents normal position for the fuse. Do not
operate the unit with the F10 fuse installed in the upward position unless absolutely necessary.
I m p o rt a n t : If fuse F10 is installed in the upward position the unit may start and run. If the HMI
Control Panel is connected and functional, the On and Off keys will still work. The Off
key will turn the unit off if Fuse F10 is in the upward position, but the Base Controller
will remain powered up.
I m p o rt a n t : If fuse F10 is installed in the upward position and the unit is turned off using the Off
key the unit will shut down but the Base Controller will remain powered up. Leaving
the unit turned off in this manner for an extended period may result in a dead battery.
Output Function
26 Pilot Solenoid
LED Functions
The LED is illuminated when the associated circuit output is energized. Not all output LEDs
shown are used on single temperature trailer applications.
44 TK 55533-2-OD-EN
(45,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
LED 5 K7 Diesel/Electric Relay Output LED 27 Evaporator Fan Low Speed Output
LED 6 K6 On/Off Relay Output LED 29 Evaporator Fan High Speed Output
LED 9 K11 Preheat Relay Output LED 37 ECU Key Switch Output
LED 12 Hot Gas Bypass Output LED 44 K10 Auto Fresh Air Door Output
LED 23 Liquid Line Solenoid Output LED 50 ETV – C Output (See Note 2)
Notes:
1. The Status LED flashes once per second when the Base Controller is powered and operating normally.
The Status LED flashes several times per second during a flash load. The Status LED is on without
flashing during reboot and when the Base Controller is under test. The Status LED flashes twice within
one second followed by one second off if a CAN communication error is present.
2. ETV LEDs are illuminated when the respective ETV output is energized.
TK 55533-2-OD-EN 45
(46,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Board Jumpers
Three sets of jumper pins are located on the Base Controller. Each set consists of a jumper and
three pins. A white bar next to each set of pins on the circuit board shows the usual jumper
placement. For normal operation, the jumpers must be installed as shown.
55533-2-2-9
The J101 jumper is used to perform a Base Controller Cold Start. For details, refer to Service
Procedure A07A Performing a Base Controller Cold Start. The J27 and J102 jumpers should not
be moved.
Jumper Functions
Jumper Function
46 TK 55533-2-OD-EN
(47,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Connector Locations
16 17 18 19 20 22 21
2AH
23
55533-2-2-10
TK 55533-2-OD-EN 47
(48,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Connector Usage
Number Connector Circuit
3 CH Chassis Ground
4 2A 2A Power
5 2 2 Power
16 J32 CAN Bus to Engine Control Unit (ECU) (J1939 CAN Port)
19 J12 CAN Bus to HMI Control Panel (Thermo Bus CAN Port)
48 TK 55533-2-OD-EN
(49,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
5 RTP-01 Display Return Air Temperature Sensor Positive (blue sensor wire)
7 DTP-01 Control Discharge Air Temperature Sensor Positive (blue sensor wire)
10 DTRP-01 Display Discharge Air Temperature Sensor Positive (blue sensor wire)
17 RTN-01 Control Return Air Temperature Sensor Negative (brown sensor wire)
19 DTN-01 Control Discharge Air Temperature Sensor Negative (brown sensor wire)
22 DTRN-01 Display Discharge Air Temperature Sensor Negative (brown sensor wire)
28 RTRP-01 Display Return Air Temperature Sensor Negative (brown sensor wire)
29 RTRN-01 Display Return Air Temperature Sensor Negative (brown sensor wire)
55533-2-2-1 1
TK 55533-2-OD-EN 49
(50,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
55533-2-2-12
50 TK 55533-2-OD-EN
(51,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
55533-2-2-13
TK 55533-2-OD-EN 51
(52,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
2 BLACK4 To HMI
(CANH)
3 SHIELD To HMI
52 TK 55533-2-OD-EN
(53,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
2 2 Battery Power
2A 2A Alternator Power
CH CH Chassis Ground
J32 - CAN Bus to Engine Control Unit (ECU) - Arranged by Pin Number
Pin # Wire # Description
3 SHLD
1 JCANH-01
2 JCANL-01
Figure 16. Mini Mate-N-Lok Harness Connectors (shown from pin side of harness connector)
55533-2-2-14
TK 55533-2-OD-EN 53
(54,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Complete SR-4 Control System with Radio Expansion Board (REB) Installed
55533-2-2-15
54 TK 55533-2-OD-EN
(55,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Early Units
For Pre March 2014 units, the Engine Control Relay/Fuse Board contains four relays and three
fuse blocks. An in-line fuse holder is also located in the wiring harness near the board.
Figure 17. Engine Relay/Fuse Board - Pre March 2014
55533-2-2-16
Relay Functions
I m p o rt a n t : The relays are socket mount relays. They can be replaced if necessary.
Relay Function
TK 55533-2-OD-EN 55
(56,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Later Units
For Post March 2014 units, the Engine Control Relay/Fuse Board contains only one relay. The
functionality of the removed auxiliary relays is now provided by the Base Controller.
Figure 18. Engine Relay/Fuse Board - Post March 2014
EGR
Relay
Relay Functions
I m p o rt a n t : The relay is a socket mount relay. It can be replaced if necessary.
Relay Function
56 TK 55533-2-OD-EN
(57,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Generator
A three phase Generator is used to supply power to the Condenser Fans and Evaporator Blower
on all Precedent units. The Generator is located below the diesel engine and is belt driven
directly from a crankshaft pulley on the front of the engine. Generator bearings are field
replaceable. If a generator winding is failed the Generator must be replaced.
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
Generator Output
The voltage and frequency of the AC output varies with the speed of the diesel engine. The
voltage and frequency at high speed and low speed diesel are used to control Fan and Blower
speed.
• Diesel engine Low Speed operation results in 230 Vac Generator Output.
• Diesel engine High Speed operation results in 345 Vac Generator Output. The Fan and Blower
Motors can run at 345 Vac without damage.
SmartPower™
™ Electric Standby Units
If the unit is equipped with the optional SmartPower, the fans and blower are also operated from
Standby Power when connected. When the unit is operating in Electric Mode, the Generator
Contactor is open to block Standby Power from reaching the Generator.
TK 55533-2-OD-EN 57
(58,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
The high voltage controls for the Condenser Fans and Evaporator Blower are located in the High
Voltage Fan and Blower Control Box mounted just above the Unit Control Box.
Detector
55533-2-2-17
58 TK 55533-2-OD-EN
(59,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
OFF Does not run. OFF Engine Coolant Temperature < 165°F and
Fan Run Timer is expired
TK 55533-2-OD-EN 59
(60,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
Table 5. S-700 Engine and Evaporator Fan Speeds (6/8 Pole Motor)
Unit Sensors
The sensors monitor air temperatures at various points in the system, as well as alternator
frequency, fuel level, and refrigerant pressures. Sensors are connected to the Base Controller via
the J1 and J2 35 Pin Connectors.
60 TK 55533-2-OD-EN
(61,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
For the S-600/S-700, engine sensors such as the engine oil pressure, engine oil level, engine
coolant temperature, and engine speed are monitored by the Engine Control Unit (ECU).
Dual Sensors
Dual temperature sensors are provided for both return air temperature and discharge air
temperature. The sensors are located next to each other to insure common readings. One sensor
is the control sensor and the other sensor is the display sensor. The return and discharge control
sensors are used for unit control. The return and discharge display sensors are used by the HMI
Control Panel to display the temperature.
TK 55533-2-OD-EN 61
(62,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
62 TK 55533-2-OD-EN
(63,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
CargoWatch™
™ Sensors
The CargoWatch Data Logger is part of the HMI Control Panel. The CargoWatch Data Logger
conforms to European standard EN12830. The Data Logger supports up to six temperature
sensors and four digital inputs.
The sensors used for the CargoWatch Data Logger are RTD thermistor-type sensors that differ
from the sensors used for unit control. The CargoWatch sensors are connected directly to the
HMI Control Panel. The Service Part Number for the optional CargoWatch sensors is 41-5436.
I m p o rt a n t : The CargoWatch sensors ARE NOT interchangeable with the unit temperature
sensors.
CargoWatch sensors can be identified by:
• No shrink tubing over sensor barrel
• Shorter sensor barrel than unit sensors
• No sensor grades
• The sensor is not polarity sensitive
• Both wires are black
Figure 19. CargoWatch Sensor - No Shrink Tubing
55533-2-2-18
CargoWatch thermistor type sensors change resistance as the temperature changes. Resistance
values can be measured using a high quality ohmmeter and are shown in the table below.
N o t e : These resistance values only apply to CargoWatch sensors.
Table 6. CargoWatch Sensor Resistance vs Temperature
°F °C Ohms
Diagnostic Procedure
1. Disconnect the sensor to be tested from the sensor harness at the 12 pin Deutsch connector in
the evaporator compartment.
2. Using a high quality meter, check the sensor resistance.
TK 55533-2-OD-EN 63
(64,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
a. The sensor resistance is dependant on the sensor temperature as shown (Table 6, p. 63).
The measured sensor resistance should approximate the value shown for the current
sensor temperature.
b. If the sensor resistance does not match (Table 6, p. 63), the sensor must be replaced.
3. If the resistance measured in the previous step is correct, proceed to Step 4. If the resistance
measured is not correct, replace the sensor.
4. Using a high quality meter, check the voltage at the sensor harness wires at the 12 pin
Deutsch connector in the evaporator compartment.
a. The voltage from the HMI Control Panel should be 2.5 Vdc with the sensor disconnected.
5. If the voltage measured in the previous step is correct, proceed to Step 7. If the voltage
measured is not correct, proceed to Step 6.
6. If the voltage measured in Step 4 is incorrect, unplug the 35 pin connector at the HMI Control
Panel and check the harness for shorts and open wires.
a. Perform a wiring harness continuity test and repair as required.
7. If the harness passes inspection, check the HMI Control Panel.
a. If the HMI Control Panel fails the test, it must be replaced.
64 TK 55533-2-OD-EN
(65,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
TK 55533-2-OD-EN 65
(66,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
A solenoid is used to open and close the Fresh Air Exchange Door. Note that the Fresh Air
Exchange door will only be open when the unit engine is running, as it is held in the open
position by the Fresh Air Exchange Solenoid. The door will close when the engine shuts down to
preserve unit battery life. The setting of the Fresh Air Exchange door will survive power off /
power on cycles - if the door is set “Open” by the operator, it will continue to open any time the
engine is running until it is set “Close” by the operator.
BA20 (and earlier) Base Controller Software and 7A25 (and earlier) HMI Control Panel Software
are required for the Fresh Air Exchange feature.
If installed and enabled, the Fresh Air Exchange is opened and closed from the Mode Menu.
Refer to Fresh Air Exchange in Section 4 for details.
66 TK 55533-2-OD-EN
(67,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
TK 55533-2-OD-EN 67
(68,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
68 TK 55533-2-OD-EN
(69,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Communication Ports
USB Ports
Thermo King Precedent Trailer Units provide Universal Serial Bus (USB) Ports located on the unit
control panel. For current production (Post March 2014), the upper port has been removed and
the lower port is reserved for USB Flash Drive only. For early production (Pre March 2014), the
upper port is reserved for connection to a Computer and the lower port is reserved for USB Flash
Drive only.
I m p o rt a n t : The Flash Drive must be properly configured and the desired features must be
enabled using the ThermoServ™ Service Tool.
Using a properly configured and enabled flash drive, the following functions may be available:
• Download the ServiceWatch Data Logger
• Download the CargoWatch Data Logger
• Flash load Base Controller Software
• Flash load HMI Control Panel Software
• Send OptiSet Plus Files
• Retrieve OptiSet Plus Files
• Flash Load REB
Printer Port
This port is used to print trip records from the CargoWatch Data Logger. The Printer port is
located inside the control box.
TK 55533-2-OD-EN 69
(70,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
Optional SmartPower™
™ Electric Standby
N o t e : Model 50 units only.
The SmartPower™ Electric Standby option allows the unit to be operated on either the diesel
engine or external standby electric power. The units are supplied to operate on 230 or 460 Vac
three phase power. Units to be operated on 460 Vac are equipped with a step-down transformer
to reduce the voltage from 460 Vac to 230 Vac. The 230 Vac is used to run the blowers while in
electric mode.
Model 50 Features
DA N G E R
H a z a r d o u s Vo l t a g e !
Dangerous three phase AC electric power is present whenever the unit is operating in
either Diesel Mode or Electric Mode and whenever the unit is connected to a source of
e x t e r n a l s t a n d b y p o w e r. Vo l t a g e s o f t h i s m a g n i t u d e c a n b e l e t h a l . E x e r c i s e e x t r e m e
caution when working on the unit.
The following features are standard equipment on units equipped with Electric Standby:
• A u t o m a t i c D i e s e l / E l e c t r i c Se l e c t i o n - The unit can be programmed to automatically switch
to electric operation when a power cord is connected and the standby power is switched on.
The unit can also be programmed to automatically switch back to diesel power if the standby
power is switched off or fails. The HMI Control Panel will prompt for electric or diesel
switchover if the respective autoswitch feature is not enabled.
N o t e : Auto-switch from electric to diesel is not recommended when the unit is running in
electric mode indoors or when below deck on a ferry.
N o t e : The unit will automatically switch to Cycle Sentry when the unit is manually switched
or autoswitched to electric mode.
• A u t o m a t i c O v e r l o a d Re s e t - The overload relay resets automatically after the motor cools.
When the overload trips, it interrupts power to the motor contactor coil.
• E l e c t r i c H e a t - Both hot gas and electric heat is utilized on model 50 units. The electric heaters
are also used during defrost. Electric heat is available on 12 HP options.
• A u t o m a t i c P h a s e C o rr e c t i o n - The control system features two motor contactors. One of the
connectors is energized by the phase detection module to insure correct motor rotation,
regardless of phase rotation on the incoming power. The motor contactors are also
mechanically interlocked.
• L o w Vo l t a g e D e t e c t i o n - The phase detection modulation will not allow the unit to run if the
supply voltage is too low.
• S i n g l e P h a s e P r o t e c t i o n - The phase detection modulation will not allow the unit to run if it
detects a single phase condition.
Diesel/Electric Relay K7
The Diesel/Electric Relay K7 is present on all units. If the Electric Standby option is not present or
if the unit is running in Diesel Mode, control power is routed through the Diesel/Electric Relay
normally closed contacts.
The Diesel/Electric Relay is energized and LED 5 is lit when the Base Controller requests Electric
Mode operation. The K7 Diesel/Electric Relay normally open contacts supply power to the 7E
circuit to enable Electric Mode operation.
70 TK 55533-2-OD-EN
(71,1)
Se c ti o n 2 - H a rd wa r e De s c ri p ti o n
Heater Contactor HC
The heater contactor is used to supply standby power to the electric heaters during heat and
defrost mode electric operation. The heater contactor is energized and LED 2 is lit when the Base
Controller energizes the K3 High Speed Relay during electric mode operation. The K3 High Speed
Relay Smart FET supplies chassis ground via the 26E wire to the heater contactor. The circuit is
protected by the Smart FET.
55533-2-2-19
SmartPower™
™ Electric Standby Components
The SmartPower™ components are located in a separate SmartPower Control Box located
behind the Unit control box. The unit control box swings out to provide access to the
SmartPower Control Box.
TK 55533-2-OD-EN 71
(72,1)
Sec t i o n 2 - Ha r d wa re D e s cr i p t i o n
3
2
1
4
7
13
ARA1909 8
12 9
10
11
4. BC1 – Battery Charger Contactor 1 (460 11. PSM – Phase Selection Module
Vac Only)
72 TK 55533-2-OD-EN
(73,1)
TK 55533-2-OD-EN 73
(74,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Standard Display
The Standard Display shows the box temperature and setpoint. The Standard Display or the
TemperatureWatch Display is shown when the unit is operating normally. All other menus are
accessed from the Standard Display.
• The box temperature is usually return air temperature, but can be discharge air temperature if
some features are enabled.
• The setpoint can be changed from the Standard Display using the SETPOINT soft key.
• The readings of the unit gauges and temperature sensors can be shown from the Standard
Display using the GAUGES and SENSORS soft keys unless these keys have been assigned
different functions from the Guarded Access > Main Menu.
• The Main Menu is accessed from the Standard Display using the MENU soft key.
• If a USB Flash Drive or a computer is connected to the unit via a USB Port, a USB Icon will
appear in the display.
N o t e : The USB Port is removed from the door in later units. A computer is connected directly
to the controller via the J11 Port (Cable P/N 204–2000). The USB icon will still appear in
the display.
TemperatureWatch™
™ Display
The TemperatureWatch Display shows the return air temperature and setpoint using large
numbers that allow unit conditions to be checked from a distance. If there are no alarms other
than Log Alarms present, the TemperatureWatch Display will appear 2½ minutes after the last key
is pressed. Press any soft key to return to the Standard Display.
Main Menu
The Main Menu consists of informational and operational functions intended for the unit
operator. The Main Menu is directly accessible from the Standard Display using the MENU Soft
Key. The Menu Soft Key is at the bottom right of the Standard Display.
Maintenance Menu
The Maintenance Menu consists of informational, operational, control, and diagnostic functions
used to help the service technician maintain and diagnose the unit. The Maintenance Menu is
indirectly accessible from the Main Menu.
Operator Features
The Precedent SR-4 control system features many special operator functions. These functions are
available from the Standard Display. A brief explanation of each menu is included here. For
complete operating details, refer to Section 4.
Standard Display
The Standard Display is the default display that appears if no other display function is selected.
The Standard Display shows the box temperature and setpoint. The box temperature is usually
return air temperature, but can be discharge air temperature if some features are enabled. The
Standard Display soft keys provide direct operator access to change the setpoint and to select the
Gauges Menu, Sensors Menu or Main Menu. The Gauges and Sensors Soft Keys may be
assigned different functions at the user’s discretion. If a USB Flash Drive or a computer is
connected to the unit via a USB Port, a USB Icon will appear in the display.
• Se t p o i n t C h a n g e
74 TK 55533-2-OD-EN
(75,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
The setpoint menu can be directly accessed from the Standard Display using the Setpoint
soft key.
• Gauges
The unit Gauges Menu can be directly accessed using the Gauges Soft Key from the
Standard Display. If desired this key can be assigned a different function from the
Guarded Access > Main Menu. If the Gauges Key is reassigned, the Gauges Menu is
available from the Main Menu. For a list of gauges available, refer to Section 4.
• Se n s o r s
The unit Sensors Menu can be directly accessed using the Sensors Soft Key from the
Standard Display. If desired this key can be assigned a different function from the
Guarded Access > Main Menu. If the Sensors Key is reassigned, the Sensors Menu is
available from the Main Menu. For a list of sensors available, refer to Section 4.
• Main Menu
The unit Main Menu can be directly accessed using a soft key from the Standard Display.
For a list of Main Menu functions, refer to Section 4.
TemperatureWatch™
™ Display
The TemperatureWatch display will not appear if any Check, Prevent, or Shutdown Alarms are
present or if the CargoWatch -15°C Alarm is active. If the TemperatureWatch display is active and
any of these alarm conditions occur, the display will return to the Standard Display. If a
Shutdown Alarm is present, the display will flash. This provides a quick method to check for units
that may have an alarm set.
If a USB Flash Drive or a computer is connected to the unit via a USB Port, a USB Icon will appear
in the display.
TK 55533-2-OD-EN 75
(76,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Main Menu
P r e c e d e n t S R - 4 Tr a i l e r S / T O p e r a t o r & M a i n M e n u - B A 2 0 & 7 A 2 5
55533-2-3-2
76 TK 55533-2-OD-EN
(77,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Pretrip
A Pretrip Test is used to confirm unit operation. This menu allows a Pretrip Test to be initiated by
the operator. If the test is started with the engine or motor off, a full test including the non-
running amp checks and the running performance tests are performed. If the test is started with
the engine or motor running, only the running tests are performed. Test results are reported as
PASS, CHECK or FAIL. For additional details, refer to Section 4.
Flash Drive
If a USB Flash Drive is connected to the Control Panel USB Flash Drive Port, this menu item
allows the operator to select the desired Flash Drive function.
I m p o rt a n t : The Flash Drive must be properly configured and the desired features must be
enabled using the ThermoServ™ Service Tool.
Using a properly configured and enabled flash drive, the following functions may be available:
• Download the ServiceWatch Data Logger
• Download the CargoWatch Data Logger
• Flash load Base Controller Software
• Flash load HMI Control Panel Software
• Send OptiSet Plus Files
• Retrieve OptiSet Plus Files
For Flash Drive details, refer to the ThermoServ Service Tool Help Menu.
Language
If more than one language is enabled, this menu item allows the operator to select a language
from a list of four languages at one time. All subsequent displays are shown in the selected
language. Any or all languages may be enabled. English is the default language. For additional
details, refer to Section 4.
Alarms
The Alarms display allows the operator to display any existing alarms. The operator can also
clear most alarms from this menu.
A list of Alarm Codes including diagnostic procedures for each code is presented in Section 5.
N o t e : Some alarms are clearable in Guarded Access only. Alarms with this feature will not
provide a soft key “Clear” function. Refer to Section 4 for additional details.
N o t e : Engine Control Unit faults can be cleared from the Main Menu > Clear All ECU Faults Menu.
The actual ECU Fault Codes can be viewed and cleared using the applicable engine
diagnostic tool. Refer to Section 7 for more information.
Gauges
The Gauges Menu allows the operator to display operating information such as coolant level and
temperature, engine RPM, battery amps, battery volts, and suction and discharge pressure. The I/
O selection under Gauges indicates the named outputs as either On or Off. Gauges can also be
viewed from other menus such as the Service Test Mode and Interface Board Test Mode displays.
For additional details, refer to Section 4.
N o t e : This menu contains the same information as the Standard Display Gauge Soft Key Menu.
TK 55533-2-OD-EN 77
(78,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Sensors
The Sensors Menu allows the operator to display the reading of all unit temperature sensors as
well as the calculated temperature differential. CargoWatch Data Logger sensors can also be
displayed. For additional details, refer to Section 4.
N o t e : This menu contains the same information as the Standard Display Sensors Soft Key Menu.
Data Logger
This menu allows the operator to send a Start of Trip marker to the ServiceWatch and
CargoWatch Data Loggers. It can also be used to print the contents of the CargoWatch Data
Logger.
The unit can also be programmed such that every time the setpoint is changed a Start of Trip
Marker is sent to the ServiceWatch and CargoWatch Data Loggers.
ServiceWatch and CargoWatch information can be downloaded and viewed by connecting a
computer loaded with the ThermoServ Service Tool software.
ServiceWatch and CargoWatch information can also be downloaded by connecting a properly
configured and enabled Universal Flash Drive to the USB Flash Drive Connector on the unit
Control Panel. The Flash Drive is then connected to a computer loaded with the ThermoServ
Service Tool software to save and view the information. For Flash Drive details, refer to the
ThermoServ Service Tool Help Menu.
Hourmeters
The Hourmeters Menu allows the operator to view the unit hourmeters that have the view feature
enabled in the Guarded Access menu. If the view feature for a particular hourmeter is not
enabled, that hourmeter cannot be viewed from the Main Menu. For additional details, refer to
Section 4.
N o t e : All active hourmeters are available for viewing in the Maintenance Menu.
Mode
The Mode Menu allows the operator to change the unit operating modes if allowed. Not all
modes may appear depending on the settings selected from the Guarded Access menu. For
additional details, refer to Section 4.
• Turn Off Cycle Sentry Mode/Turn On Cycle Sentry Mode (If Cycle Sentry Mode is turned Off
then the unit runs in Continuous Mode).
• Select temperature displays in either degrees Fahrenheit or degrees Celsius (if enabled).
• Allow Keypad Lockout to be selected (if enabled).
• Start Sleep Mode (if enabled).
• Open or close the optional Fresh Air Exchange vent (if feature is installed and enabled).
• Auto Keypad Lock Time and PIN Number.
78 TK 55533-2-OD-EN
(79,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Adjust Brightness
This menu allows the operator to adjust the HMI Control Panel display backlight intensity as
required by local conditions. If desired, the backlight can also be turned off. For additional details,
refer to Section 4.
View Time
This menu allows the operator to view the unit time and date. The time and date cannot be
changed from this menu. The time and date is loaded from the HMI Control Panel to the Base
Controller each time the unit is turned on. For additional details, refer to Section 4.
TK 55533-2-OD-EN 79
(80,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Maintenance Menu
P r e c e d e n t S R - 4 Tr a i l e r S / T M a i n t e n a n c e M e n u - B A 2 0 a n d 7 A 2 5
80 TK 55533-2-OD-EN
(81,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Software Revision
Display Software Rev
Controller Software Rev
Supervisor Software Revision
55533-2-3-4
TK 55533-2-OD-EN 81
(82,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Hourmeters
The Hourmeters Menu allows the technician to view all the active unit hourmeters, even if the
Main Menu view has been disabled. The Maintenance Menu Hourmeter Display also allows the
technician to reset the time on hourmeters with a programmed time limit.
Gauges
The Gauges Menu allows the technician to display operating information such as coolant level
and temperature, engine RPM, battery amps, battery volts, and suction and discharge pressure.
The I/O selection under Gauges indicates the named outputs as either On or Off. Some Gauges
can also be viewed from the Service Test Mode and Interface Board Test Mode displays.
N o t e : This menu contains the same information as the Standard Display Soft Key Menu and
Main Menu > Gauge Menu.
Sensors
The Sensors Menu allows the technician to display the reading of all unit temperature sensors as
well as the calculated temperature differential. CargoWatch Data Logger sensors can also be
displayed.
N o t e : This menu contains the same information as the Standard Display Soft Key Menu and
Main Menu > Gauge Menu.
Alarms
The Alarms Menu allows the technician to display any existing alarms. The technician can also
clear most alarms from this menu.
A complete list of Alarm Codes including diagnostic procedures for each code is presented in
Section 5.
N o t e : Some alarms are clearable in Guarded Access only. These alarms will not provide a Clear
Soft Key if displayed from the Main Menu or Maintenance Menu. Refer to Section 4 for
additional details.
82 TK 55533-2-OD-EN
(83,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Evacuation Test
The Evacuation Test Menu allows a full system evacuation to be performed. All normally closed
valves are opened to allow the entire system to be completely evacuated before charging with
refrigerant. The ETV will be fully opened. If the battery voltage falls below acceptable limits, the
operator is prompted to connect a battery charger to maintain sufficient battery voltage to hold
all necessary valves open during the procedure. If the voltage from the battery charger rises
above acceptable limits, the controller will be turned off to prevent damage to the electronics
and/or system components.
Software Revision
The Software Revision Menu displays the software revision of the HMI Control Panel software,
Base Controller software, and the Supervisor software.
Time Zone
The Time Zone Menu allows the time zone to be checked and set as required for the Eastern,
Central, Mountain or Pacific Time Zone as specified by the user.
TK 55533-2-OD-EN 83
(84,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
55533-2-3-5
84 TK 55533-2-OD-EN
(85,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
55533-2-3-6
TK 55533-2-OD-EN 85
(86,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
86 TK 55533-2-OD-EN
(87,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Temperature Units
Control Rev BA00 and later
Description The controller can be set to display temperatures in either degrees FAHRENHEIT or degrees
CELSIUS.
Pressure Units
Control Rev BA00 and later
Exceptions
Description The controller can be set to display system refrigerant pressures in PSIG, kPa, or BARS.
Description Standard restart alarms become permanent shutdown alarms after several attempts to start
and run. The CONTINUOUS feature is designed for rail applications where the unit runs
unattended or is inaccessible for service. It allows unlimited restart attempts to be made if the
following restart alarms occur:
• Alarm Code 10 High Discharge Pressure
• Alarm Code 18 High Engine Coolant Temp
• Alarm Code 63 Engine Stopped
• Alarm Code 82 High Compressor Temp
If restarts are disabled, the unit will shut down on the first alarm event. The following
differences exist between a Standard Restart and a Continuous Restart alarm:
• Standard Restart alarms force a permanent shutdown if the alarm occurs a pre-determined
number of times (usually 3). Continuous Restart alarms allow an unlimited number of
restarts for the four alarm codes listed above.
• Standard Restart alarms typically use a 15 minute timer before a restart is allowed.
Continuous Restart alarms use a 1-hour timer before a restart is allowed.
• With Continuous Restart alarms ETV Head Pressure Setpoint is lowered based on the alarm
type and number of occurrences.
TK 55533-2-OD-EN 87
(88,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu. The Setpoint High Limit setting
selected is used for all ranges.
Description Setpoint High Limit allows the upper setpoint limit to be set to a maximum of 90°F (32°C) in
one degree increments. The minimum setting is determined by the setting of Setpoint Low
Limit. If the driver attempts to select a setpoint higher than the Setpoint High Limit, the display
will show Setpoint Limit, indicating that the selected Setpoint High Limit has been reached.
Setting Setpoint High Limit and Setpoint Low Limit to the same temperature results in a single
setpoint temperature available.
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu. The Setpoint Low Limit setting
selected is used for all ranges.
Description Setpoint Low Limit allows the lower setpoint limit to be set to a minimum of -30°F (-34°C) in
one degree increments. The maximum setting is determined by the setting of Setpoint High
Limit. If the driver attempts to select a setpoint lower than the Setpoint Low Limit, the display
will show Setpoint Limit, indicating that the selected Setpoint Low Limit has been reached.
Setting Setpoint High Limit and Setpoint Low Limit to the same temperature results in a single
setpoint temperature available.
Setpoint temperatures lower than -25°F (-32°C) should only be used when absolutely required
by the load.
Fuel Saver II
Control Rev BA00 and later
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu.
Description If Fuel Saver II is ENABLED, and the box temperature changes a predetermined amount from
setpoint in Cycle Sentry mode operation, or if the box temperature indicates a need for high
speed in Continuous mode operation, the unit will first run in low speed. An 8-minute timer is
started and the control sensor air temperature is monitored. As long as the temperature falls
(in cool mode operation) or rises (in heat mode operation) a specified amount before the timer
expires, the 8-minute timer is reset and low speed operation continues. If the temperature has
not changed the pre-determined amount when the timer times out, high speed operation is
resumed if allowed. This provides fuel savings by delaying high speed operation, yet assures
that the temperature continues to fall or rise as required to reach setpoint.
If the unit switches to high speed from FS-II, the unit will run in high speed until setpoint is
reached. If FS-II is DISABLED, high speed cool and high speed heat are allowed with no delay.
The FS-II feature does not apply to modulation operation.
88 TK 55533-2-OD-EN
(89,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu.
Description This feature allows High Speed Pull Down for the selected range to be ENABLED or DISABLED. If
High Speed Pull Down is ENABLED, the unit will run in high speed on initial start until setpoint is
reached in both cool and heat mode. If High Speed Pull Down is DISABLED, the unit will switch
to low speed cool when the return air temperature is below low speed switch point value plus
setpoint.
Note: There is a two minute delay on initial startup before high speed operation is allowed.
If Fuel Saver II is ENABLED, there may be a delay before high speed operation is allowed.
This feature does not apply to modulation operation.
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu. The setting selected is used for
all ranges.
Description One set of general control specifications is used when operating in the Fresh range, and another
set of general operating specifications is used when operating in the Frozen range. This feature
allows the line between Fresh and Frozen ranges to be selected as either 15°F (-9°C) or 24°F
(-4°C). All setpoints less than or equal to this value will be treated as frozen ranges. All
setpoints greater than this value will be treated as Fresh ranges.
The Frozen setpoint range is from the limit of the Setpoint Limit Low setting to the Fresh Frozen
range setting. The Fresh setpoint range is from the limit of the Fresh Frozen range + 1 degree
to the setpoint high limit setting.
When programming OptiSet Plus, no range may include both Frozen and Fresh range setpoints.
This value is the high value of the last frozen range programmed. The next range programmed
will start at this value + 1 degree depending on the selection made above. Changing this
feature will reset all OptiSet Plus range values to default.
TK 55533-2-OD-EN 89
(90,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu. The optional door switch must
be installed.
Description This feature allows the Door Open action to be set. If this feature is set LOG ONLY the door
opening will be logged after 4 seconds but the unit will continue to run. Door openings are
logged in both the CargoWatch and ServiceWatch data loggers. The door switch must be open
or closed for 4 seconds before the event is logged to prevent false readings.
If this feature is set UNIT NULL, the base controller shuts the unit down and logs the door
opening 4 seconds after the door is opened. If the unit is in defrost when the door is opened, the
defrost cycle will be completed before the unit shuts down. If the Door Open Timeout feature
has been set for a door open time, the unit will restart and run if the time specified by Door
Open Timeout is exceeded. The unit will continue to run even if the door is still open. The event
is logged in both the CargoWatch and ServiceWatch data loggers.
If this feature is set UNIT NULL – NO ALARM, unit operation is the same as UNIT NULL above,
but Alarm Code 108 Door Open Timeout is not set.
Exceptions If OptiSet Plus is active the HMI Control Panel will display [Programmed in OptiSet Plus] and
this feature cannot be changed from the Guarded Access Menu. The optional door switch must
be installed. Only appears if the DOOR OPEN FORCES feature is set to UNIT NULL or UNIT NULL
– NO ALARM.
Description This feature allows the unit to restart if the door open time exceeds the set limit.
Door Open Timeout can be set to OFF or for a time limit from 1 to 4 hours, in 10-minute
increments. If set to OFF the unit will remain off until the door is closed. If the Door Open
Timeout feature has been set for a door open time, the unit will restart and run and Alarm Code
108 Door Open Timeout will be set as a Check Alarm if the time specified by Door Open Timeout
is exceeded. The unit will continue to run even if the door is still open. The event is logged in
both the CargoWatch and ServiceWatch data loggers.
Exceptions
Description If the feature is set ENABLED, the unit will enter Sleep Mode after a Pretrip Test. If the feature is
set DISABLED, the unit will not enter Sleep Mode after a Pretrip Test.
Rail Option
Control Rev BA00 and later
90 TK 55533-2-OD-EN
(91,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions The optional fuel level switch must be installed in order to use the Fuel Conserve Mode feature.
Description If the unit is a rail application, this feature is ENABLED. When the optional customer fuel level
switch closes (supplies chassis ground to the base controller fuel level input), the unit will enter
a Fuel Conserve Mode where the unit is forced to low speed operation only.
If the unit is not a rail application this feature should be DISABLED.
Important: If RAIL OPTION is ENABLED, the fuel level switch will cause the unit to enter a full
conserve mode only. The Low Fuel Shutdown Feature is not available if RAIL
OPTION is ENABLED.
Rail Alternate
Control Rev BA00 and later
Description This feature changes the alerts criteria, defrost allowed temperature and defrost termination
temperature. It should only be used when specified by the customer. If rail alternate is enabled
a defrost cycle is allowed with an evaporator coil temperature less than or equal to 55 °F (13°C)
and terminates at 70°F (21°C).
Description The Air Chute Detect feature is designed to detect a blocked or improperly installed trailer air
chute. Spare sensor 1 is located at the rear of the trailer and directly in the air flow at the end of
the chute. The temperature detected by this sensor is compared to the temperature detected
by the control discharge air temperature sensor. This feature functions only during cool mode
operation.
If this temperature differential exceeds a user defined number of degrees for a user defined
period of time, Alarm Code 46 CHECK AIR FLOW is generated as a check alarm. If the trailer is
equipped with a door switch and the feature is enabled, monitoring ceases when the door is
opened and is resumed 45 minutes after the door is closed. When the unit enters a defrost
cycle, monitoring ceases and is resumed 45 minutes after the defrost cycle terminates. Should
the control discharge temperature sensor or Spare sensor 1 fail the Air Chute Detect feature is
disabled.
Temperature Differential
Control Rev BA00 and later
Description This feature selects the temperature differential, from the front to the back of the trailer that
must be exceeded to cause an alarm to occur. The temperature differential is calculated using
the control discharge air sensor and spare sensor 1. This temperature differential must exist for
the time specified by TIME TO ALARM below in order to set Alarm Code 46 Check Air Flow.
TK 55533-2-OD-EN 91
(92,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Time to Alarm
Control Rev BA00 and later
Description This feature selects the time interval that must be exceeded to cause Alarm Code 46 CHECK
AIR FLOW to occur. This condition must exist with a temperature differential, in excess of that
specified by TEMPERATURE DIFFERENTIAL above, in order to set Alarm Code 46 Check Air Flow.
Description This feature determines if a door switch should interrupt the operation of the BLOCKED AIR
CHUTE DETECT feature. If set ENABLED, then monitoring ceases when the door is opened and
is resumed 45 minutes after the door is closed. If set DISABLED, monitoring is not interrupted
when a door opens.
Exceptions
Description This feature allows the head pressure setpoint to be adjusted. This pressure determines when
the base controller will enter a temporary operating mode to prevent unit shutdown. Do not
change this setting unless instructed to do so.
Exceptions
Description This feature allows the water temperature setpoint to be adjusted. This temperature
determines when the base controller will enter a temporary operating mode to prevent unit
shutdown. Do not change this setting unless instructed to do so.
92 TK 55533-2-OD-EN
(93,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions Does not appear unless rail is disabled and restarts are enabled.
Description This feature modifies the ability to repeatedly clear certain alarms from the Main menu or
Operators menu. If these alarms occur repeatedly, they may indicate a need for service to
prevent unit or product damage. These alarms are as follows:
• Alarm Code 23 Cooling Cycle Fault
• Alarm Code 24 Heating Cycle Fault
• Alarm Code 32 Refrigeration Capacity Low
• Alarm Code 82 High Comp Discharge Temp
Setting this feature to ENABLED will allow the above alarms to be cleared conventionally 2
times in a continuous 12 hour period. If any of these alarms are cleared more than 2 times in 12
hours, all subsequent occurrences can only be cleared from the Guarded Access Menu. This
helps ensure that the alarms receive the attention of service personnel. The 12 hour timer is
reset when any of the above alarms is cleared from the Guarded Access Menu. The 12 hour
timer is not reset with a unit or controller power-down.
Setting this feature DISABLED will allow the above alarms to be cleared conventionally an
unlimited number of times.
Remote Device
Control Rev BA00 and later
Description Setting this feature to ENABLED allows an external device, such as TracKing, to start and stop a
properly equipped unit. Setting this feature to DISABLED prevents this control.
Important: The Remote Device feature should be set DISABLED before working on the unit if
the unit is equipped with a device that allows it to be started and stopped from a
remote location.
Choices 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 BPS
Exceptions
Description This feature allows the default baud rate to be selected for the HMI Control Panel COM Port 1.
The setting of this feature should not be changed.
Choices 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 BPS
Exceptions
Description This feature allows the default baud rate to be selected for the HMI Control Panel COM Port 2.
COM Port 2 is used by the CargoWatch printer. If a customer has a mixed fleet with both SR-2/
SR-4 and µP-IV M/T controllers with DAS, the baud rate for COM 2 should be set to 2400. This
will allow printing from both the SR-2/SR-4 and µP-IV controllers without changing the printer
baud rate. The printer baud rate must be set to match the baud rate setting of the Com 2 Port.
TK 55533-2-OD-EN 93
(94,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Choices 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 BPS
Exceptions
Description This feature allows the default baud rate to be selected for the HMI Control Panel COM Port 3.
COM port 3 is currently used by R:COM or other Telematics devices. The setting of this feature
should not be changed.
Extended ServiceWatch™
™ Logging
Control Rev BA00 and later
Description If set ENABLED, this feature will cause all Multi-temperature zone mode changes to be logged
by the ServiceWatch Data Logger. If set DISABLED, zone mode changes will not be logged.
Exceptions
Description This feature changes the defrost allowed temperature and defrost termination temperature. It
should only be used when specified by the customer. If High Temperature Defrost is enabled a
defrost cycle is allowed with an evaporator coil temperature less than or equal to 55 °F (13°C)
and terminates at 70°F (21°C).
Important: Unlike the Rail Alternate feature, the Low Fuel Shutdown feature is available when
High Temperature Defrost is set ENABLED and a float or solid state fuel level
sensor is installed.
Description This feature determines if an over the air OptiSet Plus flash load requires authorization from the
HMI Control Panel. If this feature is set ENABLED, an authorization request will be shown on the
HMI and must be approved before the OptiSet Plus flash load can proceed. If this feature is set
DISABLED, no local authorization is required to perform an OptiSet Plus flash load.
94 TK 55533-2-OD-EN
(95,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Description This feature determines if an over the air flash load requires authorization from the HMI Control
Panel. If this feature is set ENABLED, an authorization request will be shown on the HMI and
must be approved before the flash load can proceed. If this feature is set DISABLED no local
authorization is required to perform a flash load.
ServiceWatch™
™ Logging Intervals
Control Rev BA00 and later
Exceptions
Description This feature allows the logging interval of the ServiceWatch Data Logger to be set from 1
minute to 4 hours.
TK 55533-2-OD-EN 95
(96,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description When enabled, Keypad Lockout allows the operator to lock the keypad to prevent tampering.
Pressing any soft key for 5 seconds will unlock the keypad.
Setting this feature Enabled adds the Keypad Lockout feature to the Mode Menu.
Setting this feature Disabled turns the Keypad Lockout feature off and removes the feature
from the Mode Menu.
Exceptions
Description When enabled, Sleep Mode allows the operator to place the unit in Sleep Mode from the Mode
Menu.
Setting this feature Enabled adds the Sleep Mode feature to the Mode Menu.
Setting this feature Disabled removes the Sleep Mode feature from the Mode Menu.
Description This feature allows the function of the 2nd HMI Control Panel Soft Key to be assigned as desired
by the end user. The Gauge function remains available in the Main Menu and Maintenance Menu
in the same manner as before. The optional selections work in the same manner as if they had
been selected from the Main Menu.
96 TK 55533-2-OD-EN
(97,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Description This feature allows the function of the 3rd HMI Control Panel Soft Key to be assigned as desired
by the end user. The Sensors function remains available in the Main Menu and Maintenance
Menu in the same manner as before. The optional selections work in the same manner as if they
had been selected from the Main Menu.
Exceptions
Description If ENABLED, this feature will automatically lock the HMI Keypad after a user selectable 3, 5 or
10 minute interval during which no HMI Key has been pressed. If this feature is DISABLED, the
HMI Keypad will not be locked.
Exceptions
Description If this feature is set NO CODE, a code is not required to unlock the keypad if it has been locked.
If a code from 1-99999 has been selected, this code must be entered in order to unlock the HMI
keypad. The code should be recorded for future use.
TK 55533-2-OD-EN 97
(98,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions If a time limit is set and exceeded then Alarm Code 132 will be set as a stored alarm.
Description Total Run Time Reminder #1 Hours is one of two hourmeters that track the total amount of time
the unit has run in both diesel and electric mode. If a time limit is set and exceeded then Alarm
Code 132 will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
98 TK 55533-2-OD-EN
(99,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions If a time limit is set and exceeded then Alarm Code 133 will be set as a stored alarm.
Description Total Run Time Reminder #2 Hours is one of two hourmeters that track the total amount of time
the unit has run in both diesel and electric mode. If a time limit is set and exceeded then Alarm
Code 133 will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
Exceptions If a time limit is set and exceeded then Alarm Code 134 will be set as a stored alarm.
Description Controller Power On Hours is the total amount of time the controller has been turned on. If a
time limit is set and exceeded then Alarm Code 134 will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
Exceptions If a time limit is set and exceeded then Alarm Code 64 will be set as a stored alarm.
Description Controller Power On Hours is the total amount of time since the last Pretrip Test was performed.
If a time limit is set and exceeded then Alarm Code 64 will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
Exceptions If a time limit is set and exceeded then Alarm Code 128 will be set as a stored alarm.
Description Engine Run Time Reminder #1 Hours is one of two hourmeters that track the total amount of
time the unit has run in diesel mode. If a time limit is set and exceeded then Alarm Code 128
will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
TK 55533-2-OD-EN 99
(100,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions If a time limit is set and exceeded then Alarm Code 129 will be set as a stored alarm.
Description Engine Run Time Reminder #2 Hours is one of two hourmeters that track the total amount of
time the unit has run in diesel mode. If a time limit is set and exceeded then Alarm Code 129
will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
Exceptions If a time limit is set and exceeded then Alarm Code 130 will be set as a stored alarm. Only
appears if the unit is configured as being equipped with optional electric standby.
Description Electric Run Time Reminder #1 Hours is one of two hourmeters that track the total amount of
time the unit has run in electric mode. If a time limit is set and exceeded then Alarm Code 130
will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
Exceptions If a time limit is set and exceeded then Alarm Code 131 will be set as a stored alarm. Only
appears if the unit is configured as being equipped with optional electric standby.
Description Electric Run Time Reminder #2 Hours is one of two hourmeters that track the total amount of
time the unit has run in electric mode. If a time limit is set and exceeded then Alarm Code 131
will be set as a stored alarm.
This feature sets the meter limits for this programmable hourmeter. The default setting is OFF.
Time limits start at 100 hours and can be decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
100 TK 55533-2-OD-EN
(101,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Total Hours
Control Rev BA00 and later
Exceptions
Description The setting of this feature determines if the Total Hours hourmeter can be viewed from the Main
Menu. If the hourmeter is Enabled it can be viewed from the Main Menu. If it is Disabled it
cannot be viewed from the Main Menu but is visible from the Maintenance Menu.
Exceptions Only appears if the unit is configured as being equipped with optional electric standby.
Description The setting of this feature determines if the Total Run Time Hours hourmeter can be viewed
from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main Menu. If it is
Disabled it cannot be viewed from the Main Menu but is visible from the Maintenance Menu.
Engine Hours
Control Rev BA00 and later
Exceptions
Description The setting of this feature determines if the Engine Hours hourmeter can be viewed from the
Main Menu. If the hourmeter is Enabled it can be viewed from the Main Menu. If it is Disabled it
cannot be viewed from the Main Menu but is visible from the Maintenance Menu.
TK 55533-2-OD-EN 101
(102,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions Only appears if the unit is configured as being equipped with optional electric standby.
Description The setting of this feature determines if the Electric Run Hours hourmeter can be viewed from
the Main Menu. If the hourmeter is Enabled it can be viewed from the Main Menu. If it is
Disabled it cannot be viewed from the Main Menu but is visible from the Maintenance Menu.
Exceptions
Description The setting of this feature determines if the Total Run Time Reminder # 1 Hours hourmeter can
be viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main
Menu. If it is Disabled it cannot be viewed from the Main Menu but is visible from the
Maintenance Menu.
Exceptions
Description The setting of this feature determines if the Total Run Time Reminder # 2 Hours hourmeter can
be viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main
Menu. If it is Disabled it cannot be viewed from the Main Menu but is visible from the
Maintenance Menu.
Exceptions
Description The setting of this feature determines if the Controller Power On Hours hourmeter can be
viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main Menu.
If it is Disabled it cannot be viewed from the Main Menu but is visible from the Maintenance
Menu.
102 TK 55533-2-OD-EN
(103,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description The setting of this feature determines if the Pretrip Reminder Hours hourmeter can be viewed
from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main Menu. If it is
Disabled it cannot be viewed from the Main Menu but is visible from the Maintenance Menu.
Exceptions
Description The setting of this feature determines if the Engine Run Time Reminder # 1 Hours hourmeter
can be viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main
Menu. If it is Disabled it cannot be viewed from the Main Menu but is visible from the
Maintenance Menu.
Exceptions
Description The setting of this feature determines if the Engine Run Time Reminder # 1 Hours hourmeter
can be viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main
Menu. If it is Disabled it cannot be viewed from the Main Menu but is visible from the
Maintenance Menu.
Exceptions Only appears if the unit is configured as being equipped with optional electric standby.
Description The setting of this feature determines if the Electric Run Time Reminder # 1 Hours hourmeter
can be viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main
Menu. If it is Disabled it cannot be viewed from the Main Menu but is visible from the
Maintenance Menu.
Exceptions Only appears if the unit is configured as being equipped with optional electric standby.
Description The setting of this feature determines if the Electric Run Time Reminder # 2 Hours hourmeter
can be viewed from the Main Menu. If the hourmeter is Enabled it can be viewed from the Main
Menu. If it is Disabled it cannot be viewed from the Main Menu but is visible from the
Maintenance Menu.
TK 55533-2-OD-EN 103
(104,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description If this feature is set Enabled, prompts appear to set a Service Due Date (Date / Month / Year).
When this date is reached, Alarm Code 128 Service Due is set as a stored alarm.
Alarm Code 128 Service Due can only be cleared from the Guarded Access Menu. When Alarm
Code 128 Service Due is cleared, the Service Due Date feature is reset to Disabled. The feature
can again be set Enabled and a new Service Due Date selected.
Choices 1L thru 9H
104 TK 55533-2-OD-EN
(105,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Factory Set 5H
Description This feature is used to set the sensor grade for the Control Return Air Sensor.
The default setting for a new base controller or after a ServiceWatch base controller cold start is
5H. This serves as a warning that the sensor grade is not set. The default grade of 5H is not a
valid grade and will not be printed on any sensor. If a sensor grade for a return air or discharge
air sensor is set to grade 5H, the alarm code for that sensor and Alarm Code 92 Sensor Grade
Not Set will be set. Alarm Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation, the grades must be properly set to match the actual sensor grades
to prevent nuisance alarm codes. Exercise care to properly identify the sensor grades. The best
way to positively identify the sensor grade is by physically checking the sensor grade printed on
each graded sensor.
The harness for the Control Return Air Sensor is further identified by one yellow cable tie.
Choices 1L thru 9H
Factory Set 5H
Description This feature is used to set the sensor grade for the Control Discharge Air Sensor.
The default setting for a new base controller or after a ServiceWatch base controller cold start is
5H. This serves as a warning that the sensor grade is not set. The default grade of 5H is not a
valid grade and will not be printed on any sensor. If a sensor grade for a return air or discharge
air sensor is set to grade 5H, the alarm code for that sensor and Alarm Code 92 Sensor Grade
Not Set will occur. Alarm Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation, the grades must be properly set to match the actual sensor grades
to prevent nuisance alarm codes. Exercise care to properly identify the sensor grades. The best
way to positively identify the sensor grade is by physically checking the sensor grade printed on
each graded sensor.
The harness for the Control Discharge Air Sensor is further identified by one red cable tie.
Choices 1L thru 9H
Factory Set 5H
Description This feature is used to set the sensor grade for the Display Return Air Sensor.
The default setting for a new base controller or after a ServiceWatch base controller cold start is
5H. This serves as a warning that the sensor grade is not set. The default grade of 5H is not a
valid grade and will not be printed on any sensor. If a sensor grade for a return air or discharge
air sensor is set to grade 5H, the alarm code for that sensor and Alarm Code 92 Sensor Grade
Not Set will occur. Alarm Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation, the grades must be properly set to match the actual sensor grades
to prevent nuisance alarm codes. Exercise care to properly identify the sensor grades. The best
way to positively identify the sensor grade is by physically checking the sensor grade printed on
each graded sensor.
The harness for the Display Return Air Sensor is further identified by two yellow cable ties.
Choices 1L thru 9H
TK 55533-2-OD-EN 105
(106,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Factory Set 5H
Description This feature is used to set the sensor grade for the Display Discharge Air Sensor.
The default setting for a new base controller or after a ServiceWatch base controller cold start is
5H. This serves as a warning that the sensor grade is not set. The default grade of 5H is not a
valid grade and will not be printed on any sensor. If a sensor grade for a return air or discharge
air sensor is set to grade 5H, the alarm code for that sensor and Alarm Code 92 Sensor Grade
Not Set will occur. Alarm Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation, the grades must be properly set to match the actual sensor grades
to prevent nuisance alarm codes. Exercise care to properly identify the sensor grades. The best
way to positively identify the sensor grade is by physically checking the sensor grade printed on
each graded sensor.
The harness for the Display Discharge Air Sensor is further identified by two red cable ties.
Choices 1L thru 9H
Factory Set 5H
Exceptions Unit Type = Trailer Single Temperature. If the optional Spare 1 Sensor is not present this
feature need not be set.
Description This feature is used to set the sensor grade for the Spare 1 Sensor.
The default setting for a new base controller or after a ServiceWatch base controller cold start is
5H. This serves as a warning that the sensor grade is not set. The default grade of 5H is not a
valid grade and will not be printed on any sensor. If a sensor grade for a return air or discharge
air sensor is set to grade 5H, the alarm code for that sensor and Alarm Code 92 Sensor Grade
Not Set will occur. Alarm Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation, the grades must be properly set to match the actual sensor grades
to prevent nuisance alarm codes. Exercise care to properly identify the sensor grades. The best
way to positively identify the sensor grade is by physically checking the sensor grade printed on
each graded sensor.
Note: Alarm Code 92 Sensor Grades Not Set is not active with spare sensors. However, if the
sensor is in used the sensor grade should be set to provide maximum sensor accuracy.
Choices 2A to 8A in 1A increments
Factory Set 5A
Exceptions Early S-600 units with the Engine Relay/Fuse Board (prior to April 2014) should be set to 8A if
equipped with an alternator. On these units, the ECU is powered by the 2 circuit and draws
approximately 3 amps. The ammeter shunt monitors the 2 circuit and detects this extra 3 amp
load. Therefore, the Cycle Sentry Amps Level should be set to 8A to allow for the extra 3 amp
load.
On later S-600 units without the Engine Relay/Fuse Board (April 2014 and later), the ECU is
powered by the 2A circuit, which is not monitored by the ammeter shunt. Therefore, the Cycle
Sentry Amps Level should be set to 5A.
Description When operating in Cycle Sentry or Sleep mode, the unit will automatically run to charge the
battery until the charging current falls below this set limit. This occurs even if cooling, heating,
or defrosting is not required.
106 TK 55533-2-OD-EN
(107,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description When operating in Cycle Sentry or Sleep mode the controller will monitor battery voltage and
restart the unit to charge the battery, if the battery voltage falls below this set limit. This occurs
even if cooling, heating or defrosting is not required.
Exceptions
Description If Check Battery Condition Alarm is ENABLED, Alarm Code 159 Check Battery Condition will be
set if indications exist that the battery may be about to fail. If this feature is set DISABLED, the
battery condition check will be disabled and Alarm Code 159 Check Battery Condition will not be
set.
Choices 2, 4, 6, 8 or 12 Hours
Exceptions
Description This feature selects the timed interval between defrost cycles with Fresh range setpoints when
the temperature is in range.
Choices 2, 4, 6, 8 or 12 Hours
TK 55533-2-OD-EN 107
(108,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description This feature selects the timed interval between defrost cycles with Fresh range setpoints when
the temperature is not in range.
Choices 2, 4, 6, 8 or 12 Hours
Exceptions
Description This feature selects the timed interval between defrost cycles with Frozen range setpoints when
the temperature is in range.
Choices 2, 4, 6, 8 or 12 Hours
Exceptions
Description This feature selects the timed interval between defrost cycles with Frozen range setpoints when
the temperature is not in range.
Choices 30 or 45 Minutes
Exceptions
Description This feature selects the maximum time the unit can remain in a defrost cycle. A defrost cycle
normally terminates when the evaporator coil temperature reaches 58°F (14°C). If Rail
Alternate is enabled a defrost cycle terminates at 70°F (21°C). If the evaporator temperature
does not reach this temperature, the defrost cycle will terminate after the elapsed time selected
here.
Enable Language
Control Rev BA00 and later
108 TK 55533-2-OD-EN
(109,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description This feature allows any or all of the included languages to be enabled. Only enabled languages
will appear in the Operators Language Menu. All languages other than English are factory set as
Disabled. If only one language is enabled then the Language Selection Menu will not appear on
startup or in the Main Menu.
OptiSet™
™ Plus Menu
The OptiSet Plus Temperature Management System allows up to 64 different Named and/or
Numeric temperature profiles to be defined and tailored for maximum operating efficiency as
determined by customer load requirements. The term “OptiSet Plus” refers to both the
programmable temperature profiles and the unit operating features that can be tailored using
OptiSet Plus.
Due to the large number of features available in OptiSet Plus, the OptiSet Plus features can no
longer be viewed or changed from the Guarded Access Menu. The only OptiSet Plus features
available from the Guarded Access Menu are OptiSet Plus Reset and Temperature Profile
Selection.
• OptiSet Plus Reset is used to reset all OptiSet Plus features to the factory default settings.
• Temperature Profile Selection is used to determine what temperature profiles are available
for use by the driver.
For details of OptiSet Plus Reset and Temperature Profile Selection, refer to the following tables.
I m p o rt a n t : All other OptiSet Plus Features are set using OptiSet Plus. They cannot be viewed or
changed from the Guarded Access Menu. OptiSet Plus and the ThermoServ™
Service Tool are required for use with the SR-4 Control System to tailor unit
performance to customer requirements.
For additional details, refer to the ThermoServ Service Tool Help Menu in OptiSet Plus.
These two features are available from the Guarded Access OptiSet Plus Menu:
Exceptions Only available if OptiSet Plus features have been previously set using OptiSet Plus.
Description If any OptiSet Plus features have been previously set using OptiSet Plus, an OptiSet Reset is
provided at the beginning of the OptiSet Plus menu to return all settings to the default values. If
this OptiSet Reset feature is used, all OptiSet Plus settings are returned to factory defaults.
TK 55533-2-OD-EN 109
(110,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description This feature determines what profiles are available to the driver.
If NUMERIC SETPOINT ONLY is selected, only numeric setpoints such as 35°F or -10°F are
available to the driver.
If NAMED PRODUCT ONLY is selected, only the named products such as Potatoes or Squash
enabled during OptiSet Plus setup are available to the driver.
If NAMED PROD & NUMERIC SP is selected, both named products and numeric setpoints are
available to the driver.
110 TK 55533-2-OD-EN
(111,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
55533-2-3-9
TK 55533-2-OD-EN 111
(112,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Description This feature allows the desired logging interval to be set for all enabled sensors and digital
inputs.
Choices ON or OFF
Exceptions
Description This feature allows the desired sensors to be turned On to be logged. If the sensor is turned on
then additional features may be selected for that sensor.
Exceptions
112 TK 55533-2-OD-EN
(113,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Description This feature allows the desired sensor name to be specified. These names appear only on
handheld printer reports. This aids in reading and understanding data logger printer reports.
Choices ON or OFF
Factory Set ON
Exceptions
Description This feature allows the Out of Range Checking feature to be turned on or off. If Out of Range
Checking is turned on, an alarm will be set if the temperature, as sensed by the specified
sensor, is above or below setpoint by more than the number of degrees determined by the
setting of LOW and HIGH programmable features. The out of range condition must exist for 1
hour before the alarm is set. A visual notification will be provided to the driver on the standard
TK 55533-2-OD-EN 113
(114,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Low
Micro Rev BA00 and later
Exceptions
Description This feature allows the low limit for Out of Range Checking to be set.
High
Micro Rev BA00 and later
Exceptions
Description This feature allows the high limit for Out of Range Checking to be set.
Italian Option
Micro Rev BA00 and later
Choices ON or OFF
Description If this feature is turned ON, the driver is presented a visual “Out of Range Limit” notification and
flashes the backlight if the box temperature rises above -15°C. The visual notification appears
on the Standard Display as shown below.
55533-2-3-7
Sensor Averaging
Micro Rev BA00 and later
Choices ON or OFF
114 TK 55533-2-OD-EN
(115,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description If this feature is turned OFF, the temperature logged will be the actual instantaneous sensor
reading at the time of log. If this feature is turned ON, the sensor is read once each minute. The
sensor readings are averaged dependant on the setting of the Logging Interval feature selected
above.
For example, if the Logging Interval is 15 minutes the previous 15 sensor readings are
averaged and logged instead of the actual instantaneous value. If the Logging Interval is set for
10 minutes, the previous 10 sensor readings are averaged and logged.
Factory Set
Exceptions
Description This feature allows the digital input to be programmed and selected.
Choices ON or OFF
Exceptions
Description This feature allows the desired digital inputs to be logged or ignored.
Exceptions
TK 55533-2-OD-EN 115
(116,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Description This feature allows the desired input name to be specified. This aids in reading and
understanding data logger downloads.
Countdown Timer
Micro Rev BA00 and later
Exceptions The Countdown Timer only affects the CargoWatch Data Logger.
Description The Countdown Mode feature will keep the HMI Control Panel powered up for a user specified
time period after the unit is turned off. Under these conditions the display and backlight are
turned off to conserve unit battery power.
Important: The four Hard Keys will remain illuminated when the unit is in Countdown Mode.
This is normal operation.
55533-2-3-8
The CargoWatch data logger will continue to record data according to the current CargoWatch
interval settings until the user specified time period expires. This allows data to be recorded
during an interval where the unit is turned off.
The programmable time intervals are OFF or from 1 Hour to 96 Hours. The default setting for
Countdown Mode is OFF.
116 TK 55533-2-OD-EN
(117,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions The Countdown Timer only affects the CargoWatch Data Logger.
Description The Conservative Mode can be utilized by the user after the Countdown Mode interval above
has expired. When the Countdown Mode has expired, Conservative Mode (if programmed)
allows the HMI Control Panel to be temporarily powered up according to the current
CargoWatch interval settings to log an additional number of CargoWatch data logs. The HMI
Control Panel will be powered up for approximately 30 seconds to perform each data log, and
will then turn back off.
The possible number of additional Conservative Mode CargoWatch data logs is from 1 Log to
400 Logs. The default setting for Conservative Mode is OFF.
SOT on Setpoint
Micro Rev BA13 and earlier
Exceptions
Description If this feature is set ENABLED, a Start of Trip is sent to the ServiceWatch and CargoWatch Data
Loggers after any setpoint change. If this feature is set DISABLED, a Start of Trip is not sent.
SOT at Midnight
Micro Rev BA13 and earlier
Exceptions
Description If this feature is set ENABLED, a Start of Trip is sent to the ServiceWatch and CargoWatch Data
Loggers after any setpoint change. If this feature is set DISABLED, a Start of Trip is not sent.
Unit Model
Control Rev BA00 and later
Factory Set To match unit as built. A Base Controller cold start will default this feature to S-600.
Exceptions
Description This feature allows the Unit Model to be selected. Set as appropriate for the unit.
TK 55533-2-OD-EN 117
(118,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Choices YES or NO
Factory Set To match unit as built. A Base Controller cold start will default this feature to NO.
Exceptions
Description If the unit was built as a High Capacity unit this setting must be set to YES. If the unit was not
built as a High Capacity unit this setting must be set to NO.
Important: Improper setting of this feature may cause Alarm Code 33 Check Engine RPM to
be set during a Pretrip Test.
Engine Type
Control Rev BA00 and later
Exceptions
Description This feature allows the engine type to be selected. Set as appropriate for the unit.
Compressor Type
Control Rev BA00 and later
Choices Recip
Exceptions
Description This feature allows the compressor type to be selected. Set as appropriate for the unit.
ETV Configured
Control Rev BA00 and later
Choices YES
Factory Set To match unit as built. A base controller cold start will default this feature to YES.
Exceptions
Description If the unit was built with an Electronic Throttling Valve (ETV) this feature must be set YES.
Battery Charger
Control Rev BA00 and later
Factory Set To match unit as built. A base controller cold start will default this feature to NONE.
118 TK 55533-2-OD-EN
(119,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description If the unit is equipped with an alternator, this feature should be set to NONE. Single
Temperature applications use a 30 Amp Battery Charger. Multi-Temperature applications use a
120 Amp Battery Charger.
Choices YES or NO
Factory Set To match unit as built. A base controller cold start will default this feature to YES.
Exceptions This setting will automatically be forced from “NO” to “YES” if the unit detects that electric
supply power is connected to the unit.
Description This feature specifies if the unit is equipped with optional Smart Power™ Electric Standby. If the
unit is equipped with Electric Standby, this feature should be set YES. If the unit is not equipped
with Electric Standby, this feature should be set NO.
Choices 14 HP or optional 24 HP
Factory Set As built. A Base Controller cold start will default this feature to 14 HP.
Exceptions
Description This feature specifies which motor is used on units equipped with the optional Smart Power
Electric Standby. A 14 HP motor is standard on units equipped with the Electric Standby option.
The 24 HP motor is an available option.
Choices YES or NO
Factory Set To match unit as built. A Base Controller cold start will default this feature to YES.
Exceptions
Description This feature specifies if the unit is equipped with the Electric Heat option. If the unit is equipped
with Electric Heat, this feature should be set YES. If the unit is not equipped with Electric Heat,
this feature should be set NO.
On multi-temp applications electric heat is applicable to Zone 1 host evaporators only.
Choices YES or NO
Factory Set NO
TK 55533-2-OD-EN 119
(120,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description This feature allows the Auto Switch from Diesel to Electric feature to be enabled or disabled. If
this feature is set YES, the unit will switch automatically to electric mode when standby power is
connected. If the feature is set NO, the operator must manually switch the unit to electric mode
using the HMI Control Panel Mode Menu or by following the HMI Control Panel prompts when
standby power is connected.
Choices YES or NO
Factory Set NO
Exceptions
Description This feature allows the Auto Switch from Electric to Diesel feature to be enabled or disabled. If
this feature is set YES, the unit will switch automatically to diesel mode when standby power is
disconnected or fails. If the feature is set NO, the operator must manually switch the unit to
diesel mode using the HMI Control Panel Mode Menu or by following the HMI Control Panel
prompts when standby power is disconnected or fails.
Note: Auto-switch from electric to diesel is not recommended when the unit is running in
electric mode indoors or when below deck on a ferry where engine operation is strictly
prohibited.
Humidity Sensor
Control Rev BA00 and later
Exceptions
Description If the optional humidity sensor is installed, this feature must be set ENABLED. If the humidity
sensor is not installed this feature must be set DISABLED.
Exceptions
Description This feature is used to select the type of fuel level sensor installed. If no fuel level sensor is
installed, this feature should be set to NONE.
120 TK 55533-2-OD-EN
(121,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Exceptions
Description This feature specifies if the unit is equipped with the optional flush mount Rear Remote Control
Panel. If the unit is equipped with the flush mount Rear Remote Control Panel this feature
should be set to COM 2 and the flush mount Rear Remote Control Panel should be connected to
the COM2 port on the interface board. If the unit is not equipped with a flush mount Rear
Remote Control Panel, this feature should be set NONE.
Refer to Section 4 for more information on using the Rear Remote Control Panel.
Exceptions Only appears if Rear Remote Control Panel is set for COM 2
Description If the Action is set to STAND BY, the unit will power up when the Rear Remote Control Panel ON
key is pressed. The setpoints can be changed from the Rear Remote Control Panel but the unit
will not start and run. The unit must be started from the HMI Control Panel on the unit. Pressing
the Rear Remote Control Panel OFF key will power down the control system. All Rear Remote
Control Panel functions are present except the engine will not start and a Manual Defrost Cycle
or Pretrip Test cannot be initiated.
If the Action is set to RUN the unit will automatically start and run when the Rear Remote
Control Panel ON key is pressed. Pressing the Rear Remote Control Panel OFF key will power
down the control system. All Rear Remote Control Panel functions are present.
Refer to Section 4 for more information on using the Rear Remote Control Panel.
Exceptions
Description This feature selects the communications port on the SR-4 Base Controller/Interface Board that
will be used by a third party control device such as satellite communications. If the unit is not
equipped with a third party device, this feature should be set NONE.
Choices NONE
IBOX
IBOX+CELL+GPS
IBOX+WPAN
IBOX+CELL+GPS+WPAN
WIFI+GPS+WPAN
IBOX+WIFI+GPS+WPAN
IBOX+CELL+GPS+WIFI+WPAN
Exceptions
Description The REB Type Configured feature should be set to match the options installed on the unit.
TK 55533-2-OD-EN 121
(122,1)
Se c t i o n 3 - So ft wa r e D e s c r i p t i o n
Choices YES or NO
Factory Set NO
Exceptions The Fresh Air Exchange Feature must be installed on the unit.
Description The Fresh Air Exchange option allows fresh outside air to be drawn into the trailer and the
interior air to be exhausted by opening the Fresh Air Exchange doors. This feature is beneficial
when hauling loads that release gas as they ripen, such as potatoes. The Fresh Air Exchange
feature should be used exactly as specified by the customer.
The Fresh Air Exchange feature is only available with setpoints above 32°F (0°C). The feature is
disabled with setpoints of 32°F (0°C) and below.
A solenoid is used to open and close the Fresh Air Exchange Door. Note that the Fresh Air
Exchange door will only be open when the unit engine is running, as it is held in the open
position by the Fresh Air Exchange Solenoid. The door will close when the engine shuts down to
preserve unit battery life. The setting of the Fresh Air Exchange door will survive power off /
power on cycles – if the door is set to “Open” by the operator it will continue to open any time
the engine is running until it is set to “Close” by the operator.
If Fresh Air Exchange is set YES, the Fresh Air Exchange Open / Close feature will be shown in
the Mode Menu. If Fresh Air Exchange is set NO, the Fresh Air Exchange Open / Close feature
will not appear in the Mode Menu.
122 TK 55533-2-OD-EN
(123,1)
Section 4 - Operation
SR-4 HMI Control Panel
WA R N I N G
Risk of Injury!
T h e u n i t c a n s t a rt a t a ny t i m e w i t h o u t w a r n i n g . P r e s s t h e O F F k e y o n t h e H M I c o n t r o l
p a n e l a n d p l a c e t h e m i c r o p r o c e s s o r O n / O f f s w i t ch i n t h e O f f p o s i t i o n b e f o r e i n s p e c t i n g o r
s e r v i c i n g a n y p a rt o f t h e u n i t .
Use the HMI control panel to operate the unit. Refer to the Precedent S-600 and S-700 Operator’s
Manual (TK 55538-2-OP) and the SR-4 Trailer Single Temperature Diagnostic Manual (TK 55533-2-
OD) for more information.
The HMI control panel has a display and eight touch sensitive keys. The display is capable of
showing both text and graphics. The four keys on the left and right sides of the display are
“hard” (dedicated) keys. The four keys under the display are “soft” keys. The function of soft
keys change depending on the operation being performed. If a soft key is active, its function will
be shown in the display directly above the key.
3 THERMO KING
1 ON
°F 4
2 OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU 5
SR4
Smart Reefer 4
AMA1422
6
1. On Key (Hard Key)
3. Display
6. Soft Keys
Display Icons
Display symbols or icons are used to present additional unit information.
TK 55533-2-OD-EN 123
(124,1)
Sec t i o n 4 - Op er at i o n
Down-Pointing Arrow: (At the left side of the display) Shows the unit is cooling. If the arrow
were pointing upward the unit would be heating.
CYCLE SENTRY/Continuous Mode Key: The unit is running in Cycle Sentry Mode as shown by
the Cycle Sentry Icon in the upper right corner of the display. If the Cycle Sentry icon is not
present, the unit is running in Continuous Mode.
USB: The USB Icon in the upper left corner of the display will appear when a USB device is
connected to any of the USB Ports on the Unit Control Panel or inside the unit control box.
Hard Keys
The keys on either side of the display are dedicated or hard keys. Their function always remains
the same.
On Key: Used to turn the unit on. First the display will briefly show the Thermo King Logo and then
the statement “Configuring System - Please Wait”. When the power-up sequence is complete the
display shows the Standard Display of box temperature and setpoint.
ON
Off Key: Used to turn the unit off. First, the display will briefly show “System is Powering Down -
Please Wait. Press On to Resume” and then “Off” will appear momentarily. When the power-down
sequence is complete the display will be blank. For more information see “Turning the Unit On and
Off” later in this section.
OFF
CYCLE SENTRY: Used to select Cycle Sentry Mode or Continuous Mode operation if allowed by
OptiSet Plus. For more information see “Selecting Cycle Sentry or Continuous Mode” later in this
section.
Soft Keys
The four soft keys under the display are multi-purpose keys. Their function changes depending on
the operation being performed. If a soft key is active the key function is shown in the display
directly above the key. The keys are numbered from left to right, with Key 1 on the far left and Key
4 on the far right.
• MENU • CLEAR • NO
• + OR — • GAUGES • EXIT
124 TK 55533-2-OD-EN
(125,1)
Sec t i o n 4 - Op er a ti o n
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1434
The functions of these two keys can be changed as required for customer convenience. The
functions of these two soft keys on the Standard Display can be re-assigned to any of the
following functions using the Guarded Access > Main Menu Configuration menu:
The GAUGES and SENSORS functions are always available from the Maintenance Menu.
In the example shown (Figure 23, p. 125), the soft key functions from the Standard Display have
been changed to PRETRIP and SOT (Start of Trip marker). The GAUGES and SENSORS functions
are always available from the Maintenance Menu.
Figure 23. PRETRIP and SOT
ON
°F
OFF
SET
POINT
35
PRETRIP
.8
SOT
35
MENU
AMA1435
Display Heater
The HMI Control Panel is equipped with a display heater. This heater is needed to make the
display visible in very cold ambient temperatures.
The HMI has its own internal temperature sensor for the display heater. The heater is energized
when the unit is turned on and the ambient temperature is below 29.4°F (-2°C). The heater turns
off when the temperature sensed by the internal sensor rises above 37.4°F (+3°C). The heater
draws from 1.4 to 1.7 amps when energized.
The colder the ambient temperature, the longer it will take for the heater to make the display
visible on a cold startup. It may take 10-15 seconds for the display to appear with extremely cold
temperatures.
Turning Unit On
The unit is turned on by pressing the ON Key (Figure 24, p. 126) and off by pressing the OFF Key.
When the On Key is pressed the display briefly shows the THERMO KING Logo as the display
initializes.
TK 55533-2-OD-EN 125
(126,1)
Sec t i o n 4 - Op er at i o n
I m p o rt a n t : The ON Key must be held down until the Thermo King Logo appears. If the ON Key is
not held down long enough (approximately ½ second), the display may flicker but the
unit will not start up. If this occurs, hold the ON Key down until the Thermo King logo
appears.
N o t e : With extremely cold ambient temperatures, it may take up to 15 seconds for the display to
appear on initial startup.
Figure 24. ON Key
ON
OFF
AMA1436
The startup screen (Figure 25, p. 126) appears while communications are established and the
unit prepares for operation.
Figure 25. Startup Screen
ON CONFIGURING SYSTEM
PLEASE W AIT
OFF
AMA1437
ON
FLASH DRIVE
OFF
AMA1438
The FLASH DRIVE DETECTED and the Flash Drive Menu will appear on the display (Figure 27, p.
126). The display will be shown for about 30 seconds and then the Standard Display will appear.
To go to the Standard Display, immediately press the EXIT Soft Key.
126 TK 55533-2-OD-EN
(127,1)
Sec t i o n 4 - Op er a ti o n
ON
FLASH DRIVE DETECTED
AMA1439
I m p o rt a n t : The engine start is not delayed by the Flash Drive Menu shown above. The engine
start prompt will appear and the engine will start. After the engine is started the
display will return to the Flash Drive Menu or the Standard Display.
If a properly configured USB Flash Drive is connected to the USB Flash Drive connector, this
feature allows the operator to select the desired Flash Drive function. If enabled when the Flash
Drive was configured, the following functions may be available:
• DOWNLOAD
– Download the ServiceWatch Data Logger
– Download the CargoWatch Data Logger
• FLASHLOAD
– Flash load Base Controller Software
– Flash load HMI Control Panel Software
• OPTISET PLUS
– SEND
• Send OptiSet Plus files
– RETRIEVE
• Retrieve OptiSet Plus files
The Flash Drive is also available from the Main Menu.
The Flash Drive Menu will time out about 30 seconds after the engine starts. When the Flash
Drive Menu times out, the Standard Display will appear. To go to the Standard Display,
immediately press the EXIT Key.
If a Language is Enabled
If more than one language has been enabled from the Guarded Access Language Menu, a
prompt will appear to allow the desired language to be chosen as shown below. Only languages
specifically enabled from the Guarded Access Menu are available. If a different language is
desired, press the NO Key (Figure 28, p. 127).
I m p o rt a n t : The engine start is not delayed by the language prompt shown below. The prompt
will appear for 10 seconds and then the engine will start. After the engine is started
the display will return to the prompt shown.
Figure 28. NO Key
CURRENT LANGUAGE IS
ON
ENGLISH
OFF OK?
YES NO
AMA1440
The Language Menu will appear as shown (Figure 29, p. 127). Press the + or - Keys to select the
desired language. When the desired language is shown, press the YES Key to confirm the choice.
TK 55533-2-OD-EN 127
(128,1)
Sec t i o n 4 - Op er at i o n
AMA1505-1
The display will briefly show PROGRAMMING LANGUAGE - PLEASE WAIT in the new language
as shown (Figure 30, p. 128).
Figure 30. New Language
AMA1591
The new language is confirmed, and the Standard Display will appear in the new language as
shown (Figure 31, p. 128). The unit is ready to run.
Figure 31. Standard Display, New Language
ON
°F
OFF
SET
POINT
35
MESSGE
RAT
.8
SENSORE
N
35
MENU
AMA1443
128 TK 55533-2-OD-EN
(129,1)
Sec t i o n 4 - Op er a ti o n
AMA1444
N o t e : The Alarm Icon does not appear on startup with log alarms present.
When the unit is ready to run, the Standard Display appears (Figure 33, p. 129).
Figure 33. Standard Display
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1445
OFF
AMA1446
The display briefly shows OFF (Figure 35, p. 129) and then goes blank. To start the unit again,
press the ON Key.
Figure 35. Display Shows OFF
ON
OFF
OFF
AMA1447
TK 55533-2-OD-EN 129
(130,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1448
Pressing the left soft key allows the user to change the SETPOINT, and pressing the right soft key
accesses the MAIN MENU. The other two soft keys access the GAUGES menu and the SENSORS
menu.
N o t e : The functions of the GAUGES and SENSORS soft keys may be re-assigned to better suit
customer requirements. The GAUGES and SENSORS functions are always available from
the Maintenance Menu.
35
ON
OFF .8
35
MENU
AMA1449
130 TK 55533-2-OD-EN
(131,1)
Sec t i o n 4 - Op er a ti o n
If an alarm condition (other than a Log Alarm) is present, the TemperatureWatch Display will not
appear. If an alarm condition occurs while the TemperatureWatch Display is present, the display
will return to the Standard Display to indicate that an alarm condition has occurred.
If the Defrost Key or Cycle Sentry Key is pressed, the display will return to the TemperatureWatch
Display immediately after the defrost cycle is initiated or the operating mode is changed.
Numerical Setpoints
If OptiSet Plus is not in use or if only Numerical Setpoints are enabled, the left soft key will be
labeled SETPOINT (Figure 38, p. 131).
Figure 38. SETPOINT
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1450
ON
°F
OFF
PRODUCT
35
GAUGES
.8
SENSORS
35
MENU
AMA1451
TK 55533-2-OD-EN 131
(132,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
PRODUCT/
SETPOINT
35GAUGES
.8
SENSORS
35
MENU
AMA1452
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1450
CURRENT SETPOINT
ON
35 F
+/- TO CHANGE
OFF
- + EXIT
AMA1454
The “-” and “+” Keys are used to increase or decrease the setpoint until the desired setpoint is
shown. The setpoint has been changed to 40 F using the “+” Key (Figure 43, p. 132).
Figure 43. Setpoint Changed Using “+” Key
ON
40 F
+/- TO CHANGE OK?
OFF
- + YES NO
AMA1455
The YES and NO Keys (Figure 44, p. 132) confirm the setpoint change. When the desired setpoint
has been selected using the “+” and/or “-” Keys, press the YES Key to confirm and load the new
setpoint. If the setpoint is changed using the “+” or “-” Keys, the change must be confirmed or
rejected by pressing the YES or NO Key within 10 seconds of changing the setpoint. A warning
beep will sound for five seconds as a reminder.
132 TK 55533-2-OD-EN
(133,1)
Sec t i o n 4 - Op er a ti o n
Failure to confirm the new setpoint by pressing Yes or No within 10 seconds of changing the
setpoint will result in no setpoint change. In addition, Alarm Code 127 Setpoint Not Entered is
set, to indicate that a setpoint change was initiated but not completed.
Figure 44. Yes and No Keys
ON
40 F
+/- TO CHANGE OK?
OFF
- + YES NO
AMA1456
After the YES Key has been pressed, the display briefly shows PROGRAMMING NEW SETPOINT-
PLEASE WAIT. The display then confirms the new setpoint for several seconds (Figure 45, p. 133).
Figure 45. New Setpoint
NEW SETPOINT IS
ON
40 F
OFF
AMA1457
If the NO Key is pressed the display will briefly show SETPOINT NOT CHANGED and return to the
Standard Display. The Standard Display will show the old setpoint.
The display then returns to the Standard Display showing the new setpoint. Notice that the arrow
now points up to indicate that the unit is heating (Figure 46, p. 133).
Figure 46. Up Arrow
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
40
MENU
AMA1458
I m p o rt a n t : If the setpoint is changed using the “+” or “-” Keys, the change must be confirmed or
rejected by pressing the YES or NO Key within 10 seconds of changing the setpoint.
• If the YES Key is pressed, the setpoint change made with the “+” or “-” Key is accepted, the
setpoint changes, and the display returns to the Standard Display.
• If the NO Key is pressed the setpoint change made with the “+” or “-” Key is not accepted, the
setpoint is not changed, and the display returns to the Standard Display.
• If the YES or NO Key is not pressed within 10 seconds of making a change with the “+” or “-”
Key, the setpoint is not changed and the display returns to the Standard Display. The display
briefly shows [SETPOINT NOT CHANGED] and Alarm Code 127 Setpoint Not Entered is set, to
indicate that a setpoint change was initiated but not completed.
See C h a n g i n g t h e S e t p o i n t - N u m e r i c a l Se t p o i n t (Figure 47, p. 133) for an overview of the
procedure.
TK 55533-2-OD-EN 133
(134,1)
Sec t i o n 4 - Op er at i o n
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
OFF
+/- TO CHANGE
- +
40 F
YES
OK?
NO OFF
40 F
ON ON
35 F 40 F ON
°F
OFF
+/- TO CHANGE
- + EXIT OFF
+/- TO CHANGE
- + YES
OK?
NO
OFF
SET
POINT
35
GAUGES
.8
SENSORS
40
MENU
AMA1568a
Yes or No Keys
GRAPEFRUIT , ARIZONA
ON
°F
OFF
PRODUCT
59 GAUGES
.8
SENSORS
59
MENU
AMA1459
The display briefly shows PRODUCT and then the setpoint display appears (Figure 49, p. 134).
Figure 49. Setpoint Display
CURRENT PRODUCT IS
ON
GRAPEFRUIT , ARIZONA
+/- TO CHANGE
OFF
- + EXIT
AMA1460
The “-” and “+” Keys are used to change the Named Product until the desired product is shown.
The product has been changed to Potato, Late Crop (Figure 50, p. 134).
Figure 50. Named Product
ON
POTATO, LATE CROP
AMA1461
134 TK 55533-2-OD-EN
(135,1)
Sec t i o n 4 - Op er a ti o n
The YES and NO Keys confirm the product change (Figure 51, p. 135). When the desired product
has been selected using the “+” and/or “-” Keys, press the YES Key to confirm and load the new
product. If the product is changed using the “+” or “-” Keys, the change must be confirmed or
rejected by pressing the YES or NO Key within 10 seconds of changing the product. A warning
beep will sound for five seconds as a reminder.
Failure to confirm the new product by pressing Yes or No within 10 seconds of changing the
product will result in no product change. In addition, Alarm Code 127 Setpoint Not Entered is set,
to indicate that the product change was initiated but not completed.
Figure 51. Yes and No Keys
ON
POTATO, LATE CROP
AMA1462
After the YES Key has been pressed, the display briefly shows PROGRAMMING NAMED
PRODUCT- PLEASE WAIT. The display then confirms the new setpoint for several seconds
(Figure 52, p. 135).
Figure 52. New Named Product
OFF
AMA1463
If the NO Key is pressed the display will briefly show SETPOINT NOT CHANGED and return to the
Standard Display. The Standard Display will show the old setpoint.
The display then returns to the Standard Display showing the new named product. Notice that
the arrow points down, to indicate that the unit is cooling (Figure 53, p. 135).
Figure 53. Standard Display
ON
°F
OFF
PRODUCT
45
GAUGES
.8
SENSORS
45
MENU
AMA1464
I m p o rt a n t : If the named product is changed using the “+” or “-” Keys, the change must be
confirmed or rejected by pressing the YES or NO Key within 10 seconds of changing
the named product.
• If the YES Key is pressed, the product change made with the “+” or “-” Key is accepted, the
product changes, and the display returns to the Standard Display.
• If the NO Key is pressed the product change made with the “+” or “-” Key is not accepted, the
product is not changed, and the display returns to the Standard Display.
• If the YES or NO Key is not pressed within 10 seconds of making a change with the “+” or “-”
Key, the product is not changed and the display returns to the Standard Display. The display
TK 55533-2-OD-EN 135
(136,1)
Sec t i o n 4 - Op er at i o n
briefly shows [SETPOINT NOT CHANGED] and Alarm Code 127 Setpoint Not Entered is set, to
indicate that the product change was initiated but not completed.
See C h a n g i n g t h e S e t p o i n t - N a m e d P r o d u c t (Figure 54, p. 136) for an overview of the
procedure.
Figure 54. Changing the Setpoint, Named Product
OFF
PRODUCT
59GAUGES
.8
SENSORS
59
MENU OFF
POTATO, LATE CROP
+/- TO CHANGE
- + YES
OK?
NO OFF
POTATO, LATE CROP
ON ON ON
°F
OFF
GRAPEFRUIT , ARIZONA
+/- TO CHANGE
- + EXIT
OFF
POTATO, LATE CROP
+/- TO CHANGE
- + YES
OK?
NO OFF
PRODUCT
45
GAUGES
.8
SENSORS
45
MENU
AMA1517
Changing the Setpoint - Both Numerical Setpoint and Named Product Available
If the TemperatureWatch display is shown, press any soft key to return to the Standard Display.
From the Standard Display, press the SETPOINT Key. Note that both PRODUCT and SETPOINT are
displayed as shown (Figure 55, p. 136).
Figure 55. PRODUCT and SETPOINT are Displayed
ON
°F
OFF
PRODUCT/
SETPOINT
35GAUGES
.8
SENSORS
35
MENU
AMA1452
The NAMED PRODUCT / NUMERIC SETPOINT prompt will appear (Figure 56, p. 136).
Figure 56. NAMED PRODUCT / NUMERIC SETPOINT Prompt
OFF
EXIT NAMED NUMERIC
AMA1466
• Press the NUMERIC Soft Key to proceed with Changing the Setpoint - Numeric Setpoint
change as previously shown.
• Press the NAMED Soft Key to proceed with Changing the Setpoint - Named Product change
as previously shown.
• Press the EXIT Soft Key to return to the Standard Display.
136 TK 55533-2-OD-EN
(137,1)
Sec t i o n 4 - Op er a ti o n
C AU T I O N
Risk of Injury!
T h e e n g i n e m a y s t a rt a u t o m a t i c a l l y a n y t i m e t h e u n i t i s t u r n e d o n .
N OT I C E
Equipment Damage!
N e v e r u s e s t a rt i n g f l u i d . D a m a g e t o t h e e n g i n e c a n o c c u r.
When the engine is preparing to start, the HMI Control Panel will display the engine start screen
as shown. The preheat buzzer sounds during the engine preheat and crank sequence.
Figure 57. Engine Start Screen
ON
DIESEL ENGINE ST ARTING
OFF
AMA1467
After the engine is started, the display returns to the Standard Display of temperature and
setpoint.
C AU T I O N
Risk of Injury!
T h e m o t o r m a y s t a rt a u t o m a t i c a l l y a ny t i m e t h e u n i t i s t u r n e d o n .
TK 55533-2-OD-EN 137
(138,1)
Sec t i o n 4 - Op er at i o n
When the motor is preparing to start, the HMI Control Panel will display the motor start screen
(Figure 59, p. 138). The preheat buzzer sounds for 20 seconds before the electric motor starts.
Figure 59. Motor Start Screen
ON
ELECTRIC MOT OR ST ARTING
OFF
AMA1468
AMA1469
If NO is selected, the unit will continue to operate in Diesel Mode. If YES is selected, the display
will briefly show the screen (Figure 61, p. 138).
Figure 61. YES Selected
PROGRAMMING ELECTRIC
ON STANDBY
AMA1470
Electric Mode operation will briefly be confirmed. If unit operation is required the electric motor
will start as shown previously under STARTING THE ELECTRIC MOTOR.
138 TK 55533-2-OD-EN
(139,1)
Sec t i o n 4 - Op er a ti o n
If the Diesel to Electric Auto-Switch Enabled feature in Guarded Access is set NO, the unit can
also be switched from Diesel mode to Electric mode operation using the Electric Standby
Selection from the Main Menu as shown later in this section.
AMA1471
If YES is selected, the display will briefly show the screen (Figure 63, p. 139).
Figure 63. Yes Selected
ON
PROGRAMMING DIESEL MODE
AMA1472
Diesel Mode operation will briefly be confirmed. If unit operation is required, the diesel engine
will start as shown previously under “Starting the Diesel Engine”.
If the Electric to Diesel Auto-Switch Enabled feature in Guarded Access is set NO, the unit can
also be switched from Diesel mode to Electric mode operation using the Diesel Selection from
the Main Menu as shown later in this section.
TK 55533-2-OD-EN 139
(140,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1473
The display briefly shows [DEFROST], [PROGRAMMING DEFROST- PLEASE WAIT] and then
[DEFROST STARTED] (Figure 65, p. 140).
Figure 65. Defrost Started
ON
DEFROST ST ARTED
OFF
AMA1474
The display then shows the Defrost display. The bar indicator shows approximately how much
time remains to complete the defrost cycle. The bar indicator shows that the defrost cycle is
about 25% complete (Figure 66, p. 140).
Figure 66. Bar Indicator
ON
35
OFF
SET GAUGES SENSORS MENU
POINT
AMA1475
If conditions do not allow a defrost cycle, the display shown (Figure 67, p. 140) will briefly appear.
The display will then return to the Standard Display.
Figure 67. Defrost Not Available
ON
DEFROST NOT AVAILABLE
OFF
AMA1476
140 TK 55533-2-OD-EN
(141,1)
Sec t i o n 4 - Op er a ti o n
ON ON
°F
OFF
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU Yes OFF
SET
POINT
GAUGES SENSORS
35
MENU
ON
DEFROST ST ARTED DEFROST NOT AVAILABLE
ON
OFF OFF
No
AMA1570a
ON
°F
OFF
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
AMA1477
If allowed by OptiSet Plus, Cycle Sentry Mode or Continuous Mode is selected by pressing the
Cycle Sentry/Continuous Key as shown (Figure 70, p. 141).
TK 55533-2-OD-EN 141
(142,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
AMA1478
N o t e : Cycle Sentry Mode or Continuous Mode can also be selected using the Main Menu > Mode
Submenu.
If the unit is in Cycle Sentry Mode, pressing the Cycle Sentry/Continuous Key changes the mode
from Cycle Sentry Mode to Continuous Mode. The display confirms the change (Figure 71, p.
141).
Figure 71. Continuous Mode
PLEASE W AIT
OFF
AMA1479
The new mode is confirmed for three seconds (Figure 72, p. 142).
Figure 72. New Mode Confirmed
CONTINUOUS
OFF
AMA1480
The display then returns to the Standard Display. In the example shown (Figure 73, p. 142), the
absence of the Cycle Sentry Icon indicates that the unit is running in Continuous Mode.
Figure 73. Cycle Sentry Icon Not Shown = Continuous Mode
ON
°F
OFF
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
AMA1481
Pressing the Cycle Sentry/Continuous Key again allows the operator to change back to Cycle
Sentry Mode operation.
I m p o rt a n t : If the unit is in Cycle Sentry Null and the mode is switched to Continuous Mode, the
unit will start automatically.
I m p o rt a n t : Cycle Sentry or Continuous Mode may not be selectable if OptiSet Plus is in use.
142 TK 55533-2-OD-EN
(143,1)
Sec t i o n 4 - Op er a ti o n
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU OFF
PLEASE W AIT
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
Continuous Mode
Selected
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU OFF
CONTINUOUS
AMA1571a
ON
°F
OFF
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
AMA1482
The first gauge display will appear. Press the NEXT and BACK Keys to scroll through the gauges.
Pressing the LOCK Key will lock the current gauge on the display (Figure 76, p. 143).
Figure 76. Gauge Display Locked
BATTERY VOLTAGE
ON
13. 8 v
OFF
EXIT LOCK BACK NEXT
AMA1483
The gauges and I/O conditions available are shown on the next page. Not all gauges or I/O
conditions may appear depending on unit configuration and software revision.
To return to the Standard Display press the EXIT Key.
Gauges Available
C o o l a n t Te m p e r a t u r e : Displays the temperature of the engine coolant.
C o o l a n t L e v e l : Displays the coolant level in the overflow tank.
E n g i n e O i l P r e s s u r e : Displays the engine oil pressure as OK or LOW.
E n g i n e O i l L e v e l S w i t ch : Displays the engine oil level as OK or LOW.
A m p s : Displays the current flow in amps flowing to or from the unit battery.
B a tt e r y Vo l t a g e : Displays the voltage of the unit battery.
TK 55533-2-OD-EN 143
(144,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1484
The first sensor display will appear. Press the NEXT and BACK Keys to scroll through the sensors.
Pressing the LOCK Key will lock the current sensor on the display (Figure 78, p. 144).
144 TK 55533-2-OD-EN
(145,1)
Sec t i o n 4 - Op er a ti o n
ON
48. 3 °F
OFF
EXIT LOCK BACK NEXT
AMA1485
Sensors Available
C o n t r o l R e t u r n A i r Te m p e r a t u r e : Displays the temperature of the control return air sensor.
D i s p l a y R e t u r n A i r Te m p e r a t u r e : Displays the temperature of the display return air sensor.
C o n t r o l D i s ch a r g e A i r Te m p e r a t u r e : Displays the temperature of the control discharge air
sensor.
D i s p l a y D i s ch a r g e A i r Te m p e r a t u r e : Displays the temperature of the display discharge air
sensor.
Te m p e r a t u r e D i ff e r e n t i a l : Displays the calculated difference between the control return air
sensor and the control discharge air sensor.
E v a p o r a t o r C o i l Te m p e r a t u r e : Displays the temperature of the evaporator coil sensor.
A m b i e n t A i r Te m p e r a t u r e : Displays the temperature of the ambient air sensor.
* S p a r e 1 Te m p e r a t u r e : Displays the temperature of the spare 1 temperature sensor.
* L o g S e n s o r 1 : Displays the temperature of the CargoWatch Data Logger temperature sensor 1.
* L o g S e n s o r 2 : Displays the temperature of the CargoWatch Data Logger temperature sensor 2.
* L o g S e n s o r 3 : Displays the temperature of the CargoWatch Data Logger temperature sensor 3.
* L o g S e n s o r 4 : Displays the temperature of the CargoWatch Data Logger temperature sensor 4.
* L o g S e n s o r 5 : Displays the temperature of the CargoWatch Data Logger temperature sensor 5.
* L o g S e n s o r 6 : Displays the temperature of the CargoWatch Data Logger temperature sensor 6.
B o a r d Te m p e r a t u r e S e n s o r : Displays the internal temperature of the HMI Control Panel pc
board.
* If sensors have been added.
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1487
TK 55533-2-OD-EN 145
(146,1)
Sec t i o n 4 - Op er at i o n
The first Main Menu choice will appear. Press and hold the UP or DOWN Keys to scroll through
the menu choices. When the desired selection is shown on the display, press the SELECT Key to
access it. The Pretrip submenu is displayed (Figure 80, p. 145).
To return to the Standard Display press the EXIT Key.
Figure 80. Pretrip Submenu
MAIN MENU
PRETRIP
ON
LANGUAGE
ALARMS
GAUGES
OFF
EXIT SELECT UP DOWN
AMA1488
Pretrip
Pretrip Test verifies unit operation. This display allows a Pretrip Test to be selected and initiated
by the operator. If the Pretrip Test is entered with the unit shut down a Full Pretrip Test with
device amp checks will be performed. If the Pretrip Test is entered with the unit running in either
diesel or electric mode a Running Pretrip Test is performed. Test results are reported as PASS,
CHECK, or FAIL when the Pretrip Test is completed.
146 TK 55533-2-OD-EN
(147,1)
Sec t i o n 4 - Op er a ti o n
TK 55533-2-OD-EN 147
(148,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Pretrip Menu.
When the Pretrip Menu is shown, press the SELECT Key to start a Pretrip Test (Figure 82, p. 147).
Figure 82. Select Key
MAIN MENU
PRETRIP
ON
LANGUAGE
ALARMS
GAUGES
OFF
EXIT SELECT UP DOWN
AMA1490
The display will briefly show PROGRAMMING PRETRIP MODE (Figure 83, p. 148). If the unit is
not running, a Full Pretrip Test will be initiated. If the unit is running in either diesel or electric
mode, a Running Pretrip Test will be performed.
Figure 83. Programming Trip Mode
OFF
AMA1491
If all alarms were not cleared, a prompt appears (Figure 84, p. 148). Exit the Pretrip Test, clear all
alarms, and repeat the Pretrip Test.
Figure 84. Alarms Not Cleared
OFF
EXIT
AMA1492
If all alarms were cleared, the Pretrip Test display appears (Figure 85, p. 148).
148 TK 55533-2-OD-EN
(149,1)
Sec t i o n 4 - Op er a ti o n
NON-RUNNING PRETRIP
TEST 1 OF 26
ON
SENSOR CHECK
OFF
HOUR SENSORS GAUGES
METERS
AMA1493
• The top line of the display indicates the unit is performing the non-running portion of the
Pretrip Test.
• The second line measures test progress. The number of tests completed of the total number
of tests to be performed is shown. In the example above the unit is performing Test 1 of 26,
Sensor Check.
• The soft keys may be used during the Pretrip Test to select the Hourmeter, Gauge or Sensor
menus.
• To stop a Pretrip Test at any time turn the unit off. This will generate Alarm Code 28 Pretrip
Abort. Other alarm codes may also be generated. This is normal when the Pretrip Test is
halted before completion.
When the non-running tests are complete, the unit will start automatically and continue with the
Running Pretrip Test. In the example shown (Figure 86, p. 149), the unit is in the Running Pretrip
and is performing Test 21 of 26, Cool Test.
Figure 86. Cool Test
RUNNING PRETRIP
TEST 21 OF 26
ON
COOL TEST
OFF
HOUR SENSORS GAUGES
METERS
AMA1494
When all tests are complete, the results are reported as PASS, CHECK or FAIL (Figure 87, p. 149).
If the results are CHECK or FAIL, the accompanying alarm codes will direct the technician to the
cause of the problem.
Figure 87. Pretrip Pass
PRETRIP
ON
PASS
OFF EXIT
AMA1495
If the Pretrip Test results are CHECK or FAIL, the problem should be diagnosed and corrected by a
Thermo King service technician before the unit is released for service.
To return to the Main Menu, press the EXIT Key. To return to the Standard display press the EXIT
Key again.
See Pe r f o r m i n g a Pr e t r i p Te s t (Figure 88, p. 149) for an overview of the procedure.
TK 55533-2-OD-EN 149
(150,1)
Sec t i o n 4 - Op er at i o n
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU OFF
Yes
OFF
HOUR
METERS
SENSORS GAUGES OFF
HOUR
METERS
COOL TEST
SENSORS GAUGES
Alarms Cleared?
No
MAIN MENU
PRETRIP PRETRIP
ON ON NO PRETRIP -- ALARM ACTIVE ON
LANGUAGE PASS
ALARMS
OFF
GAUGES
EXIT SELECT UP DOWN
OFF
EXIT
Exit Pretrip Test, clear alarms, OFF EXIT
restart Pretrip Test.
AMA1577
Flash Drive
If a properly configured USB Flash Drive is currently connected to the USB Port on the unit
Control Panel, the Flash Drive Menu will appear as a Main Menu selection. If a properly
configured USB Flash Drive is connected to the USB Flash Drive connector, this feature allows
the operator to select the desired Flash Drive function. If enabled when the Flash Drive was
configured, the following functions may be available:
Download
• Download the ServiceWatch Data Logger
• Download the CargoWatch Data Logger
Flashload
• Flash load Base Controller Software
• Flash load HMI Control Panel Software
OptiSet Plus
• SEND
– Send OptiSet Plus files
• RETRIEVE
– Retrieve OptiSet Plus files
If a USB Flash Drive is not connected to the unit, this feature will not appear in the Main Menu.
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1496
150 TK 55533-2-OD-EN
(151,1)
Sec t i o n 4 - Op er a ti o n
Selecting the Flash Drive Menu from the Main Menu (If Already Connected)
To select the Flash Drive Menu, press the MENU Key (Figure 90, p. 150). The Main Menu will
appear.
Figure 90. Menu Key
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1489
If a properly configured USB Flash Drive is connected to the Flash Drive Only USB Port on the
Control Panel, the Flash Drive Menu will appear as a main Menu selection. Press the UP or
DOWN Key as required to choose the Flash Drive Menu. When the Flash Drive Menu is shown,
press the SELECT Key to select the Flash Drive Menu (Figure 91, p. 150).
Figure 91. Flash Drive Menu
MAIN MENU
FLASH DRIVE
ON
PRETRIP
LANGUAGES
ALARMS
OFF
EXIT SELECT UP DOWN
AMA1498
ON
FLASH DRIVE DETECTED
AMA1499
TK 55533-2-OD-EN 151
(152,1)
Sec t i o n 4 - Op er at i o n
AMA1501
If the HELP Soft Key is pressed, the display shown (Figure 94, p. 151) will appear.
Figure 94. Help Soft Key Pressed
OFF EXIT
AMA1502
Available Languages
The following languages are available:
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. If more than one language is enabled, the Language Menu will
appear as a Main Menu selection (Figure 96, p. 152). Press the UP or DOWN Key as required to
choose the Language Menu. When the Language Menu is shown press the SELECT Key to select
the Language Menu.
152 TK 55533-2-OD-EN
(153,1)
Sec t i o n 4 - Op er a ti o n
MAIN MENU
PRETRIP
ON
LANGUAGE
ALARMS
GAUGES
OFF
EXIT SELECT UP DOWN
AMA1504
The Language Menu will appear as shown (Figure 97, p. 152). Press the + or - Keys to select the
desired language. Only languages enabled from the Guarded Access Menu are available. When
the desired language is shown (example is Español [Spanish]) press the YES Key to confirm the
choice.
Figure 97. Language Menu
AMA1505-1
The display will briefly show PROGRAMMING LANGUAGE - PLEASE WAIT in the new language.
The display will then return to the Language Menu, but will show the new language. Español
(Spanish) is shown (Figure 98, p. 153).
Figure 98. New Language (Example: Spanish)
AMA1506-1
Repeat the process to select a different language. To select a different Main Menu item, press the
NEXT (SIGUIENTE) Key. To return to the Standard Display, press the EXIT (SALIDA) Key.
All displays will now be in the new language. Español (Spanish) is shown (Figure 99, p. 153).
Figure 99. New Language (Example: Spanish)
AMA1507-1
To return to the Main Menu press the EXIT Key. To return to the Standard display press the EXIT
Key again.
TK 55533-2-OD-EN 153
(154,1)
Sec t i o n 4 - Op er at i o n
AMA1572-1
AMA1508-1
After five seconds, the Language Menu will appear in the current language as shown below.
Press the + or - Keys to select the desired language. When the desired language is shown, press
the SI (YES) Key to confirm the choice (Figure 102, p. 154).
Figure 102. Select Desired Language
AMA1509-1
N o t e : All languages in the installed software can be selected using this method.
Alarms
The Alarm Menu allows the operator to view any active alarms, and allows most alarms to be
cleared.
Refer to the SR-4 Trailer Single Temperature Diagnostic Manual for more information about
alarm codes and their diagnosis.
154 TK 55533-2-OD-EN
(155,1)
Sec t i o n 4 - Op er a ti o n
Log Alarms
If only Log Alarms exist, the display shown will appear and the optional remote alarm light will
light for 30 seconds when the unit is turned on.
Figure 103. Log Alarms Exist
AMA1510
Check Alarms
If a Check Alarm condition occurs while the unit is running, the alarm icon will appear in the
display as shown (Figure 104, p. 155).
Figure 104. Alarm Icon
ON
OFF
SET
35
POINT
GAUGES SENSORS
35
MENU
AMA1511
Shutdown Alarms
If a Shutdown Alarm occurs while the unit is running, it will be indicated by all of the following
(Figure 105, p. 155):
• The Alarm Icon will appear.
• The display, backlight and optional remote alarm light will flash on and off.
• The display will switch from normal to inverted and back (light areas become dark and dark
areas become light.)
Figure 105. Reverse/Normal Video
ON
OFF SET
35
POINT
GAUGES SENSORS
35
MENU
AMA1512
Pretrip Alarms
If an alarm occurs during a Pretrip Test, the alarm code will be displayed as Pretrip Alarm XX,
where XX is the alarm code.
TK 55533-2-OD-EN 155
(156,1)
Sec t i o n 4 - Op er at i o n
operation. If the unit is switched back to diesel mode, the alarm again become a diesel mode
shutdown alarm and prevents unit operation.
In the same manner, if a shutdown alarm occurs that affects only electric mode operation and the
unit is switched to diesel, the electric mode shutdown alarm becomes a diesel mode log alarm to
allow diesel mode operation. If the unit is switched back to electric mode, the alarm reverts to an
electric mode shutdown alarm and prevents unit operation. If the unit is configured for electric to
diesel Auto-Switch, it automatically starts and runs in diesel mode if an electric shutdown occurs.
ON
OFF
SET
35
POINT
GAUGES SENSORS
35
MENU
AMA1513
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Alarms Menu
(Figure 107, p. 156). When the Alarms Menu is shown, press the SELECT Key to select the Alarms
Menu.
156 TK 55533-2-OD-EN
(157,1)
Sec t i o n 4 - Op er a ti o n
MAIN MENU
PRETRIP
ON
LANGUAGE
ALARMS
GAUGES
OFF
EXIT SELECT UP DOWN
AMA1514
The number of alarms (if more than one) and a list of the alarms with the most recent alarm first
will be shown. In the example shown (Figure 108, p. 156), there are two alarms. The most recent
is Alarm Code 5 Check Ambient Temp Sensor.
Figure 108. Alarms Menu
1 OF 2 ALARMS
5 CHECK AMBIENT TEMP SENSOR
ON
64 PRETRIP REMINDER
x 64
OFF
EXIT CLEAR HELP DOWN
AMA1515
If necessary to view all alarms, scroll down using the DOWN Key (Figure 109, p. 157).
Figure 109. Down Key
1 OF 2 ALARMS
5 CHECK AMBIENT TEMP SENSOR
ON
64 PRETRIP REMINDER
x 64
OFF
EXIT CLEAR HELP DOWN
AMA1518
If the alarm situation has been resolved, press the CLEAR Key to clear the alarm (Figure 110, p.
157).
Figure 110. Clear Key
1 OF 2 ALARMS
5 CHECK AMBIENT TEMP SENSOR
ON
64 PRETRIP REMINDER
x 64
OFF
EXIT CLEAR HELP DOWN
AMA1519
The display will briefly show CLEARING ALARM 5 – PLEASE WAIT and the Alarm Menu will
reappear (Figure 111, p. 157).
Alarm Code 64 Pretrip Reminder cannot be cleared using the CLEAR Key. This alarm will clear
automatically when a Pretrip Test is run.
TK 55533-2-OD-EN 157
(158,1)
Sec t i o n 4 - Op er at i o n
1 OF 1 ALARMS
64 PRETRIP REMINDER
ON
x 64
OFF
EXIT CLEAR HELP DOWN
AMA1520
If a serious condition occurs, the unit will be shut down to prevent damage to the unit or the load.
If this occurs, the Alarm Icon will appear, the display and backlight will flash on and off (Figure
112, p. 157).
Figure 112. Unit Shutdown
ON
OFF SET
POINT
35 GAUGES SENSORS
35
MENU
AMA1521
The Alarm Menu display will display the Shutdown Alarm Code. For additional information
regarding the alarm shown on the display, press the HELP Key (Figure 113, p. 158).
Figure 113. Help Key
1 OF 1 ALARMS
66 LOW ENGINE OIL LEVEL
ON
x 64
OFF
EXIT CLEAR HELP DOWN
AMA1522
A help message will appear. Press the EXIT Key to return to the Alarms Menu (Figure 114, p. 158).
Check the oil level and add oil as required, clear the alarm and restart the engine.
Figure 114. Exit Key
ON
CHECK ENGINE OIL LEVEL. IF UNIT IS SHUT
DOWN REP AIR IMMEDIATELY. OTHER WISE
REPORT ALARM AT END OF DA Y.
OFF
EXIT
AMA1523
To return to the Main Menu press the EXIT Key. To return to the Standard display press the EXIT
Key again.
158 TK 55533-2-OD-EN
(159,1)
Sec t i o n 4 - Op er a ti o n
• If an alarm cannot be cleared from the Main menu, the Clear Key will not appear. These
alarms must be cleared from the Maintenance or Guarded Access Menus.
See D i s p l a y i n g a n d C l e a r i n g A l a r m C o d e s (Figure 115, p. 158) for an overview or the
procedure.
Figure 115. Displaying and Clearing Alarm Codes
1 OF 2 ALARMS
LOG ALARMS ACTIVE 5 CHECK AMBIENT TEMP SENSOR
ON ON ON ON
OFF
EXIT
GO T O MENU TO VIEW
OFF
SET
POINT
35 GAUGES SENSORS
35
MENU
OFF
64
x
EXIT
PRETRIP REMINDER
64
OFF
SET
35
POINT
GAUGES SENSORS
35
MENU OFF
LANGUAGE
ALARMS
GAUGES
EXIT SELECT UP DOWN
OFF
64
x
EXIT
PRETRIP REMINDER
64
EXIT
64
35
ON ON
CHECK ENGINE OIL LEVEL. IF UNIT IS SHUT
35 64
x
PRETRIP REMINDER
64 x 64
DOWN REP AIR IMMEDIATELY. OTHER WISE
REPORT ALARM AT END OF DA Y.
OFF SET GAUGES SENSORS MENU OFF OFF OFF
EXIT CLEAR HELP DOWN EXIT CLEAR HELP DOWN
POINT EXIT
AMA1578
Gauges
The Gauges Menu allows the operator to view the unit gauges and I/O conditions. The unit
gauges can always be viewed from the Main Menu. This is necessary if the GAUGES Soft Key on
the Standard Display has been reassigned to a different function.
Displaying Gauges
Gauges are displayed using the Gauges Menu. From the Standard Display, press the MENU Key
(Figure 116, p. 159).
Figure 116. Menu Key
ON
°F
OFF
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Gauges Menu.
When the Gauges Menu is selected, press the SELECT Key to choose the Gauges Menu (Figure
117, p. 159).
Figure 117. Up, Down, Select Keys
MAIN MENU
PRETRIP
ON
LANGUAGE
ALARMS
GAUGES
OFF
EXIT SELECT UP DOWN
AMA1525a
TK 55533-2-OD-EN 159
(160,1)
Sec t i o n 4 - Op er at i o n
The first gauge display will appear. Press the NEXT and BACK Keys to scroll through the gauges
and I/O conditions. Pressing the LOCK Key will lock the current gauge on the display (Figure 118,
p. 159).
Figure 118. Next, Back, Lock Keys
BATTERY VOLTAGE
ON
13. 8 v
OFF
EXIT LOCK BACK NEXT
AMA1526
The gauges and I/O conditions available are described in “Gauges Available”. Not all gauges or I/
O conditions may appear depending on unit configuration and software revision.
To return to the Main Menu, press the EXIT Key. To return to the Standard Display, press the EXIT
Key again.
Sensors
The Sensors Menu allows the operator to view the unit and CargoWatch Data Logger
temperature sensors. The sensors can always be viewed from the Main Menu. This is necessary
if the SENSORS Soft Key on the Standard Display has been reassigned to a different function.
Displaying Sensors
Sensors are displayed using the Sensors Menu. From the Standard Display, press the MENU Key
(Figure 119, p. 160).
Figure 119. Menu Key
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Sensors Menu.
When the Sensors Menu is selected, press the SELECT Key to choose the Sensors Menu (Figure
120, p. 160).
Figure 120. Up, Down, Select Keys
MAIN MENU
ALARMS
ON
GAUGES
SENSORS
DATA LOGGER
OFF
EXIT SELECT UP DOWN
AMA1528
The first sensors display will appear. Press the NEXT and BACK Keys to scroll through the
sensors and I/O conditions. Pressing the LOCK Key will lock the current sensor on the display
(Figure 121, p. 160).
160 TK 55533-2-OD-EN
(161,1)
Sec t i o n 4 - Op er a ti o n
ON
48. 3 °F
OFF
EXIT LOCK BACK NEXT
AMA1529
The sensors available are described in “Using the Sensors Key,” p. 144.
To return to the Main Menu, press the EXIT Key. To return to the Standard Display, press the EXIT
Key again.
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Data Logger
Menu. When the Data Logger Menu is selected, press the SELECT Key to choose the Data Logger
Menu (Figure 123, p. 161).
Figure 123. Up, Down, Select Keys
MAIN MENU
GAUGES
ON
SENSORS
DATA LOGGER
HOURMETERS
OFF
EXIT SELECT UP DOWN
AMA1531
TK 55533-2-OD-EN 161
(162,1)
Sec t i o n 4 - Op er at i o n
DATA LOGGER
START TRIP
ON
PRINT/VIEW
OFF
EXIT SELECT UP DOWN
AMA1532
N o t e : The start of trip marker is sent to both the CargoWatch and ServiceWatch data loggers.
DATA LOGGER
START TRIP
ON
PRINT/VIEW
OFF
EXIT SELECT UP DOWN
AMA1533
The Print Data Menu will appear. The first Print Data Menu allows the operator to print a Delivery
Ticket using a hand held printer. Pressing the SELECT Key will print the ticket (Figure 126, p. 162).
The Delivery Ticket is a short ticket that shows delivery specific details including the current
temperature. A Sample Delivery Ticket is shown (Figure 127, p. 162).
Figure 126. Select Key, Print Delivery Ticket
PRINT DATA
DELIVERY TICKET
ON
TRIP TICKET
OFF
EXIT SELECT UP DOWN
AMA1534
162 TK 55533-2-OD-EN
(163,1)
Sec t i o n 4 - Op er a ti o n
AMA1535
Pressing the DOWN Key allows the operator to print a Trip Ticket using a hand held printer. Press
the SELECT Key to print the ticket (Figure 128, p. 162). The Trip Ticket is a long ticket that shows
details for the current trip including a temperature history. The Trip Ticket is also called a Journey
Ticket. A sample Trip Ticket is shown (Figure 129, p. 163).
Figure 128. Select Key, Print Trip Ticket
PRINT DATA
DELIVERY TICKET
ON
TRIP TICKET
OFF
EXIT SELECT UP DOWN
AMA1536
30 - MAY - 2008
1305 35.0
1250 35.2
1235 35.1
1220 35.2
1205 35.1
30 - MAY - 2008
1150 35.0
1135 35.0
1120 35.0
1105 34.9
1050 35.0
1035 35.0
1020 35.0
1005 35.1
0950 35.1
To return to the Main Menu press the EXIT Key. To return to the Standard display press the EXIT
Key again.
TK 55533-2-OD-EN 163
(164,1)
Sec t i o n 4 - Op er at i o n
Hourmeters
The Hourmeters Menu allows the operator to view the unit hourmeters that have the view feature
enabled in the Guarded Access Menu. If the view feature for a particular hourmeter is not
enabled, that hourmeter will continue to accumulate time but cannot be viewed from the Main
Menu. However, all hourmeters can be viewed from the Maintenance Menu, even if they are not
enabled. The hourmeters shown below are implemented.
Viewing Hourmeters
Only Hourmeters that have been enabled in Guarded Access are shown from the Main Menu.
The Hourmeters can be viewed only.
Hourmeters are displayed using the Hourmeter Display. From the Standard Display, press the
MENU Key (Figure 130, p. 163).
Figure 130. Menu Key
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Hourmeter
Menu. When the Hourmeter Menu is selected, press the SELECT Key to choose the Hourmeter
Menu (Figure 131, p. 164).
Figure 131. Select Key
MAIN MENU
SENSORS
ON
DATA LOGGER
HOURMETERS
MODE
OFF
EXIT SELECT UP DOWN
AMA1539
Press the NEXT or PREVIOUS Key to scroll through the hourmeters (Figure 132, p. 164).
Figure 132. Up/Down Keys
HOURMETERS
TOTAL UNIT RUN HOURS
ON
TOTAL ENGINE RUN HOURS
833
TOTAL ELECTRIC RUN HOURS
OFF
EXIT SELECT UP DOWN
AMA1540
Hourmeter names and definitions are shown below in the order they appear. Only hourmeters
enabled in the Guarded Access Menu will be shown. To return to the Standard Display, press the
EXIT Key.
When shipped from the factory, only these hourmeters are enabled for viewing from the Main
Menu:
• Total Unit Run Hours
• Total Engine Run Hours
164 TK 55533-2-OD-EN
(165,1)
Sec t i o n 4 - Op er a ti o n
Total Run Time Hours Total number of hours the unit has run
in both diesel and electric mode.
Electric Run Hours Total number of hours the unit has run
in electric mode.
I m p o rt a n t : If a programmable hourmeter is not enabled or the view for that hourmeter is not
turned on it will not appear in the display sequence.
Mode
The Mode Menu allows the operator to change the unit operating modes that have been enabled
in Guarded Access. Only Operating Modes that have been enabled from the Guarded Access >
Main Menu Configuration Menu will be shown.
• Turns Off Cycle Sentry Mode/Turns On Cycle Sentry Mode (If Cycle Sentry is turned Off unit
runs in Continuous). Note that selecting Cycle Sentry Mode or Continuous Mode can also be
accomplished using the Cycle Sentry Key to the right of the display.
• Allows temperature to be displayed in either Fahrenheit or Celsius degrees (if enabled from
the Guarded Access > Main Menu Configuration Menu).
• Allows the optional Fresh Air Exchange door to be opened or closed (if enabled from the
Guarded Access > Hardware Configuration Menu).
• Allows Keypad Lockout to be selected (if enabled from the Guarded Access > Main Menu
Configuration Menu).
TK 55533-2-OD-EN 165
(166,1)
Sec t i o n 4 - Op er at i o n
• Start Sleep Mode (if enabled from the Guarded Access > Main Menu Configuration Menu).
When shipped from the factory, only the Cycle Sentry/Continuous Mode is enabled.
If OptiSet Plus is in use, some modes may not be available.
To return to the Main Menu press the EXIT Key. To return to the Standard display press the EXIT
Key again.
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Mode Menu.
When the Mode Menu is selected, press the SELECT Key to choose the Mode Menu (Figure 134,
p. 166).
Figure 134. Up, Down, Select Keys
MAIN MENU
DATA LOGGER
ON
HOURMETERS
MODE
ELECTRIC ST ANDBY
OFF
EXIT SELECT UP DOWN
AMA1542
The first enabled Change Mode Menu selection will appear. To choose that function, press the
SELECT Soft Key. To Scroll through the enabled features in the Change Mode Menu, press the UP
and DOWN Soft Keys (Figure 135, p. 166).
Figure 135. Select, Up, Down Keys
CHANGE MODE
TURN ON CYCLE SENTR Y MODE
ON
FAHRENHEIT
KEYPAD LOCKOUT
START SLEEP MODE
OFF
EXIT SELECT UP DOWN
AMA1543
166 TK 55533-2-OD-EN
(167,1)
Sec t i o n 4 - Op er a ti o n
CHANGE MODE
TURN ON CYCLE SENTR Y MODE
ON
FAHRENHEIT
KEYPAD LOCKOUT
START SLEEP MODE
OFF
EXIT SELECT UP DOWN
AMA1544
If the unit is running in Cycle Sentry Mode, press the SELECT Soft Key (Figure 137, p. 167) to turn
off Cycle Sentry Mode as shown.
Figure 137. Select Key
CHANGE MODE
TURN OFF CYCLE SENTR Y
ON
OFF
EXIT SELECT
AMA1545
Confirmation screens will appear briefly, the unit will switch to Continuous Mode operation and
the Cycle Sentry Icon will disappear.
To turn Cycle Sentry back on, press the SELECT Key again.
To leave this menu without changing the setting, press the EXIT Soft Key. To return to the
Standard Display, press the EXIT Soft Key again.
N o t e : Cycle Sentry Mode can also be turned on and off using the Cycle Sentry Key on the HMI
Control Panel.
CHANGE MODE
TURN ON CYCLE SENTR Y MODE
ON
FAHRENHEIT
KEYPAD LOCKOUT
START SLEEP MODE
OFF
EXIT SELECT UP DOWN
AMA1546
Choose the desired Temperature Units using the UP and DOWN Soft Keys and press the SELECT
Soft Key to select the choice (Figure 139, p. 167).
TK 55533-2-OD-EN 167
(168,1)
Sec t i o n 4 - Op er at i o n
OFF
EXIT SELECT UP DOWN
AMA1547
CHANGE MODE
TURN ON CYCLE SENTR Y MODE
ON
FAHRENHEIT
OPEN FRESH AIR EXCHANGE
KEYPAD LOCKOUT
OFF
EXIT SELECT UP DOWN
AMA1548
To open the Fresh Air Exchange door press the SELECT Key as shown below.
Figure 141. Select Key
OFF
EXIT SELECT
AMA1550
The Fresh Air Exchange door will open. To close the Fresh Air Exchange door press the SELECT
Key again.
I m p o rt a n t : The Fresh Air Exchange feature should be used exactly as specified by the customer.
• The Fresh Air Exchange door will only be open when the unit engine is running. The door will
close when the engine shuts down to preserve unit battery life.
• The setting of the Fresh Air Exchange door will survive power off/power on cycles - if the door
is set to “Open” by the operator it will continue to open any time the engine is running until it
is set to “Close” by the operator.
168 TK 55533-2-OD-EN
(169,1)
Sec t i o n 4 - Op er a ti o n
• To leave this menu without changing the setting, press the EXIT Soft Key. To return to the
Standard Display press the EXIT Soft Key again.
Keypad Lockout
If enabled in Guarded Access > Main Menu Configuration, the keypad can be locked to prevent
unauthorized use. If the keypad is locked, only the On Key and Off Key function. The keypad will
remain locked even if the unit is turned off and back on. If Keypad Lockout is active, press and
hold any soft key for five seconds to deactivate the feature. To turn the feature on, from the
Change Mode menu choose Keypad Lockout and press the SELECT Soft Key (Figure 142, p. 168).
Figure 142. Select Key
CHANGE MODE
TURN ON CYCLE SENTR Y MODE
ON
FAHRENHEIT
KEYPAD LOCKOUT
START SLEEP MODE
OFF
EXIT SELECT UP DOWN
AMA1551
A Confirmation Request will appear. To activate Keypad Lockout press the YES Soft Key. To leave
this menu without turning the Keypad Lockout feature on, press the NO Soft Key (Figure 143, p.
169).
Figure 143. Yes, No Soft Keys
KEYPAD LOCKOUT
ON
ARE YOU SURE?
OFF
YES NO
AMA1552
If the YES Soft Key was pressed, Keypad Lockout is active. Repeat the process to turn the Keypad
Lockout feature off.
• If the keypad is locked, only the On Key and Off Key function. The keypad will remain locked
even if the unit is turned off and back on.
• If Keypad Lockout is active, press and hold any soft key for five seconds to deactivate the
feature.
• To return to the Standard Display, press the EXIT Soft Key again.
TK 55533-2-OD-EN 169
(170,1)
Sec t i o n 4 - Op er at i o n
CHANGE MODE
TURN ON CYCLE SENTR Y MODE
ON
FAHRENHEIT
KEYPAD LOCKOUT
START SLEEP MODE
OFF
EXIT SELECT UP DOWN
AMA1553
The following features are available in Sleep Mode. Follow the display prompts to select and set
the features.
• Pr o g r a m Wa k e u p T i m e : This feature allows a wakeup time to be specified. When the
selected time is reached, the unit will start and resume normal operation. If a Wakeup Time is
selected, the following features are available:
– Day to Wake Up: This feature allows the day the unit is to wake up to be specified.
– Hour to Wake Up: This feature allows the hour the unit is to wake up to be specified.
– Minute to Wake Up: This feature allows the minute the unit is to wake up to be specified.
– Run Pretrip on Wakeup: This feature allows a Pretrip Test to be automatically run when the
unit wakes up.
SmartPower™
™ Electric Standby Option
The Diesel/Electric Standby selection from the Main Menu allows the operator to manually select
diesel or electric mode operation on units equipped with the electric standby SmartPower option.
The unit can also be programmed to automatically switch to Electric Mode operation when
standby power is available and to automatically switch to Diesel Mode operation if standby
power fails or is removed. If the unit is programmed to automatically switch from diesel to
electric and/or electric to diesel, the associated screens do not appear.
• If the unit is currently operating in Diesel Mode, the ELECTRIC STANDBY selection will appear
in the Main Menu.
• If the unit is currently operating in Electric Mode, the DIESEL MODE selection will appear in
the Main Menu.
170 TK 55533-2-OD-EN
(171,1)
Sec t i o n 4 - Op er a ti o n
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
From the Main Menu choose Electric Standby and press the SELECT Soft Key (Figure 146, p. 170).
Figure 146. Select Key
MAIN MENU
HOURMETERS
ON
MODE
ELECTRIC ST ANDBY
ADJUST BRIGHTNESS
OFF
EXIT SELECT UP DOWN
AMA1555
If the unit has standby power available and is turned on, the electric standby run screen will
appear. The new mode is confirmed for 10 seconds. The unit will start and run in Electric Mode.
Any engine related Shutdown Alarms become Log Alarms when the unit is switched to Electric
Mode operation. If the unit is switched back to Diesel Mode, these alarms again become
Shutdown Alarms.
OFF YES NO
AMA1556
• Pressing the YES Soft Key will switch unit operation back to Diesel Mode.
• Pressing the NO Soft Key will allow the unit to remain in Electric Mode even though standby
power is not available.
The unit will not run and Alarm Code 91 Check Electric Ready Input will be set as a Prevent Alarm.
TK 55533-2-OD-EN 171
(172,1)
Sec t i o n 4 - Op er at i o n
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
From the Main Menu choose Diesel Mode and press the SELECT Soft Key (Figure 149, p. 171).
Figure 149. Select Key
MAIN MENU
HOURMETERS
ON
MODE
DIESEL MODE
ADJUST BRIGHTNESS
OFF
EXIT SELECT UP DOWN
AMA1558
The new mode is confirmed for 10 seconds. The unit will start and run in Diesel Mode.
Any electric standby related Shutdown Alarms become Log Alarms when the unit is switched to
Diesel Mode operation. If the unit is switched back to Electric Mode, these alarms again become
Shutdown Alarms.
Adjust Brightness
The brightness of the HMI Control Panel display can be adjusted to allow for changing ambient
light conditions. The choices available to the operator are HIGH, MEDIUM, LOW, and OFF. OFF
actually results in a very dim screen suitable for low light conditions.
Display brightness is adjusted using the Adjust Brightness Menu. From the Standard Display,
press the MENU Key (Figure 150, p. 172).
Figure 150. Menu Key
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Adjust
Brightness Menu. When the Adjust Brightness is selected, press the SELECT Key to choose the
Adjust Brightness (Figure 151, p. 172).
172 TK 55533-2-OD-EN
(173,1)
Sec t i o n 4 - Op er a ti o n
MAIN MENU
MODE
ON
ELECTRIC ST ANDBY
ADJUST BRIGHTNESS
TIME
OFF
EXIT SELECT UP DOWN
AMA1560
The Display Brightness menu will appear as shown. Press the UP or DOWN Soft Keys to select
the desired display brightness. When the desired brightness is shown, press the SELECT Soft Key
to confirm the choice (Figure 152, p. 172).
Figure 152. Select Key
AMA1561
To return to the Main Menu press the EXIT Key. To return to the Standard Display, press the EXIT
Key again.
Time
The Time and Date held by the HMI Control Panel can be checked. Time and Date cannot be
changed from the Main Menu. The time and date is accessed using the Main Menu. From the
Standard Display, press the MENU Key (Figure 153, p. 173).
Figure 153. Menu Key
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Time Menu.
When the Time Menu is selected, press the SELECT Key to choose the Time Menu (Figure 154, p.
173).
Figure 154. Select Key
MAIN MENU
ELECTRIC ST ANDBY
ON
ADJUST BRIGHTNESS
TIME
CLEAR ALL ECU F AULTS
OFF
EXIT SELECT UP DOWN
AMA1563
TK 55533-2-OD-EN 173
(174,1)
Sec t i o n 4 - Op er at i o n
The date and time held in the HMI Control Panel will be shown on the display (Figure 155, p. 173).
Time and Date cannot be changed from the Main Menu.
Figure 155. Date and Time
TIME MENU
ON
01:18 MONDA Y 10 DEC 2012
OFF
EXIT
AMA1564
To return to the Main Menu press the EXIT Key. To return to the Standard Display, press the EXIT
Key again.
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Main Menu will appear. Press the UP or DOWN Key as required to choose the Clear All ECU
Faults Menu. When the Clear All ECU Faults Menu is selected, press the SELECT Key to choose
the Clear All ECU Faults Menu (Figure 157, p. 174).
Figure 157. Select Key
MAIN MENU
ADJUST BRIGHTNESS
ON
TIME
CLEAR ALL ECU F AULTS
OFF
EXIT SELECT UP DOWN
AMA1566
The Clear All ECU Faults Prompt will appear. To clear all ECU Faults and associated Thermo King
Faults, press the CLEAR Soft Key (Figure 158, p. 174).
174 TK 55533-2-OD-EN
(175,1)
Sec t i o n 4 - Op er a ti o n
ON
CLEAR ALL ECU F AULTS
OFF
EXIT CLEAR
AMA1567
All ECU Faults and associated Thermo King Faults will be cleared.
To return to the Main Menu press the EXIT Key. To return to the Standard Display, press the EXIT
Key again.
ON
°F
OFF
SET
POINT
35GAUGES
.8
SENSORS
35
MENU
AMA1489
The Maintenance Menu is accessed from the first Main Menu screen that appears, usually the
Pretrip Menu. The third Soft Key from the left will be unlabeled. Press and hold both the Exit Soft
Key and the unlabeled Soft Key for five seconds as shown below.
AMA5000
The Maintenance Menu will appear. Press the UP and DOWN Soft Keys to scroll thru the
Maintenance Menu selections. When the desired choice is shown on the display, press the
SELECT Soft Key to access it.
TK 55533-2-OD-EN 175
(176,1)
Sec t i o n 4 - Op er at i o n
AMA5001
The Maintenance Menu choices are shown on the following pages. For detailed information, see
the individual explanations of each Maintenance Menu item in this section.
To return to the Standard Display press the EXIT Soft Key.
The HMI Control Panel will automatically return to the Standard Display 30 seconds after the last
key is pressed.
AMA5002
• The UP and DOWN Soft Keys are used to scroll through the hourmeters.
• The EXIT Soft Key returns to the Maintenance Menu.
Hourmeter Definitions
Hourmeter Name Definition
Total Run Time Hours Total number of hours the unit has run
in both diesel and electric mode.
Electric Run Hours Total number of hours the unit has run
in electric mode.
176 TK 55533-2-OD-EN
(177,1)
Sec t i o n 4 - Op er a ti o n
Gauges
The Gauge Menu allows the technician to view the unit gauges. The Gauge Menu can also be
accessed from the Standard Display and the Main Menu.
Choose Gauges by pressing the SELECT Soft Key when GAUGES is chosen in the Maintenance
Menu. The Gauges Menu appears as shown below.
BATTERY VOLTAGE
ON
13. 8 v
OFF
EXIT LOCK BACK NEXT
AMA1526
• The NEXT and BACK Soft Keys are used to scroll through the gauges.
• The LOCK Soft Key allows a gauge display to be “locked” on the display for 15 minutes at the
operator’s discretion.
• The EXIT Soft Key returns to the Maintenance Menu.
Not all gauges are available on all units. Only gauges used by the specific unit configuration will
appear.
The I/O submenu shows the state of each named device – either On/Off, or Low or OK.
Gauge List
N o t e : Not all gauges may appear.
TK 55533-2-OD-EN 177
(178,1)
Sec t i o n 4 - Op er at i o n
Sensors
The Sensors Menu allows the technician to view the unit temperature sensors. The Sensors
Menu can also be accessed from the Standard Display.
Choose sensors by pressing the SELECT Soft Key when SENSORS is chosen in the Maintenance
Menu. The SENSORS screen appears as shown below.
ON
48. 3 °F
OFF
EXIT LOCK BACK NEXT
AMA1529
• The NEXT and BACK Soft Keys are used to scroll through the sensors.
• The LOCK Soft Key allows a sensor display to be “locked” on the display to prevent the
display from timing out.
• The EXIT Soft Key returns to the Maintenance Menu.
Sensor List
• Control Return Air Temperature
• Display Return Air Temperature
• Control Discharge Air Temperature
178 TK 55533-2-OD-EN
(179,1)
Sec t i o n 4 - Op er a ti o n
Alarms
The Alarms Menu allows the technician to view all alarms and clear most alarms. The Alarms
Menu is also available from the Main Menu.
Alarms may be one of four types.
Log Alarms
Log Alarms are indicated for 30 seconds each time the unit is turned on. This level of alarm
serves as a notice to take corrective action before a problem becomes severe. Maintenance items
such as maintenance hourmeter time-outs are log alarms. The TemperatureWatch screen is not
disabled if only log alarm(s) are active.
When the unit is turned on, the display will show the Thermo King Logo and then the
“Configuring System” message. If Log Alarm(s) are present, the Log Alarm notice will appear on
the display for 30 seconds as shown below. The remote indicator alarm light (if installed) will
also be on during this period. After 30 seconds, the Standard Display will appear and the remote
indicator alarm light will go off.
N o t e : The Alarm Icon does not appear on startup with log alarms present.
AMA1510
N o t e : If required, an engine start may occur while the display above is shown. This is normal
operation.
Check Alarms
Check Alarms are indicated by a steady Alarm Icon. This level of alarm serves as a notice to take
corrective action before a problem becomes severe. The remote indicator alarm light (if installed)
will be on. The unit will run with check alarms but some features and functions may be inhibited.
The TemperatureWatch screen is disabled if a Check Alarm is active.
TK 55533-2-OD-EN 179
(180,1)
Sec t i o n 4 - Op er at i o n
ON
OFF
SET
35
POINT
GAUGES SENSORS
35
MENU
AMA1511
Prevent Alarms
Prevent Alarms are also indicated by a steady Alarm Icon in the display. The remote indicator
alarm light (if installed) will be on. The unit will attempt to resolve the situation as shown below:
• The unit will be temporarily shut down if a Prevent Alarm is active.
• The TemperatureWatch screen is disabled if a Prevent Alarm is active.
• The unit will remain shut down for a timed restart interval or until the fault conditions are
corrected.
• If the unit is in a temporary shutdown, Alarm Code 84 Restart Null will be present along with
the associated Prevent Alarm.
• The unit will restart and run (in most cases with forced reduced performance) to determine if
continued operation is possible. The unit will run in this manner for a timed interval. If the
unit is running with forced reduced performance, Alarm Code 85 Forced Unit Operation will
also be present under some conditions.
• If the alarm does not reoccur during the timed running interval with reduced performance,
the unit will return to full performance to determine if continued operation is possible. The
unit will run in this manner for a timed interval. If the unit is successfully able to return to full
performance for the timed interval without the alarm re-occurring, the alarm is auto cleared
and the unit will run normally.
• All Prevent Alarm events and conditions are logged by the ServiceWatch Data Logger.
• In general, if the alarm condition re-occurs a defined number of times, the alarm is set as a
Shutdown Alarm and no further restarts are possible.
N o t e : If the Restart After Shutdown feature in the Guarded Access Menu is set for
CONTINUOUS, an unlimited number of restart attempts are allowed.
Shutdown Alarms
Shutdown Alarms are indicated by the following:
• The Alarm Icon will appear.
• The display and backlight will flash on and off.
• The display will switch from normal to inverted and back (light areas become dark and dark
areas become light.)
ON
OFF SET
35
POINT
GAUGES SENSORS
35
MENU
AMA1512
Shutdown alarms will force the unit into shutdown. The unit will remain in shutdown until the
shutdown alarm is manually cleared. Exceptions are some engine and electric shutdown alarms
that become log alarms when switched to the alternate operating mode (diesel to electric or
electric to diesel). The TemperatureWatch screen is disabled if a unit level shutdown alarm is
active.
180 TK 55533-2-OD-EN
(181,1)
Sec t i o n 4 - Op er a ti o n
Displaying Alarms
Choose Alarms by pressing the SELECT Soft Key when ALARMS is chosen in the Maintenance
Menu. The Alarms screen appears as shown below:
AMA5003
Clearing Alarms
Most alarm codes can be cleared conventionally from the Alarm Menu using the CLEAR Soft Key.
The following control and display sensor alarm codes can only be cleared from the Maintenance
Menu or Guarded Access Menu:
• Alarm Code 03 Check Control Return Air Sensor
• Alarm Code 04 Check Control Discharge Air Sensor
• Alarm Code 74 Controller Reset to Defaults (Guarded Access Only)
• Alarm Code 203 Check Display Return Air Sensor
• Alarm Code 204 Check Display Discharge Air Sensor
The following alarm codes clear automatically:
• Alarm Code 64 Pretrip Reminder – Clears when a Pretrip Test is performed.
• Alarm Code 84 Restart Null – Clears when the unit is no longer in a restart null due to a
Prevent Alarm.
• Alarm Code 85 Forced Unit Operation – Clears when the unit is no longer running in a forced
mode due to a Prevent Alarm.
• Alarm Code 91 Check Electric Ready Input – Clears automatically when the unit starts running.
• Alarm Code 92 Sensor Grades Not Set – Clears when all required sensor grades are changed
from 5H.
If the Limited Alarm Restarts feature is enabled the following additional alarm codes may only be
cleared from the Guarded Access Menu. If this is the case, the CLEAR Soft Key will not appear if
the alarms are displayed from the Main Menu or the Maintenance Menu. Refer to the Limited
Alarm Restarts feature in Section 3 for details.
• Alarm Code 10 High Discharge Pressure
• Alarm Code 23 Cooling Cycle Fault
• Alarm Code 24 Heating Cycle Fault
• Alarm Code 32 Refrigeration Capacity Low
TK 55533-2-OD-EN 181
(182,1)
Sec t i o n 4 - Op er at i o n
Alarm Notes
I m p o rt a n t :
1. If an alarm will not clear, it may still exist. If the alarm is not corrected, it will not
clear or may be immediately set again.
2. If an alarm cannot be cleared from the Main menu, the Clear Soft Key will not
appear. These alarms must be cleared from the Maintenance or Guarded Access
Menus.
3. All alarms must be viewed before any of the alarms can be cleared.
4. Shutdown Alarms should receive immediate attention if the truck or trailer is
loaded.
AMA5004
The SERVICE TEST Selection Menu appears as shown below. Use the + and – Soft Keys to scroll
through the available tests. When the desired test is shown, press the YES Soft Key to select it.
AMA5005
The test shown is the High Speed Cool test. Return, Discharge and Evaporator Coil temperatures
are shown. The Temperature Differential is also calculated and displayed.
182 TK 55533-2-OD-EN
(183,1)
Sec t i o n 4 - Op er a ti o n
AMA5006
• A test will remain active for 15 minutes. A countdown timer shows the time remaining for the
test. If the test times out the test will terminate, the unit will be shut down (if running) and
Alarm Code 54 Test Mode Timeout will be set.
• The GAUGES Soft Key is used to scroll through the gauges.
• The TEST Soft Key allows the various tests to be selected.
• The EXIT Soft Key returns to the Maintenance Menu.
Not all tests are available on all units. Only tests used by the specific unit configuration will
appear.
• Cool Bypass
Off/Null
Defrost ON ON Enabled ON
TK 55533-2-OD-EN 183
(184,1)
Sec t i o n 4 - Op er at i o n
If a Condenser Fan or Evaporator Blower Test is selected, only that fan or blower will be
energized.
Null
Cool ON ON Enabled
Defrost ON ON ON ON Enabled ON
If a Condenser Fan or Evaporator Blower Test is selected, only that fan or blower will be
energized.
AMA5007
184 TK 55533-2-OD-EN
(185,1)
Sec t i o n 4 - Op er a ti o n
AMA5008
• The NEXT and BACK Soft Keys are used to scroll through the tests.
• The SELECT Soft Key starts the selected test.
• The EXIT Soft Key returns to the Maintenance Menu.
TK 55533-2-OD-EN 185
(186,1)
Sec t i o n 4 - Op er at i o n
• Brightness Test – This test allows the technician to select Low, Medium or High backlight
intensity.
• Buzzer Test – This test allows the technician to turn the HMI buzzer on and off to verify
operation.
• Heater Output – This test allows the technician to turn the HMI display heater on and off.
• Serial E2 – This test allows the technician to perform an internal HMI memory test. The test
takes less than one second and the results are reported as PASS or FAIL.
• Data Log Flash – This test allows the technician to perform an internal HMI CargoWatch data
logger memory test. The test takes less than one second and the results are reported as PASS
or FAIL.
• RTC Update – This test allows the technician to perform an internal HMI real time clock test.
The test takes less than three seconds and the results are reported as PASS or FAIL.
Evacuation Test
This menu allows the technician to open all normally closed refrigeration system valves to
evacuate and charge the unit with refrigerant. If the battery voltage falls below 13.0 VDC the
technician is prompted to connect a battery charger to maintain sufficient voltage to hold all
valves open.
I m p o rt a n t : Evacuation mode has no time-out. The unit will remain in Evacuation Mode
indefinitely unless the battery voltage becomes excessive.
All selectable unit features will be disabled when in evacuation mode. Auto switch from diesel to
electric or from electric to diesel is allowed, but unit will not start.
• Evacuation mode is not allowed if:
– Any shutdown alarms are present.
– The unit is in restart null.
– The unit is in a start sequence.
• When in evacuation mode:
– If the unit is running it will shut down automatically when entering Evacuation Mode.
– Alarm Code 86 Check Discharge Pressure Sensor is disabled.
– Alarm Code 87 Check Suction Pressure Sensor is disabled.
– Door switch operation is disabled.
Choose Evacuation Test by pressing the SELECT Soft Key when EVACUATION TEST is shown by
the Maintenance Menu. The Evacuation Test display shown below will appear and remain on the
display so long as the battery voltage does not fall below 13.0 VDC. All normally closed
refrigerant valves are energized to the open position to allow system evacuation to effectively
remove air and moisture from the refrigeration system.
AMA5009
If the battery voltage falls below 13.0 VDC, the technician is prompted to install a battery charger
to guarantee sufficient voltage to keep all valves open during the evacuation process.
186 TK 55533-2-OD-EN
(187,1)
Sec t i o n 4 - Op er a ti o n
AMA5010
If the voltage from the battery charger rises above 16 Vdc, the controller will be turned off to
prevent damage to the electronics and/or system components.
• To exit Evacuation Mode press the EXIT Soft Key or turn the unit off.
Software Revision
This menu allows the technician to view the current installed software revision for the HMI
Control Panel and the Base Controller.
Choose Software Revision by pressing the SELECT Soft Key when SOFTWARE REVISION is
shown by the Maintenance Menu. The Software Revision display appears as shown below.
BA20
AMA5011
The NEXT and BACK Soft Keys allow the technician to scroll through the software revisions.
Software revisions appear in the order shown below:
• Display Software Revision
• Controller Software Revision
• Supervisor Software Revision (Determined by HMI Control Panel software revision)
The ThermoServ Service Tool is used to flash software updates to the HMI Control Panel and
Base Controller.
AMA5012
TK 55533-2-OD-EN 187
(188,1)
Sec t i o n 4 - Op er at i o n
The – and + Soft Keys are used to change the hour as required. Pressing the YES Soft Key
changes the hour to the selected time and then shows the next Time/Date screen. The screens
appear in the order shown below:
• Hour
• Minute
• Date (Day)
• Month
• Year
Time Zone
This menu allows the technician to view and change the Time Zone.
Choose Time Zone by pressing the SELECT Soft Key when Time Zone is shown by the
Maintenance Menu. The Time Zone Menu appears as shown below.
AMA5013
The UP and Down Soft Keys are used to change the Time Zone as required. Pressing the SELECT
Soft Key changes the Time Zone to the selected zone. The screens appear in the order shown
below:
• Eastern Time
• Central Time
• Mountain Time
• Pacific Time
188 TK 55533-2-OD-EN
(189,1)
Sec t i o n 4 - Op er a ti o n
N o t e : The Guarded Access Menu is entered from the last feature of the Maintenance Menu. The
unit must not be running in order to enter the Guarded Access Menu. If the unit is running,
entering Output Test Mode from the Maintenance menu will shut the unit down. Press the
EXIT Key to return to the Maintenance Menu and continue scrolling to the end of the
Maintenance Menu to enter the Guarded Access Menu
ON
°F
OFF
SET
POINT
35
GAUGES
.8
SENSORS
35
MENU
AMA1489
The Maintenance Menu is accessed from the first Main Menu screen that appears, usually the
Pretrip Menu. The third Soft Key from the left will be unlabeled. Press and hold both the Exit Soft
Key and the unlabeled Soft Key for five seconds as shown below.
AMA5014
The Maintenance Menu will appear. Press the DOWN Soft Key to scroll to CONNECT ENGINE
SERVICE TOOL at the end of the Maintenance Menu choices. The fourth Soft Key from the left will
be unlabeled. Press and hold both the unlabeled soft key and the Exit Key for five seconds.
N o t e : Guarded Access cannot be entered if the unit is running. If the unit is running, when
scrolling thru the Maintenance Menu enter Output Test Mode to shut the unit down. Press
the EXIT Key to return to the Maintenance Menu and continue scrolling to the end of the
Maintenance Menu.
AMA5015
I m p o rt a n t : If a Security Code has been set the correct code must be entered here to gain access
to the Guarded Access Menu. If an Access Code is requested and the code is not
known, enter 4444.
If an Access Code is not enabled or when the correct security code is entered (4444 always
works), the first Guarded Access Menu feature will appear. Press the UP and DOWN Soft Keys to
scroll thru the Guarded Access Menu choices. When the desired choice is shown on the display,
press the SELECT Key to access it.
TK 55533-2-OD-EN 189
(190,1)
Sec t i o n 4 - Op er at i o n
AMA5016
190 TK 55533-2-OD-EN
(191,1)
Sec t i o n 4 - Op er a ti o n
55533-2-4-10
I m p o rt a n t : There are several versions of the Rear Remote Control Panel available. They can be
identified by the color of the wide border around the actual control panel. SR-4 Single
Temperature Rear Remote Control Panels have a black border. SR-4 Multi-
Temperature Rear Remote Control Panels have a blue border. They are two separate
control panels and are not interchangeable.
TK 55533-2-OD-EN 191
(192,1)
Sec t i o n 4 - Op er at i o n
Remote Control Panel OFF Key will turn the unit off. The HMI Control Panel on the unit must be
used to start and stop unit operation.
In addition to turning the unit on and off, when set to STAND BY the Rear Remote Control Panel
allows the following:
• Turn the unit on and off
• The unit will not start and run
• Change the Setpoint
• Select Cycle Sentry or Continuous Mode (unless prevent by OptiSet Plus)
• Display discharge air temperature
• Display and clear alarm codes
• Send a Start of Trip marker to the ServiceWatch and CargoWatch Data Loggers
However, when in STAND BY, the engine will not start and a Defrost Cycle or Pretrip Test cannot
be initiated.
If the control system is powered up from the remote control panel a stand by message will
appear in both the remote control panel display and the unit HMI Control Panel display as shown
below:
55533-2-4-1 1 55533-2-4-12
When the StAnd bY display is shown, press the Select Key to show the Remote Standard Display.
When the remote standard Display is shown, the setpoint and operating mode can be changed,
the discharge air temperature can be displayed and alarms can be viewed and cleared. In
addition, a Start of Trip can be sent to the data loggers.
After the last key is pressed, the display will return to the StAnd bY display shown above in about
10 seconds.
Keypad
55533-2-4-13
The nine touch sensitive keys are used to turn the unit on and off. They also allow the setpoint to
be changed, Cycle Sentry or Continuous Mode to be selected, Alarm Codes and other operating
data to be displayed and Pretrip Tests and Defrost Cycles to be performed. A Start of Trip marker
can also be sent to the data loggers.
192 TK 55533-2-OD-EN
(193,1)
Sec t i o n 4 - Op er a ti o n
Allows Cycle Sentry to be turned on and off, displays the discharge air
SELECT KEY
temperature and alarms.
Display
55533-2-4-13
The display normally shows the Standard Display of return air temperature and setpoint. The
icons on either side of the display indicate operating modes and alarms. The display shown here
has all possible segments lighted. The display icons are defined below:
TK 55533-2-OD-EN 193
(194,1)
Sec t i o n 4 - Op er at i o n
Alarm Icon This icon appears when an alarm condition has been detected.
This icon appears during a remote control panel test but is not
Not Used
currently used.
55533-2-4-14
194 TK 55533-2-OD-EN
(195,1)
Sec t i o n 4 - Op er a ti o n
55533-2-4-15
55533-2-4-16
55533-2-4-17
TK 55533-2-OD-EN 195
(196,1)
Sec t i o n 4 - Op er at i o n
5533-2-4-18
2. When the desired setpoint is shown on the display, immediately press the Enter Key to load
the new setpoint. The display will briefly show [Lod] and then the new setpoint will reappear
in the display.
55533-2-4-19
I m p o rt a n t : The Enter Key must be pressed or the setpoint will not be changed. The display will
return to the Standard Display and the setpoint will return to the old setpoint in about
10 seconds if the Enter Key is not pressed. A l a r m C o d e 1 2 7 Se t p o i n t N o t E n t e r e d is
set, to indicate that the setpoint change was started but not completed.
I m p o rt a n t : Confirm that the correct setpoint is set.
55533-2-4-20
2. Use the Up and Down Arrow Keys to chose either YES or nO. Yes = Cycle Sentry Mode. nO =
Continuous Mode.
196 TK 55533-2-OD-EN
(197,1)
Sec t i o n 4 - Op er a ti o n
55533-2-4-21
3. When the desired selection is shown, press the Enter Key to load the setting. The display will
briefly show [Lod] and then the new selection will briefly appear in the display.
55533-2-4-22
55533-2-4-23
TK 55533-2-OD-EN 197
(198,1)
Sec t i o n 4 - Op er at i o n
55533-2-4-24
2. To clear a displayed alarm code, press the Enter Key. The display will briefly show CLEAr
ALm.
55533-2-4-25
3. If any additional alarms are present, the next alarm will be shown. If no other alarms are
present the display will briefly show [00].
55533-2-4-26
55533-2-4-27
2. When the defrost prompt is shown, press the Enter Key to start a manual defrost. The display
will briefly show LOAd dEF and then a defrost cycle will begin if conditions allow.
198 TK 55533-2-OD-EN
(199,1)
Sec t i o n 4 - Op er a ti o n
55533-2-4-28
3. The display will return to the Remote Standard Display. The Defrost Icon will be shown in the
display.
55533-2-4-29
55533-2-4-30
2. When the Start of Trip prompt is shown, press the Enter Key to send a Start of Trip marker to
the CargoWatch and ServiceWatch data loggers. The display will briefly show LOAd SOt.
55533-2-4-31
TK 55533-2-OD-EN 199
(200,1)
Sec t i o n 4 - Op er at i o n
55533-2-4-32
3. When the Pretrip prompt is shown, press the Enter Key to start a Pretrip Test. The display will
briefly show LOAd PrE. If the unit is not running a Full Pretrip Test will be performed. If the
unit is running a Running Pretrip Test will be performed.
55533-2-4-33
4. When the Pretrip Test is running the display will show PrE trP. The HMI Control Panel will
show the Pretrip Test progress.
55533-2-4-34
5. When the Pretrip Test is complete the display will show PASS, CHEC or FAIL. Pressing the
Select Key will return to the Remote Standard Display.
200 TK 55533-2-OD-EN
(201,1)
Sec t i o n 4 - Op er a ti o n
55533-2-4-35
TK 55533-2-OD-EN 201
(202,1)
Section 5 - Diagnostics
SR-4 Diagnostics
This section is devoted to diagnostic routines designed to help the technician quickly identify the
cause of a problem and repair it using the correct tools, information, and procedures. It is
important that the required procedures be followed exactly. Failure to do so may result in an
incomplete repair.
The following hints will prove helpful:
• Download the ServiceWatch™ Data Logger using the ThermoServ™ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the
alarm are recorded when the alarm is set and cleared. This data can be very helpful in
determining the cause of the alarm.
• Every effort should be made to perform a Pretrip Test on a suspect unit. In almost all cases,
the Pretrip Test will result in one or more alarm codes that will lead you directly to the
problem.
• Operators should record all alarm codes in sequence for reference. Alarm codes are
displayed in order of occurrence, with the most recent alarm code displayed last.
• Clear all alarm codes before starting a Pretrip Test.
• Use Output Test and Service Test Mode as appropriate to verify unit operation.
• Verify all connectors at the Base Controller and HMI Control Panel are properly seated.
• Verify all outboard harness connectors are properly seated.
• Verify all programmable features are set to the customer’s specifications before releasing the
unit for service.
Electrostatic Discharge
The following electrostatic precautions must be taken:
• Keep all SR-4 Base Controllers and HMI Control Panels in anti-static bags at all times.
• When working with electrical circuits that contain microprocessors, always wear an ESD wrist
strap (TK No. 204-622) and connect the opposite end to the chassis ground or CH terminal.
This precaution will prevent electrostatic discharge from damaging circuits.
Physical Protection
Protect any defective SR-4 Base Controller and HMI control panels from physical damage by
placing them in the shipping carton supplied with the replacement. They will be returned for
failure analysis and possible remanufacture.
Alarm Types
There are four types of alarms.
202 TK 55533-2-OD-EN
(203,1)
Se c ti o n 5 - D i a g n o st i c s
Log Alarms
Log Alarms are indicated for 30 seconds each time the unit is turned on. This level of alarm
serves as a notice to take corrective action before a problem becomes severe. Maintenance items
such as maintenance hourmeter time-outs are Log Alarms. The Temperature Watch screen is not
disabled if only Log Alarm(s) are active.
When the unit is turned on, the display will show the Thermo King Logo and then the
“Configuring System” message. If Log Alarm(s) are present, the Log Alarm notice will appear on
the display for 30 seconds. The remote indicator alarm light (if installed) will also be on during
this period. After 30 seconds, the Standard Display will appear and the remote indicator alarm
light will go off.
N o t e : The Alarm Icon does not appear on startup with Log Alarms present.
Check Alarms
Check Alarms are indicated by a steady alarm indication at the top of the display and the
message “Service Required within 24 Hours”. The Alarm Icon will appear. This level of alarm
serves as a notice to take corrective action before a problem becomes severe. The unit will run
with Check Alarms but some features and functions may be inhibited. The TemperatureWatch
screen is disabled if a Check Alarm is active.
Prevent Alarms
Prevent Alarms are indicated by a steady alarm indication at the top of the display and the
message “Service Required within 24 Hours”. The Alarm Icon will appear. The unit will be
temporarily shut down if a Prevent Alarm is active. The unit will remain shut down for a timed
restart interval or until the fault conditions are corrected and then restart. If the unit is in a
temporary shutdown, Alarm Code 84 Restart Null will be present along with the associated
Prevent Alarm. In most cases, the unit will restart with reduced performance to determine if
continued operation is possible. If the alarm does not reoccur with reduced performance, the unit
will return to full performance. If the unit is operating with reduced performance, Alarm Code 85
Forced Unit Operation will also be present under some conditions. In general, if the alarm
condition reoccurs a defined number of times, the alarm is set as a Shutdown Alarm and no
further restarts are possible. The Temperature Watch screen is disabled if a prevent alarm is
active.
N o t e : If the Restart After Shutdown feature in the Guarded Access Menu is set for CONTINUOUS,
an unlimited number of restart attempts are allowed.
Shutdown Alarms
Depending on software revisions, Shutdown Alarms may be indicated by the following:
• The Alarm Icon will appear.
• The display and backlight will flash on and off.
• The display will switch from normal to inverted and back (light areas become dark and dark
areas become light).
Shutdown Alarms will force the unit into shutdown. The unit will remain in shutdown until the
Shutdown Alarm is manually cleared. Exceptions are some engine and electric Shutdown Alarms
that become Log Alarms when switched to the alternate operating mode (diesel to electric or
electric to diesel). The TemperatureWatch screen is disabled if a unit level Shutdown Alarm is
active.
TK 55533-2-OD-EN 203
(204,1)
Sec t i o n 5 - Di a g n o s t ic s
204 TK 55533-2-OD-EN
(205,1)
Se c ti o n 5 - D i a g n o st i c s
00 NO ALARMS EXIST
No action required.
TK 55533-2-OD-EN 205
(206,1)
Sec t i o n 5 - Di a g n o s t ic s
3. If the differential between the coil and other sensors is too large when Alarm Code 02 is
cleared, Alarm Code 02 and Alarm Code 13 Sensor Calibration Check are set as Check Alarms.
This condition is termed a soft sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F
(-46°C), Alarm Code 02 and Alarm Code 13 Sensor Calibration Check are set as Check Alarms.
This condition is termed a soft sensor failure.
How Alarm is Cleared
This alarm can be cleared manually. When the alarm is cleared, the return air sensors, discharge
air sensors, and evaporator coil sensor must all read within 30°F (17°C) of each other. If they do
not, it is assumed that the sensor reading is not accurate. The alarm code is not cleared and
Alarm Code 13 Sensor Calibration Check will also be set. Also, if the sensor is over or under
range when the alarm clear is attempted, the alarm will not be cleared.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
• Al a r m C o d e 0 2 ( Se n s o r wa s o u t o f r a n g e ) :
1. Display the sensor reading using the Sensor Menu. If the display shows [- - - -], the sensor
is defective and should be replaced. If the condition still exists, check the sensor circuit for
an open wire or short to ground (Refer to Service Procedure D01A). Check the Base
Controller in accordance with Service Procedure A01A.
2. If the display is normal proceed as shown below.
• A l a r m C o d e 0 2 a n d A l a r m C o d e 1 3 ( S e n s o r wa s r e a d i n g e rr a t i c a l l y ) :
1. Review the ServiceWatch data logger and check the sensor reading at the time the alarm
was set. Also review the history to see if previous alarm codes exist that would indicate an
intermittent problem. If the sensor appears to have read incorrectly, it should be replaced.
2. If the problem reoccurs, check the sensor connector/sensor circuit in accordance with
Service Procedure D01A.
• I f a l l o r m a ny o f t h e S e n s o r C o d e s ( 0 2 , 0 3 , 0 4 , 0 5 , 0 6 , 11 , 1 2 a n d 1 3 ) a r e s e t :
1. Verify the 35 pin Base Controller sensor connector J1 is securely attached.
2. Check the Base Controller in accordance with Service Procedure A01A.
206 TK 55533-2-OD-EN
(207,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 207
(208,1)
Sec t i o n 5 - Di a g n o s t ic s
Alarm Code 03 if the control return air sensor failed). Alarm Code 13 will not be set if a hard
failure occurs.
N o t e : The controller may not be currently showing dashes for the sensor reading, but the
alarm will be present when the unit is inspected. If a sensor alarm code is set, a failure
did occur at some point. Checking the ServiceWatch data logger download will indicate
when the hard failure occurred.
How Alar m is Set
1. If the sensor reading is over 200°F (93°C) for 10 seconds, Alarm Code 03 is set as a Check
Alarm. The sensor reading will display dashes [ - - - ] and may return to normal. This
condition is termed a hard sensor failure.
2. If the sensor reading is under -50°F (-46°C) for 10 seconds, Alarm Code 03 is set as a Check
Alarm. The sensor reading will display dashes [ - - - ] and may return to normal. This
condition is termed a hard sensor failure.
3. If the differential between the return air temperature and other temperature sensors is too
large when Alarm Code 03 is cleared, Alarm Code 03 and Alarm Code 13 Sensor Calibration
Check are set as Check Alarms. This condition is termed a soft sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F
(-46°C), Alarm Code 03 and Alarm Code 13 Sensor Calibration Check are set as Check Alarms.
This condition is termed a soft sensor failure.
5. If the sensor grade for this sensor is set to 5H, Alarm Code 03 and Alarm Code 92 Sensor
Grades Not Set are set as Check Alarms.
6. The temperatures of the control return air sensor and display return air sensor twins are not
within a specified range. If the faulty sensor can be determined, only the alarm code for that
sensor and Alarm Code 13 Sensor Calibration Check will be set. Alarm Codes 03 Check
(Control) Return Air Sensor, 203 Check Display Return Air Sensor, and 13 Sensor Calibration
Check are set if the faulty sensor cannot be determined.
How Alarm is Cleared
N o t e : This alarm can only be cleared manually from the Guarded Access menu.
When the alarm is cleared the return air sensors, discharge air sensors and evaporator coil
sensor must all read within 30°F (17°C) of each other. If they do not, it is assumed that the sensor
reading is not accurate. The alarm code is not cleared and Alarm Code 13 Sensor Calibration
Check will also be set. Also, if the sensor is over or under range when the alarm clear is
attempted, the alarm will not be cleared.
If the alarm is set by condition #5 above, Alarm Code 92 will clear automatically if the sensor
grade is changed from 5H. If the sensor grade remains 5H, Alarm Code 92 can not be cleared.
Prog ram m ab le Fe a tur es
This is a graded sensor. The sensor grade must be correctly set in the Guarded Access Menu.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
• Al a r m C o d e 0 3 ( Se n s o r wa s o u t o f r a n g e ) :
1. Display the sensor reading using the Sensor Menu. If the display shows [- - - -], the sensor
is defective and should be replaced. If the condition still exists, check the sensor circuit for
an open wire or short to ground (Refer to Service Procedure D01A). Check the Base
Controller in accordance with Service Procedure A01A.
2. If the display is normal, proceed as shown below.
• A l a r m C o d e 0 3 a n d A l a r m C o d e 1 3 ( S e n s o r d r i ft e d o r w a s r e a d i n g e rr a t i c a l l y ) :
1. Review the ServiceWatch data logger and check the senor reading at the time the alarm
was set. Also, review the history to see if previous alarm codes exist that would indicate
an intermittent problem. If the sensor appears to have read incorrectly, it should be
replaced.
208 TK 55533-2-OD-EN
(209,1)
Se c ti o n 5 - D i a g n o st i c s
2. Verify the sensor grades are set to the actual sensor grade.
3. Check for an airflow obstruction and correct sensor mounting.
4. If the problem reoccurs, check the sensor connector/sensor circuit in accordance with
Service Procedure D01A.
• Al a r m C o d e 0 3 a n d A l a r m C o d e 9 2 ( Se n s o r g r a d e s e t t o 5 H ) :
1. Verify and set the sensor grade.
• Al a rm Code 03 an d/ or A la rm Cod e 2 03 a re s e t wi th A l a rm C ode 13 (D ua l s e ns or s d on’ t
agree):
1. Review the ServiceWatch data logger and check the senor readings at the time the alarm
was set. Also, review the history to see if previous alarm codes exist that would indicate
the problem sensor. If a sensor appears to have read incorrectly, it should be replaced.
2. Check for an airflow obstruction and correct sensor mounting. Verify the brass clamp is
installed on the two return air sensors.
3. Verify the sensor grades are set to the actual sensor grade, and are not transposed.
4. If the offending sensor cannot be determined, either ice bath both return air sensors
simultaneously to determine which sensor is inaccurate or replace both sensors.
• I f a l l o r m a ny o f t h e S e n s o r C o d e s ( 0 2 , 0 3 , 0 4 , 0 5 , 0 6 , 11 , 1 2 , 2 0 3 a n d 2 0 4 ) a r e s e t :
1. Verify the 35 pin Base Controller sensor connector J1 is connected securely.
2. Check the Base Controller in accordance with Service Procedure A01A.
TK 55533-2-OD-EN 209
(210,1)
Sec t i o n 5 - Di a g n o s t ic s
210 TK 55533-2-OD-EN
(211,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 211
(212,1)
Sec t i o n 5 - Di a g n o s t ic s
212 TK 55533-2-OD-EN
(213,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 213
(214,1)
Sec t i o n 5 - Di a g n o s t ic s
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
• Al a r m C o d e 0 5 ( Se n s o r wa s o u t o f r a n g e ) O n l y :
1. Display the sensor reading using the Sensor Menu. If the display shows [- - - - ], the sensor
is defective and should be replaced. If the condition still exists, check the sensor circuit for
an open wire or short to ground (Refer to Service Procedure D01A). Check the Base
Controller in accordance with Service Procedure A01A.
2. If the display is normal, proceed as shown below.
• A l a r m C o d e 0 5 a n d A l a r m C o d e 1 3 ( S e n s o r d r i ft e d o r w a s r e a d i n g e rr a t i c a l l y ) :
1. Review the ServiceWatch data logger and check the sensor reading at the time the alarm
was set. Also, review the history to see if previous alarm codes exist that would indicate
an intermittent problem. If the sensor appears to have read incorrectly, it should be
replaced.
2. Check for an airflow obstruction and correct sensor mounting.
3. If the problem reoccurs, check the sensor connector/sensor circuit in accordance with
Service Procedure D01A.
• I f a l l o r m a ny o f t h e S e n s o r C o d e s ( 0 2 , 0 3 , 0 4 , 0 5 , 0 6 , 11 , 1 2 , 2 0 3 a n d 2 0 4 ) a r e s e t :
1. Verify the 35 pin Base Controller sensor connector J1 is connected securely.
2. Check the Base Controller in accordance with Service Procedure A01A.
214 TK 55533-2-OD-EN
(215,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 215
(216,1)
Sec t i o n 5 - Di a g n o s t ic s
216 TK 55533-2-OD-EN
(217,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 217
(218,1)
Sec t i o n 5 - Di a g n o s t ic s
218 TK 55533-2-OD-EN
(219,1)
Se c ti o n 5 - D i a g n o st i c s
4. Check the High Pressure Cutout Switch circuit for shorts to ground or open circuits.
5. Check the Base Controller High Pressure Cutout fuse F25.
6. Check the discharge pressure transducer for correct and accurate readings.
7. Check the refrigeration system valves for correct operation. A fault that prevents refrigerant
flow from the system high side to the system low side may create high discharge pressure.
8. Review the ServiceWatch download in technician level view. The associated alarm data will
show the status of the HPCO switch and the discharge pressure at the time the alarm was set.
If this data indicates that the HPCO switch opened but the discharge pressure remained within
acceptable limits, the actual problem is a defective HPCO switch, not high discharge pressure.
TK 55533-2-OD-EN 219
(220,1)
Sec t i o n 5 - Di a g n o s t ic s
220 TK 55533-2-OD-EN
(221,1)
Se c ti o n 5 - D i a g n o st i c s
12 SENSOR SHUTDOWN
A l a r m Ty p e
Check or Shutdown
Associated Alarm Codes
03 Check (Control) Return Air Sensor
04 Check (Control) Discharge Air Sensor
203 Check Display Return Air Sensor
204 Check Display Discharge Air Sensor
Co mpon en t Description and Location
See Alarm Codes indicated above.
Circuit Description
See Alarm Codes indicated above.
How Alar m is Set
Fresh Setpoints: Both return and discharge sensors have failed or have been disabled by the dual
sensor alarm control. With a fresh range setpoint the alarm is set as a Shutdown Alarm.
Frozen Setpoints: Both return and discharge sensors have failed or have been disabled by the
dual sensor alarm control. With a frozen range setpoint the alarm is set as a Check Alarm. The
unit will be forced into continuous low speed cool.
How Alarm is Cleared
This alarm is cleared automatically when the associated sensor Alarm Codes 03 and 04 are
cleared.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
1. Determine which sensor Alarm Codes (03, 04, 203, or 204) are present. Proceed as shown for
that Alarm Code.
TK 55533-2-OD-EN 221
(222,1)
Sec t i o n 5 - Di a g n o s t ic s
222 TK 55533-2-OD-EN
(223,1)
Se c ti o n 5 - D i a g n o st i c s
N o t e : The controller may not be currently showing dashes for the sensor reading, but the alarm
will be present when the unit is inspected. If a sensor alarm code is set, a failure did occur
at some point. Checking the ServiceWatch data logger download will indicate when the
hard failure occurred.
TK 55533-2-OD-EN 223
(224,1)
Sec t i o n 5 - Di a g n o s t ic s
224 TK 55533-2-OD-EN
(225,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 225
(226,1)
Sec t i o n 5 - Di a g n o s t ic s
226 TK 55533-2-OD-EN
(227,1)
Se c ti o n 5 - D i a g n o st i c s
C AU T I O N
H a z a r d o u s Pr e s s u r e s !
Do no t remov e e xp an si on t an k ca p w hi l e cool a nt i s ho t.
2. Check the engine coolant level. Bleed air from the cooling system if necessary.
3. Check the water pump drive belt.
4. Check the radiator for airflow and coolant flow restrictions.
TK 55533-2-OD-EN 227
(228,1)
Sec t i o n 5 - Di a g n o s t ic s
5. Check the Water Temperature Sensor in accordance with Alarm Code 06.
228 TK 55533-2-OD-EN
(229,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 229
(230,1)
Sec t i o n 5 - Di a g n o s t ic s
6. Check the 20B wire in the Main Harness with an ohmmeter for continuity in accordance with
Service Procedure H04A.
7. Connect an external oil pressure gauge and confirm that adequate oil pressure (20 psig or
above) is present when the unit is running.
230 TK 55533-2-OD-EN
(231,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 231
(232,1)
Sec t i o n 5 - Di a g n o s t ic s
232 TK 55533-2-OD-EN
(233,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 233
(234,1)
Sec t i o n 5 - Di a g n o s t ic s
234 TK 55533-2-OD-EN
(235,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 235
(236,1)
Sec t i o n 5 - Di a g n o s t ic s
236 TK 55533-2-OD-EN
(237,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 237
(238,1)
Sec t i o n 5 - Di a g n o s t ic s
28 PRETRIP ABORT
A l a r m Ty p e
Shutdown
Associated Alarm Codes
The active associated alarm codes.
How Alar m is Set
If a Shutdown Alarm occurs during a Pretrip test, Alarm Code 28 is set and the unit is shut down.
The alarm condition that caused the shutdown is also set. Alarm Code 28 is also set if the unit is
turned off while a Pretrip Test is in progress.
How Alarm is Cleared
This alarm is cleared manually.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
1. This is a normal alarm any time the Pretrip Test is terminated before the completion of all
tests.
2. Proceed with the corrective actions for any alarm codes that occurred.
3. After repairs, repeat the Pretrip Test. Refer to Section 4 for details.
4. If only Alarm Code 28 is set, the unit may have been turned off during a Pretrip Test, or the
test may have been interrupted by a communications request. Clear the alarm and repeat the
Pretrip Test.
238 TK 55533-2-OD-EN
(239,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 239
(240,1)
Sec t i o n 5 - Di a g n o s t ic s
6. Check the 20B wire in the Main Harness with an ohmmeter for continuity in accordance with
Service Procedure H04A.
7. Connect an external oil pressure gauge and confirm that adequate oil pressure (20 psig or
above) is present when the unit is running.
240 TK 55533-2-OD-EN
(241,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 241
(242,1)
Sec t i o n 5 - Di a g n o s t ic s
242 TK 55533-2-OD-EN
(243,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 243
(244,1)
Sec t i o n 5 - Di a g n o s t ic s
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
1. Check the motor, motor contactor, overload relay and other associated electric standby motor
circuitry. The internal pull coil/hold coil circuits in the contactor may be defective, requiring
replacement of contactor.
2. Check the voltages at the phase detect module. Battery voltage should be present on the ER
wire and the 8 wire.
3. Check the standby power voltage at the phase detect module. Standby power should be
available at L1, L2, and L3.
4. Check the voltage at the motor contactor coils. Battery voltage should be present on either the
7EC or 7EB wire when the motor should be running.
5. Check for reason that the motor fails to turn the alternator, such as slipping belts, clutch, etc.
6. Check the alternator in accordance with Alarm Code 25.
7. Download and inspect the ServiceWatch data logger to determine the operating conditions
present when the alarm code was set. Use the running Service Test Mode Feature to duplicate
the operating conditions. The alternator frequency and engine RPM are logged in
ServiceWatch and this information is viewable in technician mode. This information can be
used to confirm the RPM sensor reading and alternator frequency when the alarm was set.
244 TK 55533-2-OD-EN
(245,1)
Se c ti o n 5 - D i a g n o st i c s
C AU T I O N
Risk of Injury!
E x e r c i s e e x t r e m e c a r e w h e n ch e ck i n g h o t c o o l a n t .
1. Check the engine coolant level. Verify coolant is above sensor when the coolant is cold.
2. Check the sensor connector for a pushed pin or missing orange pin lock, loose pin crimp or
broken wire.
3. Check that +5 VDC is present between the (CLP-01) wire from the Base Controller and chassis
ground.
N o t e : Refer to Thermo King Service Bulletin T&T 379 for additional information on testing the
coolant level switch.
TK 55533-2-OD-EN 245
(246,1)
Sec t i o n 5 - Di a g n o s t ic s
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
246 TK 55533-2-OD-EN
(247,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 247
(248,1)
Sec t i o n 5 - Di a g n o s t ic s
248 TK 55533-2-OD-EN
(249,1)
Se c ti o n 5 - D i a g n o st i c s
8. If full battery voltage is not present at Base Controller while high speed output is energized,
check Base Controller in accordance with SR-4 S/T Service Procedure A01A.
TK 55533-2-OD-EN 249
(250,1)
Sec t i o n 5 - Di a g n o s t ic s
C AU T I O N
Risk of Injury!
E x e r c i s e e x t r e m e c a r e w h e n ch e ck i n g h o t c o o l a n t .
250 TK 55533-2-OD-EN
(251,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 251
(252,1)
Sec t i o n 5 - Di a g n o s t ic s
252 TK 55533-2-OD-EN
(253,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 253
(254,1)
Sec t i o n 5 - Di a g n o s t ic s
254 TK 55533-2-OD-EN
(255,1)
Se c ti o n 5 - D i a g n o st i c s
1. Clear the alarm to reset the Smart FET. Check the operation of the Hot Gas Solenoid circuit
using Output Test Mode. Verify the Base Controller Hot Gas Solenoid circuit LED lights. For
Base Controller LED identification, see the LED decal on the control box door. If the Base
Controller Hot Gas Solenoid circuit LED lights, go to Step 2. If the Base Controller Hot Gas
Solenoid circuit LED does not light, go to Step 3.
2. If the Base Controller Hot Gas Solenoid circuit LED lights and Alarm Code 45 is set, the circuit
has high resistance or is open. Use the HMI Control Panel amps gauge to check the current
drawn by the Hot Gas Solenoid, while operating the solenoid with Output Test Mode. The
current draw should be approximately 1.1 amps. If the current is not within limits, then check
for high resistance or open in the circuit or solenoid coil as shown in Step 3. Verify that all
circuit connectors are secure.
3. If the Base Controller Hot Gas Solenoid circuit LED does not light and Alarm Code 45 is set,
check for a shorted circuit or solenoid coil. Disconnect the 35 pin Connector J4 and check the
Hot Gas Solenoid circuit at Pin 5 with an accurate ohmmeter for a short circuit, open circuit,
or loose connection. The solenoid coil resistance should be approximately 8.3 ohms.
4. If no problems are found in Steps 1-3 and the output LED does not turn on, check the Base
Controller Assembly in accordance with Service Procedure A01A.
TK 55533-2-OD-EN 255
(256,1)
Sec t i o n 5 - Di a g n o s t ic s
256 TK 55533-2-OD-EN
(257,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 257
(258,1)
Sec t i o n 5 - Di a g n o s t ic s
258 TK 55533-2-OD-EN
(259,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 259
(260,1)
Sec t i o n 5 - Di a g n o s t ic s
50 RESET CLOCK
A l a r m Ty p e
Log
How Alar m is Set
This alarm indicates that power to the HMI control panel has been interrupted for an extended
period and the hold capacitor for the clock/calendar has discharged. As a result, the clock/
calendar is no longer accurate. Turning the unit on will recharge the hold capacitor in the HMI
control panel.
How Alarm is Cleared
This alarm is cleared manually.
Di ag nosti c Pro ced ure
1. Turn the unit on to recharge the hold capacitor in the HMI control panel.
2. Reset the clock to the customer’s time zone.
260 TK 55533-2-OD-EN
(261,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 261
(262,1)
Sec t i o n 5 - Di a g n o s t ic s
1. Clear the alarm to reset the Smart FET. Check the operation of the Pilot Solenoid circuit using
Output Test Mode. Verify the Base Controller Pilot Solenoid circuit LED lights. For Base
Controller LED identification see the LED decal on the control box door. If the Base Controller
Pilot Solenoid circuit LED lights go to Step 2. If the Base Controller Pilot Solenoid circuit LED
does not light go to Step 3.
2. If the Base Controller Pilot Solenoid circuit LED lights and Alarm Code 52 is set, the circuit has
high resistance or is open. Use the HMI Control Panel amps gauge to check the current drawn
by the Pilot Solenoid, while operating the solenoid with Output Test Mode. The current draw
should be approximately 1.1 amps. If the current is not within limits, check for high resistance
or open in the circuit or solenoid coil as shown in Step 3. Verify that all circuit connectors are
secure.
3. If the Base Controller Pilot Solenoid circuit LED does not light and Alarm Code 52 is set, check
for a shorted circuit or solenoid coil. Disconnect the 35 pin Connector J4 and check the Pilot
Solenoid circuit at Pin 7 with an accurate ohmmeter for a short circuit, open circuit or loose
connection. The solenoid coil resistance should be approximately 9.6 ohms.
4. If no problems are found in Steps 1-3 and the output LED does not turn on, check the Base
Controller Assembly in accordance with Service Procedure A01A.
262 TK 55533-2-OD-EN
(263,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 263
(264,1)
Sec t i o n 5 - Di a g n o s t ic s
264 TK 55533-2-OD-EN
(265,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 265
(266,1)
Sec t i o n 5 - Di a g n o s t ic s
266 TK 55533-2-OD-EN
(267,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 267
(268,1)
Sec t i o n 5 - Di a g n o s t ic s
64 PRETRIP REMINDER
A l a r m Ty p e
Log
Associated Alarm Codes
N/A
Considerations
The alarm is cleared when Pretrip Test is entered. If the Pretrip Test is not successful, the alarm
will not be reset. If the Pretrip Test is not successful then diagnose and correct the fault.
Prog ram m ab le Fe a tur es
This feature must be programmed. See Hourmeters in Section 3 for details.
How Alar m is Set
If a programmable hour meter is set as a Pretrip Reminder and the hourmeter time expires, then
Alarm Code 64 is set as a Log Alarm.
How Alarm is Cleared
The alarm self-clears when a Pretrip Test is entered.
Di ag nosti c Pro ced ure
1. Perform a Pretrip Test to confirm unit operation.
2. Reset the Pretrip Reminder hourmeter after a Pretrip Test is entered.
268 TK 55533-2-OD-EN
(269,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 269
(270,1)
Sec t i o n 5 - Di a g n o s t ic s
270 TK 55533-2-OD-EN
(271,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 271
(272,1)
Sec t i o n 5 - Di a g n o s t ic s
70 HOURMETER FAILURE
A l a r m Ty p e
Log
Associated Alarm Codes
N/A
How Alar m is Set
If one or more hourmeters exceeds 499,999 hours, Alarm Code 70 is set as a Log Alarm.
How Alarm is Cleared
This alarm is cleared manually.
Di ag nosti c Pro ced ure
1. If the hourmeter readings are normal, perform a Cold Start in accordance with Service
Procedure A07A.
I m p o rt a n t : Any time a Cold Start is performed, the Base Controller must be set up using
Service Procedure A04A. Failure to do so may result in the unit not operating to
customer specifications.
2. If the code can now be cleared, proceed with Base Controller setup in accordance with
Service Procedure A04A.
272 TK 55533-2-OD-EN
(273,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 273
(274,1)
Sec t i o n 5 - Di a g n o s t ic s
84 RESTART NULL
A l a r m Ty p e
Prevent
Associated Alarm Codes
10 High Discharge Pressure
17 Engine Failed to Crank
18 High Engine Coolant Temperature
20 Engine Failed to Start
21 Cooling Cycle Check
22 Heating Cycle Check
36 Electric Motor Failed to Run
63 Engine Stopped - Reason Unknown
90 Electric Overload
91 Check Electric Ready Input
540 Illegal Engine Operating State
Considerations
1. This alarm is a secondary alarm that is set along with the associated primary alarm.
2. The alarm indicates that the unit is in a temporary (“prevent” or “restart null”) shutdown. The
alarm clears automatically if the condition does not re-occur.
3. Many of these actions include a “waiting period” (to allow the engine to cool down, a high
pressure condition to subside or the like). The alarm code that caused the condition and
Alarm Code 84 might be present to indicate that the Base Controller is taking a corrective
action and that a restart will be attempted when conditions permit.
4. If the corrective action is successful, the original alarm code and Alarm Code 84 are cleared
automatically. If the original alarm condition continues to occur, and the corrective actions
taken by the Base Controller are not successful, the original alarm code remains. Alarm Code
84 is automatically cleared and the unit shuts down.
5. This alarm occurs if unit operation is not allowed as a result of the associated prevent alarm.
For example, if a high discharge pressure condition shuts the unit down, a waiting period
occurs to allow system pressures to equalize. A restart occurs when conditions permit.
6. If restarts are disabled, Alarm Code 84 is also disabled.
7. Most prevent alarms become Shutdown Alarm if three occurrences of the alarm occur within
a set time period.
8. Alarm Codes 10, 18, and 63 are not promoted to shutdown level if the Continuous Restarts
feature is enabled.
9. Alarm Codes 32 and 63 are promoted to guarded access clearable Shutdown Alarms if the
Limited Restarts Feature is enabled and the Shutdown Alarm occurs three times with a 12
hour time period.
10. Some prevent alarms will result in modified unit operation after the alarm is self cleared. For
example, Alarm Code 10 High Discharge Pressure will result in Alarm Code 42 Unit Forced to
Low Speed being set and the unit being forced to low speed for a one hour period.
11. If the unit is turned off while Alarm Code 84 is present the primary alarm becomes a
Shutdown Alarm when the unit is turned back on.
How Alar m is Set
This alarm is set with the associated alarm that caused the condition.
How Alarm is Cleared
This alarm clears automatically if the condition is resolved.
Di ag nosti c Pro ced ure
274 TK 55533-2-OD-EN
(275,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 275
(276,1)
Sec t i o n 5 - Di a g n o s t ic s
276 TK 55533-2-OD-EN
(277,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 277
(278,1)
Sec t i o n 5 - Di a g n o s t ic s
278 TK 55533-2-OD-EN
(279,1)
Se c ti o n 5 - D i a g n o st i c s
below 50°F (10°C). If the suction pressure display remains at [ - - - - ], the transducer,
controller power supply, or conductors are faulty.
3. If the suction pressure is not displayed by the Base Controller, unplug the transducer and
check for +5 Vdc between SPP-01 and SPN-01. If 5 volts is not present, check the Base
Controller in accordance with Service Procedure A01A.
4. Connect refrigeration gauges to verify that the sensor is not displaying the correct pressure.
Replace the sensor.
5. Check the harness wires SPP-01, SPN-01, and SP-01 for continuity using an ohmmeter.
TK 55533-2-OD-EN 279
(280,1)
Sec t i o n 5 - Di a g n o s t ic s
280 TK 55533-2-OD-EN
(281,1)
Se c ti o n 5 - D i a g n o st i c s
90 ELECTRIC OVERLOAD
A l a r m Ty p e
Check or Prevent in Electric Mode
Log in Diesel Mode
Considerations
This alarm becomes a Log Alarm if the unit is switched from Electric Mode to Diesel Mode.
How Alar m is Set
Alarm conditions are only active when three phase power is connected (ER input is high).
1. This alarm will be set during Electric Mode operation if the Base Controller determines that
the electric motor overload relay (EOL) has tripped.
2. If during a Pretrip Test the unit is not configured electric standby and the EOL input is low,
Alarm Code 90 is set as a Check Alarm and Alarm Code 111 Unit Not Configured Correctly is
set as a Log Alarm.
How Alarm is Cleared
This alarm is cleared manually.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
1. Check the electric motor for current draw. Refer to the motor nameplate for the Full Load
Amperage rating (FLA) of the motor.
2. Check the setting of the motor overload relay. It should be 10% greater than full load rating of
the motor.
3. Check the EOL-01 circuit for continuity from J6 pin 2 on the Base Controller to the overload
relay.
4. Check for continuity between the overload relay terminals 95 and 96. The contacts should be
normally closed.
5. Check the CHHV circuit for continuity to chassis ground.
TK 55533-2-OD-EN 281
(282,1)
Sec t i o n 5 - Di a g n o s t ic s
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
1. Check the ER-01 Circuit from the phase detect module for 12 volts to chassis ground when
standby power is connected to the unit.
2. Check the 8 circuit at the phase detect module for 12 volts.
3. Check to verify standby power of the correct voltage is present at L1, L2, and L3 on the phase
detect module.
4. Check the ER-01 Circuit for continuity from J6 pin 5 on the Base Controller to the phase detect
module.
5. If steps 1-4 above are correct, check the Base Controller in accordance with Service Procedure
A01A.
6. If steps 1, 2, 4, or 5 above do not correct the fault, replace the phase detect module.
282 TK 55533-2-OD-EN
(283,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 283
(284,1)
Sec t i o n 5 - Di a g n o s t ic s
284 TK 55533-2-OD-EN
(285,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 285
(286,1)
Sec t i o n 5 - Di a g n o s t ic s
N o t e : The output voltages listed above are for the ultrasonic fuel level sensor designed to be
used with the SR-2, SR-3, and SR-4 Controllers. Other systems such as third party
telematics systems may use sensors with slightly different output voltages. Refer to the
sensor specifications for those sensors.
5. If the output voltage is incorrect, check the continuity of the wires that go from the J1
connector on the base controller to the sensor as shown in the following table and verify the
connections are clean and tight.
N o t e : The sensor cable wires are connected to the sensor wires with solder connections and
heat shrink tubing during installation. Refer to the Precedent Single Temperature
Systems Installation Manual (TK 55496–2–IM) for more information.
6. If the wires have good continuity and the connections are clean and tight, replace the sensor.
286 TK 55533-2-OD-EN
(287,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 287
(288,1)
Sec t i o n 5 - Di a g n o s t ic s
288 TK 55533-2-OD-EN
(289,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 289
(290,1)
Sec t i o n 5 - Di a g n o s t ic s
290 TK 55533-2-OD-EN
(291,1)
Se c ti o n 5 - D i a g n o st i c s
7. If the suction pressure is not displayed by the Base Controller, unplug the transducer and
check for +5 Vdc between SPP-01 and SPN-01. If 5 volts is not present, check the Base
Controller in accordance with Service Procedure A01A.
a. Connect refrigeration gauges to verify that the sensor is not displaying the correct
pressure. Replace the sensor.
b. Check the harness wires SPP-01, SPN-01, and SP-01 for continuity using an ohmmeter.
8. If harness and connections are good, check Base Controller in accordance with Service
Procedure A01A.
9. Begin a refrigeration system diagnosis. Refer to the Thermo King Truck and Trailer
Refrigeration Systems Manual (TK 5984-7) for procedures.
TK 55533-2-OD-EN 291
(292,1)
Sec t i o n 5 - Di a g n o s t ic s
292 TK 55533-2-OD-EN
(293,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 293
(294,1)
Sec t i o n 5 - Di a g n o s t ic s
294 TK 55533-2-OD-EN
(295,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 295
(296,1)
Sec t i o n 5 - Di a g n o s t ic s
296 TK 55533-2-OD-EN
(297,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 297
(298,1)
Sec t i o n 5 - Di a g n o s t ic s
298 TK 55533-2-OD-EN
(299,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 299
(300,1)
Sec t i o n 5 - Di a g n o s t ic s
300 TK 55533-2-OD-EN
(301,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 301
(302,1)
Sec t i o n 5 - Di a g n o s t ic s
302 TK 55533-2-OD-EN
(303,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 303
(304,1)
Sec t i o n 5 - Di a g n o s t ic s
304 TK 55533-2-OD-EN
(305,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 305
(306,1)
Sec t i o n 5 - Di a g n o s t ic s
306 TK 55533-2-OD-EN
(307,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 307
(308,1)
Sec t i o n 5 - Di a g n o s t ic s
308 TK 55533-2-OD-EN
(309,1)
Se c ti o n 5 - D i a g n o st i c s
Alarm Code 03 if the control return air sensor failed). Alarm Code 13 will not be set if a hard
failure occurs.
N o t e : The controller may not be currently showing dashes for the sensor reading, but the
alarm will be present when the unit is inspected. If a sensor alarm code is set, a failure
did occur at some point. Checking the ServiceWatch data logger download will indicate
when the hard failure occurred.
Prog ram m ab le Fe a tur es
This is a graded sensor. The sensor grade must be correctly set in the Guarded Access Menu.
How Alar m is Set
1. If the sensor reading is over 200°F (93°C) for 10 seconds, Alarm Code 203 is set as a Check
Alarm. The sensor reading will display dashes [ - - - ] and may return to normal. This
condition is termed a hard sensor failure.
2. If the sensor reading is under -50°F (-46°C) for 10 seconds, Alarm Code 203 is set as a Check
Alarm. The sensor reading will display dashes [ - - - ] and may return to normal. This
condition is termed a hard sensor failure.
3. If the differential between the return air temperature and other temperature sensors is too
large when Alarm Code 03 is cleared, Alarm Code 203 and Alarm Code 13 Sensor Calibration
Check are set as Check Alarms. This condition is termed a soft sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F
(-46°C), Alarm Code 203 and Alarm Code 13 Sensor Calibration Check are set as Check
Alarms. This condition is termed a soft sensor failure.
5. If the sensor grade for this sensor is set to 5H, Alarm Code 203 and Alarm Code 92 Sensor
Grades Not Set are set as Check Alarms.
6. The temperatures of the control return air sensor and display return air sensor twins are not
within a specified range. If the faulty sensor can be determined, only the alarm code for that
sensor and Alarm Code 13 Sensor Calibration Check will be set. Alarm Codes 03 Check
(Control) Return Air Sensor, 203 Check Display Return Air Sensor, and 13 Sensor Calibration
Check are set if the faulty sensor cannot be determined.
How Alarm is Cleared
This alarm can only be cleared manually from the Guarded Access menu.
When the alarm is cleared, the return air sensors, discharge air sensors, and evaporator coil
sensor must all read within 30°F (17°C) of each other. If they do not, it is assumed that the sensor
reading is not accurate. The alarm code is not cleared and Alarm Code 13 Sensor Calibration
Check will also be set. Also, if the sensor is over or under range when the alarm clear is
attempted, the alarm will not be cleared.
If the alarm is set by Condition #5 above, Alarm Code 92 will clear automatically if the sensor
grade is changed from 5H. If the sensor grade remains 5H, Alarm Code 92 cannot be cleared.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
• Alarm Code 203 (Sensor was out of range)
1. Display the sensor reading using the Sensor Menu. If the display shows [- - - -], the sensor
is defective and should be replaced. If the condition still exists, check the sensor circuit for
an open wire or short to ground (Refer to Service Procedure D01A). Check the Base
Controller in accordance with Service Procedure A01A.
2. If the display is normal, proceed as shown below.
• Alarm Code 203 and Alarm Code 13 (Sensor drifted or was reading erratically)
1. Review the ServiceWatch data logger and check the senor reading at the time the alarm
was set. Also, review the history to see if previous alarm codes exist that would indicate
an intermittent problem. If the sensor appears to have read incorrectly, it should be
replaced.
TK 55533-2-OD-EN 309
(310,1)
Sec t i o n 5 - Di a g n o s t ic s
2. Verify the sensor grades are set to the actual sensor grade.
3. Check for an airflow obstruction and correct sensor mounting.
4. If the problem reoccurs, check the sensor connector/sensor circuit in accordance with
Service Procedure D01A.
• Alarm Code 203 and Alarm Code 92 (Sensor grade set to 5H)
1. Verify and set the sensor grade.
• Alarm Code 03 and/or Alarm Code 203 are set with Alarm Code 13 (Dual sensors don’t agree)
1. Review the ServiceWatch data logger and check the sensor readings at the time the alarm
was set. Also, review the history to see if previous alarm codes exist that would indicate
the problem sensor. If a sensor appears to have read incorrectly, it should be replaced.
2. Check for an airflow obstruction and correct sensor mounting. Verify the brass clamp is
installed on the two return air sensors.
3. Verify the sensor grades are set to the actual sensor grade and are not transposed.
4. If the offending sensor cannot be determined, either ice bath both return air sensors
simultaneously to determine which sensor is inaccurate or replace both sensors.
• If all or many of the Sensor Alarm Codes (02, 03, 04, 05, 06, 11, 12, 203, and 204) are set
1. Verify the 35 pin Base Controller sensor connector J1 is connected securely.
2. Check the Base Controller in accordance with Service Procedure A01A.
310 TK 55533-2-OD-EN
(311,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 311
(312,1)
Sec t i o n 5 - Di a g n o s t ic s
N o t e : The controller may not be currently showing dashes for the sensor reading, but the
alarm will be present when the unit is inspected. If a sensor alarm code is set, a failure
did occur at some point. Checking the ServiceWatch data logger download will indicate
when the hard failure occurred.
Prog ram m ab le Fe a tur es
This is a graded sensor. The sensor grade must be correctly set in the Guarded Access Menu.
How Alar m is Set
1. If the sensor reading is over 200°F (93°C) for 10 seconds, Alarm Code 204 is set as a Check
Alarm. The sensor reading will display dashes [ - - - ] and may return to normal. This
condition is termed a hard sensor failure.
2. If the sensor reading is under -50°F (-46°C) for 10 seconds, Alarm Code 204 is set as a Check
Alarm. The sensor reading will display dashes [ - - - ] and may return to normal. This
condition is termed a hard sensor failure.
3. If the differential between the discharge and other sensors is too large when Alarm Code 04 is
cleared, Alarm Code 204 and Alarm Code 13 Sensor Calibration Check are set as Check
Alarms. This condition is termed a soft sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F
(-46°C), Alarm Code 204 and Alarm Code 13 Sensor Calibration Check are set as Check
Alarms. This condition is termed a soft sensor failure.
5. If the sensor grade for this sensor is set to 5H, Alarm Code 204 and Alarm Code 92 Sensor
Grades Not Set are set as Check Alarms.
6. The temperatures of the control discharge air sensor and display discharge air sensor twins
are not within a specified range. If the faulty sensor can be determined, only the alarm code
for that sensor and Alarm Code 13 Sensor Calibration Check will be set. Alarm Codes 04
Check (Control) Discharge Air Sensor, 204 Check Display Discharge Air Sensor, and 13 Sensor
Check are set if the faulty sensor cannot be determined.
How Alarm is Cleared
This alarm can only be cleared manually from the Guarded Access menu.
When the alarm is cleared, the return air sensors, discharge air sensors, and evaporator coil
sensor must all read within 30°F (17°C) of each other. If they do not, it is assumed that the sensor
reading is not accurate. The alarm code is not cleared and Alarm Code 13 Sensor Calibration
Check will also be set. Also, if the sensor is over or under range when the alarm clear is
attempted, the alarm will not be cleared.
If the alarm is set by Condition #5 above, Alarm Code 92 will clear automatically if the sensor
grade is changed from 5H. If the sensor grade remains 5H, Alarm Code 92 cannot be cleared.
Di ag nosti c Pro ced ure
Always download the ServiceWatch data logger using the ThermoServ Service Tool. Review the
data to determine the conditions at the time the alarm was set. Conditions relevant to the alarm
are recorded when the alarm is both set and cleared. This data can be invaluable when
determining the cause of the alarm.
• Alarm Code 204 (Sensor was out of range)
1. Display the sensor reading using the Sensor Menu. If the display shows [- - - -], the sensor
is defective and should be replaced. If the condition still exists, check the sensor circuit for
an open wire or short to ground (Refer to Service Procedure D01A). Check the Base
Controller in accordance with Service Procedure A01A.
2. If the display is normal, proceed as shown below.
• Alarm Code 204 and Alarm Code 13 (Sensor drifted or was reading erratically)
1. Review the ServiceWatch data logger and check the senor reading at the time the alarm
was set. Also, review the history to see if previous alarm codes exist that would indicate
an intermittent problem. If the sensor appears to have read incorrectly, it should be
replaced.
2. Verify the sensor grades are set to the actual sensor grade.
312 TK 55533-2-OD-EN
(313,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 313
(314,1)
Sec t i o n 5 - Di a g n o s t ic s
314 TK 55533-2-OD-EN
(315,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 315
(316,1)
Sec t i o n 5 - Di a g n o s t ic s
1. Check the operation of the Fresh Air Exchange circuit using Output Test Mode. Verify the
Fresh Air Exchange LED 44 lights.
2. Use the HMI Control Panel amps gauge to check the current drawn by the Fresh Air Exchange
Solenoid while operating the Fresh Air Exchange Door with Output Test Mode. The current
draw should be approximately 6 amps.
3. Energize the Fresh Air Exchange Solenoid using Output Test Mode and check for battery
voltage on the AFA circuit. If voltage is present and no current was measured in the step
above replace the Fresh Air Exchange Solenoid.
4. Verify that the Auto Fresh Air Reed Switch is closed when the fresh air door is closed and
open when the fresh air door is open. Battery voltage should be present at J3 pin 31 when the
switch is open (door is open). 0 volts should be present at J3 pin 31 when the switch is closed
(door is closed).
5. Inspect the Fresh Air Exchange mechanical components for binding or ice buildup.
316 TK 55533-2-OD-EN
(317,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 317
(318,1)
Sec t i o n 5 - Di a g n o s t ic s
318 TK 55533-2-OD-EN
(319,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 319
(320,1)
Sec t i o n 5 - Di a g n o s t ic s
320 TK 55533-2-OD-EN
(321,1)
Se c ti o n 5 - D i a g n o st i c s
• Generator windings will read about 50k with GFD plugged in or 150k with GFD
unplugged.
b. Disconnect each of the three high voltage wires that connect to the Battery Charger (if
equipped). Check resistance of each Battery Charger high voltage input terminal to
chassis ground.
3. For Blower Motor wires to ground, check T1, T2, and T3 at each contactor output to verify
each Blower Motor circuit.
• Motor winding should be open i.e., no reading or OL.
4. Check for pinched wires or damaged insulation.
• A high resistance reading could result.
5. To perform a Ground Fault Detect (GFD) Module Test, refer to Service Procedure G01A.
TK 55533-2-OD-EN 321
(322,1)
Sec t i o n 5 - Di a g n o s t ic s
322 TK 55533-2-OD-EN
(323,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 323
(324,1)
Sec t i o n 5 - Di a g n o s t ic s
324 TK 55533-2-OD-EN
(325,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 325
(326,1)
Sec t i o n 5 - Di a g n o s t ic s
326 TK 55533-2-OD-EN
(327,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 327
(328,1)
Sec t i o n 5 - Di a g n o s t ic s
328 TK 55533-2-OD-EN
(329,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 329
(330,1)
Sec t i o n 5 - Di a g n o s t ic s
330 TK 55533-2-OD-EN
(331,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 331
(332,1)
Sec t i o n 5 - Di a g n o s t ic s
332 TK 55533-2-OD-EN
(333,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 333
(334,1)
Sec t i o n 5 - Di a g n o s t ic s
334 TK 55533-2-OD-EN
(335,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 335
(336,1)
Sec t i o n 5 - Di a g n o s t ic s
336 TK 55533-2-OD-EN
(337,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 337
(338,1)
Sec t i o n 5 - Di a g n o s t ic s
338 TK 55533-2-OD-EN
(339,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 339
(340,1)
Sec t i o n 5 - Di a g n o s t ic s
55533-2-5-1
Yanmar Diagnostic Trouble Codes (DTC) and Associated Thermo King Alarm Codes
When a Yanmar DTC Code is set, a corresponding 600 Series Thermo King Alarm Code is also
set. The 600 Series Alarm Code is a general indication of what issues may exist. Always connect
the Yanmar Service Tool and read all existing DTC codes. Use this information to diagnose the
problem using the Yanmar Service documentation.
Clearing Yanmar DTC Codes and Associated Thermo King Alarm Codes
Yanmar DTC Codes are cleared using the Yanmar Service tool or by choosing “Clear All ECU
Faults” from the HMI Control Panel Main Menu. When the Yanmar Fault Codes are cleared, the
associated Thermo King Alarm Code is also cleared. The codes are still available by downloading
the ServiceWatch Data Logger using the ThermoServ™ Service Tool.
340 TK 55533-2-OD-EN
(341,1)
Se c ti o n 5 - D i a g n o st i c s
55533-2-5-2
TK 55533-2-OD-EN 341
(342,1)
Sec t i o n 5 - Di a g n o s t ic s
342 TK 55533-2-OD-EN
(343,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 343
(344,1)
Sec t i o n 5 - Di a g n o s t ic s
344 TK 55533-2-OD-EN
(345,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 345
(346,1)
Sec t i o n 5 - Di a g n o s t ic s
346 TK 55533-2-OD-EN
(347,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 347
(348,1)
Sec t i o n 5 - Di a g n o s t ic s
348 TK 55533-2-OD-EN
(349,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 349
(350,1)
Sec t i o n 5 - Di a g n o s t ic s
350 TK 55533-2-OD-EN
(351,1)
Se c ti o n 5 - D i a g n o st i c s
H ow Fa ul t i s Cl ea re d
This alarm is clearable using the HMI Control Panel Main Menu > Clear All ECU Faults.
This alarm is auto cleared if the ECU stops sending the P Codes shown above.
Log Alarm cleared.
Di ag nosti c Pro ced ure
Use the Yanmar SmartAssist Direct (YSAD) Diagnostic Tool to determine what DTC Codes are set.
For corrective actions consult the Yanmar Troubleshooting Guide.
TK 55533-2-OD-EN 351
(352,1)
Sec t i o n 5 - Di a g n o s t ic s
352 TK 55533-2-OD-EN
(353,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 353
(354,1)
Sec t i o n 5 - Di a g n o s t ic s
354 TK 55533-2-OD-EN
(355,1)
Se c ti o n 5 - D i a g n o st i c s
TK 55533-2-OD-EN 355
(356,1)
Sec t i o n 5 - Di a g n o s t ic s
356 TK 55533-2-OD-EN
(357,1)
TK 55533-2-OD-EN 357
(358,1)
ServiceW atch
download failed.
Replace
Base Controller .
No
Yes
No
Check problem
Download component and
ServiceW atch, then Downloads circuit using Output
performed Yes Test mode. V erify
CargoW atch. Check
download for issues successfully? operation using LED
(resets, etc.) outputs when
available.
Yes
Is 8 pin
Mate-N-Lock
Yes
connector
Replace Base
properly
Controller .
connected?
No
Does HMI
Connect as power up to No
required. main screen?
Dead HMI:
Yes Check fuses F8 (J12)
and/or F12 (J13).
Determine cause of
Complete. blown fuse. Replace
fuse as required.
SAP109
358 TK 55533-2-OD-EN
(359,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
Is ON/OFF Is 8 pin
= OFF? Mate-N-Lock
No No Connect as
From Figure 1 Lost Controller connector
Power Powering properly required.
Down connected?
Does HMI
power up to Complete. Yes Yes
main screen? Does HMI
No Yes power up to No
Turn ON.
main screen?
HMI displays Lost HMI displays Lost HMI displays Lost HMI displays Lost Yes
Controller Power Controller Power Controller Power Communications:
Powering Down: Check 8X Wiring: Powering Down: Check fuse F15.
Or Or Or
Check fuse F2. Check fuse F7. Check fuse F10. Determine cause of Complete.
Determine cause of Determine cause of Determine cause of blown fuse. Replace
blown fuse. Repair blown fuse. Repair blown fuse. Repair fuse as required.
as required. as required. fuse as required.
Return unit to
Does
normal configuration. Both LEDs
ServiceW atch Download Yes
Replace F10 to 48 & 45
download ServiceW atch. Neither
normal position and flashing?
properly? LED
power cycle.
flashing
Only one LED flashing
No
Check 2 and CH
connections at
Proceed to Base Controller
Figure 3. Replace Base Replace Base and ground plate.
Controller Controller .
Yes
No
Yes
TK 55533-2-OD-EN 359
(360,1)
Power up unit
From Figure 2 using HMI.
Verify device is
Does HMI Does HMI Yes
Yes plugged back into HMI
power up power up
J13 and power was defective.
properly? properly?
cycle unit. Leave
flush mount display
harness unplugged
No (if equipped). No
Repair or
Replace flush
replace harness
mount display
as required.
or repair/replace
harness as required.
Yes Does HMI No Replace device or
power up repair/replace
properly? harness as required.
Yes
Does HMI No
power up Replace REB.
properly?
360 TK 55533-2-OD-EN
(361,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
Av a i l a b l e Te s t s :
• L C D Te s t – This test allows the technician to select a normal or inverted display. If inverted is
chosen the display is reversed – segments that were turned on are now turned off and
segments that were turned off are now turned on. The technician visually verifies that all
display segments are functioning properly.
• Ke y p a d Te s t – This test prompts the technician to press the four soft keys, the Defrost Key
and the Cycle Sentry Key. Each time the requested key is pressed the next prompt is
displayed, allowing the technician to verify proper operation of these keys.
TK 55533-2-OD-EN 361
(362,1)
• B a ck l i g h t Te s t – This test allows the technician to turn the backlight on and off to confirm
operation.
• B r i g h t n e s s Te s t – This test allows the technician to select Low, Medium or High backlight
intensity.
• B u z z e r Te s t – This test allows the technician to turn the HMI buzzer on and off to verify
operation.
• H e a t e r O u t p u t – This test allows the technician to turn the HMI display heater on and off.
• U n i t O n / O ff O u t p u t Te s t – This test allows the technician to turn the Unit On/Off output off.
This turns the unit off to confirm that the output can be turned off. To restart the unit, press
the On key.
• S P R D i g i t a l O u t p u t Te s t – This test allows the technician to turn digital output 2 on and off.
This allows the operation of a device attached to this output to be checked.
• Se r i a l E 2 – This test allows the technician to perform an internal HMI memory test. The test
takes less than one second and the results are reported as PASS or FAIL.
• D a t a l o g F l a s h – This test allows the technician to perform an internal HMI CargoWatch data
logger memory test. The test takes less than one second and the results are reported as PASS
or FAIL.
• RT C U p d a t e – This test allows the technician to perform an internal HMI real time clock test.
The test takes less than three seconds and the results are reported as PASS or FAIL.
362 TK 55533-2-OD-EN
(363,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
2 Press the MENU key. The Operator Menu appears. Do not let the unit start. The
Guarded Access Menu cannot
be entered in the unit is
running.
3 Press and hold both the EXIT and The Maintenance Menu appears.
unlabeled key for 5 seconds.
7 Press the UP and DOWN key as The real time clock is located
required to display the Set Time and in the HMI Control Panel. The
Date Menu. Then press the SELECT time is supplied to the Base
key to enter the Set Time and Date Controller each time the unit
Menu. is turned on. If the Base
Controller is changed the
clock setting will be supplied
to the Base Controller when
the unit is turned on. If the
HMI Control Panel is changed
the time and date must be
checked and set if necessary.
8 Check the Time to determine the Record the time zone on the Setup Compare local time to unit
time zone used by the customer. Sheet. time to determine time zone.
TK 55533-2-OD-EN 363
(364,1)
10 Verify the unit is not running. The If the unit is running, scroll
unit will not enter the Guarded back and enter Output Test
Access Menu if it is running. Mode. This will cause the unit
to shut down. Press the Exit
key to return to the
Maintenance Menu. Scroll
back to the Set Time and
Date Menu and proceed with
the next step.
11 Press and hold both the EXIT and The Guarded Access Menu appears. If a Security Code is
unlabeled key for 5 seconds. requested then enter the
Security Code or [4444] to
enter the Guarded Access
Menu.
16 Use the SELECT key to enter the Use the Setup Sheet as a
next Guarded Access Menu. guide.
S i n g l e Te m p e r a t u r e S e t u p S h e e t - X X x x So ft w a r e
I m p o rt a n t : Not all features shown on the Setup Sheet may appear. This is dependent on
hardware type, software revision, and unit settings.
S O F T WA R E R E V I S I O N
364 TK 55533-2-OD-EN
(365,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
S E T D AT E A N D T I M E
Compare local time to unit time to determine time zone. The real time clock is located in the HMI
Control Panel. The time is supplied to the Base Controller/Interface Board each time the unit is
turned on. If the Base Controller/Interface Board is changed the clock setting will be supplied to
the Base Controller/Interface Board when the unit is turned on. If the HMI Control Panel is
changed the time and date must be checked and set if necessary.
SE CUR IT Y CODE
N o t e : If an unknown security code is set then use Security Code 4444 to gain access.
P R O G R A M M A B L E F E AT U R E S
Function Default Setting Recorded Setting
TK 55533-2-OD-EN 365
(366,1)
M A I N M E N U C O N F I G U R AT I O N
Function Default Setting Recorded Setting
H O U R M E T E R S E T U P - V I E WA B L E H O U R M E T E R S E T U P
Function Default Setting Recorded Setting
366 TK 55533-2-OD-EN
(367,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
H O U R M E T E R S E T U P - P R O G R A M S E RV I C E D U E DAT E
Function Default Setting Recorded Setting
S E N S O R C A L I B R AT I O N
Function Default Setting Recorded Setting
C YC L E S E N T RY S E T U P
Function Default Setting Recorded Setting
D E F R O ST S E T U P
Function Default Setting Recorded Setting
TK 55533-2-OD-EN 367
(368,1)
11 Turn the unit on. The real time clock settings will
be loaded from the HMI Control
Panel when the unit is turned on.
368 TK 55533-2-OD-EN
(369,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 369
(370,1)
12 Check the setting of the real time The clock may be set from
clock as shown in Section 4 and the Maintenance Menu or
correct if necessary. with the ThermoServ™
Service Tool.
370 TK 55533-2-OD-EN
(371,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
3 Press and hold both the EXIT and The Maintenance Menu appears.
unlabeled key for 5 seconds.
5 Use the UP and/or DOWN keys to Verify the Software revisions are
scroll through the HMI Control as desired.
Panel and Base Controller software
revisions.
7 Press the NEXT key as required to The real time clock is located
display the Set Time and Date in the HMI Control Panel. The
Menu. Then press the SELECT key time is supplied to the Base
to enter the Set Time and Date Controller each time the unit
Menu. is turned on. If the Base
Controller is changed the
clock setting will be supplied
to the Base Controller when
the unit is turned on. If the
HMI Control Panel is
changed the time and date
must be checked and set if
necessary.
TK 55533-2-OD-EN 371
(372,1)
10 Verify the unit is not running. The If the unit is running, scroll
unit will not enter the Guarded back and enter Output Test
Access Menu if it is running. Mode. This will cause the
unit to shut down. Press the
Exit key to return to the
Maintenance Menu. Scroll
back to the Set Time and
Date Menu and proceed with
the next step.
11 Press and hold both the EXIT and The Guarded Access Menu If a Security Code is
unlabeled key for 5 seconds. appears. requested then enter the
Security Code or [4444] to
enter the Guarded Access
Menu.
16 Use the SELECT key to enter the Use the Setup Sheet as a
next Guarded Access Menu. guide.
17 Use the UP and/or DOWN keys to Set all menu settings to those
scroll through all settings in the shown on the Setup Sheet.
Menu.
372 TK 55533-2-OD-EN
(373,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 373
(374,1)
1 Verify and record the sensor grades Alarm Code 92 does not
of all return air, discharge air and apply to spare sensors.
spare sensors (if used) by However, when used, spare
physically checking the sensor. sensors should still be
calibrated to achieve
maximum accuracy.
4 Press and hold both the EXIT and The Maintenance Menu appears.
unlabeled key for 5 seconds.
5 Press the DOWN key as required to The Set Time and Date Menu
display the Set Time and Date appears.
Menu.
6 Press and hold both the EXIT and The Guarded Access Menu
unlabeled key for 5 seconds. appears.
8 When the Sensor Calibration Menu The first graded sensor and the
is shown press the SELECT key to current grade appear.
access the Sensor Calibration
Menu.
9 If necessary, use the UP and/or These keys scroll thru all graded Verify the correct sensor is
DOWN keys to select the sensor to sensors installed on the unit. selected.
be calibrated.
10 When the sensor to be calibrated is The Sensor Change menu for the
shown on the display, press the selected sensor will appear.
SELECT key.
374 TK 55533-2-OD-EN
(375,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 375
(376,1)
A ft e r We l d i n g :
376 TK 55533-2-OD-EN
(377,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
3 Press the MENU key. The Main Menu appears. Press the MENU key.
4 Press and hold both the EXIT and The Maintenance Menu appears.
unlabeled key for 5 seconds.
6 Press and hold both the EXIT and The Guarded Access Menu
unlabeled key for 5 seconds. If a appears.
Security Code is requested enter
the Security Code or [4444] to
enter the Guarded Access Menu.
7 Press the DOWN key to display the The Hourmeter Setup Menu
Hourmeter Setup Menu. appears.
TK 55533-2-OD-EN 377
(378,1)
11 Press and hold both the EXIT and This will add the non-
Important: Do not exit the
unlabeled key for 5 seconds. programmable hourmeters to the
hourmeter
menu only if the number of hours
setup or allow
in these hourmeters are less than
the Guarded
100 hours.
Access keypad
timeout to
occur during
this procedure.
If the keypad
times out and
an hourmeter
exceeds 100
hours, the
hourmeters will
be locked and
can no longer
be changed.
378 TK 55533-2-OD-EN
(379,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 379
(380,1)
55533-2-6-1
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
Operation:
The brown, blue and black wires are used to sample the power at L1, L2 and L3 respectively.
Operating power from 12 to 24 VDC is supplied to the module via the 8 wire and CH wire.
When the voltage sensed rises above 180 volts AC and all three phases are present the module
ER wire will output 12-24 VDC after the conditions exist for 2 to 4 seconds. This signal informs the
base controller that electric standby operation is possible. If the voltage drops below 160 volts AC
or a phase is lost, the output is turned off after the condition exists for 8 to 10 seconds. The
module continues to monitor the power and will again output 12-24 VDC within 2 to 4 seconds
after the voltage rises above 180 volts AC and all three phases are present.
If phase rotation is L1, L2, L3, the 7EB wire will supply 12 to 24 VDC to energize the appropriate
phase rotation contactor. If phase rotation is L1, L3, L2, the 7EC wire will supply a chassis ground
to energize the appropriate phase rotation contactor. The 7EB and 7EC wires are interlocked to
prevent both phase contactors from being energized at once.
Connections:
Connections to the module are shown in the tables below.
Table 7. Power Connections
Input Description
CH Chassis ground.
380 TK 55533-2-OD-EN
(381,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
Table 8. Inputs
Input Description
L1 This brown wire supplies standby power L1 to the phase detect module.
L2 This blue wire supplies standby power L2 to the phase detect module.
L3 This black wire supplies standby power L3 to the phase detect module.
Table 9. Outputs
Input Description
7EH With 12-24 VDC is supplied, then outputs 7EB and 7EC will be at 12-24 VDC.
7EB If phase rotation is L1, L2, L3 then this wire will provide 12-24 VDC to energize the appropriate phase
rotation contactor. The 7EC wire is interlocked to prevent both phase contactors from being energized
at once.
7EC If phase rotation is L1, L3, L2 then this wire will provide 12-24 VDC to energize the appropriate phase
rotation contactor. The 7EB wire is interlocked to prevent both phase contactors from being energized
at once.
ER This wire will output 12-24 VDC 2 to 4 seconds after the voltage rises above 180 volts AC and all three
phases are present. If the voltage drops below 160 volts AC or a phase is lost and the condition remains
for 8 to 10 seconds, the output is turned off. The module continues to monitor and will again output 12-
24 VDC 2 to 4 seconds after the power returns to normal (voltage rises above 180 volts AC and all three
phases are present).
1 8F Power to Module
2 CH Chassis ground
3 ER Power OK
4 7EH Switches the 7EC and 7EB from grounding to power logic
7 Unused
8 Unused
9 Unused
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
TK 55533-2-OD-EN 381
(382,1)
WA R N I N G
H a z a r d o u s Vo l t a g e !
U n i t s f e at u r i n g o p t i o n al E l ec t r ic S t a n d b y u t i li ze 46 0 , 40 0, o r 2 30 vo lt 3 p h a s e AC e le c t r i c a l
po we r any t im e the u ni t is ope ra ti ng i n El e ct ri c M od e. Thi s vo lt a ge po te nt ia l i s a ls o
p r e s e n t a ny t i m e t h e u n i t i s c o n n e c t e d t o a s o u r c e o f e x t e r n a l s t a n d b y p o w e r. E x t r e m e
c a re m us t be us ed w he n wo rk i ng on th e un it , a s th es e vo lt ag es ar e c ap ab le of c au si n g
serious injury or death.
3 Check the 8F and CH circuits to the If this power is not present, check
phase detect module. 12-24 VDC the 8 circuit from the On/Off
must be present from 8F to CH. switch.
4 If correct power is present in the If power is not present replace the Removal and replacement of
test above then the ER circuit on phase detect module. the phase detect module is
the interface board should have 12- detailed on a previous page.
24 VDC present.
6 If the unit is calling for operation If neither contactor is energized Removal and replacement of
(LED 6 is on) one of the phase check for 12-24 VDC. If voltage is the phase detect module is
select contactors should be not present replace the phase detailed on a previous page.
energized. detect module.
382 TK 55533-2-OD-EN
(383,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 383
(384,1)
55533-2-6-2
Proce dur e:
Step Action Result Comments
384 TK 55533-2-OD-EN
(385,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-13
55533-2-6-3
7 Start the Yanmar SmartAssist To maintain current status, the This verifies the YSAD
Direct (YSAD) software. Yanmar SmartAssist Direct (YSAD) software and extends the
software must be started every 90 license for another 90 days.
days while the PC Computer is
connected to the internet.
55533-2-6-4
TK 55533-2-OD-EN 385
(386,1)
55533-2-6-6
55533-2-6-7
55533-2-6-12
386 TK 55533-2-OD-EN
(387,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-8
55533-2-6-9
TK 55533-2-OD-EN 387
(388,1)
55533-2-6-10
15 To clear all fault codes, click the All All fault codes in the ECU will be Some operations performed
Clear button. Enter your password cleared. within YSAD require
in the popup window when password verification.
prompted.
55533-2-6-1 1
388 TK 55533-2-OD-EN
(389,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 389
(390,1)
4 Locate the plug terminals for the The resistance should be from 35 This verifies a complete
sensor. Using a high quality meter, kΩ to 45 kΩ. sensor circuit but does not
check the resistance of the sensor check the accuracy of the
harness and sensor. sensor.
6 If circuit resistance is normal, check The meter should read OL. This verifies that the circuit
continuity from the positive wire to is not shorted to chassis
chassis ground. ground.
7 If the harness passes inspection, If the Base Controller fails the test,
check the Base Controller in it must be replaced.
accordance with Service Procedure
A01A.
390 TK 55533-2-OD-EN
(391,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-15
TK 55533-2-OD-EN 391
(392,1)
55533-2-6-16
55533-2-6-17
392 TK 55533-2-OD-EN
(393,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-18
55533-2-6-18a
TK 55533-2-OD-EN 393
(394,1)
55533-2-6-18b
55533-2-6-19
394 TK 55533-2-OD-EN
(395,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-20
TK 55533-2-OD-EN 395
(396,1)
55533-2-6-21
396 TK 55533-2-OD-EN
(397,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-22
55533-2-6-23
55533-2-6-24
TK 55533-2-OD-EN 397
(398,1)
55533-2-6-25
55533-2-6-26
55533-2-6-27
398 TK 55533-2-OD-EN
(399,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-28
55533-2-6-29
55533-2-6-30
TK 55533-2-OD-EN 399
(400,1)
55533-2-6-31
55533-2-6-32
400 TK 55533-2-OD-EN
(401,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-33
TK 55533-2-OD-EN 401
(402,1)
55533-2-6-34
55533-2-6-35
402 TK 55533-2-OD-EN
(403,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
1 Attach electrical connectors and Rear ECU plate alignment notch ECU programming is
bolts to the ECU. Slide ECU back must be seated properly for outer recommended before cooling
into the channel and line up mounting bolts to match up. channel is reassembled.
mounting bolts with holes.
2 Insert four outer bolts holding Seal ECU channel to road side It is not recommended to use air
plastic ECU channel to bracket. condenser. tools for fastening bolts with
Use a long extension to fasten inserts. Do not over tighten,
lower rear bolts. some inserts molded into plastic
are not replaceable.
TK 55533-2-OD-EN 403
(404,1)
55533-2-6-36
404 TK 55533-2-OD-EN
(405,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-37
55533-2-6-38
4 Upload complete.
TK 55533-2-OD-EN 405
(406,1)
55533-2-6-39
406 TK 55533-2-OD-EN
(407,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-40
55533-2-6-41
TK 55533-2-OD-EN 407
(408,1)
55533-2-6-42
55533-2-6-43
55533-2-6-44
408 TK 55533-2-OD-EN
(409,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-45
55533-2-6-46
TK 55533-2-OD-EN 409
(410,1)
55533-2-6-47
410 TK 55533-2-OD-EN
(411,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-49
55533-2-6-50
TK 55533-2-OD-EN 411
(412,1)
55533-2-6-51
55533-2-6-52
55533-2-6-53
412 TK 55533-2-OD-EN
(413,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-54
55533-2-6-55
55533-2-6-56
TK 55533-2-OD-EN 413
(414,1)
55533-2-6-57
21 Click OK.
55533-2-6-58
55533-2-6-59
414 TK 55533-2-OD-EN
(415,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
23 Click Cancel.
55533-2-6-60
55533-2-6-61
TK 55533-2-OD-EN 415
(416,1)
55533-2-6-62
55533-2-6-63
416 TK 55533-2-OD-EN
(417,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-64
55533-2-6-65
TK 55533-2-OD-EN 417
(418,1)
7 Check the voltage across the The voltage in high speed should Set the meter to read AC
sensor terminals with the FS1 and read from 1.0 to 5.0 Vac. volts.
FS2 wires removed.
10 Access the Gauge menu and The display should show the engine
display Engine RPM. RPM.
418 TK 55533-2-OD-EN
(419,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
55533-2-6-66
TK 55533-2-OD-EN 419
(420,1)
The harness wire number, wire color, and additional information for the module wiring is shown
in the table.
Table 11. Ground Fault Detect Module Harness Connections
Harness Wire # Wire Color on Module Purpose Notes
Proce dur e:
Step Action Result Comments
3 Unplug the two wire plug at the After disconnecting the plug,
Ground Fault Detect Module. the module should no longer
register a ground fault
condition.
4 Start and run the unit for 2-3 Alarm Code 518 should not be The module will be unable to
minutes. If Alarm Code 518 was present as long as the two wire sense a ground fault
present, it should clear plug at the module is condition with the two wire
automatically. disconnected. plug disconnected and the
alarm should clear
automatically.
5 Check to see if Alarm Code 518 is If Alarm Code 518 is no longer Alarm Code 518 with a
still present, then turn the unit off. present, then a ground fault disconnected sense plug
condition likely exists. Check the indicates an issue with the
generator, fans, and AC harness module or the harness
for shorts to ground. If Alarm Code between the base controller
518 was still present on the HMI, and module.
then the module or harness may
be defective. Proceed to step 6.
7 Turn the unit on and enter Service This powers the controller and The following steps check
Test Mode from the Maintenance applies power to the Ground Fault the low voltage control
Menu. Select Low Speed Cool. Detect module. circuit.
Important: The engine should not
be running for this
portion of the test.
8 Using a multimeter, check available Voltage should read between 4.9 This is a regulated +5 Vdc
voltage between the GFP-02 wire at and 5.1 Vdc. If voltage reads less source from the base
the GFD module harness plug and than 4.9 volts at the GFP-02 wire, controller.
chassis ground. proceed to step 9. If appropriate
voltage is present, proceed to step
11.
9 Disconnect the J3 connector at the Resistance should read OL on a A short to ground on the
base controller. Using a multimeter, multimeter. If resistance is less power wire will cause low
check resistance between the GFP- than OL, a short to ground is voltage at the GFD module.
02 wire at the GFD module and present and should be repaired.
chassis ground. Repair the short and retest.
420 TK 55533-2-OD-EN
(421,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
10 Using a multimeter, check available Voltage should read between 4.9 The GFP circuit contains a
voltage between the GFP-01 wire at and 5.1 Vdc. If voltage reads less plug connection between the
the base controller J3 connector pin than 4.9 volts at the GFP-01 wire, J3 connector and Ground
35 and chassis ground. inspect the J3 connector for a poor Fault Detect Module.
connection or failed base
controller. If voltage reads
between 4.9 to 5.1 Vdc, inspect
wiring between the base controller
and module for an open or resisted
circuit.
12 Using a multimeter, check Resistance of a properly operating The GFN circuit contains a
resistance of the GFN-02 wire at the circuit should read near 0 ohms on plug connection between the
module harness connector to the a multimeter. If resistance reads J3 connector and Ground
GFN-01 wire at J3 connector pin 34. greater than near 0 ohms, inspect Fault Detect Module. The
the wiring for a resisted or open ground circuit has been
circuit. If the resistance reads near checked. The next step is to
0 ohms, go to step 13. check the signal circuit.
13 Using a multimeter, check Resistance of a properly operating The GFF circuit contains a
resistance of the GFF-02 wire at the circuit should read near 0 ohms on plug connection between the
module harness connector to the a multimeter. If resistance reads J3 connector and Ground
GFF-01 wire at J3 connector pin 33. greater than near 0 ohms, inspect Fault Detect Module. The
the wiring for a resisted or open ground circuit has been
circuit. If the resistance reads near checked. The next step is to
0 ohms, go to step 14. check the signal circuit.
14 If all associated circuits are Replace the Ground Fault Detect If this procedure fails with a
operational, the module is likely Module. new Ground Fault Detect
defective. Module, the base controller
may be defective.
TK 55533-2-OD-EN 421
(422,1)
The current Electronic Throttling Valves do not have a removable connector on the valve. There is
a sheathed cable consisting of colored wires that run from the valve to the Deutsch connector on
the cable as shown above.
SR-4 Base Controllers feature yellow and green ETV LEDs located at the lower left edge of the
board. These LEDs flash when a signal is being sent to the ETV. These LEDs flash rapidly for a
brief period of time on initial startup. They flash at a slower rate when the valve is opening or
closing normally. If LEDs are flashing, a signal is being sent to the ETV.
The harness wire number, wire color and Base Controller LED number for the valve are shown in
the table.
422 TK 55533-2-OD-EN
(423,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
Proce dur e:
Step Action Result Comments
2 Disconnect Base Controller The resistance should be from 20 Identify the associated pins
connector J4 and measure to 35 ohms. If the resistance is on the ETV and check for
resistance between the EVA-01 and incorrect, check the EVA-01 and continuity at the valve. If the
EVB-01 wires at the connector. Also EVB-01 wires and connectors resistance from the EVA-01
measure the resistance between leading to the Electronic Throttling and EVB-01 pins directly on
EVA-01 and ground, and EVB-01 Valve. Verify the valve connector is the valve is not from 20 to 35
and ground (should be an open properly attached to the valve. ohms the valve is defective.
circuit). Neither pin should show a
short to ground.
• J4 Pin 25 – EVA-01 wire
• J4 Pin 28 – EVB-01 wire
3 Measure resistance between the The resistance should be from 20 Identify the associated pins
EVC-01 and EVD-01 wires at the to 35 ohms. If the resistance is on the ETV and check for
connector. Also measure the incorrect check the EVC-01 and continuity at the valve. If the
resistance between EVC-01 and EVD-01 wires and connectors resistance from the EVC-01
ground, and EVD-01 and ground leading to the Electronic Throttling and EVD-01 pins directly on
(should be an open circuit). Valve. Verify the valve connector is the valve is not from 20 to 35
properly attached to the valve. ohms the valve is defective.
• J4 Pin 27 – EVC-01 wire
Neither pin should show a
• J4 Pin 26 – EVD-01 wire short to ground.
7 Turn the unit on and enter AC voltage between EVA-01 and Prior to the LEDs blinking, it
Evacuation Test from the EVB-01 with the valve opening is normal for the AC voltage
Maintenance Menu. Pay attention to during Evacuation Test should be read on the meter to
the ETV LEDs on the board. When between 8-13 VAC. fluctuate. Pay attention to
all 4 LEDs appear to blink at the voltage only when all 4 LEDs
same time, read AC voltage are blinking. The voltage
between EVA-01 and EVB-01. read on the multimeter may
be higher (up to 16 VAC) if a
battery charger is connected
to the unit.
TK 55533-2-OD-EN 423
(424,1)
10 Turn the unit on and enter AC voltage between EVC-01 and Voltage read on the
Evacuation Test from the EVD-01 with the valve opening multimeter may be higher
Maintenance Menu. Pay attention to during Evacuation Test should be (up to 12 VAC) if a battery
the ETV LEDs on the board. When between 6-10 VAC. charger is connected to the
all 4 LEDs appear to blink at the unit.
same time, read AC voltage
Note: The voltage read
between EVC-01 and EVD-01.
between EVC-01 and
EVD-01 should be
less than voltage
between EVA-01 and
EVB-01 based on how
the controller steps
the ETV. This is
entirely normal.
424 TK 55533-2-OD-EN
(425,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
The current Electronic Throttling Valves do not have a removable connector on the valve. There is
a sheathed cable consisting of colored wires that run from the valve to the Deutsch connector on
the cable as shown above. The Stepper Motor Tester is connected to the ETV using this Deutsch
connector. A pigtail must be constructed in order to connect the tester to the ETV. The ETV may
operate backwards if the connections are reversed.
When using the Stepper Motor Tester (TK# 204-1046) the ETV position displayed on the HMI does
not indicate actual valve position; the valve is being controlled manually by the tester. The unit
harness from the Base Controller must be disconnected from the valve at the Deutsch plug in
order to connect the ETV tester. The Base Controller will attempt to control the valve position but
will be unable to since the valve is disconnected. The HMI will display requested ETV position,
however, the valve will not respond to requests from the Base Controller and the displayed
position will likely not be the actual position of the valve. Alarm Code 89 will likely not be
generated in this case.
TK 55533-2-OD-EN 425
(426,1)
I m p o rt a n t : DO NOT open the valve too far, this may cause a possible Alarm Code 10 in high
ambient or stall the engine if in low speed.
The harness wire number, wire color on ETV, and binding post color on the tester are shown in
the table.
Table 13. ETV Harness and Tester Connections
Harness Wire # Wire Color on ETV Post Color on Tester
Proce dur e:
Step Action Result Comments
3 Set the tester to 50 steps per This closes the ETV. Near the end The LEDs on the tester will
second and press the rocker switch of 10-15 seconds you will hear the blink as the valve is being
to the “CLOSE” position for 10-15 valve fully closing. positioned.
seconds.
4 Press the rocker switch to the This slightly opens the ETV and ETV position displayed on
“OPEN” position for 2-3 seconds. prevents the unit from running in a the HMI will not be accurate
vacuum on startup. as the tester is positioning
the valve, not the base
controller.
5 Turn the unit on and enter Service The engine will start and the unit
Test Mode in the Maintenance will enter low speed cool operation.
Menu. Select Engine Running Low
Speed Cool.
7 While monitoring suction pressure Suction pressure shown on the Suction pressure will go into
on the HMI, press the tester rocker HMI should decrease as the valve a vacuum if the valve fully
switch to the “CLOSED” position for is being closed. closes during this test.
3-5 seconds. Depending on suction
pressure, more than 3-5
seconds of closing the valve
may be required to notice a
pressure decrease.
426 TK 55533-2-OD-EN
(427,1)
Sec t i o n 6 - Se rv i ce Pro ce d u re s
TK 55533-2-OD-EN 427
(428,1)
3 Using jumpers as required, connect The meter must show a very low Verify the ohmmeter battery
each end of the circuit to a high resistance (less than 1.0 ohm), is good and the meter zeros
quality multimeter. indicating circuit continuity. If not, with the leads held together
the circuit is open or has excessive to prevent misleading
resistance. Troubleshoot the circuit results.
to determine the cause using the
wiring diagrams.
4 After determining that the circuit The meter should indicate an open
passes a continuity test, remove circuit. If not, the circuit is shorted
one lead and connect it to the to ground. Troubleshoot the circuit
chassis ground to check for a short to determine the cause using the
to ground. wiring diagrams.
428 TK 55533-2-OD-EN
(429,1)
Replacement Options
45–2448 OK OK OK
45–2521 OK OK OK
45–2464 OK OK OK
45–2558 OK OK OK
45–2548 OK
845–2548 OK
TK 55533-2-OD-EN 429
(430,1)
Sec t i o n 7 - Ser vi c e I n fo rm at i o n
1 6
2
3
4
5
430 TK 55533-2-OD-EN
(431,1)
Se ct i o n 7 - Se rv i c e In fo rm a ti o n
2AH
55533-2-7-2
TK 55533-2-OD-EN 431
(432,1)
Sec t i o n 7 - Ser vi c e I n fo rm at i o n
55533-2-7-3
S/N Legend
H = HMI
1071221 = Serial Number
1237 = Date Code YYWW (Year 2012 W eek 37)
0T4 = Identifier (SR-4)
432 TK 55533-2-OD-EN
(433,1)
Se ct i o n 7 - Se rv i c e In fo rm a ti o n
55533-2-7-4
TK 55533-2-OD-EN 433
(434,1)
1H75822 S-600 Schematic Diagram for Early S-600 Units with Engine Relay/Fuse Board
1H75823 S-600 Wiring Diagram for Early S-600 Units with Engine Relay/Fuse Board
2H05133 S-600 and S-700 Schematic Diagram for Later S-600 Units without Engine
Relay/Fuse Board and S-700 Units
1H84893 S-600 and S-700 Wiring Diagram for Later S-600 Units without Engine Relay/
Fuse Board and S-700 Units
434 TK 55533-2-OD-EN
(435,1)
Section 9 - Specifications
Engine
Model: C-600 TK486V25 (Tier 4)
S-600 TK488CR (Tier 4)
S-700 TK488CRH (Tier 4)
Number of Cylinders 4
TK 55533-2-OD-EN 435
(436,1)
Sec t i o n 9 - S p e c i fi c a ti o n s
Belt Tension
Belt Use of Frequency Gauge P/N 204–1903 to measure frequency (Hz) is
recommended.
AC Generator and Alternator Belt 37 or 65 Amp Alternator 106 Hz (111 lbs) 92 Hz (84 lbs)
- Standard Units: 120 Amp Alternator 121 Hz (144 lbs) 105 Hz (108 lbs)
Compressor Drive Belt - 12 HP Electric Motor 131 Hz (236 lbs) 114 Hz (177 lbs)
SmartPower Units Only 19 HP Electric Motor 150 Hz (300 lbs) 130 Hz (223 lbs)
Alternator Belt - SmartPower All Alternators 216 Hz (75 lbs) 187 Hz (56 lbs)
Units Only
Refrigeration System
Compressor Thermo King X430LSC5 or X430P
* When the compressor is removed from the unit, oil level should be noted or the oil removed from the compressor should be measured so that
the same amount of oil can be added before placing the replacement compressor in the unit.
436 TK 55533-2-OD-EN
(437,1)
Section 9 - Specifications
Battery One, group C31, 12 volt, (950 CCA recommended for operation below -15 F [-26 C])
Fuses See Base Controller Fuses, Battery Fusing, ECU Fuses, and other fuses in “Electrical Maintenance” (TK 55270–
2–MM)
Battery Charging (Alternator) 12 volt, 37 amp, brush type, Thermo King Alternator (Optional 65 amp alternator available)
Battery Charger (Optional) Bulk = up to 15.8v, Absorption = temperature compensation from 14.15v @ 77F (25 C), Float Voltage = Stage
3 @ ~ 13.6v ~ 13.8v
Electrical Components
Note: Disconnect components from unit circuit to check resistance.
S-600 AC Generator Low Engine Speed (1250 RPM) 210 Vac at 54.9 Hz Nominal Vac - Measured Vac, Load Dependent
Output
High Engine Speed (2050 RPM) 345 Vac at 90 Hz Nominal Vac - Measured Vac, Load Dependent
Output
Evaporator Fan Motor Low Speed Power Rating 1.20 hp (0.90 kW)
High Fan Speed at Low Engine 1600 RPM at low engine speed (1250 rpm)
Speed
Low Fan Speed at High Engine 1750 RPM at high engine speed (2050 rpm)
Speed
Low Fan Speed at Low Engine 1050 RPM at low engine speed (1250 rpm)
Speed
High Speed Current Draw at Low 3.8 amps at low engine speed (1250 rpm)
Engine Speed
Low Speed Current Draw at High 3.1 amps at high engine speed (2050 rpm)
Engine Speed
Low Speed Current Draw at Low 2.6 amps at low engine speed (1250 rpm)
Engine Speed
TK 55533-2-OD-EN 437
(438,1)
Sec t i o n 9 - S p e c i fi c a ti o n s
Fan Speed at High Engine Speed 2650 RPM at high engine speed (2050 rpm)
Current Draw at Low Engine 1.8 amps (per motor) at low engine speed (1250 rpm)
Speed
Current Draw at High Engine 2.0 amps (per motor) at high engine speed (2050 rpm)
Speed
S-700 AC Generator Low Engine Speed (1450 RPM) 200 Vac at 50 Hz Nominal Vac - Measured Vac, Load Dependent
Output
High Engine Speed (2600 RPM) 345 Vac at 90 Hz Nominal Vac - Measured Vac, Load Dependent
Output
Evaporator Fan Motor Low Speed Power Rating 0.60 hp (0.45 kW)
High Fan Speed at Low Engine 990 RPM at low engine speed (1450 rpm)
Speed
High Fan Speed at High Engine 1750 RPM at high engine speed (2600 rpm)
Speed
Low Fan Speed at High Engine 1350 RPM at low engine speed (2600 rpm)
Speed
High Speed Current Draw at Low 3.5 amps at low engine speed (1450 rpm)
Engine Speed
High Speed Current Draw at High 3.5 amps at high engine speed (2600 rpm)
Engine Speed
Low Speed Current Draw at High 2.0 amps at low engine speed (2600 rpm)
Engine Speed
Fan Speed at High Engine Speed 2650 RPM at high engine speed (2600 RPM)
Current Draw at Low Engine 1.8 amps (per motor) at low engine speed (1450 RPM)
Speed
Current Draw at High Engine 2.0 amps (per motor) at high engine speed (2600 RPM)
Speed
Fan Motors — Electric Standby Operation 230/3/60 or 460/3/60 (Unit transformer reduces 460/3/60 input voltage to 230/3/
60 applied to fan motors.)
S-600 Evaporator Fan Motor Low Speed Power Rating 1.20 hp (0.90 kW)
S-700 Evaporator Fan Motor Low Speed Power Rating 0.60 hp (0.45 kW)
438 TK 55533-2-OD-EN
(439,1)
Section 9 - Specifications
Extension Cord Size: 12 HP Motor 230/3/60 8 AWG Power Cable, 4-Conductor, 2000V, Type W Power Cable,
25 to 50-foot length
12 HP Motor 230/3/60 6 AWG Power Cable, 4-Conductor, 2000V, Type W Power Cable,
75-foot length
12 HP Motor 460/3/60 10 AWG Power Cable, 4-Conductor, 2000V, Type W Power Cable,
up to 75-foot length
TK 55533-2-OD-EN 439
(440,1)
Notes
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments.
Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and Trane® — work
together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables;
and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable
progress and enduring results.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2015 Thermo King All rights reserved
TK 55533-2-OD-EN 01 Jun 2015 We are committed to using environmentally
Supersedes TK 55533-2-OD-EN (December 2012) conscious print practices that reduce waste.